This is a National Environmental Balancing Bureau (NEBB) Certification test report documenting the existing air distribution and flow characteristics of the CR-1 & 2 System SUPPLY at the Hollings Marine Laboratory Cleanroom facility located on the 1st Floor Service area in Climax, NC. The report was prepared by Hahn-Mason Air Systems, Inc. on December 15, 2021, and includes terminal box flow hood measurements and register, grille, and diffuser test results across multiple cleanroom spaces.
The report measures actual existing conditions across six terminal box locations (C102, C103, C104, C105, D103, and D104) using flow hood instrumentation to quantify cubic feet per minute (CFM) and air changes per hour. Key measured flows include: C102 at 2,603 CFM (189.64 air changes), C103 at 32,488 CFM across multiple test sheets totaling approximately 32,488 CFM (282.44 air changes), C104 at 4,934 CFM (78.22 air changes), C105 at 5,067 CFM (75.07 air changes), D103 at 620 CFM (55.37 air changes), and D104 at 13,112 CFM (48.75 air changes). All diffusers tested are 24X48 inch HEPA-type units. The report includes system diagrams showing the spatial layout of the cleanroom spaces (Ante Room C102, Cleanroom C103, SRM Production C104, Cryomill C105, Ante Room D103, and Specimen Bank D104) and identifies that exhaust fans 3 & 4 at location C103 achieved 90-95% of design flow. The report explicitly states it reflects measured existing conditions only and that the contractor remains responsible for field verification of air distribution and conditions necessary for final sizing and selection of replacement air handling units per the Statement of Work.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 03 Amd 5 F.pdf | ||
| 03 Amd 4 F.pdf | ||
| 03 Amd 3 F.pdf | ||
| 03 Amd 3 Att G F.pdf | ||
| 03 Amd 2 Att F.pdf | ||
| 03 Amd 2.pdf | ||
| 03 Amd 1.pdf | ||
| 03 Amd 1 Att E.pdf | ||
| Sol Att A WD Charleston.pdf | ||
| Sol Att C SOW.pdf | ||
| Sol Att B DBA Charleston.pdf | ||
| Sol Att D Price Schedule.xlsx | XLSX spreadsheet | |
| 03 Sol F.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project:
Unit CR-1 & 2 System SUPPLY
Location 1st Floor Service Cleanroom
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc. 4289 Crooked
Creek Rd. Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
**This TAB reflects measured existing conditions and is being furnished for reference only. The Contractor shall remain responsible for field verification of the existing air distribution, controls, space relationships, and other conditions necessary for final sizing and selection of the replacement AHU in accordance with the SOW. PLEASE BE AWARE: The TAB report identifies the clean-room supply system collectively as CR-1 & 2 System SUPPLY, so it does not provide a clear room-by-room breakdown showing which individual AHU serves each space nor identify the exising AHU's orignal design flow therefore 13,112 CFM does not characterize the AHU's design CFM.**
Unit System
Location Service
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Text Box C102
Number Type %
C102 1 HEPA
C102 2 HEPA
C102 3 HEPA
C102 4 HEPA
C102 5 HEPA
C102 6 HEPA
Total 2603
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C102
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 430
24X48 N/S 448
Size (") Flow Flow Flow
24X48 N/S 449
24X48 N/S 418
24X48 N/S 431
24X48 N/S 427
Remarks: 2603 CFM / 823.54 Cubic Ft. x 60 = 189.64 Air Changes.
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Location Service
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita
C103
C103 1 HEPA
C103 2 HEPA
C103 3 HEPA
C103 4 HEPA
C103 5 HEPA
C103 6 HEPA
C103 7 HEPA
C103 8 HEPA
C103 9 HEPA
C103 10 HEPA
C103 11 HEPA
C103 12 HEPA
C103 13 HEPA
C103 14 HEPA
C103 15 HEPA
C103 16 HEPA
C103 17 HEPA
C103 18 HEPA
C103 19 HEPA
C103 20 HEPA
Total 6738
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C103
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 392
24X48 N/S 320
Size (") Flow Flow Flow
24X48 N/S 389
24X48 N/S 300
24X48 N/S 96
24X48 N/S 363
24X48 N/S 288
24X48 N/S 367
24X48 N/S 366
24X48 N/S 81
24X48 N/S 273
24X48 N/S 326
24X48 N/S 407
24X48 N/S 508
24X48 N/S 356
24X48 N/S 531
24X48 N/S 325
24X48 N/S 327
24X48 N/S 288
Remarks: 32,488 CFM / 6901.47 Cubic Ft. x 60 = 282.44 Air Changes.
