Attachment 9 Revised Drawings.pdf
PDF 7 MB Posted
- Attached to
- New Farm Storage Building (Kimberly, ID)
- Solicitation number
- 12905B25R0005
About this file
These architectural and engineering drawings detail a new Farm Storage Building project for the USDA Agricultural Research Service in Kimberly, Idaho. The project involves constructing a pre-engineered metal building with a base bid of approximately 4,800 square feet, with an optional 1,200 square foot lean-to. The site plans include detailed demolition, utility, grading, structural, electrical, and fire alarm plans for the new facility.
Key technical specifications include a metal building with vinyl-faced insulation, 22-gauge PBR-style metal wall and roof panels, an 8-inch concrete slab, overhead doors, electrical infrastructure with a new 208V transformer and panel, and integration with an existing fire alarm system. The design accounts for local environmental conditions, with snow load calculations, wind speed ratings, and seismic design category considerations. The project is planned for completion in April 2025, with a site visit scheduled for April 3, 2025, and the estimated project cost between $500,000 and $1,000,000.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EP
EGEGEGEGEG
XXXXXX
EP
EP
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
EG
EGEGEG
EG
EG
XXXXXXX
X X
X X
X X
X X
X X
X
EG
EG
EG
EG
EGEG
EG
EG
EG
EG EG
EG
EG
EG
EG
UP
UP UP UP UP
OHP OHP OHP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
X X
X X
X
X X X X X
EXISTING BLDG 6 EXISTING BLDG 2
EX
IS
TI
NG
B
LD
G
X X X X X X X
FENCE TO BE REMOVED (BY OTHERS -NOT IN THIS CONTRACT).
CLEAR AND GRUB BUILDING LOCATION.
TREE AND BRUSH TO BE REMOVED (BY OTHERS - NOT IN THIS CONTRACT).
LOCATE AND PROTECT EXISTING UNDERGROUND ELECTRICAL SERVICE AND ALL OTHER
UTILITIES.
SAWCUT, REMOVE AND DISPOSE OF EXISTING ASPHALT PAVEMENT AND GRAVEL.
SALVAGE CLEAN GRAVEL AND STOCK ON SITE WHERE DIRECTED BY THE CONTRACTING
OFFICER.
3LINEAR DEMOLITION
DEMOLITION AND SITE PREP AREA
SAWCUT
LIMITS OF ANTICIPATED DISTURBANCE (APPROX 17,000
SF OR 13 ACRE)
BEG
END
SOIL SAMPLE LOCATION
SEE SOIL LOG SHEET C200
D-1 PROTECT ASSETS AND FINISHES NOT SHOWN TO BE REMOVED. ANY DAMAGE
CAUSED BY CONSTRUCTION OPERATIONS SHALL BE REPAIRED TO MATCH THE
EXISTING CONDITIONS AT NO COST TO THE GOVERNMENT.
D-2 AT A MINIMUM, PROVIDE 4' TALL, TEMPORARY ORANGE HIGH DENSITY POLYETHYLENE
SAFETY FENCE TO ISOLATE HAZARD AND CONSTRUCTION FROM UNAUTHORIZED
ACCESS.
D-3 CARE SHALL BE TAKEN IN ALL OPEN SUBGRADES TO PREVENT DETERIORATION
CAUSED BY WEATHER. DEWATER ALL OPEN SUBGRADES AS REQUIRED TO MAINTAIN
STABILITY.
D-4 THE CONTRACTOR SHALL CONTROL THE SPREAD OF DUST AND IRRITANTS TO OTHER
SPACES, ADJACENT BUILDINGS AND OUTSIDE OF DESIGNATED WORK AREAS.
D-5 THE CONTRACTOR SHALL PROVIDE CLEAN, STRAIGHT, NEAT CUTS FOR DEMOLITION
THAT MINIMIZE IMPACTS AND ADVERSE AFFECTS ON EXISTING FINISHES.
COORDINATE THE LOCATION OF THE CUTS TO ACCOMMODATE FINAL FINISHES.
D-6 THE REPAIR IS DESIGNED TO BE VIABLE IN ITS FULLY CONSTRUCTED, FINAL
CONFIGURATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THE SAFETY
AND STABILITY OF ALL COMPONENTS DURING CONSTRUCTION.
D-7 PRIOR TO THE THE CONSTRUCTION CONTRACT AWARD, THE USDA WILL RELOCATE
ALL MOBILE ASSETS AND INVENTORY TO A LOCATION THAT WILL NOT INHIBIT
CONSTRUCTION OPERATIONS.
D-8 ITEMS NOTED AS "NOT IN CONTRACT" WILL BE REMOVED PRIOR TO THE AWARD OF
THE CONSTRUCTION CONTRACT
D-9 BELOW THE NEW BUILDING, NEW PAVEMENT AND NEW GRAVEL FOOTPRINT, THE
CONTRACTOR SHALL STRIP ALL ORGANIC MATERIAL AND STOCKPILE (FOR USE AS
TOPSOIL). SCARIFY, STABILIZE AND COMPACT ALL BUILDING, PAVEMENT AND GRAVEL
PRIOR TO PLACING ANY ADDITIONAL FILL.
