13-12- Addendum 1 - PAR133709 Acord Ice Center Ammonia Condenser Replacement.pdf
PDF 2 MB Posted
- Solicitation number
- SLCo PAR133709 Acord Ice Center Ammonia Condenser Replacement - CONST
- Issued by
- Utah
About this file
This Addendum 1 document, issued by Architectural Nexus, Inc. on behalf of Salt Lake County for the Acord Ice Center Ammonia Condenser Replacement project located at 5353 W 3100 S, West Valley, Utah, addresses pre-bid questions and modifies the original construction documents. The addendum clarifies electrical requirements for Variable Frequency Drives (VFDs) and associated disconnects, specifically confirming NEMA 3R rating requirements and whether combination VFD/disconnect units or separate enclosures are acceptable. Additionally, it resolves questions regarding exhaust fan compliance for ammonia ventilation, confirming that fans must discharge vertically upward with a minimum velocity of 2500 ft/min and 30 air changes per hour, and removes the Area of Refuge/Area of Rescue signal system from the project scope. The addendum replaces eight drawing sheets (S101, M501, M601, EG001, EG002, EG003, EG005, EP401) and includes structural amendments requiring demolition of an existing ammonia diffusion tank vault lid with flowable concrete fill to 30 inches below grade, accounting for an estimated 1500-gallon vault capacity.
The document establishes that the electrical contractor (Division 26) is responsible for furnishing and installing combination VFD/disconnect units for the EF-9 exhaust fan motor, with detailed electrical specifications provided for 480V, 3-phase power systems rated at 460 volts. The revised mechanical drawings clarify EF-9 requirements including an upblast exhaust fan detail, while electrical drawings specify conductor sizing, raceway systems, grounding requirements, and protective device coordination in compliance with the National Electrical Code (NEC). The project encompasses HVAC equipment connections, structural modifications including footing and foundation work, and comprehensive mechanical and electrical installations with delivery of operations manuals and as-built drawings required upon substantial completion.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum Page 1 of 2
ADD #01
ARCHITECTURAL NEXUS, Inc archnexus.com
SALT LAKE CITY
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000
SACRAMENTO
930 R Street Sacramento, California 95811 T 916.443.5911
ISSUE DATE: September 4, 2026 RESPONSE TO: Pre-Bid Questions
PROJECT: Acord Ice Condensing Tower Replacement 5353 W 3100 S West Valley, UT 84120
OWNER: Salt Lake County 2001 S State St Salt Lake City, UT 84190
ARCHITECT’S
PROJECT #:
25019
PAGES: 2 + Attachments (8) = 10 Replaced attached drawings: S101, M501, M601, EG001, EG002, EG003, EG005, EP401 Replace attached specifications: NA Remove specification: NA Add attached specification: NA
This Addendum forms a part of the Contract Documents and modifies the original Bid Documents as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject the Bidder to disqualification. This Addendum includes all attachments noted, included herein by reference.
Q1: PRE-BID AMENDMENT QUESTIONS:
Q1.1 QUESTION: Are there specifications available for the VFDs? Based on the installation conditions, please confirm whether the VFDs and associated disconnects are required to be NEMA 3R rated.
A/E RESPONSE: Electrical drawings have been issued in this addendum to clarify.
Q1.2 QUESTION: Please clarify the EF-9 electrical requirements. Sheet EP101 circuits EF-9 to panel P1-33 as a
120V circuit, while the M601 mechanical schedule indicates 480V, 3-phase power.
Q1.3 QUESTION: Please confirm whether EF-9 requires a combination VFD/disconnect unit, or whether a separate disconnect and VFD enclosure are acceptable.
Q1.4 QUESTION: The EF-9 VFD shown on M401 appears to be located on the interior wall, and the details do not show a roof disconnect. Please clarify whether a roof-mounted disconnect is required and where it should be located.
Q1.5 QUESTION: Please confirm whether the electrical contractor is responsible for furnishing and/or installing the Area of Refuge/Area of Rescue signal system.
A/E RESPONSE: Area of Refuge/ Area of Rescue will be removed from the project.
Q1.6 QUESTION: Looking at the equipment schedule the exhaust fan shown is not compliant for ammonia, it is showing as a downdraft fan. Ammonia ventilation fans must discharge vertically upward with a minimal velocity of 2500 ft/min, and 30 air changes an hour. Please review and provide proper exhaust equipment
A/E RESPONSE: Reference attached mechanical drawings.
Addendum Page 2 of 2
DRAWING AMENDMENTS:
D1 Structural:
Item # Sheet(s) Drawing(s) Amendment
D1.01 S101 1 ADD: Note to demolish the vault lid and fill vault below tower with flowable concrete fill up to 30” below grade (frost depth).
Note: The existing ammonia diffusion tank (aka “vault”) capacity is an estimated 1500 gallons.
D2 Mechanical:
Item # Sheet(s) Drawing(s) Amendment
D2.01 M501 ADD: Clarified exhaust fan detail to upblast
D2.02 M601 ADD: Clarified EF-9 requirements
D3 Electrical:
Item # Sheet(s) Drawing(s) Amendment
D3.01 EG001 ADD: Sheet EG003 to sheet index
D3.02 EG002 ADD: Clarified specifications on sheets
D3.03 EG003 ADD: Entire sheet
D3.04 EG005 ADD: Clarified EF-9 electrical requirements
D3.05 EP401 ADD: Clarified EF-9 electrical requirements
Kevin Miller 801.924.5000 kmiller@archnexus.com 9.4.2026
Name Phone Email Date
99'-0"
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X1/4
5' -6
TY
P
2' -3
S-101
2'-6" 2'-6"
99'-0"
2' -3
2'
-3
10'-0"x5'-0"x18" MAT FOOTING
TOP AND BOT BAR: (7) #5 LONG
#5 AT 9"oc TRANS
S-501 TYP
EXTERIOR PAVING BY OTHERS
CJ
CJ
DEMOLISH THE VAULT LID. FILL
VAULT BELOW TOWER WITH
FLOWABLE CONCRETE FILL UP TO
30" BELOW GRADE (FROST DEPTH).
AFTER 7 DAYS, FOOTINGS MAY BE
POURED ON TOP OF FILL. IF VAULT
WALLS CONFLICT WITH FOOTINGS,
DEMOLISH THE WALL DOWN TO 30"
BELOW GRADE.
HSS10X6X1/4
H S
S1 0X
6X 1/
HSS10X6X1/4
H S
S1 0X
6X 1/
S-101
S-501 TYP
LEVEL 1
100'-0"
TOP OF FRAME
103'-0"
S-501
1 TYP
S-501
5 TYP
CONDENSER, SEE MECH DRAWINGS
CONNECTION OF CONDENSER
TO BE COORDINATED WITH
MEP
CONCRETE FOUNDATION NOTES MARKS AND SYMBOL LEGEND
1. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR
EXTERIOR CONCRETE WORK AT DOORS, SIDEWALKS, ETC.
2. SEE ARCHITECTURAL DRAWINGS FOR DIMENSIONS TO
COLUMNS, WALLS, SLAB EDGES, SLOPES, ELEVATIONS,
CURBS, DEPRESSIONS AND DRAINS.
3. SEE TYPICAL FOUNDATION DETAILS ON S-50X SHEET SERIES
FOR:
• STRUCTURAL FILL
• FROST COVER
• PIPES PARALLEL TO FOOTINGS
• PIPES PERPENDICULAR TO FOOTINGS AND WALLS
• SLAB CONSTRUCTION AND CONTROL JOINT
• REINFORCING AT SLAB DISCONTINUITIES
SECTION MARK
SHEET NUMBER
SHEET NUMBER
FRAME ELEVATION
FOOTING DESIGNATION
TOF ELEVATION
FTG EL
STEEL COLUMNor
CJ CONTROL JOINT
LATERAL FRAME MOMENT CONNECTIONSSTEEL NOTES
1. VERIFY SIZE, WEIGHT, AND LOCATION OF ALL MECHANICAL
UNITS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS.
COORDINATE OPENINGS WITH MECHANICAL, ELECTRICAL, AND
GENERAL CONTRACTORS.
2. FRAME MEMBERS TO BE G90 COMMERCIAL GRADE GALVANIZED
STEEL. WELDS MAY BE ACCOMPLISHED IN SHOP.
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
AGENCY APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
STAMP
/4
/2
:0
:1
P
M
A u to d e s k D o c s /2
S
L C o A c o rd
I c e C e n te r
C o n d e n s in g U n it r2
/2
S
L C o A c o rd I c e
C e n te r_ S
T
.r v t
FOOTING AND
FRAMING PLANS
AND
ELEVATIONS
Author
W
S W
E S
T V
A L
L E
Y C
IT
Y
U
T
S A
L T
L A
K E
C O
U N
T Y
260036
08.21.2026
A c o rd
I c e E v a p o ra ti v e
C o n d e n s e r R e p la c e m e n t
CONSTRUCTION
DOCUMENTS
S-101
Checker
S-101 SCALE: 1/2" = 1'-0"
1 FOOTING AND FOUNDATION PLAN
S-101 SCALE: 1/2" = 1'-0"
2 TOP OF FRAME
S-101 SCALE: 1/2" = 1'-0"
3 FRAME ELEVATION
LEVEL 01 KEYPLAN
A
AREA OF CONSTRUCTION
# Date Revision
1 09.04.20
Addendum 1
GilbertNichols Phil J Miller - Ut
FLOW
FLOW
PLAN
ELEVATION
FLOW
F
LO
W
PLAN
ELEVATION
NOTE:
ALL LINE SIZES AS PER REFRIGERATION SCHEMATIC.
