14-2025-12-16922 GENR ELECT Specs BID.pdf
PDF 3 MB Posted
- Attached to
- Courthouse Generator
- Solicitation number
- 2026018
- Issued by
- Indian River County, Florida
About this file
This is a specifications document for an emergency diesel generator set (KD1000 model) manufactured by Rehlko (Discovery Energy, LLC) in support of a Florida courthouse generator replacement project. The project requires installation of a 1000 kW diesel-powered emergency generator with related electrical connections, a structural concrete pad foundation, and a 10-foot aluminum perimeter screen enclosure wall. The specification details the GMKD1000 generator model, which features a Tier 2 EPA-certified KD27V12 engine rated at 1000 kW standby (1250 kVA) or 900 kW prime power (1125 kVA) at 60 Hz. The generator set includes three alternator options (KH04070TO4D, KH04830TO4D, or KH05520TO4D), operates at various voltage configurations ranging from 120/208V to 347/600V three-phase, and is equipped with advanced Rehlko controllers (APM603 or APM802) for system monitoring and diagnostics. The unit provides one-step 100% load acceptance, meets NFPA 110 Level 1 standards when properly equipped, and is UL 2200 listed for stationary emergency applications.
The generator set specifications include a 27-liter, 12-cylinder turbocharged diesel engine with electronic KODEC governor providing isochronous frequency regulation at 0.25% steady-state accuracy. Fuel consumption ranges from 269 liters per hour (70.9 gph) at 100% standby load to 84 liters per hour (22.2 gph) at 25% load, with fuel tank capacities ranging from 3,475 to 19,381 liters depending on configuration. The unit weighs approximately 8,083 kilograms (17,821 pounds) in radiator model configuration and measures 4,224 x 1,986 x 2,200 millimeters. Standard features include a three-year unlimited-hour warranty for standby applications, closed crankcase ventilation, integral vibration isolation, local emergency stop switch, and operation/installation literature. Available options encompass various sound enclosure levels (Sound Level 1 and 2), subbase fuel tanks with secondary containment meeting UL 142 requirements, multiple controller configurations, electrical packages including distribution panels and block heaters, exhaust silencers, remote monitoring capabilities, and various cooling system enhancements. The generator is certified for use with renewable Hydrotreated Vegetable Oil (HVO) and Renewable Diesel (RD) fuels compliant with EN15940/ASTM D975 standards in addition to standard #2 ULSD diesel fuel.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EMERGENCY GENERATOR
rcheer Revised cflores Released
Industrial Diesel Generator Set - KD1000
Tier 2 EPA-Certified for Stationary Emergency Applications
G5-580_9/24o
Discovery Energy, LLC 200 Twin Oaks Road, Kohler, WI 53044 USA
For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 1/6
KDxxxx designates a generator set with a Tier 2 EPA-Certified engine.
KDxxxx-F designates a 60 Hz generator set with a fuel optimized engine.
Ratings Range
60 Hz
Standby: kW kVA
975-1000 1219-1250
Prime: kW kVA
810-900 1012-1125
Standard Features Rehlko provides one-source responsibility for the generating system and accessories.
Approved for use with certified renewable Hydrotreated
Vegetable Oil (HVO)/Renewable Diesel (RD) fuels compliant with EN15940/ASTM D975.
The generator set and its components are prototype-tested, factory-built, and production-tested.
The 60 Hz generator set offers a UL 2200 listing.
The generator set accepts rated load in one step.
The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
A standard three-year unlimited-hour limited warranty for standby applications in the U.S. And Canada. Five-year basic, five-year comprehensive, and ten-year extended limited warranties are also available.
A standard two-year or 8700-hour limited warranty for prime power applications.
Other features:
o Rehlko designed controllers for one-source system integration and remote communication. See Controllers on page 4.
o The low coolant level shutdown prevents overheating (standard on radiator models only).
General Specifications
Orderable Generator Model Number GMKD1000
Manufacturer Rehlko
Engine: model KD27V12
Alternator Choices KH04070TO4D
KH04830TO4D
KH05520TO4D
Performance Class Per ISO 8528-5
One Step Load Acceptance 100%
Voltage Wye or 600 V
Controller APM603, APM802
Fuel Tank Capacity, L (gal.) 3475-19381 (918-5120)
Fuel Consumption, L/hr (gal./hr) 100% at Standby 269 (70.9)
Fuel Consumption, L/hr (gal./hr) 100% at Prime Power 247 (65.3)
Emission Level Compliance (KDxxxx) Tier 2
Open Unit Noise Level @ 7 m dB(A) at Rated Load 96
Data Center Continuous (DCC) Rating (Refer to TIB-101 for definitions)
Same as the Standby Rating below
Conscious Care™ Qualified Reduce operating costs, fuel consumption, and greenhouse gas emissions with Conscious Care™ maintenance program.
Generator Set Ratings
Alternator Voltage Ph Hz
150°C Rise Standby Rating
130°C Rise Standby Rating
125°C Rise Prime Rating
105°C Rise Prime Rating kW/kVA Amps kW/kVA Amps kW/kVA Amps kW/kVA Amps
KH04070TO4D
120/208 3 60 1000/1250 3470 1000/1250 3470 900/1125 3123 810/1012 2810 127/220 3 60 1000/1250 3281 1000/1250 3281 900/1125 2953 810/1012 2656 139/240 3 60 1000/1250 3008 975/1219 2933 900/1125 2707 — — 220/380 3 60 1000/1250 1900 1000/1250 1899 900/1125 1710 900/1125 1710 240/416 3 60 1000/1250 1735 1000/1250 1735 900/1125 1562 870/1088 1510 254/440 3 60 1000/1250 1641 1000/1250 1641 900/1125 1477 900/1125 1477 277/480 3 60 1000/1250 1504 1000/1250 1504 900/1125 1354 900/1125 1354 347/600 3 60 1000/1250 1203 1000/1250 1203 900/1125 1083 900/1125 1083
KH04830TO4D
230/400 3 60 1000/1250 1805 1000/1250 1805 900/1125 1624 900/1125 1624 240/416 3 60 1000/1250 1735 1000/1250 1735 900/1125 1562 900/1125 1562 254/440 3 60 1000/1250 1641 1000/1250 1641 900/1125 1477 900/1125 1477 277/480 3 60 1000/1250 1504 1000/1250 1504 900/1125 1354 900/1125 1354
RATINGS: All three-phase units are rated at 0.8 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings guidelines, complete ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Line
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1-800-544-2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 2/6
Alternator Voltage Ph Hz
150°C Rise Standby Rating
130°C Rise Standby Rating
125°C Rise Prime Rating
105°C Rise Prime Rating kW/kVA Amps kW/kVA Amps kW/kVA Amps kW/kVA Amps
KH05520TO4D
220/380 3 60 1000/1250 1900 1000/1250 1900 900/1125 1710 900/1125 1710 230/400 3 60 1000/1250 1805 1000/1250 1805 900/1125 1624 900/1125 1624 240/416 3 60 1000/1250 1735 1000/1250 1735 900/1125 1562 900/1125 1562 254/440 3 60 1000/1250 1641 1000/1250 1641 900/1125 1477 900/1125 1477 277/480 3 60 1000/1250 1504 1000/1250 1504 900/1125 1354 900/1125 1354 347/600 3 60 1000/1250 1203 1000/1250 1203 900/1125 1083 900/1125 1083
Engine Specifications 60 Hz
Engine: model KD27V12 Engine: type 4-Cycle, Turbocharged, Charge Air Cooled Cylinder arrangement 12-V Displacement, L (cu. in.) 27 (1648) Bore and stroke, mm (in.) 135 x 157 (5.31 x 6.18) Compression ratio 15.0:1 Piston speed, m/min. (ft./min.) 565 (1854) Main bearings: quantity, type 7, Precision Half Shells Rated rpm 1800 Max. power at rated rpm, kWm (BHP) 1114 (1494) Cylinder head material Cast Iron Crankshaft material Steel Valve (exhaust) material Steel Governor: type, make/model KODEC Electronic Control Frequency regulation, no-load to full-load Isochronous Frequency regulation, steady state ±0.25% Frequency Fixed Air cleaner type, all models Dry
Lubricating System 60 Hz
Type Full Pressure Oil pan capacity dipstick mark max., L (qt.) § 79 (83.5)
Oil pan capacity, initial filling, L (qt.) § 101 (106.7)
Oil filter: quantity, type § 2, Cartridge
Oil cooler Water-Cooled § Rehlko recommends the use of Rehlko Genuine oil and filters.
