13-12- Addendum 1 - PAR133709 Acord Ice Center Ammonia Condenser Replacement.pdf

PDF 2 MB Posted

Attached to
SLCo PAR133709 Acord Ice Center Ammonia Condenser Replacement - CONST
Solicitation number
SLCo PAR133709 Acord Ice Center Ammonia Condenser Replacement - CONST
Issued by
Utah

About this file

This Addendum 1 document, issued by Architectural Nexus, Inc. on behalf of Salt Lake County for the Acord Ice Center Ammonia Condenser Replacement project located at 5353 W 3100 S, West Valley, Utah, addresses pre-bid questions and modifies the original construction documents. The addendum clarifies electrical requirements for Variable Frequency Drives (VFDs) and associated disconnects, specifically confirming NEMA 3R rating requirements and whether combination VFD/disconnect units or separate enclosures are acceptable. Additionally, it resolves questions regarding exhaust fan compliance for ammonia ventilation, confirming that fans must discharge vertically upward with a minimum velocity of 2500 ft/min and 30 air changes per hour, and removes the Area of Refuge/Area of Rescue signal system from the project scope. The addendum replaces eight drawing sheets (S101, M501, M601, EG001, EG002, EG003, EG005, EP401) and includes structural amendments requiring demolition of an existing ammonia diffusion tank vault lid with flowable concrete fill to 30 inches below grade, accounting for an estimated 1500-gallon vault capacity.

The document establishes that the electrical contractor (Division 26) is responsible for furnishing and installing combination VFD/disconnect units for the EF-9 exhaust fan motor, with detailed electrical specifications provided for 480V, 3-phase power systems rated at 460 volts. The revised mechanical drawings clarify EF-9 requirements including an upblast exhaust fan detail, while electrical drawings specify conductor sizing, raceway systems, grounding requirements, and protective device coordination in compliance with the National Electrical Code (NEC). The project encompasses HVAC equipment connections, structural modifications including footing and foundation work, and comprehensive mechanical and electrical installations with delivery of operations manuals and as-built drawings required upon substantial completion.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum Page 1 of 2

ADD #01

ARCHITECTURAL NEXUS, Inc archnexus.com

SALT LAKE CITY

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000

SACRAMENTO

930 R Street Sacramento, California 95811 T 916.443.5911

ISSUE DATE: September 4, 2026 RESPONSE TO: Pre-Bid Questions

PROJECT: Acord Ice Condensing Tower Replacement 5353 W 3100 S West Valley, UT 84120

OWNER: Salt Lake County 2001 S State St Salt Lake City, UT 84190

ARCHITECT’S

PROJECT #:

25019

PAGES: 2 + Attachments (8) = 10 Replaced attached drawings: S101, M501, M601, EG001, EG002, EG003, EG005, EP401 Replace attached specifications: NA Remove specification: NA Add attached specification: NA

This Addendum forms a part of the Contract Documents and modifies the original Bid Documents as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject the Bidder to disqualification. This Addendum includes all attachments noted, included herein by reference.

Q1: PRE-BID AMENDMENT QUESTIONS:

Q1.1 QUESTION: Are there specifications available for the VFDs? Based on the installation conditions, please confirm whether the VFDs and associated disconnects are required to be NEMA 3R rated.

A/E RESPONSE: Electrical drawings have been issued in this addendum to clarify.

Q1.2 QUESTION: Please clarify the EF-9 electrical requirements. Sheet EP101 circuits EF-9 to panel P1-33 as a

120V circuit, while the M601 mechanical schedule indicates 480V, 3-phase power.

Q1.3 QUESTION: Please confirm whether EF-9 requires a combination VFD/disconnect unit, or whether a separate disconnect and VFD enclosure are acceptable.

Q1.4 QUESTION: The EF-9 VFD shown on M401 appears to be located on the interior wall, and the details do not show a roof disconnect. Please clarify whether a roof-mounted disconnect is required and where it should be located.

Q1.5 QUESTION: Please confirm whether the electrical contractor is responsible for furnishing and/or installing the Area of Refuge/Area of Rescue signal system.

A/E RESPONSE: Area of Refuge/ Area of Rescue will be removed from the project.

Q1.6 QUESTION: Looking at the equipment schedule the exhaust fan shown is not compliant for ammonia, it is showing as a downdraft fan. Ammonia ventilation fans must discharge vertically upward with a minimal velocity of 2500 ft/min, and 30 air changes an hour. Please review and provide proper exhaust equipment

A/E RESPONSE: Reference attached mechanical drawings.

Addendum Page 2 of 2

DRAWING AMENDMENTS:

D1 Structural:

Item # Sheet(s) Drawing(s) Amendment

D1.01 S101 1 ADD: Note to demolish the vault lid and fill vault below tower with flowable concrete fill up to 30” below grade (frost depth).

Note: The existing ammonia diffusion tank (aka “vault”) capacity is an estimated 1500 gallons.

D2 Mechanical:

Item # Sheet(s) Drawing(s) Amendment

D2.01 M501 ADD: Clarified exhaust fan detail to upblast

D2.02 M601 ADD: Clarified EF-9 requirements

D3 Electrical:

Item # Sheet(s) Drawing(s) Amendment

D3.01 EG001 ADD: Sheet EG003 to sheet index

D3.02 EG002 ADD: Clarified specifications on sheets

D3.03 EG003 ADD: Entire sheet

D3.04 EG005 ADD: Clarified EF-9 electrical requirements

D3.05 EP401 ADD: Clarified EF-9 electrical requirements

Kevin Miller 801.924.5000 kmiller@archnexus.com 9.4.2026

Name Phone Email Date

99'-0"

HSS6X6X1/4

HSS6X6X1/4

HSS6X6X1/4

HSS6X6X1/4

5' -6

TY

P

2' -3

S-101

2'-6" 2'-6"

99'-0"

2' -3

2'

-3

10'-0"x5'-0"x18" MAT FOOTING

TOP AND BOT BAR: (7) #5 LONG

#5 AT 9"oc TRANS

S-501 TYP

EXTERIOR PAVING BY OTHERS

CJ

CJ

DEMOLISH THE VAULT LID. FILL

VAULT BELOW TOWER WITH

FLOWABLE CONCRETE FILL UP TO

30" BELOW GRADE (FROST DEPTH).

AFTER 7 DAYS, FOOTINGS MAY BE

POURED ON TOP OF FILL. IF VAULT

WALLS CONFLICT WITH FOOTINGS,

DEMOLISH THE WALL DOWN TO 30"

BELOW GRADE.

HSS10X6X1/4

H S

S1 0X

6X 1/

HSS10X6X1/4

H S

S1 0X

6X 1/

S-101

S-501 TYP

LEVEL 1

100'-0"

TOP OF FRAME

103'-0"

S-501

1 TYP

S-501

5 TYP

CONDENSER, SEE MECH DRAWINGS

CONNECTION OF CONDENSER

TO BE COORDINATED WITH

MEP

CONCRETE FOUNDATION NOTES MARKS AND SYMBOL LEGEND

1. SEE ARCHITECTURAL DRAWINGS AND CIVIL DRAWINGS FOR

EXTERIOR CONCRETE WORK AT DOORS, SIDEWALKS, ETC.

2. SEE ARCHITECTURAL DRAWINGS FOR DIMENSIONS TO

COLUMNS, WALLS, SLAB EDGES, SLOPES, ELEVATIONS,

CURBS, DEPRESSIONS AND DRAINS.

3. SEE TYPICAL FOUNDATION DETAILS ON S-50X SHEET SERIES

FOR:

• STRUCTURAL FILL

• FROST COVER

• PIPES PARALLEL TO FOOTINGS

• PIPES PERPENDICULAR TO FOOTINGS AND WALLS

• SLAB CONSTRUCTION AND CONTROL JOINT

• REINFORCING AT SLAB DISCONTINUITIES

SECTION MARK

SHEET NUMBER

SHEET NUMBER

FRAME ELEVATION

FOOTING DESIGNATION

TOF ELEVATION

FTG EL

STEEL COLUMNor

CJ CONTROL JOINT

LATERAL FRAME MOMENT CONNECTIONSSTEEL NOTES

1. VERIFY SIZE, WEIGHT, AND LOCATION OF ALL MECHANICAL

UNITS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS.

COORDINATE OPENINGS WITH MECHANICAL, ELECTRICAL, AND

GENERAL CONTRACTORS.

2. FRAME MEMBERS TO BE G90 COMMERCIAL GRADE GALVANIZED

STEEL. WELDS MAY BE ACCOMPLISHED IN SHOP.

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

AGENCY APPROVAL

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

STAMP

/4

/2

:0

:1

P

M

A u to d e s k D o c s /2

S

L C o A c o rd

I c e C e n te r

C o n d e n s in g U n it r2

/2

S

L C o A c o rd I c e

C e n te r_ S

T

.r v t

FOOTING AND

FRAMING PLANS

AND

ELEVATIONS

Author

W

S W

E S

T V

A L

L E

Y C

IT

Y

U

T

S A

L T

L A

K E

C O

U N

T Y

260036

08.21.2026

A c o rd

I c e E v a p o ra ti v e

C o n d e n s e r R e p la c e m e n t

CONSTRUCTION

DOCUMENTS

S-101

Checker

S-101 SCALE: 1/2" = 1'-0"

1 FOOTING AND FOUNDATION PLAN

S-101 SCALE: 1/2" = 1'-0"

2 TOP OF FRAME

S-101 SCALE: 1/2" = 1'-0"

3 FRAME ELEVATION

LEVEL 01 KEYPLAN

A

AREA OF CONSTRUCTION

# Date Revision

1 09.04.20

Addendum 1

GilbertNichols Phil J Miller - Ut

FLOW

FLOW

PLAN

ELEVATION

FLOW

F

LO

W

PLAN

ELEVATION

NOTE:

ALL LINE SIZES AS PER REFRIGERATION SCHEMATIC.