LIMITS OF ASPHALT PAVEMENT REMOVAL
PROPOSED
CONTRACTOR LAYDOWN
AREA
ALL WORK THIS SHEET IS PART OF THE BASE BID
TH1
U
D A
S
KIMBERLY, ID
1 04/2025 AEJ PPI CLARIFICATIONS
SCALE: 1" =
020 2010
20'
DEMO SITE PLAN1
SCALE: 1" = 20'C101
NORTH
DEMO SITE PLAN
C101
KEYED NOTES:
DEMOLITION NOTES:
LEGEND:
TH2
lhenderson kimberly
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
EG
EG
EG
EG
EG
EG EG
EG
UP
UP UP UP UP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
EXISTING BLDG 6 EXISTING BLDG 2
EX
IS
TI
NG
B
LD
G
NE
W
B
LD
G
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
UP
UP UP UP UP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
EX
IS
TI
NG
B
LD
G
NE
W
B
LD
G
SCALE: 1" =
020 2010
20'
BUILDING ADDITION
NEW FENCE (BY OTHERS - NOT IN THIS CONTRACT).
PROVIDE NEW PRE-ENGINEERED METAL BUILDING. (SEE ARCHITECTURAL).
PROVIDE NEW PRE-ENGINEERED METAL LEAN-TO. (BID OPTION - BO)
PROVIDE NEW 24' WIDE OVERHEAD DOOR (SEE ARCHITECTURAL).
PROVIDE NEW 114" WATERLINE. REDUCE AT BUILDING TO MATCH PLUMBING. (2/C201 & 5/C201).
PROVIDE WATER VALVE (4/C201).
EXISTING WATER VALVE WITH CAPPED 114" TERMINATION. ANTICIPATED POINT OF WATER CONNECTION. (FIELD
VERIFY MATERIAL AND LOCATION PRIOR TO BEGINNING WORK).
PROVIDE GAS SERVICE VALVE IN VALVE BOX.
PROVIDE A NATURAL GAS LOCKING WING COCK, PRESSURE REGULATOR.
PROVIDE NEW 1-1/4" POLYETHYLENE GAS PIPE. ANTICIPATED TIE TO EXISTING 4" (1#) GAS LINE (FIELD VERIFY
MATERIAL AND LOCATION PRIOR TO BEGINNING WORK).
PROVIDE NEW GRAVEL PAVEMENT FROM BUILDING FACE TO TIE TO SURROUNDING PAVEMENT SURFACES/GRADE.
PROVIDE NEW BOLLARDS AT LOCATIONS INDICATED. (3/C201).
BEG
END
BEG
END
GRAVEL
NEW WATER VALVE VW
NEW WATER LINE
12 12
BO
VW
TIE (END)
BEG
NEW GAS LINE
U-1 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE LOCAL UTILITY COMPANY, OBTAIN ALL REQUIRED PERMITS AND PAY ALL ASSOCIATED FEES.
U-2 WORK PERFORMED ON THE SERVICE SHALL BE PERFORMED BY AN APPROVED UTILITY CONTRACTOR FOR THE RELATED WORK. WHERE IN CONFLICT, THE
CONTRACTOR SHALL COMPLY WITH THE MORE STRINGENT OF THE UTILITY OR DESIGN DOCUMENT REQUIREMENTS.
U-3 SEE MECHANICAL AND ELECTRICAL PLANS FOR ADDITIONAL DETAILS ON NATURAL GAS AND ELECTRICAL SERVICE.
U-4 THE CONTRACTOR SHALL PROVIDE AN ACCURATE AS-BUILT DRAWING OF ALL UNDERGROUND INSTALLED UTILITIES TO THE OWNER ON A 24"X36" PLAN SHEET.
DETAILS SHALL INCLUDE, AT A MINIMUM; SIZES, DIMENSIONS FROM VISIBLE SITE FEATURES AND DEPTH OF BURY.
U-5 NEW GAS AND WATER LINES CAN BE LOCATED ADJACENT IN TRENCH AT CONTRACTOR'S OPTION.
VG
VGNEW GAS VALVE
VW
ALL WORK THIS SHEET IS PART OF THE BASE BID
G-1 AT THE COMPLETION OF GRADING, THE CONTRACTOR SHALL SPREAD 4" TOPSOIL ON ALL DISTURBED UNIMPROVED AREAS AS REQUIRED TO ESTABLISH
VEGETATIVE COVER. AT THE COMPLETION OF THE PROJECT, HAUL EXCESS MATERIAL OFF SITE.
G-2 TEMPORARY SEED OR STABILIZE ALL AREAS OF EXPOSED EARTH THAT ARE PLANNED TO BE UNFINISHED OR UNWORKED FOR A PERIOD EXCEEDING 14 DAYS.