Fuel System 60 Hz
Fuel supply line, min. ID, mm (in.) 14 (0.55) Fuel return line, min. ID, mm (in.) 14 (0.55) Max. fuel flow, Lph (gph) 380 (100) Min./max. fuel pressure at engine supply connection, kPa (in. Hg) -30/30 (-8.8/8.8) Max. return line restriction, kPa (in. Hg) 30 (8.8) Fuel filter: quantity, type 1, Primary Engine Filter
1, Fuel/Water Separator Recommended fuel #2 Diesel ULSD/HVO/RD
Fuel Consumption** 60 Hz
Diesel, Lph (gph) at % load Standby Rating
100% 269 (70.9)
75% 209 (55.3) 50% 146 (38.6) 25% 84 (22.2)
Diesel, Lph (gph) at % load Prime Rating
100% 247 (65.3)
75% 191 (50.4) 50% 135 (35.6) 25% 79 (20.8)
** Volumetric Fuel consumption is up to 4% higher when using HVO/RD than #2 ULSD.
Radiator System 60 Hz
Ambient temperature, °C (°F)* 50 (122) 40 (104)
Radiator system capacity, including engine, L (gal.) 123 (32.4) 113 (29.5) Engine jacket water capacity, L (gal.) 55 (14.4) Engine jacket water flow, Lpm (gpm) 1015 (268)
Charge cooler air inlet temperature at 25C (77F) ambient, C (F) 219 (426)
Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) 404 (22996)
Heat rejected to charge air cooler at rated kW, dry exhaust, kW (Btu/min.) 260 (14799) Turbocharger boost (abs) bar (psi) 3.4 (49) Water pump type Vane Wheel Fan diameter, including blades, mm (in.) 1350 (53.1)
Fan, kWm (HP) 48 (64.3)
Max. restriction of cooling air, intake and discharge side of radiator, kPa (in. H2O) 0.125 (0.5)
* Enclosure with enclosed silencer reduces ambient temperature capability by 5°C (9°F).
Remote Radiator System† 60 Hz
Exhaust manifold type Dry Connection sizes:
Water inlet/outlet, mm (in.) 85 (3.35) Charge air cooler inlet/outlet (pipe dia. of flange), mm (in.) 127 (5)
Static head allowable above engine, kPa (ft. H2O) 70 (23.5)
† Contact your local distributor for cooling system options and specifications based on your specific requirements.
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1-800-544-2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 3/6
Exhaust System 60 Hz
Exhaust flow at rated kW, m3/min. (cfm) 201.6 (7119) Exhaust temperature at rated kW at 25°C (77°F) ambient, dry exhaust, °C (°F) 530 (986) Maximum allowable back pressure, kPa (in. Hg) 8.5 (2.5) Exh. outlet size at eng. hookup, mm (in.) See ADV drawing
Electrical System 60 Hz
Battery charging alternator:
Ground (negative/positive) Negative Volts (DC) 24 Ampere rating 140
Starter motor qty. at starter motor power rating, rated voltage (DC)
Standard: 1 @ 7.8 kW, 24;
Redundant (optional):
2 @ 7.8 kW, 24 Battery, recommended cold cranking amps
(CCA):
Quantity, CCA rating each, type (with standard starter) 2, 1110, AGM Quantity, CCA rating each, type (with optional redundant starters) 4, 1110, AGM
Battery voltage (DC) 12
Air Requirements 60 Hz
Radiator-cooled cooling air, m3/min. (scfm)‡
1212 (42801)
High ambient radiator- cooled cooling air, m3/min (scfm)‡
1350 (47700)
Cooling air required for generator set when equipped with city water cooling or remote radiator, based on 14°C (25°F) rise, m3/min. (scfm)‡ 653.9 (23092) Combustion air, m3/min. (cfm) 72.7 (2566) Heat rejected to ambient air:
Engine, kW (Btu/min.) 136 (7741) Alternator, kW (Btu/min.) 48 (2732)
‡ Air density = 1.20 kg/m3 (0.075 lbm/ft3)
Alternator Specifications 60 Hz
Type 4-Pole, Rotating-Field Exciter type Brushless, Permanent-
Magnet Pilot Exciter
Voltage regulator Solid-State, Volts/Hz
Insulation: NEMA MG1, UL 1446, Vacuum Pressure Impregnated (VPI)
Material Class H, Synthetic, Nonhygroscopic
Temperature rise 130°C, 150°C Standby Bearing: quantity, type 1, Sealed Coupling type Flexible Disc
Amortisseur windings Full Alternator winding type Random Wound Rotor balancing 125%
Voltage regulation, no-load to full-load ±0.25% One-step load acceptance 100% of Rating Unbalanced load capability 100% of Rated
Standby Current
Peak motor starting kVA: (35% dip for voltages below)
480 V KH04070TO4D 3774
480 V KH04830TO4D 4193
480 V KH05520TO4D 4612
Alternator Standard Features The pilot-excited, permanent magnet (PM) alternator provides superior short-circuit capability.