DISCHARGE CONNECTION SUCTION CONNECTION

.0

.0

FLOW

DRAIN & EQUALIZING

LINE

F

LO

W

NOTE:

1. LINE SIZE AS INDICATED ON REFRIGERATION SCHEMATIC

2. R = NOMINAL RADIUS OF PIPE.

1 1/2 R

EVAPORATIVE

CONDENSER

12"

4"

TO HIGH PRESSURE

RECEIVER, MINIMUM

VERTICAL DROP 5'-0"

CONCENTRIC

REDUCER

LONG RADIUS

ELBOW

1/2" HAND EXPANSION VALVE

AIR PURGE

1/2" SERVICE VALVE

COPPER PIPE

INSULATED OR NON-INSULATED)

ANCHOR UNISTRUT TO WALL

20 MIL THICK PVC ISOLATION TAPE

(DUCT TAPE OR ELECTRICIAN TAPE ARE NOT ACCEPTABLE)

P1000 UNISTRUT

UNISTRUT PIPE CLAMP

CLAMP BOLT

WOOD JOIST

I-BEAM

CLAMP

S

EYE BOLTS

THRU-BOLT

ADJUSTABLE

PIPE STAND

WELDED STEEL

WALL BRACKET

TURNBUCKLE

TURNBUCKLE

U-BOLTS

U-BOLTS

U-BOLTS

U-BOLTS

ANGLE

ANGLE

INSERTS

CINCH ANCHORS

C

IN

C H

A N

C H

O R

S

STEEL OFFSET

WALL BRACKET

NOTE:

FIGURE NUMBERS ARE TYPICAL TO GRINNELL SUPPORT NUMBERS.

HANGER ROD ATTACHED TO

STRUCTURE ABOVE

PROVIDE RIB-LOCK INSULATION

PROTECTION SHIELD (FIGURE 168) FOR

INSULATED PIPING

(FIGURE CT-65 FOR COPPER TUBING)

PIPE INSULATION

NON-INSULATED

PIPE

INSULATED

PIPE

CLEVIS HANGER

(PROVIDE OVERSIZED HANGER FOR

INSULATED PIPING)

TYPE 1

ADJUSTABLE CLEVIS

HANGER

(FIGURE 260)

TYPE 1

ADJUSTABLE CLEVIS

HANGER

(FIGURE 260)

EXISTING BUILT UP

INSULATED ROOF

4"X4" REDWOOD

SLEEPER

CUT PIECE OF SINGLE PLY

ROOF MEMBRANE, 2" LARGER

THAN REDWOOD (ALL SIDES)

3/8"x2-1/2"x8" PLATE

WITH (2) 3/8"Ø EXPANSION

BOLTS 3" LONG (SIMILAR

CONNECTION AT WALL)

ROOF STRUCTURE

BELOW

SECURE REFRIGERANT

PIPING TO SUPPORTS

WITH "UNISTRUT" PIPE

CLAMP OR EQUAL

RUN INSULATION OF

SUCTION LINE THROUGH

CLAMP ASSEMBLY

18 GAUGE GALVANIZED

SHEET METAL COVER

INSULATION AROUND

SUCTION LINES

5/16"x1-1/4" FLAT

HEAD MACHINE

SCREW AND NUT

1/4

1/4

NOTE:

RUN STEEL COVER CONTINUOUS FROM

CONDENSING UNITS TO RISERS OR

PENETRATIONS AT BUILDING WALL.

1-5/8" P-1000 "UNISTRUT"

CHANNEL OR EQUAL (TYPICAL)

P-2626 "UNISTRUT"

NINETY DEGREE ANGLE

FITTING OR EQUAL

2"x2"x3/16" ANGLE

6"

TOP VIEW

FRONT VIEW SIDE VIEW

DESCRIPTION NOTESITEMS

A

B

C

D

E

F

G

CT-1235 TANK

21" THREADED MCPHEE LID (NON-VENTED)

4" PVC SPOOL FLANGE W/SS-EPDM DONKER BOLTS

4" PVC SPOOL FLANGE W/SS-EPDM DONKER BOLTS

2" PVC SPOOL FLANGE W/SS-EPDM DONKER BOLTS

1" FNPT PVC TANK ADAPTER WITH PVC FLANGE ADAPTER

GRADUATED ADHESIVE STRIP

NOTES:

1. TANK IS MANUFACTURED TO ASTM-D-1998 STANDARD.

2. ALL DIMENSIONS ARE APPROXIMATE.

A

D

G

B

E

F

C

180°

90°270°

0°

C B

A

E

G

ALUMINUM PIPE

COVERING,

EXPOSED PIPE ONLY.

EXISTING

RIGID INSULATION

NOTE:

ROOFER TO FLASH, SEAL FLASHING IN PLACE

EXISTING

STEEL DECKING

BUILT UP ROOFING

MATERIAL

20 GAUGE GALVANIZED

FLASHING COLLAR

20 GA. GALVANIZED

FLASHING ANGLE

DRAW BAND

WELD PIPE CLAMP

TO ANGLE SUPPORT 1 1/2" x 1 1/2" x 1 1/4"

ANGLE SUPPORT

EXTERIOR WALL,

SEE ARCHITECTURAL

DETAILS FOR WALL TYPE,

THICKNESS, ETC.

CAULK & SEAL

ALL AROUND

ALUMINUM MESH

BIRD SCREEN

DRAINABLE LOUVER

APPROPRIATE MOUNTING

AND SILL SELECTED

ACCORDING

TO WALL CONSTRUCTION

EXTERIOR WALL

DRAINABLE FRAME

AND SILL

CAULK & SEAL

ALL AROUND

PLENUM

SHEET METAL COVER PROVIDE WEATHER

TIGHT SEALANT AT

ALL PIPE

PENETRATIONS

PLENUM

SHEET

METAL

COVER

CUT /

REMOVE

LOUVER

PIPE

12" MIN.

MOTORIZED BACKDRAFT

DAMPER

FLASH AND

COUNTERFLASH

ROOF CURB

INSULATION

SUPPORT ANGLE FOR

DAMPER ATTACHED

TO CURB

ROOF MEMBRANE

DECK

EXHAUST DUCT

SEE PLANS FOR

SIZE

CANT

STRIP

DOME EXHAUST FAN

OR ROOF HOOD

W/BIRD SCREEN

NOTE:

EXHAUST FAN TO BE MOUNTED LEVEL

OVER ROOF CURB DESIGNED FOR

PITCHED ROOF WHERE REQUIRED.

Project #: 250382

L I C

E N

S E

D

P

ROFESS IONA

L

E N

G I N

E E

R

No. 4775391-2202

S

T A

T E OF U

TA

H

SPENCER W.

HOWELL

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

AGENCY APPROVAL

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

08.21.2026

/4

/2

:0

:0

P M

A u to d e s k D o c s /2

S L

C o A c o rd I c e

C e n te r

C o n d e n s in g U n it r2 /2

S L

C o

A c o rd E v a p C o n d e n s e r

R e p la c e m e n t_

M E

C H v

.r v t

MECHANICAL

DETAILS

JN

W

S W e s t

V a ll e y C it y U

T

S A

L T

L A

K E

C O

U N

T Y

25019

08.31.2026

A c o rd

I c e E v a p o ra ti v e

C o n d e n s e r R e p la c e m e n t

CONSTRUCTION

DOCUMENTS

M501

GR

NOT TO SCALEM501

1 TYPICAL COMPRESSOR SUCTION & DISCHARGE HEADER CONNECTIONS DETAIL

NOT TO SCALEM501

2 DISCHARGE RISER TRAP DETAIL

NOT TO SCALEM501

3 REFRIGERANT CONNECTIONS AT EVAPORATIVE CONDENSTER DETAIL

NOT TO SCALEM501

4 PIPE SUPPORT DETAIL

NOT TO SCALEM501

5 PIPE SUPPORT DETAIL

NOT TO SCALEM501

6 SINGLE PIPE CLEVIS HANGER

NOT TO SCALEM501

7 REFRIGERANT PIPE SUPPORT ON ROOF

NOT TO SCALEM501

8 DIFFUSION TANK DETAIL

# Date Revision

1 9.4.2026 ADDENDUM 1

NOT TO SCALEM501

10 SINGLE PIPE ROOF PENETRATION DETAIL

NOT TO SCALEM501

11 PIPE THROUGH LOUVER

NOT TO SCALEM501

9 UP BLAST EXHAUST FAN DETAIL

Project #: 250382

L I C

E N

S E

D

P

ROFESS IONA

L

E N

G I N

E E

R

No. 4775391-2202

S

T A

T E OF U

TA

H

SPENCER W.