DISCHARGE CONNECTION SUCTION CONNECTION
.0
.0
FLOW
DRAIN & EQUALIZING
LINE
F
LO
W
NOTE:
1. LINE SIZE AS INDICATED ON REFRIGERATION SCHEMATIC
2. R = NOMINAL RADIUS OF PIPE.
1 1/2 R
EVAPORATIVE
CONDENSER
12"
4"
TO HIGH PRESSURE
RECEIVER, MINIMUM
VERTICAL DROP 5'-0"
CONCENTRIC
REDUCER
LONG RADIUS
ELBOW
1/2" HAND EXPANSION VALVE
AIR PURGE
1/2" SERVICE VALVE
COPPER PIPE
INSULATED OR NON-INSULATED)
ANCHOR UNISTRUT TO WALL
20 MIL THICK PVC ISOLATION TAPE
(DUCT TAPE OR ELECTRICIAN TAPE ARE NOT ACCEPTABLE)
P1000 UNISTRUT
UNISTRUT PIPE CLAMP
CLAMP BOLT
WOOD JOIST
I-BEAM
CLAMP
S
EYE BOLTS
THRU-BOLT
ADJUSTABLE
PIPE STAND
WELDED STEEL
WALL BRACKET
TURNBUCKLE
TURNBUCKLE
U-BOLTS
U-BOLTS
U-BOLTS
U-BOLTS
ANGLE
ANGLE
INSERTS
CINCH ANCHORS
C
IN
C H
A N
C H
O R
S
STEEL OFFSET
WALL BRACKET
NOTE:
FIGURE NUMBERS ARE TYPICAL TO GRINNELL SUPPORT NUMBERS.
HANGER ROD ATTACHED TO
STRUCTURE ABOVE
PROVIDE RIB-LOCK INSULATION
PROTECTION SHIELD (FIGURE 168) FOR
INSULATED PIPING
(FIGURE CT-65 FOR COPPER TUBING)
PIPE INSULATION
NON-INSULATED
PIPE
INSULATED
PIPE
CLEVIS HANGER
(PROVIDE OVERSIZED HANGER FOR
INSULATED PIPING)
TYPE 1
ADJUSTABLE CLEVIS
HANGER
(FIGURE 260)
TYPE 1
ADJUSTABLE CLEVIS
HANGER
(FIGURE 260)
EXISTING BUILT UP
INSULATED ROOF
4"X4" REDWOOD
SLEEPER
CUT PIECE OF SINGLE PLY
ROOF MEMBRANE, 2" LARGER
THAN REDWOOD (ALL SIDES)
3/8"x2-1/2"x8" PLATE
WITH (2) 3/8"Ø EXPANSION
BOLTS 3" LONG (SIMILAR
CONNECTION AT WALL)
ROOF STRUCTURE
BELOW
SECURE REFRIGERANT
PIPING TO SUPPORTS
WITH "UNISTRUT" PIPE
CLAMP OR EQUAL
RUN INSULATION OF
SUCTION LINE THROUGH
CLAMP ASSEMBLY
18 GAUGE GALVANIZED
SHEET METAL COVER
INSULATION AROUND
SUCTION LINES
5/16"x1-1/4" FLAT
HEAD MACHINE
SCREW AND NUT
1/4
1/4
NOTE:
RUN STEEL COVER CONTINUOUS FROM
CONDENSING UNITS TO RISERS OR
PENETRATIONS AT BUILDING WALL.
1-5/8" P-1000 "UNISTRUT"
CHANNEL OR EQUAL (TYPICAL)
P-2626 "UNISTRUT"
NINETY DEGREE ANGLE
FITTING OR EQUAL
2"x2"x3/16" ANGLE
6"
TOP VIEW
FRONT VIEW SIDE VIEW
DESCRIPTION NOTESITEMS
A
B
C
D
E
F
G
CT-1235 TANK
21" THREADED MCPHEE LID (NON-VENTED)
4" PVC SPOOL FLANGE W/SS-EPDM DONKER BOLTS
4" PVC SPOOL FLANGE W/SS-EPDM DONKER BOLTS
2" PVC SPOOL FLANGE W/SS-EPDM DONKER BOLTS
1" FNPT PVC TANK ADAPTER WITH PVC FLANGE ADAPTER
GRADUATED ADHESIVE STRIP
NOTES:
1. TANK IS MANUFACTURED TO ASTM-D-1998 STANDARD.
2. ALL DIMENSIONS ARE APPROXIMATE.
A
D
G
B
E
F
C
180°
90°270°
0°
C B
A
E
G
ALUMINUM PIPE
COVERING,
EXPOSED PIPE ONLY.
EXISTING
RIGID INSULATION
NOTE:
ROOFER TO FLASH, SEAL FLASHING IN PLACE
EXISTING
STEEL DECKING
BUILT UP ROOFING
MATERIAL
20 GAUGE GALVANIZED
FLASHING COLLAR
20 GA. GALVANIZED
FLASHING ANGLE
DRAW BAND
WELD PIPE CLAMP
TO ANGLE SUPPORT 1 1/2" x 1 1/2" x 1 1/4"
ANGLE SUPPORT
EXTERIOR WALL,
SEE ARCHITECTURAL
DETAILS FOR WALL TYPE,
THICKNESS, ETC.
CAULK & SEAL
ALL AROUND
ALUMINUM MESH
BIRD SCREEN
DRAINABLE LOUVER
APPROPRIATE MOUNTING
AND SILL SELECTED
ACCORDING
TO WALL CONSTRUCTION
EXTERIOR WALL
DRAINABLE FRAME
AND SILL
CAULK & SEAL
ALL AROUND
PLENUM
SHEET METAL COVER PROVIDE WEATHER
TIGHT SEALANT AT
ALL PIPE
PENETRATIONS
PLENUM
SHEET
METAL
COVER
CUT /
REMOVE
LOUVER
PIPE
12" MIN.
MOTORIZED BACKDRAFT
DAMPER
FLASH AND
COUNTERFLASH
ROOF CURB
INSULATION
SUPPORT ANGLE FOR
DAMPER ATTACHED
TO CURB
ROOF MEMBRANE
DECK
EXHAUST DUCT
SEE PLANS FOR
SIZE
CANT
STRIP
DOME EXHAUST FAN
OR ROOF HOOD
W/BIRD SCREEN
NOTE:
EXHAUST FAN TO BE MOUNTED LEVEL
OVER ROOF CURB DESIGNED FOR
PITCHED ROOF WHERE REQUIRED.
Project #: 250382
L I C
E N
S E
D
P
ROFESS IONA
L
E N
G I N
E E
R
No. 4775391-2202
S
T A
T E OF U
TA
H
SPENCER W.
HOWELL
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
AGENCY APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
08.21.2026
/4
/2
:0
:0
P M
A u to d e s k D o c s /2
S L
C o A c o rd I c e
C e n te r
C o n d e n s in g U n it r2 /2
S L
C o
A c o rd E v a p C o n d e n s e r
R e p la c e m e n t_
M E
C H v
.r v t
MECHANICAL
DETAILS
JN
W
S W e s t
V a ll e y C it y U
T
S A
L T
L A
K E
C O
U N
T Y
25019
08.31.2026
A c o rd
I c e E v a p o ra ti v e
C o n d e n s e r R e p la c e m e n t
CONSTRUCTION
DOCUMENTS
M501
GR
NOT TO SCALEM501
1 TYPICAL COMPRESSOR SUCTION & DISCHARGE HEADER CONNECTIONS DETAIL
NOT TO SCALEM501
2 DISCHARGE RISER TRAP DETAIL
NOT TO SCALEM501
3 REFRIGERANT CONNECTIONS AT EVAPORATIVE CONDENSTER DETAIL
NOT TO SCALEM501
4 PIPE SUPPORT DETAIL
NOT TO SCALEM501
5 PIPE SUPPORT DETAIL
NOT TO SCALEM501
6 SINGLE PIPE CLEVIS HANGER
NOT TO SCALEM501
7 REFRIGERANT PIPE SUPPORT ON ROOF
NOT TO SCALEM501
8 DIFFUSION TANK DETAIL
# Date Revision
1 9.4.2026 ADDENDUM 1
NOT TO SCALEM501
10 SINGLE PIPE ROOF PENETRATION DETAIL
NOT TO SCALEM501
11 PIPE THROUGH LOUVER
NOT TO SCALEM501
9 UP BLAST EXHAUST FAN DETAIL
Project #: 250382
L I C
E N
S E
D
P
ROFESS IONA
L
E N
G I N
E E
R
No. 4775391-2202
S
T A
T E OF U
TA
H
SPENCER W.
