This document provides specifications for a modular work/storage building to be leased by the 187th Fighter Wing Contracting Office of the Alabama Army National Guard. The specifications require a 40' x 60' shelter with a minimum 10' working height and 110 mph wind rating. The building must have 1.5" thick HDPE flooring throughout, insulated exterior walls, a roll-up door, personnel door, HVAC, electrical service including lighting and outlets, and an eyewash station. The related federal contract opportunity is solicitation W50S6N-21-Q-0002 seeking quotes to lease modular buildings and work space for the 187th Fighter Wing in Montgomery, Alabama.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix 5

Work/Storage Building Specifications – F-35 Transition

1.0 DIMENSIONS

Shelter Dimensions= 40’-0" X 60'-0". Dimensions are approximate and may vary, provided that an equivalent square footage is provided.

Minimum working height = 10’-0” Wing Speed = 110 mph

2.0 FLOORING

a. Provide flooring on top of existing pavements throughout facility, with the following properties:

· High-Density Polyethylene (HDPE)

· Minimum weight capacity of 200 psi

· Thickness minimum of 1.5 inches

· Flooring may be continuous or interlocking panels

· Ramp section is required at the roll-up door

3.0 WALLS & PARTITIONS

a. Exterior wall material will be at the contractor’s discretion. However, if the contractor chooses a material that can be easily intruded (i.e. fabric) then interior walls or fencing must be provided to make the storage area secure.

c. System will be secured to existing pavements, per manufacturer recommendations.

d. One (1) personnel access door.

e. One (1) 10’ x 10’ metal roll-up door.

f. Interior walls or fencing to provide a lockable area within the facility.

· 8’ minimum height

· One (1) interior double swing door or fence gate.

· See Drawings for interior walls and door/gate.

4.0 HVAC

a. Provide Heating, Ventilation, and Air Conditioning per manufacturer recommendations for the Montgomery, AL Region.

b. Provide ventilation fan with a minimum rating of 100 cfm. Ventilation fan will be installed approximately 8 feet above finished floor. Provide approximately 8 feet of 6 inch duct, capable of connecting to the ventilation fan and touching the finished floor.

5.0 INSULATION

Provide insulation per manufacturer recommendations for the Montgomery, AL region.

6.0 ELECTRICAL

a. Contractor is responsible for installing subpanel(s) and connecting to base infrastructure to provide electrical service to operate all systems in this contract. Transformers are shown in Appendix 1.

· Electrical connection to base infrastructure will be sole sourced to KWest Enterprises, LLC.

b. Combination lighted exit sign/emergency light with battery backup at each exterior door.

c. LED Light kit as required to provide minimum illumination of 20 foot-candles at a height of 2’-0” above finished floor.

d. Locate one empty junction box with conduit and pull string, within 12” of each standard receptacle for installation of structural cabling (by others).

e. Provide a minimum of ten (10) standard 110v receptacles (5 on each long wall, equally spaced).

7.0 ADDITIONAL

a. Provide and install one portable eye wash station, with the following requirements:

· Activates by gravity feed

· Capacity minimum of 7.0 gallons

· Provide eyewash solution per manufacturer recommendation