HOWELL

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

AGENCY APPROVAL

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

08.21.2026

/4

/2

:0

:5

P M

A u to d e s k D o c s /2

S L

C o A c o rd I c e

C e n te r

C o n d e n s in g U n it r2 /2

S L

C o

A c o rd E v a p C o n d e n s e r

R e p la c e m e n t_

M E

C H v

.r v t

MECHANICAL

SCHEDULES

JN

W

S W e s t

V a ll e y C it y U

T

S A

L T

L A

K E

C O

U N

T Y

25019

08.31.2026

A c o rd

I c e E v a p o ra ti v e

C o n d e n s e r R e p la c e m e n t

CONSTRUCTION

DOCUMENTS

M601

GR

7. PROVIDE ACCESS DOORS INTO DISCHARGE PLENUM.

6. PROVIDE SELF SUPPORTING SERVICE PLATFORMS WITH LADDERS.

5. PROVIDE WITH OVERSIZED ACCESS DOORS

4. PROVIDE LOW SOUND FANS.

3. PROVIDE WITH COMBINATION VFD AND DISCONNECT FOR FAN MOTOR, INSTALLED BY DIV. 26.

2. PUMP MOTOR, FAN AND SUMP HEATER REQUIRE SEPARATE ELECTRICAL CONNECTIONS.

1. JOB SITE ELEVATION IS 4,500 FEET ABOVE SEA LEVEL

EC-1 EVAPCO LSC-240E BLOW THRU R717 3,600 37,200 95 66 345 2 1 460/3/60 4 20 1 460/3/60 8 460/3/60 84 / 127.125 / 143.5 11,500 1 2 / 2 1-7

ID MANUFACTURER NUMBER (2) TYPE. REFRIG MBH (1) CFM (°F) (°F) (GPM) (HP) PUMP PHASE/HZ FANS HP MOTOR PHASE/HZ KW PHASE/HZ (IN) (LBS) (IN) (IN) NOTES

MODEL CAPACITY AIR TEMP WB RATE PUMP SPRAY VOLTS/ NO. OF MOTOR FAN VOLTS/ VOLTS/ WIDTH WEIGHT SIZE SIZE

TOTAL TOTAL CONDENSING ENTERING FLOW SPRAY QUANITY ELECTRICAL FAN QUANITY ELECTRICAL HEIGHT / OPERATING CONNECTION CONNECTION

WATER LENGTH / HEIGHT / WATER OVER FLOW / DRAIN

PUMP FAN SUMP HEATER PHYSICAL

EVAPORATIVE CONDENSING UNIT SCHEDULE - WATER COOLED

3. COMBINATION VFD / DISCONNECT PROVIDED AND INSTALLED BY DIV. 26.

2. PROVIDE WITH 14" TALL CURB, HINGE MOUNT AND LATCH, 115V / 1PH MOTORIZED DAMPER (DAMPER TO OPEN WHEN FAN IS OPERATING), SPARK RESISTANCE - SPARK B, EXPLOSION PROOF MOTOR, AUTOMATIC BELT TENSIONER, ALUMINUM RUB RING, ALUMINUM WHEEL, EXTENED BEARING LUBE LINE.

1. PERFORMANCE LISTED IS AT 4,500 FEET ELEVATION.

EF-9 GREENHECK CUBE-099-4 ROOF BELT DRIVE, UPBLAST EXHAUST 530 0.5 1282 50 0.25 0.11 1725 460 / 60 / 3 24.88ø / 40.09 105 6.5 REFIGERANT ALARM 1,2,3

ID MODEL NUMBER LOCATION TYPE TYPE (CFM) (IN. WATER) (RPM) (%) (HP) (HP) (RPM) VOLT/PH/HZ (IN) (LBS) SONES CONTROLS NOTES

AND AIR RATE PRESSURE SPEED EFFICIENCY SIZE BHP SPEED HEIGHT WEIGHT

MANUFACTURER AIRFLOW STATIC FAN STATIC MOTOR MOTOR MOTOR WIDTH/

MAXIMUM LENGTH/

AIR ELECTRICAL PHYSICAL

FAN SCHEDULE

1. CUSTOM TANK. REFERENCE DETAIL SHEET FOR ADDITIONAL REQUIREMENTS.

DT-1 ACO CONTAINER SYSTEMS CT-1235 SEE PLAN AMMONIA DIFFUSION 1235 1483 1482 64 / 119 12,360 1

ID MANUFACTURER MODEL NUMBER LOCATION USE ( IMP. GAL) ( US GAL) (GAL) (IN) (LBS) NOTES

VOLUME VOLUME VOLUME HEIGHT WEIGHT

TOTAL TOTAL REQUIRED DIAMETER /

TANK TANK

PHYSICAL

DIFFUSION TANK SCHEDULE

# Date Revision

1 9.4.2026 ADDENDUM 1

EV EV

DO

TV

J

FB PT

#-a

LC

J

#-a

X##

TC

CR

D

F

VFD

M

XX

EXIT SIGNAGE

SHADING & ARROWS INDICATE FACES &

DIRECTIONAL CHEVRONS

WALL-MOUNTED FIXTURES, TYPICAL

(VARIOUS SYMBOLS)

LINEAR, CEILING MOUNTED LIGHT FIXTURE

(VARIOUS DIMENSIONS, DOTS INDICATE PENDANT

MOUNT)

RECESSED DOWNLIGHT FIXTURE

CHEVRON INDICATES WALL WASH

DIRECTIONAL LIGHT, TRACK OR FLOOD LIGHT

LINEAR LIGHT, TAPE LIGHT

LIGHTING FIXTURE SYMBOLS LEGEND

NOTE:

1. SWITCH IDs ARE UNIQUE PER SPACE.

2. ID TAGS MAY BE USED ON CONTROL DEVICES OTHER THAN SWITCHES, SUCH AS OCCUPANCY

SENSORS, POWER PACKS OR ROOM CONTROLLERS.

3. ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING FIXTURE INDICATES FIXTURE IS

CONTROLLED BY THE ONLY SWITCH IN THE SPACE.

4. AN "x" IN PLACE OF THE SWITCH DESIGNATION INDICATES UNSWITCHED.

a

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

CEILING 1, 2, 4

CEILING

AS NOTED

AS NOTED

WALL/CEILING

WALL/CEILING

1, 2

1,2

1, 2, 14

1, 2

1, 3, 5, 7, 12

1, 3, 5, 7, 12

POWER SYMBOLS LEGEND

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

S

WALL MOUNTED RECEPTACLE

SWITCHED RECEPTACLE

EMERGENCY RECEPTACLE

GROUND FAULT RECEPTACLE

RECEPTACLE MODIFIERS:

##": HEIGHT AFF O.C.

WP: WEATHERPROOF W/ IN-USE COVER

T: TAMPER-PROOF

U: RECEPTACLE WITH USB OUTLET

G: GROUND FAULT PROTECTED @ BREAKER

H: HOSPITAL GRADE

18"

18"

D Q SP

18"

18"

RECEPTACLE (SPECIFIC HEIGHT)

ISOLATED GROUND RECEPTACLE

7, 25, 30

7, 8

18"

SWITCH MODIFIERS:

K: KEYED

T: TIMER

M: MANUAL STARTER THERMAL

OVERLOAD SWITCH

EMERGENCY POWER OFF PUSH BUTTON

DOOR OPENER PUSH PLATE

ELECTRICAL POWER METER

FUSED DISCONNECT SWITCH

TOMBSTONE RECEPTACLE

CORD REEL, DEVICE VARIES

CORD DROP, DEVICE VARIES

MULTI-OUTLET ASSEMBLY

FILLED SQUARES INDICATE 120V OUTLET

OPEN SQUARES INDICATE WITH USB

SINGLE / DUAL PORT ELECTRICAL VEHICLE

CHARGER

POWER POLE

NON-FUSED DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC STARTER WITH FUSED DISCONNECT

PUSHBUTTON

VARIABLE FREQUENCY DRIVE

TRANSFORMER:

SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &

REQUIREMENTS.

GENERAL LEGEND

SYMBOL DESCRIPTION NOTES

SOLID ARCHED LINES INDICATE UNSWITCHED

POWER CIRCUITING

DASHED ARCHED LINES INDICATE SWITCHED

POWER CIRCUITING

ONE CIRCUIT, HOME RUN TO PANEL

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

4" CONCRETE

BASE

POWER DISTRIBUTION PANEL 6'-6" TO TOP

FLUSH PANELBOARD 6'-6" TO TOP

SURFACE PANELBOARD 6'-6" TO TOP

TWO CIRCUITS, HOME RUN TO PANEL -

THREE CIRCUITS, HOME RUN TO PANEL -

CONDUIT RUN CONCEALED IN FLOOR OR GROUND -

CONDUIT RUN CONCEALED IN WALL OR CEILING -

CONDUIT UP -

CONDUIT DOWN -

CONDUIT STUB LOCATION CAP CONDUIT

CONDUIT / CIRCUIT CONTINUATION -

GROUND BUS BAR

CABLE TRAY

SOLID BOTTOM

LADDER

BASKET

MOUNTING

AS NOTED

7+18"

EQUIPMENT CEILING RACK

EQUIPMENT CABINET/RACK

EQUIPMENT 2-POST CABINET/RACK

TELEPHONE DEMARCATION BOARD +18"

FLOOR 18,

SEE SPEC.

WALL / FLOOR 18,

SEE SPEC.

CEILING

EXISTING --

DEMO --

TEMPORARY --

NEW --

CONDUIT

OHP: OVERHEAD POWER SERVICE

UGP: UNDERGROUND POWER

SERVICE

UGF: UNDERGROUND FIBER

SERVICE

TEL: TELEPHONE SERVICE

POWER DISTRIBUTION EQUIPMENT SYMBOLS

CIRCULAR, CEILING MOUNTED LIGHT FIXTURE

CENTER DOT INDICATES PENDANT

CEILING 1, 2, 4

CONTROLLED RECEPTACLE 7, 8+18" OR AS

NOTED

SPD PROTECTED RECEPTACLE 7+18" OR AS

NOTED

TIME CLOCK +48"

NOT IN CONTRACT --

MAGNETIC STARTER WITH BREAKER DISCONNECT

MOTOR

CEILING MOUNTED RECEPTACLE CEILING

TV BACKBOX FLAT PANEL

HEIGHT +12"

EMERGENCY LIGHTING UNIT, INTEGRAL BATTERY WALL/CEILING 1, 2, 3, 7

CW W: WALL C: CEILING

LIGHTING TAGS LEGEND

NOTES:

1. HATCHED FILL INDICATES SWITCHBOARD OR POWER

DISTRIBUTION PANEL.

2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.

3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE

(WIDTH & DEPTH).