NOTE:
SEE 2/C102 FOR REQUIRED PAVEMENT
IMPROVEMENTS
TH2
SOIL BORING
EP EP
EG EG
EDGE OF PAVEMENT
EDGE OF GRAVEL
BO
BO
U
D A
S
KIMBERLY, ID
1 04/2025 AEJ PPI CLARIFICATIONS
NEW SITE/UTILITY PLAN
C102
NEW SITE/UTILITY PLAN1
SCALE: 1" = 20'C102
NORTH
PAVEMENT SURFACING PLAN2
SCALE: 1" = 20'C102
NORTH
KEYED NOTES:LEGEND (PROPOSED):
GENERAL NOTES:
UTILITY NOTES:
TH1
TH1
EP
EP
EP
EGEGEGEGEG
EP TOPTOP TOPTOP
XXXXXXXX
EP
EP
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
EG
EGEGEG
EG
EG
XXXXXXX
X X
X X
X X
X X
X X
X
EG
EG
EG
EG
EGEG
EG
EG
EG
EG EG
EG
EG
EG
EG
UP
UP UP UP UP
OHP OHP OHP OHP OHP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
X X
X X
X
X X X X X X X X X
EXISTING BLDG 6 EXISTING BLDG 2
EX
IS
TI
NG
B
LD
G
X X X X X X X
SCALE: 1" =
020 2010
20'
PROP FF =
3913.8
3913NEW CONTOUR
SPOT ELEVATION 3913.8
FE =
3913.5
FE =
3913.5
GRADE TO
DRAIN
GRADE TO
DRAIN
ALL WORK THIS SHEET IS PART OF THE BASE BID
GRADE SWALE
PAVEMENT
LIMITS
U
D A
S
KIMBERLY, ID
1 04/2025 AEJ PPI CLARIFICATIONS
GRADING PLAN
C103
GRADING PLAN1
SCALE: 1" = 20'C103
NORTH
LEGEND (GRADING):
TH1
TH2
11 2 3 4
A
B
C
1. THE BUILDING SHALL BE A PRE-ENGINEERED BUILDING AS SPECIFIED IN SPECIFICATION SECTION 13 34 19, "METAL BUILDING SYSTEMS". THE BUILDING SHALL BE A MANUFACTURER'S STANDARD PREFABRICATED METAL STRUCTURE OF THE INSIDE AREA SHOWN. OVERALL DIMENSIONS AND CONSTRUCTION DETAILS MAY VARY TO
SUIT MANUFACTURER'S STANDARD DESIGN.
2. THE BUILDING SHALL BE DESIGNED AND FABRICATED ACCORDING TO AISC (AMERICAN INSTITUTE OF STEEL CONSTRUCTION) AND AISI (AMERICAN IRON AND STEEL INSTITUTE) LATEST SPECIFICATIONS. THE
DIMENSIONAL TOLERANCES OUTLINED IN THE AWS (AMERICAN WELDING SOCIETY) CODE UNDER
WORKMANSHIP AND THE TOLERANCES APPLICABLE TO ROLL FORM STEEL UNDER THE AISC "STANDARD MILL PRACTICE" SECTION SHALL BE REQUIRED IN THE FABRICATION OF THE STEEL BUILDING FRAMES.
3. DETAILS SHOWN ON THESE CONSTRUCTION DRAWINGS ARE THE ENGINEER OF RECORD'S ESTIMATE OF REQUIREMENTS BASED ON ANTICIPATED METAL SYSTEMS AND CONFIGURATION. THE FINAL SYSTEMS SHALL BE PROVIDED IN A DELEGATED DESIGN PROVIDED BY A LICENSED ENGINEER EMPLOYED BY THE CONTRACTOR/MANUFACTURER. PROVIDE A COMPLETE DESIGN ANALYSIS SHOWING ALL CALCULATIONS FOR THE RIGID FRAMES, GIRTS, AND PURLINS, MODIFIED FOUNDATION REQUIREMENTS, LAYOUT OF ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE SUBMITTED FOR APPROVAL WITH THE SHOP DRAWINGS. SHOP DRAWINGS SHALL INCLUDE DETAILS OF ALL MAIN MEMBERS, TYPICAL CONNECTIONS (SHOWING BOLT HOLES
AND WELDS), AND ERECTION DRAWINGS.
4. THE BUILDING SHALL BE DESIGNED TO SUPPORT ALL FLOORS, DOORS, EQUIPMENT AND ALL OTHER DEVICES.
ADDITIONAL STRUCTURAL STEEL, GIRTS OR PURLINS SHALL BE PLACED IN CONVENIENT LOCATIONS FOR
ATTACHMENT OF ALL EQUIPMENT AND DEVICES.
5. CROSS BRACING WILL NOT BE ALLOWED IN THE WALLS OR AT LEAN-TO COLUMNS. USE PORTAL FRAMES FOR
LATERAL LOAD TRANSFER IN VERTICAL STRUCTURAL MEMBERS.