All models are brushless, rotating-field alternators.
NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
Self-ventilated and dripproof construction.
Superior voltage waveform from two-thirds pitch windings and skewed stator.
Brushless alternator with brushless pilot exciter for excellent load response.
NOTE: See TIB-102 Alternator Data Sheets for alternator application data and ratings, efficiency curves, voltage dip with motor starting curves, and short circuit decrement curves.
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1-800-544-2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 4/6
Controllers
APM802 Controller Provides advanced control, system monitoring, and system diagnostics for optimum performance and compatibility.
12-inch graphic display with touch screen and menu control provide easy local data access
Measurements are selectable in metric or English units
User language is selectable Two USB ports allow connection of a flash drive, mouse, or keypad
Electrical data, mechanical data, and system settings can be saved to a flash drive
Ethernet port allows connection to a PC type computer or Ethernet switch
The controller supports Modbus® RTU and TCP protocols NFPA 110 Level 1 capability Refer to G6-152 for additional controller features and accessories.
Modbus® is a registered trademark of Schneider Electric.
APM603 Controller Provides advanced control, system monitoring, and system diagnostics for optimum performance and compatibility.
7-inch graphic display with touch screen and menu control provides easy local data access
Measurements are selectable in metric or English units
Paralleling capability to control up to 8 generators on an isolated bus with first-on logic, synchronizer, kW and kVAR load sharing, and protective relays Note: Parallel with other APM603 controllers only
Generator management to turn paralleled generators off and on as required by load demand
Load management to connect and disconnect loads as required Controller supports Modbus® RTU, Modbus® TCP, SNMP and
BACnet®
Integrated voltage regulator with ±0.25% regulation
Built-in alternator thermal overload protection UL-listed overcurrent protective device
NFPA 110 Level 1 capability Refer to G6-162 for additional controller features and accessories.
BACnet® is a registered trademark of ASHRAE.
Codes and Standards Engine-generator set is designed and manufactured in facilities certified to ISO 9001.
Generator set meets NEMA MG1, BS5000, ISO, DIN EN, and IEC standards, NFPA 110.
Engine generator set is tested to ISO 8528-5 for transient response.
The generator set and its components are prototype-tested, factory-built, and production-tested.
Third-Party Compliance Tier 2 EPA-Certified for Stationary Emergency Applications
Available Approvals and Listings
California OSHPD Pre-Approval cULus (UL 2200 and CSA) IBC Seismic Certification Florida Dept. of Environmental Protection (FDEP) Compliance (fuel tanks only)
Warranty Information A standard three-year unlimited-hour limited warranty for standby applications in the U.S. And Canada. Five-year basic, five-year comprehensive, and ten-year extended limited warranties are also available.
A standard two-year or 8700-hour limited warranty for prime power applications.
Available Warranties for Standby Applications
5-Year Basic Limited Warranty 5-Year Comprehensive Limited Warranty 10-Year Major Components Limited Warranty
Standard Features Closed Crankcase Ventilation (CCV) Filters
Customer Connection Integral Vibration Isolation
Local Emergency Stop Switch Oil Drain and Coolant Drain Extension
Operation and Installation Literature Battery Rack and Cables
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1-800-544-2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 5/6
Available Options Circuit Breakers
Type Magnetic Trip Thermal Magnetic Trip Electronic Trip (LI) Electronic Trip with Short
Time (LSI)
Rating 80% 100%
Operation Manual Electrically Operated
(for paralleling)
Circuit Breaker Mounting Generator Mounted
Remote Mounted
Bus Bar (for remote mounted breakers)
Enclosed Remote Mounted Circuit Breakers
NEMA 1 (15-5000 A)
NEMA 3R (15-1200 A)
Engine Type
KDxxxx Tier 2 EPA-Certified Engine
KDxxxx-F Fuel Optimized Engine
Approvals and Listings
California OSHPD Pre-Approval cULus (UL 2200 and CSA)
IBC Seismic Certification
Florida Dept. of Environmental Protection (FDEP) Compliance (fuel tanks only)
Hurricane Rated Enclosure
Enclosed Unit
Sound Level 1 Enclosure/Fuel Tank Package Sound Level 2 Enclosure/Fuel Tank Package
Open Unit
Exhaust Silencer, Critical (kits: PA-354880 qty. 2 or PA-354898 qty. 1)
Exhaust Silencer, Hospital (kits: PA-354905 qty. 2 or PA-354912 qty. 1)
Flexible Exhaust Connector, Stainless Steel
Controller
Input/Output, Digital Load Shed (APM802 only)
Manual Key Switch
Remote Emergency Stop Switch Lockable Emergency Stop Switch
Remote Serial Annunciator Panel
Cooling System
Block Heater, 6000 W, 208 V, (select 1 Ph or 3 Ph) *
Block Heater; 6000 W, 240 V, (select 1 Ph or 3 Ph) * Block Heater; 6000 W, 480 V, (select 1 Ph or 3 Ph) *
* Required for ambient temperatures below 10C (50F).
Block heater kit includes air intake manifold grid heater.
Radiator Guard and Duct Flange
Electrical System
Battery, AGM (kit with qty. 2)
Battery Charger
Battery Heater; 80 W, 120 V, 1Ph
Generator Heater
Redundant Starters
Fuel System
Flexible Fuel Lines
Restriction Gauge (for fuel/water separator)
Literature
General Maintenance
NFPA 110
Overhaul
Production
Miscellaneous
Air Cleaner, Heavy Duty (loose)
Air Cleaner Restriction Indicator
Alternator Air Filter (will reduce generator set rating by 7%)
Automatic Oil Replenishment System
Engine Fluids (oil and coolant) Added
Rated Power Factor Testing
Electrical Package (Requires Enclosure selection)
Basic Electrical Package (select 1 Ph or 3 Ph)
Wire Battery Charger (1 Ph)
Wire Block Heater (select 1 Ph or 3 Ph)
Wire Controller Heater (1 Ph)
Wire Generator Heater (1 Ph)
Warranty (Standby Applications only)
5-Year Basic Limited Warranty
5-Year Comprehensive Limited Warranty
10-Year Major Components Limited Warranty
Other
Dimensions and Weights Overall Size, max., L x W x H, mm (in.): 4224 x 1986 x 2200
(166.3 x 78.2 x 86.6) Weight, radiator model, max. wet, kg (lb.): 8083 (17821)
NOTE: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.
H
LW
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1-800-544-2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 6/6
Sound Enclosures and Subbase Fuel Tank
Sound Level 1 Enclosure Standard Features Lift base or tank-mounted, aluminum construction enclosure with internal-mounted, exhaust silencers.
Every enclosure has a sloped roof to reduce the buildup of moisture and debris.
Sound attenuated enclosure that offers noise reduction using acoustic insulation, acoustic-lined air inlets and an acoustic-lined air discharge.