4. DOOR INDICATES FRONT OF RECESSED PANEL.

H P

1A

LP

1A

M D

P

SB1

POWER TAGS LEGEND

GENERAL LEGEND

SYMBOL DESCRIPTION NOTESMOUNTING

KEYNOTE

ROOM NAME & NUMBER

DIAGRAM TAG

MATCH LINE TAG

ROOM NAME & NUMBER W/ ZONE I.D.

JUNCTION BOX

x

EXIT SIGNAGE WITH AUXILIARY HEAD

SHADING & ARROWS INDICATE FACES &

DIRECTIONAL CHEVRONS

AS NOTED S: SIMPLEX D: DUPLEX

Q: FOURPLEX SP: SPECIAL PURPOSE

FLOOR BOX / POKE-THRU

- SEE SCHEDULE FOR TYPE INFORMATION

AREA LIGHT POLE & FIXTURE

POST-TOP LIGHT POLE & FIXTURE

BOLLARD LIGHT

ARROWS INDICATE DIRECTION

SWITCH

SWITCH MODIFIERS:

3: 3-WAY

4: 4-WAY

K: KEYED

D: DIMMING

T: TIMER

P: SWITCH W/ PILOT LIGHT

CONCRETE

BASE

CONCRETE

BASE

CONCRETE

BASE

LIGHTING CONTROL SYMBOLS

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

46"

1, 14

REFER TO DIA

1, 14

REFER TO DIA

1, 14

REFER TO DIA

6, 7

STEP LIGHT FIXTURE AS NOTED 1,7

IN-GRADE LIGHT FIXTURE AS NOTED 1

MOMENTARY CONTACT SWITCH 46" 6, 7, 27

LOW VOLTAGE WALL STATION

(SUBSCRIPT INDICATES CONFIGURATION)

46" 6, 7

CEILING FAN CEILING 1

LIGHTING CONTACTOR

LIGHTING CONTROL TOUCH SCREEN

WALL

46"

SENSORS/SWITCHES:

PC: PHOTO-ELECTRIC CONTROL

OS: OCCUPANCY SENSOR SWITCH

DL: DAYLIGHT HARVESTING SENSOR

AS NOTED 6, 7, 27

6, 7

6, 7

SWITCH PACKS:

AP: AUXILIARY PACK

PP: POWER PACK

ABOVE

CEILING

CONTROL:

RC: DIGITAL ROOM CONTROLLER

(SUBSCRIPT = NUMBER OF RELAYS)

EP: EMERGENCY LIGHTING CONTROL

UNIT

ABOVE

CEILING

REFER TO DIA

AND SPEC GROUND ROD

GROUND ROD WITH TEST WELL

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CONDUCTOR SPLICE

STATIC GROUND RECEPTACLE

GROUNDING AND LIGHTNING PROTECTION SYMBOLS

SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES

AS NOTED -

AS NOTED -

AS NOTED -

AS NOTED -

AS NOTED -

CW W: WALL C: CEILING

EQUIPMENT SYSTEM PANELS

ACS: ACCESS CONTROL PANEL

IDS: INTRUSION DETECTION PANEL

PSP: POWER SUPPLY PANEL

RP#: LIGHTING PANEL

DAS: DISTRIBUTED ANTENNA SYSTEM

ERCCS: FIRST RESPONDERS RADIO SYSTEM

CATV: CABLE TV CONTENT EQUIPMENT

7, 8, 13

CEILING

CEILING

+46"OR AS

NOTED

7, REFER TO

SPEC

+46" 7

+46" 7

9, 10

9, 10, 11

+72" TO TOP

+60" TO TOP

18, SEE SPEC.

7, 22

Space

Space

XX

A a

FIXTURE ID (UPPERCASE UNDERLINED LETTER)

PANEL ID (NUMBERS & UPPERCASE LETTERS) - CIRCUIT NUMBER

RELAY ID (UPPERCASE LETTERS)

FIXTURE CONTROL ZONE ID (LOWERCASE LETTER)

#: INDICATES SWITCH TYPE

LOWERCASE LETTER: INDICATES SWITCH ID

DEVICES WITH A CHEVRON INDICATE TO

COORDINATE WITH MILLWORK PRIOR TO ROUGH-IN.

ELEVATION TAG. HATCHED AREA INDICATES

WHICH WALL, NUMBER INDICATES VIEW, AND

CENTER NUMBER INDICATES WHICH SHEET.

REVISION CLOUD DELTA. SHOWN WITH CLOUD

AND INDICATES A CHANGE PER THE TITLE BLOCK.

TAG FOR MECHANICAL, KITCHEN, AND SHOP

DEVICES. REFER TO SCHEDULES FOR INFO.

EF-XX

EMERGENCY EGRESS LIGHT FIXTURE CEILING 1, 2, 3, 4

CRITICAL EGRESS LIGHT FIXTURE CEILING 1, 2, 3, 4

9, 10, 11

9, 10, 11

+46" 7

9, 10

+46" 7

+60" TO TOP

+60" TO TOP

+60" TO TOP

+60" TO TOP

+60" TO TOP 9, 10, 11

+60" TO TOP

FLOOR

AS NOTED 20

25, 30

+46" 7

COUNTER TOP

MATCH LINE

SEE -/---

181 E 5600 S, Ste #200

Murray, UT 84107

(801) 530-3148 | www.resolutgroup.com

Resolut Project #: 250382

Electrical PM: SYDNEE ANDERSON

L I C

E N

S E

D

PROFESS I ONAL

E N

G I N

E E

R

S

TA T E O F U TA

H

No. 9075170

Lewis Wong

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

AGENCY APPROVAL

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

STAMP

/4

/2

:3

:1

P M

A u to d e s k D o c s /2

S

L C o A c o rd I c e

C e n te r

C o n d e n s in g U n it r2

/2

S

L C o

A c o rd E v a p C o n d e n s e r

R e p la c e m e n t_ E

L E

C v

.r v t

ELECTRICAL

TITLE SHEET

SA

W

S W e s t

V a ll e y C it y U

T

S a lt L a k e C o u n ty

250382

08/21/2026

S L

C o

A c o rd E v a p C o n d e n s e r

R e p la c e m e n t

CONSTRUCTION

DOCUMENTS

EG001

LW

ELECTRICAL ABBREVIATIONS INDEX

ABBREV. DESCRIPTION

A AMPS

AC ALTERNATING CURRENT

ACLG ABOVE CEILING

ADC ANALOG-TO-DIGITAL

CONVERTER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT

AFCI ARC FAULT CIRCUIT

INTERRUPTER

AFF / A.F.F. ABOVE FINISH FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPS INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AM AMPS METER

AMP AMPERE

AMPL AMPLIFIER

ANN ANNUNCIATOR

AOE AUDIO-OVER-ETHERNET

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIOVISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BC BARE COPPER

BD BOARD

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BLDG BUILDING

BMS BUILDING MANAGEMENT

SYSTEM

BPM BEATS-PER-MINUTE

C, CND CONDUIT

C.O. CONDUIT ONLY

C/W COMPLETE WITH

CAB CABINET

CAT CATEGORY CABLE

CAT# CATALOG

CATB COMMUNITY ANTENNA

TELEVISION

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CF CREST FACTOR

CKT CIRCUIT

CLG CEILING

CMPR COMPRESSOR

CNTR CONTRACTOR

CO CONDUIT ONLY

CODEC CODER-DECORDER

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONV CONVECTOR

CP CIRCULATING PUMP

CRT COMPUTER TERMINAL

CT CURRENT TRANSFORMER

CU COPPER

CV CONSTANT VOLTAGE

DAC DIGITAL-TO-ANALOG

CONVERTER

DB DECIBEL

DBFS DB REF. FULL SCALE

DBM DB REF. 0.001 WATT

DBU DB REF. 0.775 V

DBV DB REF. 1 V

DC DIRECT CURRENT

DCP DOMESTIC CIRCULATING PUMP

DED DEDICATED

DEPT DEPARTMENT

DET DETAIL

DFA DROP FROM ABOVE

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DR DYNAMIC RANGE

DS DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EG EMERGENCY GENERATOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY/EGRESS BATTERY

EMI ELECTRO-MAGNETIC

INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

ENT ELEC. NON-METAL. TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

ER EXISTING TO BE RELOCATED

ES SOURCE VOLTAGE

EWC ELECTRIC WATER COOLER

FA FIRE ALARM

FABP FIRE ALARM BOOSTER PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOT CANDLE

FCU FAN COIL UNIT

FIR FINITE IMPULSE RESPONSE

FILTER

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FMC FLEXIBLE METAL CONDUIT

FU FUSE

FUDS FUSE SAFETY DISCONNECT

SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEC GRND. ELEC. COND. AT SES

GEN GENERATOR

GFCI GROUND FAULT CURRENT

INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

ABBREV. DESCRIPTION

GRC GALVANIZED RIGID CONDUIT

GYP BD GYPSUM BOARD

HOA HAND-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSE POWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING & AIR

CONDITIONING

HZ HERTZ

I/W INTERLOCK WITH

IC INTERRUPTING CAPACITY

IFC INTERNATIONAL FIRE CODE

IG ISOLATED GROUND

IIR INFINITE IMPULSE RESPONSE

FILTER

IMC INTERMEDIATE METALLIC

CONDUIT

INCAND INCANDESCENT

IR INFRARED

IT TOTAL CURRENT

J-BOX JUNCTION BOX

KCMIL 1000 CIRCULAR MILS (MCM)

KHZ THOUSANDS OF HZ

KV KILOVOLT

KVA KILOVOLT AMPERES

KVAR KILOVARS

KW KILOWATT

KWH KILOWATT HOUR

LCS C-WEIGHTED SLOW SOUND

LEVEL

LEQ EQUIVALENT SOUND LEVEL

LFMC LIQUID-TIGHT FLEX.

METAL. COND.

LFNC LIQUID-TIGHT FLEX. NON-METAL.