6. THE FOUNDATIONS SHOWN ARE ESTIMATES FOR THE BUILDING TYPE SHOWN ON THE DRAWINGS AND ARE TO BE USED AS A GUIDE FOR THE BUILDING SUPPLIED. THESE FOUNDATIONS ARE SIZED FOR THE VALUES SHOWN IN THE "FOUNDATION REACTION DIAGRAM". THE CONTRACTOR'S ENGINEER SHALL DESIGN THE FOUNDATIONS
FOR THE SPECIFIC LOADS FOR THE BUILDING SUPPLIED.
7. THE CONTRACTOR SHALL USE IN HIS DESIGN THE BASIC CRITERIA SHOWN BY THIS DRAWING, SUCH AS SLAB
THICKNESS, CONTROL JOINTS, DESIGN LOADS AND MINIMUM DEPTH OF FOOTING.
8. FOOTINGS SHALL BE SIZED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 1300 PSF. THE ALLOWABLE SOIL PRESSURE IS BASED UPON A GEOTECHNICAL REPORT PREPARED BY HLE, INC.(BLACKFOOT, ID) DATED JULY 2, 2019.
9. DESIGN THE BUILDING SYSTEM FOR THE LIVE LOADS OR SNOW LOADS (WHICHEVER IS GREATER) INDICATED AND A COLLATERAL LOAD OF 5 PSF IN ADDITION TO THE BUILDING DEAD LOADS, WIND LOADS AND SEISMIC LOADS. PARAMETERS FOR THE DEVELOPMENT OF THE SNOW, WIND AND SEISMIC LOADS ARE LISTED IN THE DESIGN LOAD SUMMARY ON THIS SHEET. ROOF PURLINS SHALL BE DESIGNED FOR AN ADDITIONAL CONCENTRATED LIVE LOAD OF 300 POUNDS LOCATED ANYWHERE ALONG THE LENGTH OF THE PURLIN.
10. ALL CONCRETE SHALL CONFORM TO ACI (AMERICAN CONCRETE INSTITUTE) 301 AND SHALL DEVELOP A
MINIMUM COMPRESSIVE STRENGTH (F'C) OF 3500 PSI @ 28 DAYS.
11. CONCRETE COVER ON REINFORCEMENT SHALL BE AS FOLLOWS:
CONCRETE CAST AGAINST EARTH 3 INCHES
CONCRETE EXPOSED TO EARTH OR WEATHER 2 INCHES CONCRETE SLABS
2 INCHES
12. REINFORCING STEEL SHALL BE ASTM A 615, GRADE 60 FOR BARS OR ASTM A 185 FOR WELDED WIRE FABRIC.
REINFORCING STEEL SHALL BE LAPPED AS SPECIFIED IN ACI 318-02.
13. GROUT SHALL BE NON-SHRINK WITH COMPRESSIVE STRENGTH (F'C) OF 4500 PSI @ 28 DAYS.
14. PROVIDE VAPOR BARRIER (ASTM E1745) OVER A 6 INCH CAPILLARY (WASHED STONE (NO. 57)) BARRIER UNDER
SLABS.
15. PROVIDE A BY-PASS OR OUTSET MOUNTED GIRT SYSTEM TO FACILITATE ARCHITECTURAL FEATURES.
PRE-ENGINEERED METAL BUILDING AND STRUCTURAL NOTES:
HORIZONTAL MIDDLEHM
VALUES WITH (-) SIGN ACT IN OPPOSITE (2)
FOUNDATION REACTION DIAGRAM (MAX. VALUES)
DIRECTION OF ARROWS IN DIAGRAMS
VERTICAL MIDDLE
VERTICAL LEFT
VERTICAL
NOT TO SCALE
V
VL
VM
MAXIMUM ESTIMATED REACTIONS
ALL VALUES ARE IN KIPS (1000 LBS).
-3
VL+
(1) ±1
HL
HL+
HORIZONTAL
HORIZONTAL LEFT
ABBREVIATIONS
7.6
VL
-10.3
HR
±7.6
VR
13.7
H
HL
VR+
HR+
(3) NO MOMENTS SHALL BE TRANSFERRED FROM THE
METAL BUILDING SYSTEM TO THE FOUNDATION
FOR SOIL BORING INFORMATION SEE GEOTECHNICAL ENGINEERING REPORT 'PROPOSED FARM
SHOP BUILDING' PREPARED BY HLE, INC. DATED JULY 2, 2019 INCLUDED WITH SOLICITATION REFERENCE DOCUMENTS. SEE CIVIL SHEET FOR BORING LOCATIONS AND SOIL BORING PROFILES.