HOWELL
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
AGENCY APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
08.21.2026
/4
/2
:0
:5
P M
A u to d e s k D o c s /2
S L
C o A c o rd I c e
C e n te r
C o n d e n s in g U n it r2 /2
S L
C o
A c o rd E v a p C o n d e n s e r
R e p la c e m e n t_
M E
C H v
.r v t
MECHANICAL
SCHEDULES
JN
W
S W e s t
V a ll e y C it y U
T
S A
L T
L A
K E
C O
U N
T Y
25019
08.31.2026
A c o rd
I c e E v a p o ra ti v e
C o n d e n s e r R e p la c e m e n t
CONSTRUCTION
DOCUMENTS
M601
GR
7. PROVIDE ACCESS DOORS INTO DISCHARGE PLENUM.
6. PROVIDE SELF SUPPORTING SERVICE PLATFORMS WITH LADDERS.
5. PROVIDE WITH OVERSIZED ACCESS DOORS
4. PROVIDE LOW SOUND FANS.
3. PROVIDE WITH COMBINATION VFD AND DISCONNECT FOR FAN MOTOR, INSTALLED BY DIV. 26.
2. PUMP MOTOR, FAN AND SUMP HEATER REQUIRE SEPARATE ELECTRICAL CONNECTIONS.
1. JOB SITE ELEVATION IS 4,500 FEET ABOVE SEA LEVEL
EC-1 EVAPCO LSC-240E BLOW THRU R717 3,600 37,200 95 66 345 2 1 460/3/60 4 20 1 460/3/60 8 460/3/60 84 / 127.125 / 143.5 11,500 1 2 / 2 1-7
ID MANUFACTURER NUMBER (2) TYPE. REFRIG MBH (1) CFM (°F) (°F) (GPM) (HP) PUMP PHASE/HZ FANS HP MOTOR PHASE/HZ KW PHASE/HZ (IN) (LBS) (IN) (IN) NOTES
MODEL CAPACITY AIR TEMP WB RATE PUMP SPRAY VOLTS/ NO. OF MOTOR FAN VOLTS/ VOLTS/ WIDTH WEIGHT SIZE SIZE
TOTAL TOTAL CONDENSING ENTERING FLOW SPRAY QUANITY ELECTRICAL FAN QUANITY ELECTRICAL HEIGHT / OPERATING CONNECTION CONNECTION
WATER LENGTH / HEIGHT / WATER OVER FLOW / DRAIN
PUMP FAN SUMP HEATER PHYSICAL
EVAPORATIVE CONDENSING UNIT SCHEDULE - WATER COOLED
3. COMBINATION VFD / DISCONNECT PROVIDED AND INSTALLED BY DIV. 26.
2. PROVIDE WITH 14" TALL CURB, HINGE MOUNT AND LATCH, 115V / 1PH MOTORIZED DAMPER (DAMPER TO OPEN WHEN FAN IS OPERATING), SPARK RESISTANCE - SPARK B, EXPLOSION PROOF MOTOR, AUTOMATIC BELT TENSIONER, ALUMINUM RUB RING, ALUMINUM WHEEL, EXTENED BEARING LUBE LINE.
1. PERFORMANCE LISTED IS AT 4,500 FEET ELEVATION.
EF-9 GREENHECK CUBE-099-4 ROOF BELT DRIVE, UPBLAST EXHAUST 530 0.5 1282 50 0.25 0.11 1725 460 / 60 / 3 24.88ø / 40.09 105 6.5 REFIGERANT ALARM 1,2,3
ID MODEL NUMBER LOCATION TYPE TYPE (CFM) (IN. WATER) (RPM) (%) (HP) (HP) (RPM) VOLT/PH/HZ (IN) (LBS) SONES CONTROLS NOTES
AND AIR RATE PRESSURE SPEED EFFICIENCY SIZE BHP SPEED HEIGHT WEIGHT
MANUFACTURER AIRFLOW STATIC FAN STATIC MOTOR MOTOR MOTOR WIDTH/
MAXIMUM LENGTH/
AIR ELECTRICAL PHYSICAL
FAN SCHEDULE
1. CUSTOM TANK. REFERENCE DETAIL SHEET FOR ADDITIONAL REQUIREMENTS.
DT-1 ACO CONTAINER SYSTEMS CT-1235 SEE PLAN AMMONIA DIFFUSION 1235 1483 1482 64 / 119 12,360 1
ID MANUFACTURER MODEL NUMBER LOCATION USE ( IMP. GAL) ( US GAL) (GAL) (IN) (LBS) NOTES
VOLUME VOLUME VOLUME HEIGHT WEIGHT
TOTAL TOTAL REQUIRED DIAMETER /
TANK TANK
PHYSICAL
DIFFUSION TANK SCHEDULE
# Date Revision
1 9.4.2026 ADDENDUM 1
EV EV
DO
TV
J
FB PT
#-a
LC
J
#-a
X##
TC
CR
D
F
VFD
M
XX
EXIT SIGNAGE
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
WALL-MOUNTED FIXTURES, TYPICAL
(VARIOUS SYMBOLS)
LINEAR, CEILING MOUNTED LIGHT FIXTURE
(VARIOUS DIMENSIONS, DOTS INDICATE PENDANT
MOUNT)
RECESSED DOWNLIGHT FIXTURE
CHEVRON INDICATES WALL WASH
DIRECTIONAL LIGHT, TRACK OR FLOOD LIGHT
LINEAR LIGHT, TAPE LIGHT
LIGHTING FIXTURE SYMBOLS LEGEND
NOTE:
1. SWITCH IDs ARE UNIQUE PER SPACE.
2. ID TAGS MAY BE USED ON CONTROL DEVICES OTHER THAN SWITCHES, SUCH AS OCCUPANCY
SENSORS, POWER PACKS OR ROOM CONTROLLERS.
3. ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING FIXTURE INDICATES FIXTURE IS
CONTROLLED BY THE ONLY SWITCH IN THE SPACE.
4. AN "x" IN PLACE OF THE SWITCH DESIGNATION INDICATES UNSWITCHED.
a
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
CEILING 1, 2, 4
CEILING
AS NOTED
AS NOTED
WALL/CEILING
WALL/CEILING
1, 2
1,2
1, 2, 14
1, 2
1, 3, 5, 7, 12
1, 3, 5, 7, 12
POWER SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
S
WALL MOUNTED RECEPTACLE
SWITCHED RECEPTACLE
EMERGENCY RECEPTACLE
GROUND FAULT RECEPTACLE
RECEPTACLE MODIFIERS:
##": HEIGHT AFF O.C.
WP: WEATHERPROOF W/ IN-USE COVER
T: TAMPER-PROOF
U: RECEPTACLE WITH USB OUTLET
G: GROUND FAULT PROTECTED @ BREAKER
H: HOSPITAL GRADE
18"
18"
D Q SP
18"
18"
RECEPTACLE (SPECIFIC HEIGHT)
ISOLATED GROUND RECEPTACLE
7, 25, 30
7, 8
18"
SWITCH MODIFIERS:
K: KEYED
T: TIMER
M: MANUAL STARTER THERMAL
OVERLOAD SWITCH
EMERGENCY POWER OFF PUSH BUTTON
DOOR OPENER PUSH PLATE
ELECTRICAL POWER METER
FUSED DISCONNECT SWITCH
TOMBSTONE RECEPTACLE
CORD REEL, DEVICE VARIES
CORD DROP, DEVICE VARIES
MULTI-OUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
SINGLE / DUAL PORT ELECTRICAL VEHICLE
CHARGER
POWER POLE
NON-FUSED DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC STARTER WITH FUSED DISCONNECT
PUSHBUTTON
VARIABLE FREQUENCY DRIVE
TRANSFORMER:
SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &
REQUIREMENTS.
GENERAL LEGEND
SYMBOL DESCRIPTION NOTES
SOLID ARCHED LINES INDICATE UNSWITCHED
POWER CIRCUITING
DASHED ARCHED LINES INDICATE SWITCHED
POWER CIRCUITING
ONE CIRCUIT, HOME RUN TO PANEL
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
4" CONCRETE
BASE
POWER DISTRIBUTION PANEL 6'-6" TO TOP
FLUSH PANELBOARD 6'-6" TO TOP
SURFACE PANELBOARD 6'-6" TO TOP
TWO CIRCUITS, HOME RUN TO PANEL -
THREE CIRCUITS, HOME RUN TO PANEL -
CONDUIT RUN CONCEALED IN FLOOR OR GROUND -
CONDUIT RUN CONCEALED IN WALL OR CEILING -
CONDUIT UP -
CONDUIT DOWN -
CONDUIT STUB LOCATION CAP CONDUIT
CONDUIT / CIRCUIT CONTINUATION -
GROUND BUS BAR
CABLE TRAY
SOLID BOTTOM
LADDER
BASKET
MOUNTING
AS NOTED
7+18"
EQUIPMENT CEILING RACK
EQUIPMENT CABINET/RACK
EQUIPMENT 2-POST CABINET/RACK
TELEPHONE DEMARCATION BOARD +18"
FLOOR 18,
SEE SPEC.
WALL / FLOOR 18,
SEE SPEC.
CEILING
EXISTING --
DEMO --
TEMPORARY --
NEW --
CONDUIT
OHP: OVERHEAD POWER SERVICE
UGP: UNDERGROUND POWER
SERVICE
UGF: UNDERGROUND FIBER
SERVICE
TEL: TELEPHONE SERVICE
POWER DISTRIBUTION EQUIPMENT SYMBOLS
CIRCULAR, CEILING MOUNTED LIGHT FIXTURE
CENTER DOT INDICATES PENDANT
CEILING 1, 2, 4
CONTROLLED RECEPTACLE 7, 8+18" OR AS
NOTED
SPD PROTECTED RECEPTACLE 7+18" OR AS
NOTED
TIME CLOCK +48"
NOT IN CONTRACT --
MAGNETIC STARTER WITH BREAKER DISCONNECT
MOTOR
CEILING MOUNTED RECEPTACLE CEILING
TV BACKBOX FLAT PANEL
HEIGHT +12"
EMERGENCY LIGHTING UNIT, INTEGRAL BATTERY WALL/CEILING 1, 2, 3, 7
CW W: WALL C: CEILING
LIGHTING TAGS LEGEND
NOTES:
1. HATCHED FILL INDICATES SWITCHBOARD OR POWER
DISTRIBUTION PANEL.