Fade-, scratch-, and corrosion-resistant Power Armor™ automotive-grade textured finish.
Acoustic insulation that meets UL 94 HF1 flammability classification.
Enclosure has large access doors that are hinged and removable which allow for easy maintenance.
Lockable, flush-mounted door latches.
Air inlet louvers reduce rain and snow entry.
High wind bracing, 241 kph (150 mph).
Sound Level 2 Enclosure Standard Features Includes all of the sound level 1 enclosure features with the addition of up to 51 mm (2 in.) acoustic insulation material, intake sound baffles, vertical air discharge, and secondary silencers.
Louvered air inlet and vertical outlet hood with 90 degree angles to redirect air and reduce noise.
Subbase Fuel Tank Features The fuel tank has a black powder-coat finish texture.
The above-ground rectangular secondary containment tank mounts directly to the generator set, below the generator set skid (subbase).
Both the inner and outer tanks have UL-listed emergency relief vents.
Flexible fuel lines are provided with subbase fuel tank selection.
The containment tank’s construction protects against fuel leaks or ruptures. The inner (primary) tank is sealed inside the outer (secondary) tank. The outer tank contains the fuel if the inner tank leaks or ruptures.
The above ground secondary containment subbase fuel tank meets UL 142 requirements.
Features include:
o Additional fittings for optional accessories (qty. 3) o Electrical stub-up area open to bottom o Emergency inner and outer tank relief vents o Fuel fill with lockable cap and 51 mm (2 in.) riser o Fuel leak detection switch o Fuel level mechanical gauge o Fuel level sender o Normal vent o Removable engine supply and return diptubes
Sound Level 1 Enclosure
(Shown with available spill containment)
Sound Level 2 Enclosure
(Shown with available spill containment)
Subbase Fuel Tank (Top View)
Jack Kline Highlight
Industrial Generator Set Accessories
Sound Enclosure and Subbase Fuel Tank Package
G6-154_6/25u
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2025 Discovery Energy, LLC - All rights reserved. 1/12
Applicable to the following models:
KD800-KD2500 (includes KD1250A, KD1250-4, KD2500-4)
Sound Level 1 Enclosure Standard Features
• Internal silencers with flexible exhaust connectors and exhaust elbows.
• Mounts to lift base and optional subbase fuel tank.
• Aluminum construction with six large, hinged, removable doors for easy maintenance.
• Fade-, scratch-, and corrosion-resistant Power Armor automotive-grade textured finish.
• Lockable, flush-mounted door latches.
• Air inlet louvers to reduce rain and snow entry.
• Sloped roof to reduce the buildup of moisture and debris.
• Acoustic insulation that meets UL 94 HF1 flammability classification.
• Sound level 1 enclosure is designed to 150 mph (241 kph) wind load rating.
• Sound level 1 enclosure uses internal silencers, acoustic insulation and acoustic-lined air inlet hoods.
Sound Level 2 Enclosure Standard Features
• Includes all of the sound level 1 enclosure features with the addition of up to 51 mm (2 in.) acoustic insulation material, intake sound baffles, secondary silencers, and vertical air discharge with rain caps.
• Vertical outlet hood with 90 degree angles to redirect air and reduce noise.
• Sound level 2 enclosure is certified to 186 mph (299 kph) wind load rating for KD800-2500 models.
Subbase Fuel Tank Features
• The fuel tank has a Power Armor Plus textured epoxy-based rubberized coating.
• The above-ground rectangular secondary containment tank mounts directly to the generator set, below the generator set skid (subbase).
• Both the inner and outer tanks have UL-listed emergency relief vents.
• Flexible fuel lines are provided with subbase fuel tank selection.
• The containment tank’s construction protects against fuel leaks or ruptures. The inner (primary) tank is sealed inside the outer (secondary) tank. The outer tank contains the fuel if the inner tank leaks or ruptures.
• The above ground secondary containment subbase fuel tank meets UL 142 requirements.
• State tanks with varying capacities are available. Florida Dept. of Environmental Protection (FDEP) File No. EQ-634 approved.
Available Approvals and Listings
❑ cULus (UL 2200 and CSA C22.2 No. 100) ❑ UL142 Listing (fuel tanks) ❑ IBC Seismic Certification ❑ California OSHPD Approval (KD800-KD1750 models) ❑ cUL Listing (fuel tanks only) ❑ Hurricane Rated Enclosure - Available on aluminum
Sound Level 2 enclosures, KD800-KD1750 models (Impact rated for Large Missile Level E and Wind load rated per Florida Building Code, tested to TAS201-94, TAS202-94 and TAS203-94 standards)
NOTE: Some models may have limited third-party approvals;
see your local distributor for details.
Level 1 Sound Enclosure with Lift Base
Level 2 Sound Enclosure with Subbase Fuel Tank (Shown with optional spill containment)
Enclosure and Subbase Fuel Tank Combinations
Four enclosure configurations are available with the subbase fuel tanks:
o Sound Enclosure Level 1 o Sound Enclosure Level 1, AQMD Ready o Sound Enclosure Level 2 o Sound Enclosure Level 2, AQMD Ready
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2025 Discovery Energy, LLC - All rights reserved. 3/12
Aluminum Sound Enclosures
Level 2 Sound Enclosure Features
• Heavy-duty formed panels, solid construction.
Preassembled package offering corrosion resistant, dent resilient structure mounting directly to lift base or fuel tank.
• Polyurethane enamel paint. Superior finish, durability, and appearance.
• The enclosure has a sloped roof to reduce the buildup of moisture and debris.
• Internal exhaust silencers offering maximum component life and operator safety.
• Service access. Multiple personnel doors on both sides for easy access to generator set control and servicing of the fuel fill, fuel gauge, oil fill, and battery.
• Interchangeable modular panel construction. Allows complete serviceability or replacement without compromising enclosure design.
• Bolted panels facilitate service, future modification upgrades, or field replacement.
• Cooling/combustion air intake. Fixed air intake louvers.
• Sound-attenuating design using additional secondary silencers and up to 51 mm (2 inches) of added acoustic insulation, UL 94 HF1 listed for flame resistance.
• Vertical air discharge. Sound level 2 (SL2) models use a vertical air discharge design that redirects exhaust and cooling air up and above the enclosure to reduce noise.
ADV-8927
Fade, scratch, and corrosion resistant polyurethane finish
Acoustic insulation meets UL 94 HF1 flammability classification and repels moisture Radiator ducted to enclosure air outlet prevents air recirculation within the enclosure
Enclosed insulated exhaust silencers for improved safety and noise reduction.