COND.

LOC LOCATE OR LOCATION

LP, SPL SOUND PRESSURE LEVEL

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LU LOUDNESS UNIT METERING

LUFS LOUDNESS UNIT FULL SCALE

LV LOW VOLTAGE

M/C MOMENTARY CONTACT

MAC MEDIA ACCESS CONTROL

MAG.S MAGNETIC STARTER

MAX MAXIMUM

MB MAIN BUS

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCM 1000 CIRCULAR MILLS

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MEP MECHANICAL, ELECTRICAL, AND

PLUMBING

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT

SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MNF MANUFACTURER

MOA MULTI-OUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MSP MOTOR STARTER PANELBOARD

MSS MOTOR STARTER SWITCH

MTG MOUNTING

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

N NEW

N.I.C. NOT IN CONTRACT

N/A NOT APPLICABLE

N1 NEMA 1

N3R NEMA 3R

NAC NOTIFICATION APPLIANCE

CIRCUIT PANEL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECT.

MANUFAC. ASSOC.

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NFPA NATIONAL FIRE PROTECTION

ASSOC.

NL NIGHT LIGHT, BYPASS LOCAL

SWITCHING

NO NORMALLY OPENED

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

OC ON CENTER

OH OVERHEAD

OL OVERLOADS

OS & Y OUTSIDE SCREW & YOKE

OSI OPEN SYSTEM INTEGRATION

PA PASCAL

PB PUSHBUTTON

PBB PRIMARY BONDING BUSBAR

PC PLUMBING CONTRACTOR

PCM PULSE CODE MODULATION

PDU POWER DISTRIBUTION UNIT

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PFR PHASE FAILURE RELAY

PIV POST INDICATING VALVE

PLEN PLENUM

PNL PANEL

POC POINT OF CONNECTION

POE POWER OVER ETHERNET

POS POINT OF SALE

PP POWER POLE

PPM PEAK PROGRAM METER

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PSI POUNDS-PER-SQUARE-INCH

PT POTENTIAL TRANSFORMER

PTP POINT TO POINT

PTZ PAN, TILT, AND ZOOM

ABBREV. DESCRIPTION

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

QUAN QUANTITY

R RESISTANCE

RECEP, RECPT RECEPTACLE

REQ,REQD REQUIRED

REX REQUEST TO EXIT

RF RADIO FREQUENCY

RFM ROOF MOUNTED

RL LOAD RESISTANCE

RLA RATED LOAD AMPS

RM ROOM

RMC RIGID METALLIC CONDUIT

RMP ROCKY MOUNTAIN POWER

RMS ROOT MEAN SQUARE

RNC RIGID NON-METALLIC COND.

RPM ROTATIONS-PER-MINUTE

RS SOURCE RESISTANCE

RT TOTAL RESISTANCE

RTU ROOF TOP UNIT

RX RECEIVER

S/N SOLID NEUTRAL

S/S STOP/START PUSHBUTTONS

SBB SECONDARY BONDING BUSBAR

SBG SUPPLEMENTARY BONDING

GRID

SBJ SYSTEM BONDING JUMPER

SC SURFACE CONDUIT

SCA SHORT CIRCUIT AMPERES

SDI SERIAL DIGITAL INTERFACE

SE SERVICE ENTRANCE

SEC SECONDARY

SES SMOKE EVACUATION SYSTEM

SHT SHEET

SIM SIMILAR

SLD SINGLE-LINE DIAGRAM

SNR SIGNAL-TO-NOISE RATIO

SP SPARE

SPDIF SONY PHILLIPS DIGITAL

INTERFACE

SPEC SPECIFICATIONS

SPKR LOUDSPEAKER

SPL SOUND PRESSURE LEVEL

SPP SINGLE-POINT POWER

SR SURFACE RACEWAY

SS SELECTOR SWITCH

SSW SELECTOR SWITCH

STA STATION

STD STANDARD

STP SHIELDED TWISTED PAIR

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

SYS SYSTEM

TBB TELECOMMUNICATIONS

BONDING BACKBONE

TBC TELECOMMUNICATIONS

BONDING CONDUCTOR

TC TEMP. CONTROL CONTR.

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL

TX TRANSMITTER

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTED POWER

SUPPLY

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UTP UNSHIELDED TWISTED PAIR

UV ULTRAVIOLET

V VOLT (KV-KILOVOLT)

VA VOLT/AMPS

VA/R, VAR VOLT-AMPS/REACTIVE

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DC CURRENT

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VI VOLUME INDICATOR

VIF VERIFY IN FIELD

VM VOLT METER

VOL VOLUME

VU VOLUME UNIT

W WATTS

W/ WITH

W/O WITHOUT

WG WIRE GUARD

WH WATTHOUR METER

WP WEATHERPROOF/NEMA 3R

XFMR TRANSFORMER

XFMR SW SW TRANSFER SWITCH

XFR TRANSFER

XL X-CONNECTOR LOCKING

XLR X-CONNECTOR LOCKING

RUBBERIZED

XP EXPLOSION PROOF

XR EXISTING TO BE REMOVED

1P ONE-POLE

2P TWO-POLE

3P THREE-POLE

4P FOUR-POLE

∠ ANGLE

& AND

@ AT

° DEGREE

▲ DELTA

', FT FOOT, FEET

", IN INCH, INCHES

# NUMBER

Ω, OHM UNIT OF ELECTRICAL

RESISTANCE

Ø, PH PHASE

℄, CTR CENTER LINE, CENTER

P PLATE

SYMBOL LEGEND GENERAL NOTES

1. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE

& DETAILS.

2. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.

3. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.

4. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.

5. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.

6. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.

7. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.

8. NOT USED.

9. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR

480 VOLT.

10. SIZE TO THE EQUIPMENT BEING CONTROLLED.

11. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.

12. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.

13. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,

MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.

14. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.

15. COORDINATE WITH DOOR HARDWARE SUPPLIER.

16. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS

A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.

17. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.

19. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.

20. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.

21. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.

22. ROUGH-IN TO BE HORIZONTAL.

23. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE

REQUIRED.

24. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.

25. SUBSCRIPT INDICATES NEMA CONFIGURATION.

26. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.

27. USE WITH POWER PACK.

28. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.

29. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.

30. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE

INDICATES INSTALLED IN CEILING.

31. WALL DEVICES NOTED WITH A CHEVRON INDICATE THE PROPOSED INSTALLATION HEIGHT.

COORDINATE WITH MILLWORK SHOP DRAWINGS & ELEVATIONS FOR HEIGHT.

ELECTRICAL GENERAL NOTES

1. GENERAL SCOPE & COMPLIANCE

A. INSTALL COMPLETE, OPERABLE ELECTRICAL SYSTEMS AS SHOWN AND SPECIFIED. BID

SHALL INCLUDE ALL WORK, MATERIALS, AND COORDINATION NECESSARY FOR A FULLY

FUNCTIONAL INSTALLATION.

B. ALL WORK SHALL COMPLY WITH THE NEC, NFPA 72, IBC/IFC, APPLICABLE LOCAL AND

STATE CODES, AHJ REQUIREMENTS, AND INDUSTRY STANDARDS.

C. ALL EQUIPMENT SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY RECOGNIZED

TESTING LABORATORY (E.G., UL, ETL) FOR ITS INTENDED USE.

D. ALL EQUIPMENT PROVIDED SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY

RECOGNIZED TESTING LABORATORY (NRTL).

E. FINAL INSTALLATION SHALL BE FREE OF DEFECTS AND APPROVED BY THE AHJ, OWNER,

ARCHITECT, AND ENGINEER.

F. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS SHALL BE

CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND BID WITH THIS INTENT.

G. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL APPLICABLE CONTRACT

DOCUMENTS, INCLUDING ARCHITECTURAL, MECHANICAL, STRUCTURAL, AND OTHER

TRADE DRAWINGS, TO COORDINATE LOCATIONS, DIMENSIONS, AND REQUIREMENTS. NO

ADDITIONAL COSTS WILL BE ALLOWED FOR FAILURE TO COORDINATE.

H. CONTRACTOR SHALL VERIFY ALL EQUIPMENT DIMENSIONS, ELECTRICAL LOADS

(VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC.), AND ROUGH-IN LOCATIONS

BEFORE INSTALLATION. VERIFY NEC CODE CLEARANCES AROUND ALL ELECTRICAL

EQUIPMENT.

I. ALL WORK SHALL CONFORM TO LOCAL AND STATE CODES, THE LATEST EDITION OF THE

NEC, AND ALL APPLICABLE INDUSTRY STANDARDS.

J. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND REPRESENT

THE GENERAL SCOPE OF WORK. RACEWAY ROUTING, UNLESS SPECIFICALLY SHOWN,

SHALL BE FIELD-DETERMINED IN COORDINATION WITH OTHER TRADES.

K. COORDINATE WITH ALL APPLICABLE SPECIFICATIONS, INCLUDING SECTION 265100

(16510) FOR REQUIRED COORDINATION MEETINGS WITH MECHANICAL AND CEILING

CONTRACTORS.

2. DRAWINGS & COORDINATION

A. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SHOWING GENERAL SCOPE AND INTENT

ONLY. EXACT ROUTING, BENDS, PULL BOXES, AND OTHER INSTALLATION DETAILS ARE

THE CONTRACTOR’S RESPONSIBILITY.

B. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE/DEVICE

LOCATIONS, MECHANICAL PLANS FOR COORDINATED PENETRATIONS, AND SHOP

DRAWINGS FOR EQUIPMENT DIMENSIONS.

C. COORDINATE WITH ALL OTHER TRADES BEFORE ROUGH-IN TO AVOID CONFLICTS WITH

DUCTWORK, PIPING, STRUCTURE, AND EQUIPMENT.