2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH & DEPTH).
4. DOOR INDICATES FRONT OF RECESSED PANEL.
H P
1A
LP
1A
M D
P
SB1
POWER TAGS LEGEND
GENERAL LEGEND
SYMBOL DESCRIPTION NOTESMOUNTING
KEYNOTE
ROOM NAME & NUMBER
DIAGRAM TAG
MATCH LINE TAG
ROOM NAME & NUMBER W/ ZONE I.D.
JUNCTION BOX
x
EXIT SIGNAGE WITH AUXILIARY HEAD
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
AS NOTED S: SIMPLEX D: DUPLEX
Q: FOURPLEX SP: SPECIAL PURPOSE
FLOOR BOX / POKE-THRU
- SEE SCHEDULE FOR TYPE INFORMATION
AREA LIGHT POLE & FIXTURE
POST-TOP LIGHT POLE & FIXTURE
BOLLARD LIGHT
ARROWS INDICATE DIRECTION
SWITCH
SWITCH MODIFIERS:
3: 3-WAY
4: 4-WAY
K: KEYED
D: DIMMING
T: TIMER
P: SWITCH W/ PILOT LIGHT
CONCRETE
BASE
CONCRETE
BASE
CONCRETE
BASE
LIGHTING CONTROL SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
46"
1, 14
REFER TO DIA
1, 14
REFER TO DIA
1, 14
REFER TO DIA
6, 7
STEP LIGHT FIXTURE AS NOTED 1,7
IN-GRADE LIGHT FIXTURE AS NOTED 1
MOMENTARY CONTACT SWITCH 46" 6, 7, 27
LOW VOLTAGE WALL STATION
(SUBSCRIPT INDICATES CONFIGURATION)
46" 6, 7
CEILING FAN CEILING 1
LIGHTING CONTACTOR
LIGHTING CONTROL TOUCH SCREEN
WALL
46"
SENSORS/SWITCHES:
PC: PHOTO-ELECTRIC CONTROL
OS: OCCUPANCY SENSOR SWITCH
DL: DAYLIGHT HARVESTING SENSOR
AS NOTED 6, 7, 27
6, 7
6, 7
SWITCH PACKS:
AP: AUXILIARY PACK
PP: POWER PACK
ABOVE
CEILING
CONTROL:
RC: DIGITAL ROOM CONTROLLER
(SUBSCRIPT = NUMBER OF RELAYS)
EP: EMERGENCY LIGHTING CONTROL
UNIT
ABOVE
CEILING
REFER TO DIA
AND SPEC GROUND ROD
GROUND ROD WITH TEST WELL
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR SPLICE
STATIC GROUND RECEPTACLE
GROUNDING AND LIGHTNING PROTECTION SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTED -
CW W: WALL C: CEILING
EQUIPMENT SYSTEM PANELS
ACS: ACCESS CONTROL PANEL
IDS: INTRUSION DETECTION PANEL
PSP: POWER SUPPLY PANEL
RP#: LIGHTING PANEL
DAS: DISTRIBUTED ANTENNA SYSTEM
ERCCS: FIRST RESPONDERS RADIO SYSTEM
CATV: CABLE TV CONTENT EQUIPMENT
7, 8, 13
CEILING
CEILING
+46"OR AS
NOTED
7, REFER TO
SPEC
+46" 7
+46" 7
9, 10
9, 10, 11
+72" TO TOP
+60" TO TOP
18, SEE SPEC.
7, 22
Space
Space
XX
A a
FIXTURE ID (UPPERCASE UNDERLINED LETTER)
PANEL ID (NUMBERS & UPPERCASE LETTERS) - CIRCUIT NUMBER
RELAY ID (UPPERCASE LETTERS)
FIXTURE CONTROL ZONE ID (LOWERCASE LETTER)
#: INDICATES SWITCH TYPE
LOWERCASE LETTER: INDICATES SWITCH ID
DEVICES WITH A CHEVRON INDICATE TO
COORDINATE WITH MILLWORK PRIOR TO ROUGH-IN.
ELEVATION TAG. HATCHED AREA INDICATES
WHICH WALL, NUMBER INDICATES VIEW, AND
CENTER NUMBER INDICATES WHICH SHEET.
REVISION CLOUD DELTA. SHOWN WITH CLOUD
AND INDICATES A CHANGE PER THE TITLE BLOCK.
TAG FOR MECHANICAL, KITCHEN, AND SHOP
DEVICES. REFER TO SCHEDULES FOR INFO.
EF-XX
EMERGENCY EGRESS LIGHT FIXTURE CEILING 1, 2, 3, 4
CRITICAL EGRESS LIGHT FIXTURE CEILING 1, 2, 3, 4
9, 10, 11
9, 10, 11
+46" 7
9, 10
+46" 7
+60" TO TOP
+60" TO TOP
+60" TO TOP
+60" TO TOP
+60" TO TOP 9, 10, 11
+60" TO TOP
FLOOR
AS NOTED 20
25, 30
+46" 7
COUNTER TOP
MATCH LINE
SEE -/---
181 E 5600 S, Ste #200
Murray, UT 84107
(801) 530-3148 | www.resolutgroup.com
Resolut Project #: 250382
Electrical PM: SYDNEE ANDERSON
L I C
E N
S E
D
PROFESS I ONAL
E N
G I N
E E
R
S
TA T E O F U TA
H
No. 9075170
Lewis Wong
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
AGENCY APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
STAMP
/4
/2
:3
:1
P M
A u to d e s k D o c s /2
S
L C o A c o rd I c e
C e n te r
C o n d e n s in g U n it r2
/2
S
L C o
A c o rd E v a p C o n d e n s e r
R e p la c e m e n t_ E
L E
C v
.r v t
ELECTRICAL
TITLE SHEET
SA
W
S W e s t
V a ll e y C it y U
T
S a lt L a k e C o u n ty
250382
08/21/2026
S L
C o
A c o rd E v a p C o n d e n s e r
R e p la c e m e n t
CONSTRUCTION
DOCUMENTS
EG001
LW
ELECTRICAL ABBREVIATIONS INDEX
ABBREV. DESCRIPTION
A AMPS
AC ALTERNATING CURRENT
ACLG ABOVE CEILING
ADC ANALOG-TO-DIGITAL
CONVERTER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFF / A.F.F. ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AM AMPS METER
AMP AMPERE
AMPL AMPLIFIER
ANN ANNUNCIATOR
AOE AUDIO-OVER-ETHERNET
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIOVISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BC BARE COPPER
BD BOARD
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
BPM BEATS-PER-MINUTE
C, CND CONDUIT
C.O. CONDUIT ONLY
C/W COMPLETE WITH
CAB CABINET
CAT CATEGORY CABLE
CAT# CATALOG
CATB COMMUNITY ANTENNA
TELEVISION
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CF CREST FACTOR
CKT CIRCUIT
CLG CEILING
CMPR COMPRESSOR
CNTR CONTRACTOR
CO CONDUIT ONLY
CODEC CODER-DECORDER
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONV CONVECTOR
CP CIRCULATING PUMP
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
CV CONSTANT VOLTAGE
DAC DIGITAL-TO-ANALOG
CONVERTER
DB DECIBEL
DBFS DB REF. FULL SCALE
DBM DB REF. 0.001 WATT
DBU DB REF. 0.775 V
DBV DB REF. 1 V
DC DIRECT CURRENT
DCP DOMESTIC CIRCULATING PUMP
DED DEDICATED
DEPT DEPARTMENT
DET DETAIL
DFA DROP FROM ABOVE
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DR DYNAMIC RANGE
DS DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EG EMERGENCY GENERATOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY/EGRESS BATTERY
EMI ELECTRO-MAGNETIC
INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
ENT ELEC. NON-METAL. TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
ER EXISTING TO BE RELOCATED
ES SOURCE VOLTAGE
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FABP FIRE ALARM BOOSTER PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FCU FAN COIL UNIT
FIR FINITE IMPULSE RESPONSE
FILTER
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FMC FLEXIBLE METAL CONDUIT
FU FUSE
FUDS FUSE SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GRND. ELEC. COND. AT SES
GEN GENERATOR
GFCI GROUND FAULT CURRENT
INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
ABBREV. DESCRIPTION
GRC GALVANIZED RIGID CONDUIT
GYP BD GYPSUM BOARD
HOA HAND-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSE POWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING & AIR
CONDITIONING
HZ HERTZ
I/W INTERLOCK WITH
IC INTERRUPTING CAPACITY
IFC INTERNATIONAL FIRE CODE
IG ISOLATED GROUND
IIR INFINITE IMPULSE RESPONSE
FILTER
IMC INTERMEDIATE METALLIC
CONDUIT
INCAND INCANDESCENT
IR INFRARED
IT TOTAL CURRENT
J-BOX JUNCTION BOX
KCMIL 1000 CIRCULAR MILS (MCM)
KHZ THOUSANDS OF HZ
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
KWH KILOWATT HOUR
LCS C-WEIGHTED SLOW SOUND
LEVEL
LEQ EQUIVALENT SOUND LEVEL
LFMC LIQUID-TIGHT FLEX.
METAL. COND.
LFNC LIQUID-TIGHT FLEX. NON-METAL.
COND.