Sloped roof reduces water accumulation
Door hold-backs provide positive door positioning during wind gusts
Recessed and lockable door handles minimize potential damage Hinged and removable doors on both sides of the enclosure for easy maintenance
Rubber sealed access Doors prevent water infiltration and minimize noise
Air outlet internal Plenum lined with acoustic insulation
Silencers include rain caps
90 degree vertical air outlet redirects air to reduce noise
(SL2 enclosure only)
Air inlet lined with acoustic insulation
Air inlet louvers reduce rain and snow entry
Note:
Sample sound level 2 (SL2) enclosure shown; other models are similar.
Enclosure ships assembled on lifting base.
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2025 Discovery Energy, LLC - All rights reserved. 4/12
Aluminum Sound Enclosure Options
ADV-8919-5
DC Lights LED light
LED Lights
Exhaust ventilation fan
Fixed air intake louver/baffle assembly, both sides Enclosure heater
Enclosure heater
Top view of SL2 enclosure, shown with roof removed for illustration only:
Note:
Sample sound level 2 (SL2) enclosure shown; other models are similar.
LED Light
Side view of SL2 enclosure, shown with side panels removed for illustration only:
Spill containment
Fuel tank alarm panel
3-way switch with GFCI, qty. 2
Motorized damper
Load center
Emergency stop switch
3-way switch with GFCI, qty. 2
Motorized or gravity discharge damper
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2025 Discovery Energy, LLC - All rights reserved. 6/12
Aluminum Sound Enclosure Options
Basic Electrical Package (BEP)
Distribution Panel/Load Center. Prewired AC power distribution of all factory-installed features including block heater, two GFCI-protected internal 120-volt service receptacles, internal lighting, and commercial grade wall switches. Single-phase or three-phase load center powered by building source power and protected by a main circuit breaker, rated for 100, 125, or 200 amps as noted, with capacity and circuit positions for future expansion. AC power distribution installed in accordance with NEC and all wiring within EMT thin wall conduit. LED AC lights located within UL-listed fixtures designed for wet locations.
❑ BEP, single-phase, 120/208, 60 Hz or 120/240 VAC, 60 Hz.
Includes 100 amp electrical panel, two 3-way switches, four LED lights, and two GFCI receptacles. *
❑ BEP, three-phase, 120/208, 60 Hz or 120/240VAC, 60 Hz.
Includes 125 amp electrical panel, two 3-way switches, four LED lights, and two GFCI receptacles.
❑ BEP, 200 amp, single-phase, 120/208, 60 Hz or 120/240 VAC, 60 Hz. Includes 200 amp electrical panel, two 3-way switches, four LED lights, and two GFCI receptacles. *
❑ BEP, 200 amp, three-phase, 120/208, 60 Hz or 120/240VAC, 60 Hz. Includes 200 amp electrical panel, two 3-way switches, four LED lights, and two GFCI receptacles.
DC Light Package
DC Light Package (DLP). Prewired, internal DC light package offering an economical alternative light source within the enclosure, as a complement to the BEP or a source of light when AC power is not available. Battery drain limited with fuse protection and controlled through a 0-60 minute, spring-wound, no-hold timer.
Available in LED.
Electrical Accessories
Wiring Kits. Electrical wiring for accessories. BEP required.
❑ Alternator heater wiring (KD1250-2500 only) ❑ Block heater wiring, single-phase * ❑ Block heater wiring, three-phase ❑ Battery charger wiring ❑ Wire DEF tank heater † ❑ Wire power supply (Tier 4 system heaters) §
Emergency Stop Switch ❑ Generator set emergency stop switch, qty. 1.
Note:
Not available with hurricane rated enclosures.
* Not available options with Tier 4 generator set enclosures.
† Only available on enclosed Tier 4 generator set enclosures.
§ Only available on open or enclosed Tier 4 generator sets.
Stepdown Transformers. 100 amp BEP required, 60 Hz only. KD1250-2500 only.*
❑ Single-phase, 120/240 V*
❑ Three-phase, 120/208 V *
Disconnect Switches. Disconnect switch for stepdown transformer. 60 Hz only. *
❑ Single-phase *
❑ Three-phase *
Enclosure Heater
Heater, 3.7/5 kW Ceiling Mounted. Electrical utility heater prewired to load center internal to enclosure. Rated at 17100 Btu. Includes adjustable louvers offering down flow and horizontal air tuning, built-in thermostat with automatic fan delay controls.
❑ Heater kit with 1 heater, single/three phase, 208/240 VAC, 60 Hz. BEP required.
❑ Heater kit with 2 heaters, for KD1250-2500 only, single/three phase, 208/240 VAC, 60 Hz. 200 amp BEP required.
Exhaust Fan
❑ Exhaust Ventilation Fan. Mounted inside the enclosure.
BEP required.
Motorized Inlet Louvers. 60 Hz only; BEP required.
❑ Aluminum construction ❑ Insulated aluminum construction ❑ Galvanized construction
Motorized Outlet Louvers. 60 Hz only; BEP required.
❑ Aluminum construction ❑ Insulated aluminum construction ❑ Galvanized construction
Gravity Air Outlet
❑ Aluminum construction
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2025 Discovery Energy, LLC - All rights reserved. 7/12
Subbase Fuel Tank
ADV-8927
Note: Sample model shown, other models are similar.
Emergency tank relief vents
Electrical stub-up areas open to bottom
Fuel level gauge with sender
Additional fittings for optional accessories
Check valve with dip tube assembly
Dip tube assembly
Fuel level gauge, mechanical
2 in. NPTF for optional fuel level switch
2 in. normal vent with riser
Fuel fill with lockable cap and 203 mm (8 in.) riser
Fuel basin Switch
Fuel Fill Options
❑ Fill pipe extension to within 152 mm (6 in.) of bottom of fuel tank
❑ 18.9 L (5 gallon) spill containment ❑ 18.9 L (5 gallon) spill containment with 95% shutoff ❑ 18.9 L (5 gallon) spill containment fill to within 152 mm (6 in.)
of bottom of fuel tank ❑ 18.9 L (5 gallon) spill containment, OSHPD/IBC ❑ 18.9 L (5 gallon) spill containment with 95% shutoff, OSHPD/IBC
❑ 28.4 L (7.5 gallon) spill containment, Florida Dept. of
Environmental Protection (FDEP) File No. EQ-345 approved ❑ 28.4 L (7.5 gallon) spill containment with 95% shutoff, Florida
Dept. of Environmental Protection (FDEP) File No. EQ- 345/EQ-257 approved
High Fuel Level Switch
❑ High fuel level switch, 24V ❑ High fuel level switch, 24V, Florida Dept. of Environmental
Protection (FDEP) File No. EQ-682 approved ❑ Fuel tank panel, 3 alarm, 24 V ❑ Fuel tank panel, 3 alarm, 24 V, Florida Dept. of Environmental
Protection (FDEP) File No. EQ-682 approved
Normal Vent Options
❑ 3.7 m (12 ft.) above grade (without spill containment) ❑ 3.7 m (12 ft.) above grade (with spill containment)
Freestanding Stairs
❑ Stairs only, single door access ❑ Stairs with platform, single door access ❑ Stairs with catwalk, 2 door access, door length only ❑ Stairs with catwalk, 2 door access, full length of enclosure
Tank Marking Options
❑ Decal, Combustible Liquids - Keep Fire Away (qty. 2) ❑ Decal, NFPA 704 identification (qty. 2) ❑ Decal, tank number and safe fuel fill height (qty. 2)
Subbase Fuel Tank Standard Features
• Extended operation. State tanks with various capacities for multiple hour requirements.