ASCE-7 (16)
MINIMUM DESIGN LOAD SUMMARY
RISK CATEGORY 'II'
WIND
WIND SPEED103 VMPH
10-YEAR MRI 72 VMPH
25-YEAR MRI78 VMPH
50-YEAR MRI83 VMPH
100-YEAR MRI88 VMPH
SEISMIC
SOIL CLASS 'D'
SS 0.21
S1 0.081
FA 1.6
FV 2.4
SMS 0.336
SM1 0.195
SDS 0.224
SD1 0.13
TL 6
PGA 0.084
PGAM 0.127
FPGA 1.6
LE 1
CV 0.7
SEISMIC DESIGN CATEGORYB
ICE
THICKNESS 0.25 IN.
CONCURRENT TEMPERATURE 15 F
GUST SPEED40 MPH
SNOW
GROUND SNOW LOAD, PG14 LB/FT2
GROUND SNOW LOAD, PG14 LB/FT2 (3924.0 FT)
ELEVATION 3917.2 FT
RAIN
ANNUAL = APPROX 12 INCHES
5 MIN, 25 YR = 6 INCHES/HR
FLOOD
FLOOD ZONEX (UNSHADED)
STATIC BFE REFER TO MAP 16083C1425C (9/26/2008).
24'
OHD
20'
3'
SLAB ON GRADE
20'-10"
24'
OHD
ANY STRUCTURAL FILL SHALL BE IN ACCORDANCE WITH THE STRUCTURAL FILL PORTION OF THE
GEOTECHNICAL REPORT AND BE COMPACTED TO A MINIMUM 95% OF THE MAXIMUM DENSITY AS
DETERMINED BY ASTM D-1557.
PLACEMENT OF ANY FILL MATERIAL BENEATH THE FOOTING ELEVATION, IF NECESSARY, SHOULD BE ACCOMPLISHED WITH A GW OR GP CLASS SANDY GRAVEL MATERIAL, PLACED IN LIFTS NOT EXCEEDING 8 INCHES AND COMPACTED TO A MINIMUM OF 95% OF OPTIMUM DRY DENSITY AS DETERMINED BY ASTM
D-1557 "MODIFIED PROCTOR."
A QUALIFIED INSPECTOR APPROVED BY THE CONTRACTING OFFICER SHOULD VERIFY THE COMPACTION.
PROVIDE THE CONTRACTING OFFICER WITH THE INSPECTOR'S CREDENTIALS A MINIMUM 7 DAYS PRIOR
TO BEGINNING WORK.
ALL EARTHWORK SHALL BE PERFORMED TO THE MORE STRINGENT REQUIREMENTS OF THE CONTRACT
DOCUMENTS OR THE GEOTECHNICAL REPORT.
SUBSURFACE SOIL
Soil Classification TEST HOLES ENCOUNTERED Depths Encountered Net Allowable Bearing
Capacity(FS=3)
Asphalt/Crushed Gravel TH # 1,2 0.0 - 0.5 feet -
Silt (ML) TH # 1,2 0.5 - 7.5 feet 1,300 lbs/ft²
Caliche Hardpan TH # 1,2 7.5 - 11.0 feet 3,000 lbs/ft²
Basalt TH # 1,2 11.0 - 12.0 feet (refusal) 6,000 lbs/ft²
VM+
HM+
HORIZONTAL RIGHTHR
VERTICAL RIGHTVR
-13.3±8.6
HM
19.3
VM
LEAN-TO
A.B.I.
MAIN
BUILDING
ENCLOSURE
CONTROL
(CONTRACTION) JOINT
TYP.
FOUNDATION MARK,
F3
F3 F3 F3
FINISHED FLOOR
≈ 3913.8'
3/4" 3/4"
BOLLARD, TYP. ( SEE CIVIL)
OVERHEAD
DOOR
RECESS
OVERHEAD DOOR RECESS
LEAN-TO
INTERIOR GRADE BEAM,
SEE 2/S101
GRADE BEAM, SEE
2/S101
TIE BEAM, (SEE
5/S101)
BOLLARD, TYP. (SEE
CIVIL AND 3/C201)
F2 F1 F1 F2
F2 F1 F1 F2
MAIN FAN SUPPORT PROVIDE INSET (2) 8ZS2.25X85
PURLINS FULLY SPANNING BETWEEN CENTER BAY OF
BUILDING FRAME.
PROVIDE INSET (2) 6ZS2.25X65 FOR FAN SUPPORT
BETWEEN 8ZS2.25X85 PURLINS
GUY PER
MANUFACTURER'S
WRITTEN
REQUIREMENTS
(NOT IN CONTRACT)
HIGH SPEED LOW
VOLUME FAN (130#, MAX)
(NOT IN CONTRACT)
BASE BID BASE BID
SEE DETAIL 3/S101
EXTERIOR GRADE BEAM, TYP.
(SEE 1/S101)
SEE DETAIL 3/S101
BID OPTION
BID OPTION
SUPPLEMENTAL ROOF FRAMING - (2)
8ZS2.25X85 ZEE (MAIN) AND (2)
6ZS2.25X65 ZEES (INSET OR FLUSH TO
FRAMING) SEE 2/S001.