LOC LOCATE OR LOCATION
LP, SPL SOUND PRESSURE LEVEL
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LU LOUDNESS UNIT METERING
LUFS LOUDNESS UNIT FULL SCALE
LV LOW VOLTAGE
M/C MOMENTARY CONTACT
MAC MEDIA ACCESS CONTROL
MAG.S MAGNETIC STARTER
MAX MAXIMUM
MB MAIN BUS
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MEP MECHANICAL, ELECTRICAL, AND
PLUMBING
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MNF MANUFACTURER
MOA MULTI-OUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MSS MOTOR STARTER SWITCH
MTG MOUNTING
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
N NEW
N.I.C. NOT IN CONTRACT
N/A NOT APPLICABLE
N1 NEMA 1
N3R NEMA 3R
NAC NOTIFICATION APPLIANCE
CIRCUIT PANEL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT.
MANUFAC. ASSOC.
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NFPA NATIONAL FIRE PROTECTION
ASSOC.
NL NIGHT LIGHT, BYPASS LOCAL
SWITCHING
NO NORMALLY OPENED
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
OC ON CENTER
OH OVERHEAD
OL OVERLOADS
OS & Y OUTSIDE SCREW & YOKE
OSI OPEN SYSTEM INTEGRATION
PA PASCAL
PB PUSHBUTTON
PBB PRIMARY BONDING BUSBAR
PC PLUMBING CONTRACTOR
PCM PULSE CODE MODULATION
PDU POWER DISTRIBUTION UNIT
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PIV POST INDICATING VALVE
PLEN PLENUM
PNL PANEL
POC POINT OF CONNECTION
POE POWER OVER ETHERNET
POS POINT OF SALE
PP POWER POLE
PPM PEAK PROGRAM METER
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PSI POUNDS-PER-SQUARE-INCH
PT POTENTIAL TRANSFORMER
PTP POINT TO POINT
PTZ PAN, TILT, AND ZOOM
ABBREV. DESCRIPTION
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
QUAN QUANTITY
R RESISTANCE
RECEP, RECPT RECEPTACLE
REQ,REQD REQUIRED
REX REQUEST TO EXIT
RF RADIO FREQUENCY
RFM ROOF MOUNTED
RL LOAD RESISTANCE
RLA RATED LOAD AMPS
RM ROOM
RMC RIGID METALLIC CONDUIT
RMP ROCKY MOUNTAIN POWER
RMS ROOT MEAN SQUARE
RNC RIGID NON-METALLIC COND.
RPM ROTATIONS-PER-MINUTE
RS SOURCE RESISTANCE
RT TOTAL RESISTANCE
RTU ROOF TOP UNIT
RX RECEIVER
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SBB SECONDARY BONDING BUSBAR
SBG SUPPLEMENTARY BONDING
GRID
SBJ SYSTEM BONDING JUMPER
SC SURFACE CONDUIT
SCA SHORT CIRCUIT AMPERES
SDI SERIAL DIGITAL INTERFACE
SE SERVICE ENTRANCE
SEC SECONDARY
SES SMOKE EVACUATION SYSTEM
SHT SHEET
SIM SIMILAR
SLD SINGLE-LINE DIAGRAM
SNR SIGNAL-TO-NOISE RATIO
SP SPARE
SPDIF SONY PHILLIPS DIGITAL
INTERFACE
SPEC SPECIFICATIONS
SPKR LOUDSPEAKER
SPL SOUND PRESSURE LEVEL
SPP SINGLE-POINT POWER
SR SURFACE RACEWAY
SS SELECTOR SWITCH
SSW SELECTOR SWITCH
STA STATION
STD STANDARD
STP SHIELDED TWISTED PAIR
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
TBB TELECOMMUNICATIONS
BONDING BACKBONE
TBC TELECOMMUNICATIONS
BONDING CONDUCTOR
TC TEMP. CONTROL CONTR.
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
TX TRANSMITTER
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTED POWER
SUPPLY
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UTP UNSHIELDED TWISTED PAIR
UV ULTRAVIOLET
V VOLT (KV-KILOVOLT)
VA VOLT/AMPS
VA/R, VAR VOLT-AMPS/REACTIVE
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DC CURRENT
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VI VOLUME INDICATOR
VIF VERIFY IN FIELD
VM VOLT METER
VOL VOLUME
VU VOLUME UNIT
W WATTS
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WH WATTHOUR METER
WP WEATHERPROOF/NEMA 3R
XFMR TRANSFORMER
XFMR SW SW TRANSFER SWITCH
XFR TRANSFER
XL X-CONNECTOR LOCKING
XLR X-CONNECTOR LOCKING
RUBBERIZED
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
1P ONE-POLE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∠ ANGLE
& AND
@ AT
° DEGREE
▲ DELTA
', FT FOOT, FEET
", IN INCH, INCHES
# NUMBER
Ω, OHM UNIT OF ELECTRICAL
RESISTANCE
Ø, PH PHASE
℄, CTR CENTER LINE, CENTER
P PLATE
SYMBOL LEGEND GENERAL NOTES
1. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE
& DETAILS.
2. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.
3. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.
4. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
5. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
6. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
7. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
8. NOT USED.
9. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR
480 VOLT.
10. SIZE TO THE EQUIPMENT BEING CONTROLLED.
11. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.
12. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
13. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
14. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.
15. COORDINATE WITH DOOR HARDWARE SUPPLIER.
16. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS
A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
17. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
19. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.
20. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
21. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.
22. ROUGH-IN TO BE HORIZONTAL.
23. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE
REQUIRED.
24. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.
25. SUBSCRIPT INDICATES NEMA CONFIGURATION.
26. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.
27. USE WITH POWER PACK.
28. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
29. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.
30. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE
INDICATES INSTALLED IN CEILING.
31. WALL DEVICES NOTED WITH A CHEVRON INDICATE THE PROPOSED INSTALLATION HEIGHT.
COORDINATE WITH MILLWORK SHOP DRAWINGS & ELEVATIONS FOR HEIGHT.
ELECTRICAL GENERAL NOTES
1. GENERAL SCOPE & COMPLIANCE
A. INSTALL COMPLETE, OPERABLE ELECTRICAL SYSTEMS AS SHOWN AND SPECIFIED. BID
SHALL INCLUDE ALL WORK, MATERIALS, AND COORDINATION NECESSARY FOR A FULLY
FUNCTIONAL INSTALLATION.
B. ALL WORK SHALL COMPLY WITH THE NEC, NFPA 72, IBC/IFC, APPLICABLE LOCAL AND
STATE CODES, AHJ REQUIREMENTS, AND INDUSTRY STANDARDS.
C. ALL EQUIPMENT SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY (E.G., UL, ETL) FOR ITS INTENDED USE.
D. ALL EQUIPMENT PROVIDED SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY (NRTL).
E. FINAL INSTALLATION SHALL BE FREE OF DEFECTS AND APPROVED BY THE AHJ, OWNER,
ARCHITECT, AND ENGINEER.
F. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS SHALL BE
CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND BID WITH THIS INTENT.
G. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL APPLICABLE CONTRACT
DOCUMENTS, INCLUDING ARCHITECTURAL, MECHANICAL, STRUCTURAL, AND OTHER
TRADE DRAWINGS, TO COORDINATE LOCATIONS, DIMENSIONS, AND REQUIREMENTS. NO
ADDITIONAL COSTS WILL BE ALLOWED FOR FAILURE TO COORDINATE.
H. CONTRACTOR SHALL VERIFY ALL EQUIPMENT DIMENSIONS, ELECTRICAL LOADS
(VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC.), AND ROUGH-IN LOCATIONS
BEFORE INSTALLATION. VERIFY NEC CODE CLEARANCES AROUND ALL ELECTRICAL
EQUIPMENT.
I. ALL WORK SHALL CONFORM TO LOCAL AND STATE CODES, THE LATEST EDITION OF THE
NEC, AND ALL APPLICABLE INDUSTRY STANDARDS.
J. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND REPRESENT
THE GENERAL SCOPE OF WORK. RACEWAY ROUTING, UNLESS SPECIFICALLY SHOWN,
SHALL BE FIELD-DETERMINED IN COORDINATION WITH OTHER TRADES.
K. COORDINATE WITH ALL APPLICABLE SPECIFICATIONS, INCLUDING SECTION 265100
(16510) FOR REQUIRED COORDINATION MEETINGS WITH MECHANICAL AND CEILING
CONTRACTORS.
2. DRAWINGS & COORDINATION
A. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SHOWING GENERAL SCOPE AND INTENT
ONLY. EXACT ROUTING, BENDS, PULL BOXES, AND OTHER INSTALLATION DETAILS ARE
THE CONTRACTOR’S RESPONSIBILITY.
B. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE/DEVICE
LOCATIONS, MECHANICAL PLANS FOR COORDINATED PENETRATIONS, AND SHOP
DRAWINGS FOR EQUIPMENT DIMENSIONS.
C. COORDINATE WITH ALL OTHER TRADES BEFORE ROUGH-IN TO AVOID CONFLICTS WITH
DUCTWORK, PIPING, STRUCTURE, AND EQUIPMENT.
D. ARCHITECTURAL AND MECHANICAL PLANS ARE PART OF THE ELECTRICAL DOCUMENTS
WHERE THEY PERTAIN TO ELECTRICAL WORK.
E. NO ADDITIONAL COST WILL BE ALLOWED FOR FIELD CONFLICTS OR EQUIPMENT
DIMENSION VARIATIONS DUE TO FAILURE TO COORDINATE.