• UL listed. Secondary containment generator set base tank meeting UL 142 requirements.
• NFPA compliant. Designed to comply with the installation standards of NFPA 30 and NFPA 37.
• Integral external lift lugs. Enables crane with spreader-bar lifting of the complete package (empty tank, mounted generator set, and enclosure) to ensure safety.
• Emergency pressure relief vents. Vents ensure adequate venting of inner and outer tank under extreme pressure and/or emergency conditions.
• Normal vent with cap. Vent is raised above lockable fuel fill.
• Fuel level gauge with sender.
• Mechanical fuel level gauge.
• Leak detection switch. Annunciates a contained primary tank fuel leak condition at generator set control.
• Electrical stub-up area open to bottom.
• Additional 2 in. NPT fittings for optional accessories.
Subbase Fuel Tank Options
Bottom Clearance
❑ I-beams, provide 102 mm (4 in.) of ground clearance (not available with OSHPD or IBC seismic certification)
Emergency Vent Options
❑ 127 mm (5 in.), IBC ❑ 152.4 mm (6 in.), IBC KD800-1000 12 hr. tank only
Fuel in Basin Options
❑ Fuel in basin switch, Florida Dept. of Environmental Protection (FDEP) File No. EQ-682 approved
❑ 100% engine fluid containment
Fuel Supply Options
❑ Fire safety valve (installed on fuel supply line)
❑ Ball valve (installed on fuel supply line)
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2025 Discovery Energy, LLC - All rights reserved. 8/12
Enclosure and Subbase Fuel Tank Specifications
Fuel Tank Capacity, L (gal.)
Est. Fuel Supply
Hours at 60 Hz with Full Load
(nominal)
Max. Dimensions, mm (in.)
Max. Weight, † kg (lb.)
Fuel Tank Height, mm (in.)
Sound Pressure
Level at 60 Hz with Full
Load, dB(A) ‡ Length Width § Height
KD800 SL1 Sound Enclosure with Internal Silencer and State Code Subbase Fuel Tank *
Lifting Base 0 6582 (259)
2616 (103)
3350 (132) 10184 (22452) —
3475 (918) 12
7309 (288)
3706 (146) 13772 (30362) 356 (14.0)
6621 (1749) 24 3934 (155) 14252 (31421) 584 (23.0)
10573 (2793) 48 4264 (168) 14831 (32698) 914 (36.0)
15740 (4158) 72 9144 (360) 4366 (172) 16242 (35808) 1016 (40.0)
KD800 SL2 Sound Enclosure with Internal Silencer and State Code Subbase Fuel Tank *
Lifting Base 0 7707 (303)
2616 (103)
3350 (132) 10587 (23340) —
3475 (918) 12
8434 (332)
3706 (146) 14175 (31250) 356 (14.0)
6621 (1749) 24 3934 (155) 14655 (32309) 584 (23.0)
10573 (2793) 48 4290 (169) 15234 (33586) 915 (36.0)
15740 (4158) 72 9144 (360) 4366 (172) 16645 (36696) 1016 (40.0)
KD900 SL1 Sound Enclosure with Internal Silencer and State Code Subbase Fuel Tank *
Lifting Base 0 6582 (259)
2616 (103)
3350 (132) 10497 (23343) —
3475 (918) 12 7309 (288)
3706 (146) 14085 (31253) 356 (14.0)
6621 (1749) 24 3934 (155) 14565 (32312) 584 (23.0)
12969 (3426) 48 8400 (331) 4293 (169) 16348 (36243) 940 (37.0)
19381 (5120) 72 11050 (435) 4369 (172) 17527 (38840) 1016 (40.0)
KD900 SL2 Sound Enclosure with Internal Silencer and State Code Subbase Fuel Tank *
Lifting Base 0 7707 (303)
2616 (103)
3350 (132) 10900 (24231) —
3475 (918) 12
8434 (332)
3706 (146) 14488 (32141) 356 (14.0)
6621 (1749) 24 3934 (155) 14968 (33200) 584 (23.0)
12969 (3426) 48 4290 (169) 16751 (37131) 940 (37.0)
19381 (5120) 72 11050 (435) 4366 (172) 17930 (39728) 1016 (40.0)
KD1000 SL1 Sound Enclosure with Internal Silencer and State Code Subbase Fuel Tank *
Lifting Base 0 6582 (259)
2616 (103)
3350 (132) 10810 (23833) —
3475 (918) 12 7309 (288)
3706 (146) 14398 (31743) 356 (14.0)
6621 (1749) 24 3934 (155) 14878 (32802) 584 (23.0)
12969 (3426) 48 8400 (331) 4290 (169) 16661 (36733) 940 (37.0)
19381 (5120) 72 11050 (435) 4366 (172) 17840 (39330) 1016 (40.0)
KD1000 SL2 Sound Enclosure with Internal Silencer and State Code Subbase Fuel Tank *
Lifting Base 0 7707 (303)
2616 (103)
3353 (132) 11213 (24721) —
3475 (918) 12
8434 (332)
3706 (146) 14801 (32631) 356 (14.0)
6621 (1749) 24 3934 (155) 15281 (33690) 584 (23.0)
12969 (3426) 48 4290 (169) 17064 (37621) 940 (37.0)
19381 (5120) 72 11050 (435) 4366 (172) 18243 (40218) 1016 (40.0)
* Data in table is for reference only. Height includes enclosure, lift base, and tank (if equipped). Refer to your authorized Rehlko distributor for enclosure and subbase fuel tank specification details.
† Max. weight includes the generator set (wet) with the largest alternator option, enclosure, silencers, lift base, and tank (no fuel).
‡ Log average sound pressure level of 8 measured positions around the perimeter of the unit at a distance of 7 m (23 ft). Refer to TIB-114 for details. Enclosed generator set sound data for some models was not available at time of print.
§ An additional 940 mm (37 inches) of clearance on each side for opening and closing the access doors is recommended.
If the Est. Fuel Supply Hours column shows more than one number, the numbers represent each model in that range.