D. ARCHITECTURAL AND MECHANICAL PLANS ARE PART OF THE ELECTRICAL DOCUMENTS

WHERE THEY PERTAIN TO ELECTRICAL WORK.

E. NO ADDITIONAL COST WILL BE ALLOWED FOR FIELD CONFLICTS OR EQUIPMENT

DIMENSION VARIATIONS DUE TO FAILURE TO COORDINATE.

3. PRE-BID & PRE-INSTALLATION REQUIREMENTS

A. VISIT THE SITE, REVIEW ALL CONTRACT DOCUMENTS, AND VERIFY EXISTING

CONDITIONS BEFORE BIDDING.

B. NOTIFY THE ENGINEER IN WRITING OF ERRORS, OMISSIONS, OR CONFLICTS PRIOR TO

BID. CHANGES WILL BE ISSUED VIA PRE-BID ADDENDUM.

C. VERIFY ALL ELECTRICAL LOADS, VOLTAGES, PHASES, AND CONNECTION

REQUIREMENTS FOR NEW AND EXISTING EQUIPMENT TO BE REUSED.

D. OBTAIN AND REVIEW WIRING DIAGRAMS FROM EQUIPMENT SUPPLIERS BEFORE ROUGH-

IN.

4. CLEARANCES & CODE-REQUIRED SPACE

A. MAINTAIN NEC-REQUIRED WORKING CLEARANCES AROUND ALL ELECTRICAL

EQUIPMENT.

B. IF CLEARANCE ISSUES ARE FOUND, NOTIFY THE DESIGNER IMMEDIATELY. IF

DISCOVERED AFTER INSTALLATION, RELOCATE AT THE CONTRACTOR’S EXPENSE

UNLESS OTHERWISE DIRECTED.

C. DO NOT ALLOW FOREIGN PIPING, DUCTWORK, OR UNRELATED EQUIPMENT IN

ELECTRICAL ROOMS OR ABOVE/BELOW ELECTRICAL EQUIPMENT.

5. MATERIALS & INSTALLATION STANDARDS

A. MINIMUM CONDUIT SIZE: 3/4".

a. INTERIOR: EMT WITH SET-SCREW FITTINGS.

b. EXTERIOR: EMT WITH COMPRESSION GLAND TYPE FITTINGS.

c. UNDERGROUND: PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN

CORROSION-RESISTANT MATERIAL WHERE IN DIRECT SOIL CONTACT.

B. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS IN ALL

CONDUITS; CONDUIT SHALL NOT BE USED AS A GROUNDING CONDUCTOR.

C. COPPER CONDUCTORS, 600V RATED, THHN/THWN-2: #10 AWG AND SMALLER SOLID.

#8 AWG AND LARGER STRANDED. INCREASE CONDUCTOR SIZE TO #10 FOR 20A RUNS

OVER 125 FEET.

D. FLEXIBLE/SEALTITE CONDUIT LIMITED TO 6 FEET FOR FIXTURE AND MOTOR

CONNECTIONS AS NOTED OR VIBRATION-PRONE EQUIPMENT.

E. ALL EMPTY CONDUITS/RACEWAYS SHALL HAVE NYLON BUSHINGS AND 200 LB-RATED

PULL STRINGS.

F. SECURE CONDUIT AND BOXES TO STRUCTURE PER INDUSTRY STANDARDS. EXPOSED

CONDUIT SHALL BE PLUMB, LEVEL, PARALLEL TO BUILDING LINES, AND PAINTED TO

MATCH ADJACENT FINISHES IF VISIBLE.

G. CONDUITS/RACEWAYS SHALL BE CONCEALED WHERE PRACTICABLE. EXPOSED

CONDUIT/RACEWAY SHALL BE PAINTED TO MATCH ADJACENT SURFACES.

H. WIRING DEVICES SHALL BE WHITE WITH STAINLESS STEEL COVER PLATES UNLESS

OTHERWISE NOTED.

I. CONDUCTORS SHALL BE COPPER.

6. DEVICE & EQUIPMENT PLACEMENT

A. MOUNT WIRING DEVICES ABOVE BACKSPLASHES UNLESS SERVING UNDER-COUNTER

EQUIPMENT.

B. INSTALL SWITCHES, RECEPTACLES, AND CONTROLS AT ADA-COMPLIANT HEIGHTS.

C. OFFSET DEVICES ON OPPOSITE SIDES OF A WALL AT LEAST 12" TO REDUCE SOUND

TRANSMISSION.

D. COORDINATE FURNITURE LAYOUTS FOR FLOOR BOX AND POKE-THRU LOCATIONS

BEFORE ROUGH-IN.

E. LABEL ALL RECEPTACLE AND SWITCH FACEPLATES WITH CIRCUIT ID (XX-XX FORMAT).

F. PROVIDE TAMPER-RESISTANT RECEPTACLES AT ALL CODE-REQUIRED AND CHILD-

ACCESSIBLE LOCATIONS.

G. PROVIDE GFCI PROTECTION PER NEC, IN BATHROOMS, KITCHENS, OUTDOORS, WITHIN 6

FEET OF SINKS, AND WHERE REQUIRED FOR DIAGNOSTIC EQUIPMENT, TOOLS, OR

LIGHTING.

H. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS

SHALL BE RUN WITH CONDUCTORS PER TABLE BELOW.

a. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.

b. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO

KEEP BRANCH CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.

c. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT

STAYS WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF

NECESSARY,CONTRACTOR SHALL INCREASE WIRE AND CONDUIT SIZE TO MEET

THE STANDARD AT NO ADDITIONAL COST TO OWNER.

I. MAINTAIN ELECTRICAL CONTINUITY TO REMAINING EQUIPMENT WHEN REMOVING

EXISTING EQUIPMENT.

J. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE

SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.

K. EXTERIOR OUTLETS SHALL HAVE CAST COVERS WITH FLIP-TYPE LIDS UNLESS

OTHERWISE NOTED. ALL WP OUTLET HOODS SHALL BE EXTRA-DUTY, WHILE-IN-USE

TYPE, AND LOW-PROFILE WHERE PRACTICAL.

7. SPECIAL SYSTEMS

A. PROVIDE ADDRESSABLE FIRE ALARM SYSTEM PER NFPA 72, IBC/IFC, AND LOCAL CODES.

INCLUDE MONITORING OF SPRINKLER/TAMPER SWITCHES, AHU DUCT DETECTORS (>2000

CFM), PULL STATIONS AT EXITS, AND HEAT/SMOKE DETECTION AS SHOWN. SUBMIT

SHOP DRAWINGS FOR APPROVAL BEFORE INSTALLATION.

B. PROVIDE STRUCTURED CABLING FROM TELECOM/DATA/CATV OUTLETS TO THE MAIN

RACK/BOARD, WITH LABELING AT BOTH ENDS. INSTALL IN CONDUIT UNLESS ABOVE

ACCESSIBLE CEILINGS. USE PLENUM-RATED CABLE IN PLENUM SPACES.

C. PROVIDE HEAVY-DUTY FUSED DISCONNECTS.

D. SUBMIT SCALED LAYOUTS OF ELECTRICAL ROOMS (1/4" = 1') BASED ON FINAL

EQUIPMENT SUBMITTALS.

E. OBTAIN ALL WIRING DIAGRAMS FOR EQUIPMENT FROM SUPPLIERS BEFORE ROUGH-IN.

F. COORDINATE WITH EQUIPMENT SUPPLIERS FOR EXACT EQUIPMENT LOCATIONS AND

ELECTRICAL CONNECTIONS PRIOR TO ROUGH-IN.

G. THE ELECTRICAL CONTRACTOR SHALL MAKE FINAL EQUIPMENT CONNECTIONS UNLESS

OTHERWISE DIRECTED.

8. PENETRATIONS & SEALING

A. SEAL ALL PENETRATIONS OF FIRE-RATED FLOORS, WALLS, AND CEILINGS WITH

APPROVED FIRESTOP SYSTEMS TO MAINTAIN RATING.

B. ROOF PENETRATIONS FOR CONDUIT SHALL USE SEALED ROOF JACKS COMPATIBLE

WITH THE ROOF WARRANTY.

C. UNDERGROUND/UNDERFLOOR CONDUITS SHALL BE AT LEAST 24" BELOW GRADE/SLAB

UNLESS NOTED OTHERWISE.

D. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE

SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.

9. TESTING, CLEANING, & TURNOVER

A. TEST AND VERIFY PROPER OPERATION OF ALL ELECTRICAL SYSTEMS AT COMPLETION.

B. CLEAN ALL FIXTURES, DEVICES, AND EQUIPMENT; REMOVE LABELS, DIRT, PAINT,

GREASE, AND DEBRIS BEFORE FINAL ACCEPTANCE.

C. PROVIDE ALL O&M MANUALS AND AS-BUILT DRAWINGS WITH WIRING DIAGRAMS INSIDE

EQUIPMENT AND IN THE PROJECT CLOSEOUT DOCUMENTS.