3. PRE-BID & PRE-INSTALLATION REQUIREMENTS
A. VISIT THE SITE, REVIEW ALL CONTRACT DOCUMENTS, AND VERIFY EXISTING
CONDITIONS BEFORE BIDDING.
B. NOTIFY THE ENGINEER IN WRITING OF ERRORS, OMISSIONS, OR CONFLICTS PRIOR TO
BID. CHANGES WILL BE ISSUED VIA PRE-BID ADDENDUM.
C. VERIFY ALL ELECTRICAL LOADS, VOLTAGES, PHASES, AND CONNECTION
REQUIREMENTS FOR NEW AND EXISTING EQUIPMENT TO BE REUSED.
D. OBTAIN AND REVIEW WIRING DIAGRAMS FROM EQUIPMENT SUPPLIERS BEFORE ROUGH-
IN.
4. CLEARANCES & CODE-REQUIRED SPACE
A. MAINTAIN NEC-REQUIRED WORKING CLEARANCES AROUND ALL ELECTRICAL
EQUIPMENT.
B. IF CLEARANCE ISSUES ARE FOUND, NOTIFY THE DESIGNER IMMEDIATELY. IF
DISCOVERED AFTER INSTALLATION, RELOCATE AT THE CONTRACTOR’S EXPENSE
UNLESS OTHERWISE DIRECTED.
C. DO NOT ALLOW FOREIGN PIPING, DUCTWORK, OR UNRELATED EQUIPMENT IN
ELECTRICAL ROOMS OR ABOVE/BELOW ELECTRICAL EQUIPMENT.
5. MATERIALS & INSTALLATION STANDARDS
A. MINIMUM CONDUIT SIZE: 3/4".
a. INTERIOR: EMT WITH SET-SCREW FITTINGS.
b. EXTERIOR: EMT WITH COMPRESSION GLAND TYPE FITTINGS.
c. UNDERGROUND: PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN
CORROSION-RESISTANT MATERIAL WHERE IN DIRECT SOIL CONTACT.
B. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS IN ALL
CONDUITS; CONDUIT SHALL NOT BE USED AS A GROUNDING CONDUCTOR.
C. COPPER CONDUCTORS, 600V RATED, THHN/THWN-2: #10 AWG AND SMALLER SOLID.
#8 AWG AND LARGER STRANDED. INCREASE CONDUCTOR SIZE TO #10 FOR 20A RUNS
OVER 125 FEET.
D. FLEXIBLE/SEALTITE CONDUIT LIMITED TO 6 FEET FOR FIXTURE AND MOTOR
CONNECTIONS AS NOTED OR VIBRATION-PRONE EQUIPMENT.
E. ALL EMPTY CONDUITS/RACEWAYS SHALL HAVE NYLON BUSHINGS AND 200 LB-RATED
PULL STRINGS.
F. SECURE CONDUIT AND BOXES TO STRUCTURE PER INDUSTRY STANDARDS. EXPOSED
CONDUIT SHALL BE PLUMB, LEVEL, PARALLEL TO BUILDING LINES, AND PAINTED TO
MATCH ADJACENT FINISHES IF VISIBLE.
G. CONDUITS/RACEWAYS SHALL BE CONCEALED WHERE PRACTICABLE. EXPOSED
CONDUIT/RACEWAY SHALL BE PAINTED TO MATCH ADJACENT SURFACES.
H. WIRING DEVICES SHALL BE WHITE WITH STAINLESS STEEL COVER PLATES UNLESS
OTHERWISE NOTED.
I. CONDUCTORS SHALL BE COPPER.
6. DEVICE & EQUIPMENT PLACEMENT
A. MOUNT WIRING DEVICES ABOVE BACKSPLASHES UNLESS SERVING UNDER-COUNTER
EQUIPMENT.
B. INSTALL SWITCHES, RECEPTACLES, AND CONTROLS AT ADA-COMPLIANT HEIGHTS.
C. OFFSET DEVICES ON OPPOSITE SIDES OF A WALL AT LEAST 12" TO REDUCE SOUND
TRANSMISSION.
D. COORDINATE FURNITURE LAYOUTS FOR FLOOR BOX AND POKE-THRU LOCATIONS
BEFORE ROUGH-IN.
E. LABEL ALL RECEPTACLE AND SWITCH FACEPLATES WITH CIRCUIT ID (XX-XX FORMAT).
F. PROVIDE TAMPER-RESISTANT RECEPTACLES AT ALL CODE-REQUIRED AND CHILD-
ACCESSIBLE LOCATIONS.
G. PROVIDE GFCI PROTECTION PER NEC, IN BATHROOMS, KITCHENS, OUTDOORS, WITHIN 6
FEET OF SINKS, AND WHERE REQUIRED FOR DIAGNOSTIC EQUIPMENT, TOOLS, OR
LIGHTING.
H. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS
SHALL BE RUN WITH CONDUCTORS PER TABLE BELOW.
a. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
b. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO
KEEP BRANCH CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
c. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT
STAYS WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF
NECESSARY,CONTRACTOR SHALL INCREASE WIRE AND CONDUIT SIZE TO MEET
THE STANDARD AT NO ADDITIONAL COST TO OWNER.
I. MAINTAIN ELECTRICAL CONTINUITY TO REMAINING EQUIPMENT WHEN REMOVING
EXISTING EQUIPMENT.
J. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE
SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.
K. EXTERIOR OUTLETS SHALL HAVE CAST COVERS WITH FLIP-TYPE LIDS UNLESS
OTHERWISE NOTED. ALL WP OUTLET HOODS SHALL BE EXTRA-DUTY, WHILE-IN-USE
TYPE, AND LOW-PROFILE WHERE PRACTICAL.
7. SPECIAL SYSTEMS
A. PROVIDE ADDRESSABLE FIRE ALARM SYSTEM PER NFPA 72, IBC/IFC, AND LOCAL CODES.
INCLUDE MONITORING OF SPRINKLER/TAMPER SWITCHES, AHU DUCT DETECTORS (>2000
CFM), PULL STATIONS AT EXITS, AND HEAT/SMOKE DETECTION AS SHOWN. SUBMIT
SHOP DRAWINGS FOR APPROVAL BEFORE INSTALLATION.
B. PROVIDE STRUCTURED CABLING FROM TELECOM/DATA/CATV OUTLETS TO THE MAIN
RACK/BOARD, WITH LABELING AT BOTH ENDS. INSTALL IN CONDUIT UNLESS ABOVE
ACCESSIBLE CEILINGS. USE PLENUM-RATED CABLE IN PLENUM SPACES.
C. PROVIDE HEAVY-DUTY FUSED DISCONNECTS.
D. SUBMIT SCALED LAYOUTS OF ELECTRICAL ROOMS (1/4" = 1') BASED ON FINAL
EQUIPMENT SUBMITTALS.
E. OBTAIN ALL WIRING DIAGRAMS FOR EQUIPMENT FROM SUPPLIERS BEFORE ROUGH-IN.
F. COORDINATE WITH EQUIPMENT SUPPLIERS FOR EXACT EQUIPMENT LOCATIONS AND
ELECTRICAL CONNECTIONS PRIOR TO ROUGH-IN.
G. THE ELECTRICAL CONTRACTOR SHALL MAKE FINAL EQUIPMENT CONNECTIONS UNLESS
OTHERWISE DIRECTED.
8. PENETRATIONS & SEALING
A. SEAL ALL PENETRATIONS OF FIRE-RATED FLOORS, WALLS, AND CEILINGS WITH
APPROVED FIRESTOP SYSTEMS TO MAINTAIN RATING.
B. ROOF PENETRATIONS FOR CONDUIT SHALL USE SEALED ROOF JACKS COMPATIBLE
WITH THE ROOF WARRANTY.
C. UNDERGROUND/UNDERFLOOR CONDUITS SHALL BE AT LEAST 24" BELOW GRADE/SLAB
UNLESS NOTED OTHERWISE.
D. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE
SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.
9. TESTING, CLEANING, & TURNOVER
A. TEST AND VERIFY PROPER OPERATION OF ALL ELECTRICAL SYSTEMS AT COMPLETION.
B. CLEAN ALL FIXTURES, DEVICES, AND EQUIPMENT; REMOVE LABELS, DIRT, PAINT,
GREASE, AND DEBRIS BEFORE FINAL ACCEPTANCE.
C. PROVIDE ALL O&M MANUALS AND AS-BUILT DRAWINGS WITH WIRING DIAGRAMS INSIDE
EQUIPMENT AND IN THE PROJECT CLOSEOUT DOCUMENTS.