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Rectangle
Line
24V, 20A Battery Charger
G6-153_11/25c For the nearest sales and service, go to powersystems.rehlko.com. © 2025 Discovery Energy, LLC - All rights reserved. 1/2
The battery charger uses High Frequency charging technology.
The battery charger incorporates Power Factor Correction Circuitry to achieve high efficiency and a wide input range.
This filtered output unit is designed and built to charge VRLA (Gel- Cell, AGM), Flooded Lead Acid, and Nickel Cadmium batteries.
The battery charger is equipped with an LCD display showing DC Volts, DC Amps, and three status LEDs. Integrated Battery Charge Divider / Isolator provides connections for charging up to three independent batteries simultaneously.
Applicable to the following:
KD Model Generator Sets
Standard Features
• Microprocessor Controlled High Frequency Charging Technology
• Single Phase AC Input 105- 264VAC, 45- 65Hz
• LCD Display
• Charger Failure Alarm with LED Indicator and Form “C” Dry Type Relay Contact
• Adjustable Float Voltage
• AC to DC Isolation
• Filtering Suitable for VRLA Batteries
• Internal Temperature Compensation with Disable Option
• Input and Output Fuses
• Adjustable Current Limiting
• Meets NFPA 110 and C62.41A
• UL/cUL 1236 Listed
Front Panel Display
DC Output AC Input Overall Dimensions W x D x H
Shipping Weight
Volts (Nominal) Amps Volts (Nominal) Amps kgs lbs
24 20 105/264 5.0/2.45 243 x 116.1 x 403 mm
9.63 x 4.58 x 16.25 in
5.05 11.14
24V, 20A Battery Charger
G6-153_11/25c For the nearest sales and service, go to powersystems.rehlko.com. © 2025 Discovery Energy, LLC - All rights reserved. 2/2
Specifications
AC Input 105- 264 VAC, 45- 65 HZ, Single Phase
Nominal DC Output 20A @ 24 V
Regulation - Power Stage Only
Line: ± 10%
Load: <± 0.5%
Protection
Input: Fuse with surge and transient protection
Output: Fuse with surge protection
Reverse current polarity
Short circuit protection
Thermal: Shuts down when overheated
AC Over Voltage
Output Current Limit Factory set at 100%
Adjustable from 50-105%
Metering LCD DC Output Digital Voltmeter and Ammeter (1%)
Adjustable Voltage Range (Per Cell) 2.15-2.35 volts/cell (Lead)
1.39-1.49 volts/cell (NiCad)
Alarm Contacts Charger Failure (Form “C” Contact for Charger Failure)
Monitoring
LCD Display: Volts
Amps
LED Indications: Current Limit (Red)
AC ON (Green)
Charger Fail (Red)
Low Current (Red- Blinking)
Environmental
Operating: -20°C to 50°C (-4°F to 122°F) (Derated up to 70°C (158°F))
Storage: -40°C to 85°C (-40°F to 185°F)
Relative Humidity: 0% to 95% non condensing
Enclosure
Structural Design:
Cable Entry:
Wall Mounting / Powder coat finish Bottom
Standards USCG requirements
ANSI C62- 41
cUL
NFPA 110
Availability is subject to change without notice. Discovery Energy, LLC and its affiliates dba Rehlko reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Rehlko generator set distributor for availability.
Remote Serial Annunciator III (RSA III)
G6-139_11/25e For the nearest sales and service, go to powersystems.rehlko.com. © 2025 Discovery Energy, LLC - All rights reserved. 1/4 for Rehlko Controllers
• Monitors the generator set equipped with one of the following controllers:
APM402 Decision-Maker® 3000 APM603 Decision-Maker® 3500 APM802 Decision-Maker® 6000 Decision-Maker® 3+ Decision-Maker® 8000 Decision-Maker® 550 KPC 1000
• Allows monitoring of the common alarm, remote testing of the automatic transfer switch, and monitoring of the normal/emergency source for up to four ATS with any of the following controllers:
Decision-Maker® MPAC® 750, 1200, and 1500 MPAC® 1000 and 1500
• Configuration via a personal computer (PC) software.
• Writable surfaces (white boxes in illustrations) for user-defined selections.
• Uses Modbus® RTU protocol.
• Controller connections:
RS-485 for serial bus network USB port. Connect a personal computer and use SiteTech™ software to view events and adjust settings.
12-/24-volt DC power supply 120/208 VAC power supply (available accessory)
• Meets the National Fire Protection Association Standard NFPA 110, Level 1.
Dimensions
• Dimensions—W x H x D, mm (in.).
Surface Mounted:
203 x 203 x 83 (8.0 x 8.0 x 3.3)
Flush Mounted (Inside Wall):
203 x 203 x 76 (8.0 x 8.0 x 3.0) Flush mounting plate W1: 254 (10.0)
* SiteTech™ software is available to authorized distributors and dealers.
RSA III
RSA III with a Single ATS Control
RSA III with Four ATS Controls
W W
H
H
D
Surface Mounted
W1
Flush Mounted
D
Jack Kline Highlight
Jack Kline Highlight
Jack Kline Line
Jack Kline Line
Jack Kline Line
Jack Kline Line powersystems.rehlko.com. © 2025 Discovery Energy, LLC - All rights reserved. 2/4
Fault and Status Conditions Fault LEDs Fault Horn System Ready LED Generator
Running LED Communication
Status LED
Overcrank Shutdown Red On Red Off Green
High Engine Temperature Warning * Yellow On Red Green Green
High Engine Temperature Shutdown Red On Red Off Green
Low Oil Pressure Warning * Yellow On Red Green Green
Low Oil Pressure Shutdown Red On Red Off Green
Overspeed Shutdown Red On Red Off Green
Emergency Stop * Red On Red Off Green
Low Coolant Level/Aux. Shutdown Red On Red Off Green
Low Coolant Temperature * Yellow On Red Off Green
Low Cranking Voltage Yellow On Red Off Green
Low Fuel—Level or Pressure * Yellow On Red Green or Off Green
Not-In-Auto Red On Red Green or Off Green
Common Fault Red/Yellow On Green Green or Off Green
Battery Charger Fault (1) * Yellow On Red Green or Off Green
Battery Charger Fault (2) * Yellow On Green Green or Off Green
High Battery Voltage * Yellow Off Green Green or Off Green
Low Battery Voltage * Yellow Off Green Green or Off Green
User Input #1 (Warning) Yellow Off Green Green or Off Green
User Input #1 (Shutdown) Red On Green Off Green
User Input #2 (Warning) Yellow Off Green Green or Off Green
User Input #2 (Shutdown) Red On Green Off Green
User Input #3 (Warning) (1) [ Yellow Off Green Green or Off Green
User Input #3 (Shutdown) (1) [ Red On Green Off Green
User Input #4 (Warning) (1) Yellow Off Green Green or Off Green
User Input #4 (Shutdown) (1) Red On Green Off Green
User Input #5 (Warning) (1) Yellow Off Green Green or Off Green
User Input #5 (Shutdown) (1) Red On Green Off Green
EPS Supplying Load Yellow Off Green Green Green
Communications Status (Fault mode) — Off Green or Red Green or Off Red
ATS Fault (RSA III with ATS Controls only) Red On Red or Yellow Green or Off Green
Green LEDs appear as steady on when activated.