MAXIMUM LENGTH

20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING

BRANCH CIRCUIT VOLTAGE

CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT

<70 MIN. #12 AWG

70 - 115

115 - 170

170 - 270

271 - 380

>380

MIN. #12 AWG

MIN. #10 AWG MIN. #12 AWG

MIN. #8 AWG MIN. #10 AWG

MIN. #6 AWG MIN. #8 AWG

NOTE B MIN. #8 AWG

NOTE B NOTE B

SHEET INDEX

Sheet Number Sheet Name

EG001 ELECTRICAL TITLE SHEET

EG002 ELECTRICAL SPECIFICATIONS

EG003 ELECTRICAL SPECIFICATIONS

EG005 ELECTRICAL NOTES, LEGENDS, & SCHEDULES

EP401 ENLARGED ELECTRICAL PLANS

# Date Revision

1 9/4/2026 ADDENDUM 1

ELECTRICAL GENERAL PROVISIONS

DESCRIPTION OF WORK: EXTENT OF ELECTRICAL WORK IS INDICATED ON DRAWINGS. PROVIDE ALL

LABOR, MATERIALS, EQUIPMENT, SUPERVISION AND SERVICE NECESSARY FOR A COMPLETE

ELECTRICAL SYSTEM. WORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOWING

ITEMS:

• ELECTRICAL CONNECTIONS FOR EQUIPMENT

• CONDUCTORS AND CABLES

• GROUNDING

• SUPPORTING DEVICES

• CONDUIT RACEWAYS

• ELECTRICAL BOXES AND FITTINGS

• RACEWAYS SYSTEMS

• ELECTRICAL SEISMIC CONTROL

• ELECTRICAL IDENTIFICATION

• PROTECTIVE DEVICE STUDY

• OCCUPANCY SENSORS

• LIGHTING CONTROL EQUIPMENT

• TRANSFORMERS

• SWITCHGEAR AND SWITCHBOARDS

• PANELBOARDS

• SERVICE ENTRANCE

• WIRING DEVICES

• OVERCURRENT PROTECTIVE DEVICES

• MOTOR AND CIRCUIT DISCONNECTS

• MOTOR STARTERS

• VARIABLE FREQUENCY DRIVES

• EMERGENCY ELECTRICAL SYSTEMS

• DEMOLITION

• SURGE PROTECTIVE DEVICES

• INTERIOR AND EXTERIOR BUILDING LIGHTING

• TELECOMMUNICATIONS RACEWAYS

• TWO-WAY COMMUNICATIONS SYSTEMS

• SECURITY SYSTEM RACEWAYS

• FIRE ALARMS AND DETECTION SYSTEMS

INTERPRETATION OF DRAWINGS AND SPECIFICATIONS: BEFORE BIDDING, CONTRACTOR SHALL

FAMILIARIZE THEMSELVES WITH THE DRAWINGS, SPECIFICATIONS AND PROJECT SITE.

VISIT THE SITE DURING THE BIDDING PERIOD TO DETERMINE EXISTING CONDITIONS AFFECTING

ELECTRICAL AND OTHER WORK, ALL COSTS ARISING FROM SITE CONDITIONS AND/OR PREPARATION

SHALL BE INCLUDED IN THE BASE BID. NO ADDITIONAL CHARGES WILL BE ALLOWED DUE TO

INADEQUATE SITE INSPECTION.

QUALITY ASSURANCE: PERFORM WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE

(NEC). COMPLY WITH REQUIREMENTS FOR STATE AND LOCAL ORDINANCES. OBTAIN ALL PERMITS, INSPECTIONS, ETC FOR AUTHORITY HAVING JURISDICTION (AHJ). EMPLOY ONLY QUALIFIED

CRAFTSMEN WITH AT LEAST THREE (3) YEARS OF EXPERIENCE. WORKMANSHIP SHALL BE NEAT, HAVE A GOOD MECHANICAL APPEARANCE AND CONFORM TO BEST ELECTRICAL STATE

CONTRACTING LICENSE. PROVIDE EQUIPMENT AND MATERIALS THAT ARE UNDERWRITERS

LABORATORIES INC. (UL) LISTED AND LABELED.

SUBMITTALS: AFTER THE CONTRACT IS AWARDED BUT PRIOR TO MANUFACTURE OR INSTALLATION

OF ANY EQUIPMENT, PREPARE COMPLETE SHOP DRAWINGS.

1. PROVIDE SUBMITTALS IN PORTABLE DOCUMENT FORMAT (PDF).

2. DOCUMENTS MUST BE ELECTRONICALLY BOOKMARKED AND KEYWORD SEARCHABLE

USING

(HTTP://ADOBE.COM/ACROBAT) ADOBE ACROBAT OR BLUEBEAM REVU

(HTTP://BLUEBEAM.COM) FOR EACH RELEVANT SECTION. (I.E. INCLUDE ELECTRONIC

BOOKMARKS SEPARATION “LIGHT FIXTURES” FROM “PANELBOARDS”.)

3. ELECTRONICALLY HIGHLIGHT ALL OPTIONS FOR LIGHT FIXTURES, ELECTRICAL

EQUIPMENT, ETC. MANUAL HIGHLIGHTING AND SCANNING OF THE DOCUMENTS IS NOT

ACCEPTABLE AND WILL NOT BE REVIEWED.

4. PROVIDE ONLY COMPLETED CUTSHEETS FOR ALL FIXTURE AND EQUIPMENT TYPES.

BLANK CUTSHEETS SUBMITTED WITH A SCHEDULE ARE NOT ACCEPTABLE AND WILL NOT

BE REVIEWED.

5. A MAXIMUM OF ONE SUBMITTAL PER SPECIFICATION SECTION IS ALLOWED, IT IS NOT

ACCEPTABLE TO PROVIDE PRODUCT BY PRODUCT SUBMITTAL. SINGLE PRODUCT

SUBMITTALS WILL NOT BE REVIEWED.

A. ELECTRICAL CONNECTIONS FOR EQUIPMENT

B. CONDUCTORS AND CABLES

C. GROUNDING

D. SUPPORTING DEVICES

E. CONDUIT RACEWAYS

F. ELECTRICAL BOXES AND FITTINGS

G. RACEWAYS SYSTEMS

H. ELECTRICAL SEISMIC CONTROL

I. ELECTRICAL IDENTIFICATION

J. PROTECTIVE DEVICE STUDY

K. OCCUPANCY SENSORS

L. LIGHTING CONTROL EQUIPMENT

M. TRANSFORMERS

N. SWITCHGEAR AND SWITCHBOARDS

O. PANELBOARDS

P. SERVICE ENTRANCE

Q. WIRING DEVICES

R. OVERCURRENT PROTECTIVE DEVICES

S. MOTOR AND CIRCUIT DISCONNECTS

T. MOTOR STARTERS

U. VARIABLE FREQUENCY DRIVES

V. EMERGENCY ELECTRICAL SYSTEMS

W. SURGE PROTECTIVE DEVICES

X. INTERIOR AND EXTERIOR BUILDING LIGHTING

Y. TELECOMMUNICATIONS SYSTEMS RACEWAYS

Z. TWO-WAY COMMUNICATIONS SYSTEMS

AA. SECURITY SYSTEM RACEWAYS

BB. FIRE ALARMS AND DETECTION SYSTEMS

6. PRODUCTS: PRODUCTS ARE SPECIFIED BY MANUFACTURE NAME, DESCRIPTION AND/OR

CATALOG NUMBER. PROVIDE PRODUCTS OF MANUFACTURERS SPECIFIED.

SUBSTITUTIONS WILL BE CONSIDERED IF A DUPLICATE WRITTEN APPLICATION IS

SUBMITTED. NO MATERIAL MAY BE SUBSTITUTED AFTER THE BID OPENING. PROVIDE

BLOCK OUTS, SLEEVES, ETC. REQUIRED FOR INSTALLATION OF WORK SPECIFIED.

7. RECORD DRAWINGS: MAINTAIN ON A DAILY BASIS, A COMPLETE SET OF RECORD

DRAWINGS, REFLECTING AN ACCURATE DIMENSIONAL RECORD OF ALL BURIED OR

CONCEALED WORK. MARK RECORD DRAWINGS TO SHOW THE PRECISE LOCATION OF

CONCEALED WORK AND EQUIPMENT, INCLUDING CONCEALED OR EMBEDDED CONDUIT

AND JUNCTION BOXES AND ALL CHANGES AND DEVIATIONS IN THE WORK FROM THAT

SHOWN ON THE CONTRACT DOCUMENTS.

8. OPERATION AND MAINTENANCE MANUALS: PROVIDE OPERATION AND MAINTENANCE

DATA BOOKS FOR ALL EQUIPMENT AND MATERIALS FURNISHED UNDER THIS DIVISION.

9. GUARANTEE: ENSURE THAT ELECTRICAL SYSTEMS INSTALLED UNDER THIS CONTRACT

IS IN PROPER WORKING ORDER AND IN COMPLIANCE WITH DRAWINGS, SPECIFICATIONS,

AND/OR AUTHORIZED CHANGES, WITHOUT ADDITIONAL CHARGE, REPLACE ANY WORK OR

MATERIALS WHICH DEVELOP DEFECTS, EXCEPT FROM ORDINARY WEAR AND TEAR,

WITHIN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE CERTIFICATE.

10. FIRE PROTECTION SEALS: SEAL ALL PENETRATIONS FOR WORK OF THIS SECTION

THROUGH FIRE RATED FLOORS, WALLS, CEILINGS TO PREVENT THE SPREAD OF SMOKE,

FIRE, TOXIC GAS, OR WATER THROUGH THE PENETRATION EITHER BEFORE, DURING OR

AFTER FIRE.

11. POWER OUTAGES: ALL POWER OUTAGES REQUIRED FOR EXECUTION OF THIS WORK

SHALL OCCUR DURING NON-STANDARD WORKING HOURS AND AT THE CONVENIENCE OF

THE OWNER. INCLUDE ALL COSTS FOR OVERTIME WORK IN BID.

12. EXCAVATING FOR ELECTRICAL WORK: LOCATE AND PROTECT EXISTING UTILITIES AND

OTHER UNDERGROUND WORK. PERFORM EXCAVATION IN A MANNER WHICH PROTECTS

WALLS, FOOTINGS AND OTHER STRUCTURAL MEMBERS.

13. CONCRETE BASES: PROVIDE 4” CONCRETE BASES FOR ELECTRICAL EQUIPMENT.

14. ROOF PENETRATIONS: PROVIDE ROOF JACK, SIZED TO FIT TIGHTLY TO RACEWAY FOR

WEATHERTIGHT SEAL.