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
24X48 N/S 435
C103 21 HEPA
C103 22 HEPA
C103 23 HEPA
C103 24 HEPA
C103 25 HEPA
C103 26 HEPA
C103 27 HEPA
C103 28 HEPA
C103 29 HEPA
C103 30 HEPA
C103 31 HEPA
C103 32 HEPA
C103 33 HEPA
C103 34 HEPA
C103 35 HEPA
C103 36 HEPA
C103 37 HEPA
C103 38 HEPA
C103 39 HEPA
C103 40 HEPA
Total 7962
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C103
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 339
24X48 N/S 485
Size (") Flow Flow Flow
24X48 N/S 373
24X48 N/S 321
24X48 N/S 410
24X48 N/S 445
24X48 N/S 284
24X48 N/S 356
24X48 N/S 516
24X48 N/S 394
24X48 N/S 333
24X48 N/S 375
24X48 N/S 352
24X48 N/S 284
24X48 N/S 427
24X48 N/S 492
24X48 N/S 494
24X48 N/S 375
24X48 N/S 569
Remarks:
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
24X48 N/S 338
C103 41 HEPA
C103 42 HEPA
C103 43 HEPA
C103 44 HEPA
C103 45 HEPA
C103 46 HEPA
C103 47 HEPA
C103 48 HEPA
C103 49 HEPA
C103 50 HEPA
C103 51 HEPA
C103 52 HEPA
C103 53 HEPA
C103 54 HEPA
C103 55 HEPA
C103 56 HEPA
C103 57 HEPA
C103 58 HEPA
C103 59 HEPA
C103 60 HEPA
Total 8650
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C103
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 505
24X48 N/S 510
Size (") Flow Flow Flow
24X48 N/S 591
24X48 N/S 352
24X48 N/S 495
24X48 N/S 334
24X48 N/S 320
24X48 N/S 514
24X48 N/S 367
24X48 N/S 504
24X48 N/S 523
24X48 N/S 406
24X48 N/S 522
24X48 N/S 331
24X48 N/S 370
24X48 N/S 360
24X48 N/S 330
24X48 N/S 487
24X48 N/S 479
Remarks:
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
24X48 N/S 350
C103 61 HEPA
C103 62 HEPA
C103 63 HEPA
C103 64 HEPA
C103 65 HEPA
C103 66 HEPA
C103 67 HEPA
C103 68 HEPA
C103 69 HEPA
C103 70 HEPA
C103 71 HEPA
C103 72 HEPA
C103 73 HEPA
C103 74 HEPA
C103 75 HEPA
C103 76 HEPA
C103 77 HEPA
C103 78 HEPA
C103 79 HEPA
C103 80 HEPA
C103 81 HEPA
C103 82 HEPA
Total 9138
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C103
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Size (") Flow Flow Flow
24X48 N/S 443
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 453
24X48 N/S 352
24X48 N/S 393
24X48 N/S 524
24X48 N/S 365
24X48 N/S 508
24X48 N/S 380
24X48 N/S 384
24X48 N/S 308
24X48 N/S 339
24X48 N/S 484
24X48 N/S 425
24X48 N/S 504
24X48 N/S 380
24X48 N/S 340
24X48 N/S 447
24X48 N/S 391
24X48 N/S 454
N/S 335
Remarks:
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
24X48 N/S 354
24X48
24X48 N/S 575
Location Service
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita
C104
C104 1 HEPA
C104 2 HEPA
C104 3 HEPA
C104 4 HEPA
C104 5 HEPA
C104 6 HEPA
C104 7 HEPA
C104 8 HEPA
C104 9 HEPA
C104 10 HEPA
C104 11 HEPA
C104 12 HEPA
Total 4934
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C104
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 315
24X48 N/S 424
Size (") Flow Flow Flow
24X48 N/S 373
24X48 N/S 460
24X48 N/S 313
24X48 N/S 365
24X48 N/S 448
24X48 N/S 434
24X48 N/S 430
24X48 N/S 573
24X48 N/S 427
24X48 N/S 372
Remarks: 4934 CFM / 3784.83 Cubic Ft. x 60 = 78.22 Air Changes.