MAXIMUM LENGTH
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
SHEET INDEX
Sheet Number Sheet Name
EG001 ELECTRICAL TITLE SHEET
EG002 ELECTRICAL SPECIFICATIONS
EG003 ELECTRICAL SPECIFICATIONS
EG005 ELECTRICAL NOTES, LEGENDS, & SCHEDULES
EP401 ENLARGED ELECTRICAL PLANS
# Date Revision
1 9/4/2026 ADDENDUM 1
ELECTRICAL GENERAL PROVISIONS
DESCRIPTION OF WORK: EXTENT OF ELECTRICAL WORK IS INDICATED ON DRAWINGS. PROVIDE ALL
LABOR, MATERIALS, EQUIPMENT, SUPERVISION AND SERVICE NECESSARY FOR A COMPLETE
ELECTRICAL SYSTEM. WORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOWING
ITEMS:
• ELECTRICAL CONNECTIONS FOR EQUIPMENT
• CONDUCTORS AND CABLES
• GROUNDING
• SUPPORTING DEVICES
• CONDUIT RACEWAYS
• ELECTRICAL BOXES AND FITTINGS
• RACEWAYS SYSTEMS
• ELECTRICAL SEISMIC CONTROL
• ELECTRICAL IDENTIFICATION
• PROTECTIVE DEVICE STUDY
• OCCUPANCY SENSORS
• LIGHTING CONTROL EQUIPMENT
• TRANSFORMERS
• SWITCHGEAR AND SWITCHBOARDS
• PANELBOARDS
• SERVICE ENTRANCE
• WIRING DEVICES
• OVERCURRENT PROTECTIVE DEVICES
• MOTOR AND CIRCUIT DISCONNECTS
• MOTOR STARTERS
• VARIABLE FREQUENCY DRIVES
• EMERGENCY ELECTRICAL SYSTEMS
• DEMOLITION
• SURGE PROTECTIVE DEVICES
• INTERIOR AND EXTERIOR BUILDING LIGHTING
• TELECOMMUNICATIONS RACEWAYS
• TWO-WAY COMMUNICATIONS SYSTEMS
• SECURITY SYSTEM RACEWAYS
• FIRE ALARMS AND DETECTION SYSTEMS
INTERPRETATION OF DRAWINGS AND SPECIFICATIONS: BEFORE BIDDING, CONTRACTOR SHALL
FAMILIARIZE THEMSELVES WITH THE DRAWINGS, SPECIFICATIONS AND PROJECT SITE.
VISIT THE SITE DURING THE BIDDING PERIOD TO DETERMINE EXISTING CONDITIONS AFFECTING
ELECTRICAL AND OTHER WORK, ALL COSTS ARISING FROM SITE CONDITIONS AND/OR PREPARATION
SHALL BE INCLUDED IN THE BASE BID. NO ADDITIONAL CHARGES WILL BE ALLOWED DUE TO
INADEQUATE SITE INSPECTION.
QUALITY ASSURANCE: PERFORM WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(NEC). COMPLY WITH REQUIREMENTS FOR STATE AND LOCAL ORDINANCES. OBTAIN ALL PERMITS, INSPECTIONS, ETC FOR AUTHORITY HAVING JURISDICTION (AHJ). EMPLOY ONLY QUALIFIED
CRAFTSMEN WITH AT LEAST THREE (3) YEARS OF EXPERIENCE. WORKMANSHIP SHALL BE NEAT, HAVE A GOOD MECHANICAL APPEARANCE AND CONFORM TO BEST ELECTRICAL STATE
CONTRACTING LICENSE. PROVIDE EQUIPMENT AND MATERIALS THAT ARE UNDERWRITERS
LABORATORIES INC. (UL) LISTED AND LABELED.
SUBMITTALS: AFTER THE CONTRACT IS AWARDED BUT PRIOR TO MANUFACTURE OR INSTALLATION
OF ANY EQUIPMENT, PREPARE COMPLETE SHOP DRAWINGS.
1. PROVIDE SUBMITTALS IN PORTABLE DOCUMENT FORMAT (PDF).
2. DOCUMENTS MUST BE ELECTRONICALLY BOOKMARKED AND KEYWORD SEARCHABLE
USING
(HTTP://ADOBE.COM/ACROBAT) ADOBE ACROBAT OR BLUEBEAM REVU
(HTTP://BLUEBEAM.COM) FOR EACH RELEVANT SECTION. (I.E. INCLUDE ELECTRONIC
BOOKMARKS SEPARATION “LIGHT FIXTURES” FROM “PANELBOARDS”.)
3. ELECTRONICALLY HIGHLIGHT ALL OPTIONS FOR LIGHT FIXTURES, ELECTRICAL
EQUIPMENT, ETC. MANUAL HIGHLIGHTING AND SCANNING OF THE DOCUMENTS IS NOT
ACCEPTABLE AND WILL NOT BE REVIEWED.
4. PROVIDE ONLY COMPLETED CUTSHEETS FOR ALL FIXTURE AND EQUIPMENT TYPES.
BLANK CUTSHEETS SUBMITTED WITH A SCHEDULE ARE NOT ACCEPTABLE AND WILL NOT
BE REVIEWED.
5. A MAXIMUM OF ONE SUBMITTAL PER SPECIFICATION SECTION IS ALLOWED, IT IS NOT
ACCEPTABLE TO PROVIDE PRODUCT BY PRODUCT SUBMITTAL. SINGLE PRODUCT
SUBMITTALS WILL NOT BE REVIEWED.
A. ELECTRICAL CONNECTIONS FOR EQUIPMENT
B. CONDUCTORS AND CABLES
C. GROUNDING
D. SUPPORTING DEVICES
E. CONDUIT RACEWAYS
F. ELECTRICAL BOXES AND FITTINGS
G. RACEWAYS SYSTEMS
H. ELECTRICAL SEISMIC CONTROL
I. ELECTRICAL IDENTIFICATION
J. PROTECTIVE DEVICE STUDY
K. OCCUPANCY SENSORS
L. LIGHTING CONTROL EQUIPMENT
M. TRANSFORMERS
N. SWITCHGEAR AND SWITCHBOARDS
O. PANELBOARDS
P. SERVICE ENTRANCE
Q. WIRING DEVICES
R. OVERCURRENT PROTECTIVE DEVICES
S. MOTOR AND CIRCUIT DISCONNECTS
T. MOTOR STARTERS
U. VARIABLE FREQUENCY DRIVES
V. EMERGENCY ELECTRICAL SYSTEMS
W. SURGE PROTECTIVE DEVICES
X. INTERIOR AND EXTERIOR BUILDING LIGHTING
Y. TELECOMMUNICATIONS SYSTEMS RACEWAYS
Z. TWO-WAY COMMUNICATIONS SYSTEMS
AA. SECURITY SYSTEM RACEWAYS
BB. FIRE ALARMS AND DETECTION SYSTEMS
6. PRODUCTS: PRODUCTS ARE SPECIFIED BY MANUFACTURE NAME, DESCRIPTION AND/OR
CATALOG NUMBER. PROVIDE PRODUCTS OF MANUFACTURERS SPECIFIED.
SUBSTITUTIONS WILL BE CONSIDERED IF A DUPLICATE WRITTEN APPLICATION IS
SUBMITTED. NO MATERIAL MAY BE SUBSTITUTED AFTER THE BID OPENING. PROVIDE
BLOCK OUTS, SLEEVES, ETC. REQUIRED FOR INSTALLATION OF WORK SPECIFIED.
7. RECORD DRAWINGS: MAINTAIN ON A DAILY BASIS, A COMPLETE SET OF RECORD
DRAWINGS, REFLECTING AN ACCURATE DIMENSIONAL RECORD OF ALL BURIED OR
CONCEALED WORK. MARK RECORD DRAWINGS TO SHOW THE PRECISE LOCATION OF
CONCEALED WORK AND EQUIPMENT, INCLUDING CONCEALED OR EMBEDDED CONDUIT
AND JUNCTION BOXES AND ALL CHANGES AND DEVIATIONS IN THE WORK FROM THAT
SHOWN ON THE CONTRACT DOCUMENTS.
8. OPERATION AND MAINTENANCE MANUALS: PROVIDE OPERATION AND MAINTENANCE
DATA BOOKS FOR ALL EQUIPMENT AND MATERIALS FURNISHED UNDER THIS DIVISION.
9. GUARANTEE: ENSURE THAT ELECTRICAL SYSTEMS INSTALLED UNDER THIS CONTRACT
IS IN PROPER WORKING ORDER AND IN COMPLIANCE WITH DRAWINGS, SPECIFICATIONS,
AND/OR AUTHORIZED CHANGES, WITHOUT ADDITIONAL CHARGE, REPLACE ANY WORK OR
MATERIALS WHICH DEVELOP DEFECTS, EXCEPT FROM ORDINARY WEAR AND TEAR,
WITHIN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE CERTIFICATE.
10. FIRE PROTECTION SEALS: SEAL ALL PENETRATIONS FOR WORK OF THIS SECTION
THROUGH FIRE RATED FLOORS, WALLS, CEILINGS TO PREVENT THE SPREAD OF SMOKE,
FIRE, TOXIC GAS, OR WATER THROUGH THE PENETRATION EITHER BEFORE, DURING OR
AFTER FIRE.
11. POWER OUTAGES: ALL POWER OUTAGES REQUIRED FOR EXECUTION OF THIS WORK
SHALL OCCUR DURING NON-STANDARD WORKING HOURS AND AT THE CONVENIENCE OF
THE OWNER. INCLUDE ALL COSTS FOR OVERTIME WORK IN BID.
12. EXCAVATING FOR ELECTRICAL WORK: LOCATE AND PROTECT EXISTING UTILITIES AND
OTHER UNDERGROUND WORK. PERFORM EXCAVATION IN A MANNER WHICH PROTECTS
WALLS, FOOTINGS AND OTHER STRUCTURAL MEMBERS.
13. CONCRETE BASES: PROVIDE 4” CONCRETE BASES FOR ELECTRICAL EQUIPMENT.
14. ROOF PENETRATIONS: PROVIDE ROOF JACK, SIZED TO FIT TIGHTLY TO RACEWAY FOR
WEATHERTIGHT SEAL.