ELECTRICAL CONNECTIONS FOR EQUIPMENT

1. VERIFY EXACT LOAD AND LOCATION OF ALL EQUIPMENT BEFORE ROUGH-IN FOR EACH

ELECTRICAL CONNECTION. PROVIDE COMPLETE ASSEMBLY OF MATERIAL, INCLUDING

BUT NOT NECESSARILY LIMITED TO, RACEWAYS, CONDUCTORS, CORDS, CORD CAPS,

PLUGS, WIRING DEVICES, PRESSURE CONNECTORS, TERMINALS (LUGS), ELECTRICAL

INSULATION TAPE, HEAT-SHRINKABLE INSULATION TUBING, CABLE TIES, SOLDERLESS

WIRE NUTS, AND OTHER ITEMS AND ACCESSORIES AS NEEDED TO COMPLETE SPLICES,

TERMINATIONS, AND CONNECTIONS AS REQUIRED. FOR PERMANENTLY INSTALLED FIXED

EQUIPMENT, PROVIDE FLEXIBLE SEAL-TITE CONNECTIONS. FOR MOVABLE AND/OR

PORTABLE EQUIPMENT, PROVIDE WIRE DEVICE, CORD CAP, AND MULTI-CONDUCTOR

CORD.

CONDUCTORS AND CABLES

1. PROVIDE FACTORY FABRICATED CONDUCTORS FOR SIZES, RATINGS, MATERIAL, AND

TYPES INDICATED FOR EACH SERVICE. PROVIDE COPPER CONDUCTORS, WITH

THHN/THWN INSULATION. SIZE ALL CONDUCTORS IN ACCORDANCE WITH NEC: MINIMUM

SIZE TO BE #12 AWG. PROVIDE STRANDED CONDUCTORS FOR #8 AWG AND LARGER.

2. THE FOLLOWING COLOR SCHEME SHALL BE USED:

3. MC CABLE:

A. MC CABLE IS ACCEPTABLE FOR ALL BRANCH CIRCUITS INSTALLED IN GYPSUM

WALLBOARD WALLS FROM THE HOME RUN DEVICE BOX TO THE LAST DEVICE BOX

ON THE BRANCH CIRCUIT AND ALL BOXES IN BETWEEN, FROM THE HOME RUN

DEVICE BOX TO THE BRANCH PANEL, THE CIRCUIT SHALL BE INSTALLED IN AN

APPROVED RACEWAY. MC CABLE IS ACCEPTABLE FOR ALL LIGHT FIXTURE WHIPS

NOT LONGER THAN SIX FEET IN LENGTH. LOCATED IN REMOVABLE GRID CEILINGS.

MC CABLE IS UNACCEPTABLE TO BE INSTALLED FROM LIGHT FIXTURE TO LIGHT

FIXTURE. ALL MC CABLE SHALL BE PROVIDED WITH ANTI SHORT FITTINGS.

B. THE USE OF MC-PCS CABLE IS ACCEPTABLE FOR LIGHT FIXTURE WHIPS UTILIZING

0-10V CONTROL SCHEMES, NOT LONGER THAN 72” IN LENGTH, LOCATED ABOVE

REMOVABLE GRID CEILINGS. ALL MC CABLE SHALL BE PROVIDED WITH ANTI-SHORT

FITTINGS.

a. ACCEPTABLE MANUFACTURERS

• AFC – MC LUMINARY CABLE

• ENCORE – MC-LED LIGHTING CABLE

• SOUTHWIRE – MC-PCS DUO

GROUNDING

• PROVIDE GROUNDING AND BONDING OF ALL ELECTRICAL AND COMMUNICATION

APPARATUS, MACHINERY, APPLIANCES, BUILDING COMPONENTS, AND ITEMS REQUIRED

BY THE NEC TO PROVIDE A PERMANENT, CONTINUOUS LOW IMPEDANCE, GROUNDING

SYSTEM. PROVIDE AN NEC BONDING/GROUNDING CONDUCTOR IN ALL RACEWAYS USE

FOR POWER DISTRIBUTION.

SUPPORTING DEVICES

• PROVIDE SUPPORTS, ANCHORS, SLEEVES AND SEALS AS REQUIRED FOR A COMPLETE

RACEWAY SUPPORT SYSTEM, INCLUDING BUT NOT LIMITED TO: CLEVIS HANGERS, RISER

CLAMPS, C-CLAMPS, BEAM CLAMPS, ONE- AND TWO-HOLE CONDUIT STRAPS, OFFSET

CONDUIT CLAMPS, EXPANSION ANCHORS, TOGGLE BOLTS, THREADED RODS, U-CHANNEL

STRUT SYSTEM, AND ALL OTHER ASSOCIATED ACCESSORIES. INSTALL IN ACCORDANCE

WITH MANUFACTURER’S WRITTEN INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY

PRACTICES TO ENSURE SUPPORTING DEVICES COMPLY WITH REQUIREMENTS. PROVIDE

RIGID ATTACHMENT OF ALL FLOOR MOUNTED EQUIPMENT TO THE FLOOR SLAB OR

STRUCTURAL SYSTEM.

CONDUIT RACEWAYS

1. PROVIDE METAL CONDUIT, TUBING, AND FITTINGS OF TYPES, GRADES, SIZES, AND

WEIGHTS (WALL THICKNESS) AS REQUIRED; WITH MINIMUM TRADE SIZE OF 3/4”. INSTALL

ELECTRICAL RACEWAY SYSTEMS IN ACCORDANCE WITH MANUFACTURER’S WRITTEN

INSTRUCTIONS AND APPLICABLE REQUIREMENTS OF NEC AND NECA “STANDARD OF

INSTALLATION” IN ACCORDANCE WITH THE FOLLOWING:

A. FEEDERS: INSTALL FEEDERS RATED 100 AMPS AND GREATER, IN ELECTRICAL

METALLIC CONDUIT (EMT); WHERE BURIED BELOW GRADE, INSTALL IN CONCRETE

ENCASED N0N-METALIC CONDUIT OR DUCT (SCHEDULE 40 PVC).

B. BRANCH CIRCUITS, AND INDIVIDUAL EQUIPMENT CIRCUITS RATED LESS THAT 100

AMPS; INSTALL IN ELECTRICAL METALLIC TUBING (EMT). WHERE LOCATED IN

POURED WALLS, BELOW CONCRETE SLAB-ON-GRADE, OR IN EARTH FILL, INSTALL IN

NON-METALLIC PLASTIC DUCT (SCHEDULE 40 PVC). ENCASE NON-METALLIC PLASTIC

DUCT 1-1/4” AND LARGER IN CONCRETE.

C. PROVIDE RIGID METAL CONDUIT (RMC) FOR ALL BENDS IN BURIED CONDUIT

GREATER THAN 30 DEGREES. PROVIDE PROTECTIVE COATING FOR RIGID METAL

CONDUIT BENDS.

D. INSTALL FLEXIBLE CONDUIT FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND

OTHER ELECTRICAL EQUIPMENT WHERE SUBJECT TO MOVEMENT AND VIBRATIONS.

E. PROVIDE “OZ” EXPANSION FITTINGS ON ALL CONDUITS CROSSING BUILDING

EXPANSION JOINTS, BOTH IN SLAB AND SUSPENDED.

F. DUCT BANKS” PROVIDE DUCT BANK CONSTRUCTION AS INDICATED USING 3000 PSI

CONCRETE WITH RED MARKER DYE. INSTALL #4 REINFORCING BAR IN EACH

CORNER OF DUCT BANK. PROVIDE MINIMUM OF 4” CONCRETE COVER ON ALL SIDES

OF EXTERIOR CONDUITS.

ELECTRICAL BOXES AND FITTINGS

1. PROVIDE ONE PIECE GALVANIZED FLAT ROLLED SHEET STEEL INTERIOR OUTLET WIRING

BOXES, CORROSION-RESISTANT CAST-METAL WEATHERPROOF OUTLET WIRING BOXES,

CODE GAUGE SHEET STEEL JUNCTION AND PULL BOXES, GALVANIZED CAST IRON

CONDUIT BODIES, CORROSION-RESISTANT PUNCH-STEEL BOX KNOCKOUT CLOSURES,

CONDUIT LOCKOUTS AND MALLEABLE STEEL CONDUIT BUSHINGS AND OFFSET

CONNECTORS, AND ALL ACCESSORIES AS REQUIRED TO SUIT EACH RESPECTIVE

LOCATION AND INSTALLATION. FASTEN BOXES RIGIDLY TO SUBSTRATES OR

STRUCTURAL SURFACES TO WHICH ATTACHED, OR SOLIDLY EMBED ELECTRICAL BOXES

IN CONCRETE OR MASONRY. USE BAR HANGERS FOR STUD CONSTRUCTION.

2. FLOOR BOXES – PROVIDE LEVELING AND FULLY ADJUSTABLE FLOOR SERVICE

RECEPTACLE OUTLETS AND FITTINGS OF TYPE AND RATINGS AS INDICATED ON THE

DRAWINGS. ALL BOXES SHALL COMPLY WITH UL STANDARD UL514A.

ELECTRICAL SPECIFICATIONS

RACEWAY SYSTEMS

1. EXTENT OF RACEWAYS IS INDICATED BY DRAWINGS AND SCHEDULES.

2. COMPLY WITH APPLICABLE PORTIONS OF NEMA STANDARDS PERTAINING TO RACEWAYS.

COMPLY WITH APPLICABLE PORTIONS OF UL SAFETY STANDARDS PERTAINING TO

ELECTRICAL RACEWAY SYSTEMS AND PROVIDE PRODUCTS AND COMPONENTS WHICH

HAVE BEEN UL-LISTED AND LABELED. COMPLY WITH NEC REQUIREMENTS AS

APPLICABLE TO CONSTRUCTION AND…