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Location Service
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita
C105
C105 1 HEPA
C105 2 HEPA
C105 3 HEPA
C105 4 HEPA
C105 5 HEPA
C105 6 HEPA
C105 7 HEPA
C105 8 HEPA
C105 9 HEPA
C105 10 HEPA
C105 11 HEPA
C105 12 HEPA
C105 13 HEPA
Total 5067
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location C105
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 185
24X48 N/S 419
Size (") Flow Flow Flow
24X48 N/S 365
24X48 N/S 305
24X48 N/S 634
24X48 N/S 390
24X48 N/S 373
24X48 N/S 375
24X48 N/S 406
24X48 N/S 593
24X48 N/S 400
24X48 N/S 293
24X48 N/S 329
Remarks: 5067 CFM / 4049.98 Cubic Ft. x 60 = 75.07 Air Changes.
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Location Service
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita
D103
D103 1 HEPA
D103 2 HEPA
Total 620
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location D103
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 287
Size (") Flow Flow Flow
24X48 N/S 333
Remarks: 620 CFM / 671.82 Cubic Ft. x 60 = 55.37 Air Changes.
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Location Service
Page:Test Date:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
System Diagram
HOLLINGS MARINE LABORATORY CLEANROOM
hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita Engineer hmita
D104
D104 1 HEPA
D104 2 HEPA
D104 3 HEPA
D104 4 HEPA
D104 5 HEPA
D104 6 HEPA
D104 7 HEPA
D104 8 HEPA
D104 9 HEPA
D104 10 HEPA
D104 11 HEPA
D104 12 HEPA
D104 13 HEPA
D104 14 HEPA
D104 15 HEPA
D104 16 HEPA
D104 17 HEPA
D104 18 HEPA
D104 19 HEPA
D104 20 HEPA
Total 6814
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location D104
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 338
24X48 N/S 282
Size (") Flow Flow Flow
24X48 N/S 387
24X48 N/S 362
24X48 N/S 318
24X48 N/S 327
24X48 N/S 330
24X48 N/S 338
24X48 N/S 340
24X48 N/S 287
24X48 N/S 360
24X48 N/S 349
24X48 N/S 322
24X48 N/S 356
24X48 N/S 355
24X48 N/S 338
24X48 N/S 401
24X48 N/S 359
24X48 N/S 398
Remarks: 13,112 CFM / 16138.12 Cubic Ft. x 60 = 48.75 Air Changes.
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
24X48 N/S 267
D104 21 HEPA
D104 22 HEPA
D104 23 HEPA
D104 24 HEPA
D104 25 HEPA
D104 26 HEPA
D104 27 HEPA
D104 28 HEPA
D104 29 HEPA
D104 30 HEPA
D104 31 HEPA
D104 32 HEPA
D104 33 HEPA
D104 34 HEPA
D104 35 HEPA
D104 36 HEPA
D104 37 HEPA
D104 38 HEPA
D104 39 HEPA
D104 40 HEPA
Total 6298
Test Date: Readings By: Page:
Unit CR-1&2 System SUPPLY
Terminal Box - Location D104
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report (Flow Hood)
HOLLINGS MARINE LABORATORY CLEANROOM
Manufacturer - Test Instrument FLOW HOOD
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
24X48 N/S 306
24X48 N/S 320
Size (") Flow Flow Flow
24X48 N/S 299
24X48 N/S 373
24X48 N/S 367
24X48 N/S 332
24X48 N/S 327
24X48 N/S 314
24X48 N/S 307
24X48 N/S 306
24X48 N/S 298
24X48 N/S 147
24X48 N/S 324
24X48 N/S 327
24X48 N/S 303
24X48 N/S 268
24X48 N/S 285
24X48 N/S 433
24X48 N/S 356
Remarks:
15-Dec-21 K.Brewer / M.Dixon
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
24X48 N/S 306
Number Type Size (") AK VEL Flow VEL Flow VEL Flow %
C103 1 HOOD 62.5 x 18.5 8.03 156 1250 148 1188 95%
C103 2 HOOD 62.5 x 19.5 8.46 148 1250 133 1125 90%
Total
Test Date: Readings By: Page:
Report is not valid unless it is submitted with an accompanying NEBB Certification form stamped with a National Environmental Balancing Bureau Certification Seal
Remarks:
15-Dec-21 K.Brewer / M.Dixon
Manufacturer - Test Instrument VEL-GRID
Location or
Address
Register, Grille, Diffuser Design Preliminary Final
Unit EF'S 3&4 System EXHAUST
Terminal Box - Location C103
Hahn-Mason Air Systems, Inc.
4289 Crooked Creek Rd.
Climax, NC 27233
Register, Grille, Diffuser Test Report
HOLLINGS MARINE LABORATORY CLEANROOM
Untitled