4' 4'
U
D A
S
KIMBERLY, ID
1 04/2025 AEJ PPI CLARIFICATIONS
STRUCTURAL NOTES
S001
08' 8'
1'-0"
4'
SCALE: 1/8" = 1'-0"
06' 6'3'
SCALE: 3/16" =
APPROXIMATED STRUCTURAL SECTION2
SCALE: 1/8" = 1'-0"S001
GENERAL LAYOUT1
SCALE: 1/8" = 1'-0"S001
GEOTECHNICAL ENGINEERING (SOIL BORING) REPORT:
INTERIOR METAL
WALL LINER
PANEL WITH
CLOSURE TRIM,
SEE GENERAL
NOTE B
STRAIGHT SIDEWALL
COLUMNS
8" WALL GIRTS
VINYL FACED R-13
METAL BUILDING
INSULATION
22 GAUGE 'PBR' STYLE
METAL WALL PANEL WITH
EXPOSED FASTENER, SEE
GENERAL NOTE C
VINYL FACED R-19
METAL BUILDING
INSULATION
22 GAUGE 'PBR' STYLE METAL ROOF
PANEL WITH EXPOSED FASTENERS'PBR' DIE-FORMED METAL RIDGE CAP
8" CONCRETE SLAB (SEE
STRUCTURAL)
METAL GUTTER (TYP.)
PROVIDE BIRD CONTROL SYSTEM @
UNDERSIDE OF LEAN TO, ATTACH TO
BOTTOM OF EXPOSED STEEL
STRUCTURE (BID OPTION) (**SEE
NOTE ON A201)
' E
AV
E
HE
IG
HT
8" EAVE STRUT
8" ROOF PURLINS WITH R-5
THERMAL SPACER BLOCK
FASTENED TO TOP OF PURLINS,
TYP. FOR ALL
8" EAVE STRUT
24' BY 16' INSULATED, HEAVY
DUTY OVERHEAD SECTIONAL
STEEL DOOR
METAL GUTTER
WITH SUPPORT
STRAP (BID OPTION)
A501
8" CONCRETE SLAB (SEE
STRUCTURAL)
INTERIOR METAL
WALL LINER PANEL,
SEE GENERAL NOTE B
STRAIGHT
SIDEWALL
COLUMNS
8" WALL GIRTS
VINYL FACED R-13 METAL
BUILDING INSULATION
RAKE TRIM FASTENED
WITH STITCH SCREW
SPACED EVERY 12"
WITH CONTINUOUS
TAPE SEAL (TYP.)
COLUMNS BEYOND (SEE
STRUCTURAL)
22 GAUGE 'PBR' STYLE ROOF PANEL WITH
EXPOSED FASTENERS
VINYL FACED R-19
METAL BUILDING
INSULATION
20'
BID OPTION
BID OPTIONBASE BID
GUTTER AND DOWNSPOUT TO
MATCH OPPOSITE SIDE IF BID
OPTION IS NOT EXECUTED
EYE WASH,
SEE PLUMBING
PERSONNEL DOOR
AND FRAME (BID
OPTION)
A501
A501
A501
22 GAUGE 'PBR' STYLE
METAL WALL PANEL WITH
EXPOSED FASTENER, SEE
GENERAL NOTE C
8" ROOF PURLINS WITH R-5
THERMAL SPACER BLOCK
FASTENED TO TOP OF PURLINS,
TYP. FOR ALL
U
D A
S
KIMBERLY, ID
BUILDING SECTIONS
A301
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
SCALE:
SECTION
1/4" = 1'-0"
A301
SCALE:
SECTION
1/4" = 1'-0"
A301
GENERAL NOTES
A. ALL EXPOSED STRUCTURAL STEEL MUST BE PAINTED,
SEE SPEC SECTION 09 90 00. COLOR TO BE DETERMINED
BY OWNER/USER.
B. INTERIOR METAL LINER PANEL TO BE MIN.12' HIGH (BASED
ON WALL GIRT SPACING AS DESIGNED BY PEMB
MANUFACTURER). LINER PANEL MUST MATCH PROFILE
AND GAUGE OF EXTERIOR WALL PANEL. COLOR TO BE
DETERMINED BY A/E AND COR.
C. PROVIDE MIN. 1/4" SELF-ADHERING THERMAL BREAK TAPE
AT ALL GIRTS, EAVE STRUTS, AND BASE ANGLES.
1 04/2025 JTP PPI CLARIFICATIONS
VINYL FACED
INSULATION
8" "C" CHANNEL
METAL WALL PANEL
METAL TRIM
SEALANT W/BACKER ROD
LOUVER (SEE MECHANICAL)
1-1/2"x 1-1/2"x 1/8" ANGLE CONT.
1-1/2"x 1-1/2"x 1/8" ANGLE CONT.