ELECTRICAL CONNECTIONS FOR EQUIPMENT
1. VERIFY EXACT LOAD AND LOCATION OF ALL EQUIPMENT BEFORE ROUGH-IN FOR EACH
ELECTRICAL CONNECTION. PROVIDE COMPLETE ASSEMBLY OF MATERIAL, INCLUDING
BUT NOT NECESSARILY LIMITED TO, RACEWAYS, CONDUCTORS, CORDS, CORD CAPS,
PLUGS, WIRING DEVICES, PRESSURE CONNECTORS, TERMINALS (LUGS), ELECTRICAL
INSULATION TAPE, HEAT-SHRINKABLE INSULATION TUBING, CABLE TIES, SOLDERLESS
WIRE NUTS, AND OTHER ITEMS AND ACCESSORIES AS NEEDED TO COMPLETE SPLICES,
TERMINATIONS, AND CONNECTIONS AS REQUIRED. FOR PERMANENTLY INSTALLED FIXED
EQUIPMENT, PROVIDE FLEXIBLE SEAL-TITE CONNECTIONS. FOR MOVABLE AND/OR
PORTABLE EQUIPMENT, PROVIDE WIRE DEVICE, CORD CAP, AND MULTI-CONDUCTOR
CORD.
CONDUCTORS AND CABLES
1. PROVIDE FACTORY FABRICATED CONDUCTORS FOR SIZES, RATINGS, MATERIAL, AND
TYPES INDICATED FOR EACH SERVICE. PROVIDE COPPER CONDUCTORS, WITH
THHN/THWN INSULATION. SIZE ALL CONDUCTORS IN ACCORDANCE WITH NEC: MINIMUM
SIZE TO BE #12 AWG. PROVIDE STRANDED CONDUCTORS FOR #8 AWG AND LARGER.
2. THE FOLLOWING COLOR SCHEME SHALL BE USED:
3. MC CABLE:
A. MC CABLE IS ACCEPTABLE FOR ALL BRANCH CIRCUITS INSTALLED IN GYPSUM
WALLBOARD WALLS FROM THE HOME RUN DEVICE BOX TO THE LAST DEVICE BOX
ON THE BRANCH CIRCUIT AND ALL BOXES IN BETWEEN, FROM THE HOME RUN
DEVICE BOX TO THE BRANCH PANEL, THE CIRCUIT SHALL BE INSTALLED IN AN
APPROVED RACEWAY. MC CABLE IS ACCEPTABLE FOR ALL LIGHT FIXTURE WHIPS
NOT LONGER THAN SIX FEET IN LENGTH. LOCATED IN REMOVABLE GRID CEILINGS.
MC CABLE IS UNACCEPTABLE TO BE INSTALLED FROM LIGHT FIXTURE TO LIGHT
FIXTURE. ALL MC CABLE SHALL BE PROVIDED WITH ANTI SHORT FITTINGS.
B. THE USE OF MC-PCS CABLE IS ACCEPTABLE FOR LIGHT FIXTURE WHIPS UTILIZING
0-10V CONTROL SCHEMES, NOT LONGER THAN 72” IN LENGTH, LOCATED ABOVE
REMOVABLE GRID CEILINGS. ALL MC CABLE SHALL BE PROVIDED WITH ANTI-SHORT
FITTINGS.
a. ACCEPTABLE MANUFACTURERS
• AFC – MC LUMINARY CABLE
• ENCORE – MC-LED LIGHTING CABLE
• SOUTHWIRE – MC-PCS DUO
GROUNDING
• PROVIDE GROUNDING AND BONDING OF ALL ELECTRICAL AND COMMUNICATION
APPARATUS, MACHINERY, APPLIANCES, BUILDING COMPONENTS, AND ITEMS REQUIRED
BY THE NEC TO PROVIDE A PERMANENT, CONTINUOUS LOW IMPEDANCE, GROUNDING
SYSTEM. PROVIDE AN NEC BONDING/GROUNDING CONDUCTOR IN ALL RACEWAYS USE
FOR POWER DISTRIBUTION.
SUPPORTING DEVICES
• PROVIDE SUPPORTS, ANCHORS, SLEEVES AND SEALS AS REQUIRED FOR A COMPLETE
RACEWAY SUPPORT SYSTEM, INCLUDING BUT NOT LIMITED TO: CLEVIS HANGERS, RISER
CLAMPS, C-CLAMPS, BEAM CLAMPS, ONE- AND TWO-HOLE CONDUIT STRAPS, OFFSET
CONDUIT CLAMPS, EXPANSION ANCHORS, TOGGLE BOLTS, THREADED RODS, U-CHANNEL
STRUT SYSTEM, AND ALL OTHER ASSOCIATED ACCESSORIES. INSTALL IN ACCORDANCE
WITH MANUFACTURER’S WRITTEN INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY
PRACTICES TO ENSURE SUPPORTING DEVICES COMPLY WITH REQUIREMENTS. PROVIDE
RIGID ATTACHMENT OF ALL FLOOR MOUNTED EQUIPMENT TO THE FLOOR SLAB OR
STRUCTURAL SYSTEM.
CONDUIT RACEWAYS
1. PROVIDE METAL CONDUIT, TUBING, AND FITTINGS OF TYPES, GRADES, SIZES, AND
WEIGHTS (WALL THICKNESS) AS REQUIRED; WITH MINIMUM TRADE SIZE OF 3/4”. INSTALL
ELECTRICAL RACEWAY SYSTEMS IN ACCORDANCE WITH MANUFACTURER’S WRITTEN
INSTRUCTIONS AND APPLICABLE REQUIREMENTS OF NEC AND NECA “STANDARD OF
INSTALLATION” IN ACCORDANCE WITH THE FOLLOWING:
A. FEEDERS: INSTALL FEEDERS RATED 100 AMPS AND GREATER, IN ELECTRICAL
METALLIC CONDUIT (EMT); WHERE BURIED BELOW GRADE, INSTALL IN CONCRETE
ENCASED N0N-METALIC CONDUIT OR DUCT (SCHEDULE 40 PVC).
B. BRANCH CIRCUITS, AND INDIVIDUAL EQUIPMENT CIRCUITS RATED LESS THAT 100
AMPS; INSTALL IN ELECTRICAL METALLIC TUBING (EMT). WHERE LOCATED IN
POURED WALLS, BELOW CONCRETE SLAB-ON-GRADE, OR IN EARTH FILL, INSTALL IN
NON-METALLIC PLASTIC DUCT (SCHEDULE 40 PVC). ENCASE NON-METALLIC PLASTIC
DUCT 1-1/4” AND LARGER IN CONCRETE.
C. PROVIDE RIGID METAL CONDUIT (RMC) FOR ALL BENDS IN BURIED CONDUIT
GREATER THAN 30 DEGREES. PROVIDE PROTECTIVE COATING FOR RIGID METAL
CONDUIT BENDS.
D. INSTALL FLEXIBLE CONDUIT FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND
OTHER ELECTRICAL EQUIPMENT WHERE SUBJECT TO MOVEMENT AND VIBRATIONS.
E. PROVIDE “OZ” EXPANSION FITTINGS ON ALL CONDUITS CROSSING BUILDING
EXPANSION JOINTS, BOTH IN SLAB AND SUSPENDED.
F. DUCT BANKS” PROVIDE DUCT BANK CONSTRUCTION AS INDICATED USING 3000 PSI
CONCRETE WITH RED MARKER DYE. INSTALL #4 REINFORCING BAR IN EACH
CORNER OF DUCT BANK. PROVIDE MINIMUM OF 4” CONCRETE COVER ON ALL SIDES
OF EXTERIOR CONDUITS.
ELECTRICAL BOXES AND FITTINGS
1. PROVIDE ONE PIECE GALVANIZED FLAT ROLLED SHEET STEEL INTERIOR OUTLET WIRING
BOXES, CORROSION-RESISTANT CAST-METAL WEATHERPROOF OUTLET WIRING BOXES,
CODE GAUGE SHEET STEEL JUNCTION AND PULL BOXES, GALVANIZED CAST IRON
CONDUIT BODIES, CORROSION-RESISTANT PUNCH-STEEL BOX KNOCKOUT CLOSURES,
CONDUIT LOCKOUTS AND MALLEABLE STEEL CONDUIT BUSHINGS AND OFFSET
CONNECTORS, AND ALL ACCESSORIES AS REQUIRED TO SUIT EACH RESPECTIVE
LOCATION AND INSTALLATION. FASTEN BOXES RIGIDLY TO SUBSTRATES OR
STRUCTURAL SURFACES TO WHICH ATTACHED, OR SOLIDLY EMBED ELECTRICAL BOXES
IN CONCRETE OR MASONRY. USE BAR HANGERS FOR STUD CONSTRUCTION.
2. FLOOR BOXES – PROVIDE LEVELING AND FULLY ADJUSTABLE FLOOR SERVICE
RECEPTACLE OUTLETS AND FITTINGS OF TYPE AND RATINGS AS INDICATED ON THE
DRAWINGS. ALL BOXES SHALL COMPLY WITH UL STANDARD UL514A.
ELECTRICAL SPECIFICATIONS
RACEWAY SYSTEMS
1. EXTENT OF RACEWAYS IS INDICATED BY DRAWINGS AND SCHEDULES.
2. COMPLY WITH APPLICABLE PORTIONS OF NEMA STANDARDS PERTAINING TO RACEWAYS.
COMPLY WITH APPLICABLE PORTIONS OF UL SAFETY STANDARDS PERTAINING TO
ELECTRICAL RACEWAY SYSTEMS AND PROVIDE PRODUCTS AND COMPONENTS WHICH
HAVE BEEN UL-LISTED AND LABELED. COMPLY WITH NEC REQUIREMENTS AS
APPLICABLE TO CONSTRUCTION AND…