Yellow (common warning) LEDs slow flash when activated except steady on with EPS supplying load and high battery voltage.
Red (common fault) LEDs slow flash when activated except fast flash with loss of communication and not-in-auto.
powersystems.rehlko.com. © 2025 Discovery Energy, LLC - All rights reserved. 3/4
Specifications
• LED indicating lights for status, warning, and/or shutdown.
• Power source with circuit protection: 12- or 24-volt DC
• Power source with120/208 VAC, 50/60 Hz adapter
(option)
• Power draw: 200 mA
• Humidity range: 0% to 95% noncondensing
• Operating temperature range: -20°C to +70°C
(-4°F to +158°F)
• Storage temperature range: -40°C to +85°C
(-40°F to +185°F)
• Standards:
o NFPA 110, level 1 o UL 508 recognized o CE directive o NFPA 99 o ENS 61000-4-4 o EN6II-4-4 fast transient immunity
• RS-485 Modbus® isolated port @ 9.6/19.2/38.4/57.6 kbps (default is 19.2 kbps)
• USB device port
• NEMA 1 enclosure
(1) All generator set controllers except Decision-Maker®
3+ controller.
(2) Decision-Maker® 3+ controller only.
* May require optional kit or user-provided device to enable function and LED indication.
† Digital input #3 is factory-set for high battery voltage on the Decision-Maker® 3+ controller.
ATS Controls (RSA III with ATS controls only)
• ATS position LED (normal or emergency)
• Power source indicator LED (normal or emergency)
• ATS fault LED
• Key-operated lock/unlock switch for Test feature
• Test pushbutton
NFPA Requirements
• NFPA 110 compliant
• Engine functions:
o High battery voltage warning * o High engine temperature shutdown o High engine temperature warning * o Low battery voltage warning * o Low coolant level/aux. shutdown o Low coolant temperature warning * o Low cranking voltage o Low fuel warning (level or pressure) * o Low oil pressure shutdown o Low oil pressure warning * o Overcrank shutdown o Overspeed shutdown
• General functions:
o Audible alarm silence o Battery charger fault * o Lamp test o Master switch not-in-auto powersystems.rehlko.com. © 2025 Discovery Energy, LLC - All rights reserved. 4/4
Alarm Horn. Horn sounds giving a minimum 90 dB at
0.1 m (0.3 ft.) audible alarm when a warning or shutdown fault condition exists except on high/low battery voltage or EPS supplying load.
Alarm Silenced. Red LED on lamp test switch lights when alarm horn is deactivated by alarm silence switch.
Alarm Silence Switch. Lamp test switch quiets the alarm during servicing. The horn will reactivate upon additional faults.
ATS Fault. Red LED lights when ATS fails to transfer.
Battery Charger Fail. LED lights if battery charger malfunctions. Requires battery charger with alarm contact.
Battery Voltage Hi/Lo. LED flashes if battery or charging voltage drops below preset level. LED lights steady if battery voltage exceeds preset level.
Common Fault. LED lights when a single or multiple common faults occur.
Communication Status. Green LED lights indicating annunciator communications functional. Red LED indicates communication fault.
EPS Supplying Load. LED lights when the Emergency Power System (EPS) generator set is supplying the load (APM402, APM603, APM802, and Decision-Maker® 550, 3000, 3500, 6000, and 8000 controllers) or when transfer switch is in the emergency position (Decision-Maker® 3+ controller).
Emergency Stop. LED lights and engine stops when emergency stop is made. May require a local emergency stop switch on some Decision-Maker® 3+ controllers.
Generator Running. LED lights when generator set is in operation.
High Engine Temperature. Red LED lights if engine has shut down because of high engine coolant temperature. Yellow LED lights if engine coolant temperature approaches shutdown range. Requires warning sender on some models.
Accessories ❑ Power source adapter kit 120/208 VAC, 50/60 Hz.
❑ Modbus®/Ethernet converter GM41143-KP2 for serial to Ethernet communication.
❑ Communication module GM32644-KA1 or GM32644-KP1 is required with Decision-Maker® 3+ controllers.
Lamp Test (Switch). Switch tests all the annunciator indicator LEDs and horn.
Low Coolant Level/Aux. LED lights when engine coolant level is below acceptable range on radiator-mounted generator sets only. When used with a Decision-Maker® 3+ controller, the LED indicates low coolant level or an auxiliary fault shutdown.
Requires user-supplied low coolant level switch on remote radiator models.
Low Coolant Temperature. LED lights if optional engine block heater malfunctions and/or engine coolant temperature is too low. Requires prealarm sender on some models.
Low Cranking Voltage. LED lights if battery voltage drops below preset level during engine cranking.
Low Fuel (Level or Pressure). LED lights if fuel level in tank approaches empty with diesel models or fuel pressure is low on gas models. Requires customer-supplied switch.
Low Oil Pressure. Red LED lights if generator set shuts down because of insufficient oil pressure. Yellow LED lights if engine oil pressure approaches shutdown range. Requires warning sender on some models.
Not In Auto. LED lights when the generator set controller is not set to automatic mode.
Overcrank. LED lights and cranking stops if engine does not start in either continuous cranking or cyclic cranking modes.
Overspeed. LED lights if generator set shuts down because of overspeed condition.
System Ready. Green LED lights when generator set master switch is in AUTO position and the system senses no faults.
Red LED indicates system fault.
User-Defined Digital Inputs #1- #5. Monitors five digital auxiliary inputs (can be configured as warnings or shutdowns).
User-defined digital inputs are selected via the RSA III master for local or remote (generator set or ATS). The user-defined digital input can be assigned via PC using SiteTech™ setup software.
Fault and Status LEDs and Lamp Test Switch
Availability is subject to change without notice. Discovery Energy, LLC and its affiliates dba Rehlko reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local authorized generator set distributor for availability.
Model - KUS/KUP
Automatic Transfer Switches Contactor-Based Service Entrance
G11-153_9/24c
200 Twin Oaks Road, Kohler, WI 53044 USA
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 1/16
Controller
• Decision-Maker® MPAC 1500
Ratings
Model Current Voltage, Frequency
KUS 70-4000 amps 208-600 VAC 50/60 Hz KUP 150-4000 amps
Transfer Switch Standard Features
• UL 1008 listed (cULus) file #E58962 (automatic)
•…