LOUVER (SEE MECHANICAL)
METAL "J" TRIM
8" "C" CHANNEL
VINYL FACED
INSULATION
METAL WALL PANEL
3-1/2" VINYL FACED
INSULATION
8" "C" CHANNEL
METAL WALL PANEL
METAL SILL TRIM
SEALANT W/BACKER ROD
LOUVER (SEE MECHANICAL)
1-1/2"x 1-1/2"x 1/8" ANGLE CONT.
HEAD
SILL
JAMB
1"
5 1/4"
1 1 /2"
7"
PROVIDE 22 GAUGE 'PBR' STYLE
METAL WALL PANEL WITH
EXPOSED FASTENER OVER VINYL
FACED INSULATION
8" WALL GIRTMETAL FRAME 2"
SEALANT
DOOR AS SCHEDULED
JAMB ANCHOR
SILL
DOOR AS SCHEDULED
PROVIDE 22 GAUGE 'PBR' STYLE METAL
WALL PANEL WITH EXPOSED FASTENER
1/2" EXPANSION
MATERIAL
EXISTING
FOUNDATION
THRESHOLD SET IN BED OF SEALANT
W/MIN. (3) 1/4" DIA. ANCHORS
DOOR SWEEP
RAIN DRIP
HEAD/JAMB
RAKE TRIM
STITCH SCREW AT 12" O.C. (TYP.) CONTINUOUS TAPE SEAL
22 GAUGE 'PBR' STYLE
ROOF PANEL WITH
EXPOSED FASTENERS
STITCH SCREW AT
12" O.C. (TYP.)
CLOSURE
22 GAUGE 'PBR' STYLE
METAL WALL PANEL
(SEE GENERAL NOTE C
ON SHEET A301)
'PBR' DIE-FIRMED METAL RIDGE CAP
22 GAUGE 'PBR' STYLE
ROOF PANEL WITH
EXPOSED FASTENERS
8" ROOF
PURLINS TYP.
TAPE SEALER (EACH SIDE)
RIDGE ℄
'TYPE AB' SELF-TAPPER WITH
WASHER (6 PER PANEL)
THERMAL SPACER BLOCK
(MIN. R-5) TYPICAL AT ALL
PURLIN TO ROOF PANEL
CONNECTION POINTS 6"x6" METAL
GUTTER (TYP.)
8" EAVE STRUT (WALL
INSULATION TO EXTEND TO
TOP OF EAVE STRUT)
22 GAUGE 'PBR' STYLE METAL
WALL PANEL (SEE GENERAL
NOTE C ON SHEET A301)
22 GAUGE 'PBR' STYLE
ROOF PANEL WITH
EXPOSED FASTENERS
GUTTER STRAP
@ 3'-0" O.C. MAX.
INSIDE CLOSURE
OUTSIDE CLOSURE
22 GAUGE 'PBR'
STYLE WALL PANEL
STRAIGHT SIDEWALL
COLUMN
VINYL FACED R-13
METAL BUILDING
INSULATION
INTERIOR METAL
WALL LINER PANEL,
SEE GENERAL NOTE B
ON SHEET A301
BASE TRIM
BASE ANGLE
12 - 14 X 1-1/4 LONG-LIFE
SELF-DRILLER WITH
WASHER (6 PER PANEL)
METAL "J" TRIM
COILING DOOR
AS SCHEDULED
METAL WALL PANEL
8" "C" CHANNEL
3"x 3"x 14" CLIP ANGLE
SECTIONAL
OVERHEAD
DOOR AS
SCHEDULED
JAMB
SILL
VINYL FACED
INSULATION
METAL TRIM
SLOPED BOTTOM BAR TO
MATCH EXISTING FLOOR
SLOPE
U
D A
S
KIMBERLY, ID
DETAILS
A501
GRAPHIC SCALE
SCALE:
LOUVER HEAD/JAMB/SILL DETAILS
3" = 1'-0"
A501
SCALE:
EXTERIOR DOOR HEAD/JAMB/SILL DETAILS
1-1/2" = 1'-0"
A501 SCALE:
RAKE TRIM DETAIL
1-1/2" = 1'-0"
A501
SCALE:
ROOF RIDGE DETAIL
1-1/2" = 1'-0"
A501 SCALE:
GUTTER DETAIL
3" = 1'-0"
A501
08" 8"
1'-0'SCALE: 1-1/2" =
4"
04" 4"
1'-0'SCALE: 3" =
2"
SCALE:
WALL BASE DETAIL
1-1/2" = 1'-0"
A501
SCALE:
OVERHEAD DOOR DETAILS
1-1/2" = 1'-0"
A501
1 04/2025 JTP PPI CLARIFICATIONS
7LA
6A
FA
CP
U
D A
S
KIMBERLY, ID
E001
ABBREVIATIONS AND GENERAL NOTESBSN
1. ALL EQUIPMENT AND DEVICES ARE TO BE SURFACE
MOUNTED UNLESS OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT
CIRCUIT INTERRUPTING DEVICES.
3. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF
WHILE-IN-USE.
4. DEVICES NOTED AS "NL" SHALL BE NIGHT LIGHTS. PROVIDE
UNSWITCHED POWER TO FIXTURE.
5. DEVICES NOTED AS "WG" SHALL BE PROVIDED AND
INSTALLED WITH A WIRE GUARD.
6. PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY
PACKS.
GENERAL NOTES
LUMINAIRES
GEAR
E
HIGH BAY LED FIXTURE
EXIT SIGN WITH EMERGENCY LIGHTING
WALL MOUNTED FIXTURE
PANELBOARD
TRANSFORMER
? NEMA 3R-SS SAFETY SWITCH, AMPERAGE IDENTIFIED.
RECEPTACLES
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18"
A.F.F. TO CENTERLINE OF BOX UNLESS NOTED
OTHERWISE.
DUPLEX RECEPTACLE, NEMA 5-20R, GFCI, WPIU,
MOUNTED 18" A.F.F. TO CENTERLINE OF BOX UNLESS
NOTED OTHERWISE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, ONE
COVER PLATE, MOUNTED 18" A.F.F. TO CENTERLINE
OF BOX UNLESS NOTED OTHERWISE.
RECEPTACLE 3P, 4W, 208/120V, 50A, TWIST-LOCK,
MOUNTED 48" A.F.F. TO CENTERLINE OF RECEPTACLE
UNLESS NOTED OTHERWISE.
LIGHT FIXTURES
HIGH BAY LED FIXTURE
WALL MOUNT LED FIXTURE
2X2 LED FIXTURE
EMERGENCY EXIT SIGN/LIGHTE
M
FIRE ALARM SYSTEM
MANUAL PULL STATION. MOUNT 48" A.F.F. TO
CENTERLINE OF BOX.
STROBE. MOUNT 80" A.F.F. TO BOTTOM OF BOX
COMBINATION HORN AND STROBE. MOUNT 80" A.F.F.
TO BOTTOM OF BOX.
SMOKE DETECTOR
THERMAL DETECTOR
FIRE ALARM CONTROL PANEL
Voltage Circuit Length Conductor Size (AWG)
120 < 90' #12
120 > 90' #10
120 > 145' #8
120 > 230' #6
VOLTAGE DROP CHART NOTES:
1) CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM
REQUIREMENTS. REFER TO THIS CHART FOR UPSIZING
CONDUCTORS AS NEEDED.
2) DO NOT CONNECT CONDUCTORS LARGER THAN #10 DIRECTLY TO
A RECEPTACLE OR A SWITCH. PROVIDE A JUNCTION BOX TO
DOWNSIZE THE CONDUCTOR TO #12 AT THE DEVICE.
VOLTAGE DROP CHART
Panel Name:7LA MLO OR MCB:MCB Panel Location:BLDG 7 SURFACE OR FLUSH:SURFACE
Voltage120/208V FRAME AMPS:225A Phase/Wire:3PH/4W GROUNDING:EQUIPMENT GROUND
Min Interrupt Rating:22,000A SECTIONS:ONE SECTION - 42X New/Existing:NEW NEMA RATING:NEMA 1
LOAD VA BRANCH LOAD DATA BREAKER # PH # BREAKER BRANCH LOAD DATA LOAD VA
A B C TRIP POLE TRIP POLE A B C
720 RECEP - NW INTERIOR 20 1 1 A 2
50 3 50A RECEPTACLE
WEST WALL
720 RECEP - SW INTERIOR 20 1 3 B 4 5633
720 RECEP - NE INTERIOR 20 1 5 C 6 5633
720 RECEP - SE INTERIOR 20 1 7 A 8
50 3 50A RECEPTACLE
WEST WALL
720 RECEP - SHED 20 1 9 B 10 5633
360 RECEP - N EXTERIOR 20 1 11 C 12 5633
360 RECEP - S EXTERIOR 20 1 13 A 14
50 3 50A RECEPTACLE
EAST WALL (1)
1284 LIGHTS - INTERIOR 20 1 15 B 16 0
720 LIGHTS - EXTERIOR 20 1 17 C 18 0
516 LIGHTS - SHED (2) 20 1 19 A 20
50 3 50A RECEPTACLE
EAST WALL (1)
500 FACP 20 1 21 B 22 0
780 EF-1 20 1 23 C 24 0
780 EF-2 20 1 25 A 26 20 1 EQUIP - GH-1,2,3,4 1000
SPARE 20 1 27 B 28 20 1 EQUIP - L1 & L2 320
SPARE 20 1 29 C 30 20 1 EQUIP - WH 1500
SPARE 20 1 31 A 32
15 3 EQUIP - OH DOOR 1
SPARE 20 1 33 B 34 933
SPARE 20 1 35 C 36 933
SPARE 20 1 37 A 38
15 3 EQUIP - OH DOOR 2
SPARE 20 1 39 B 40 933
SPARE 20 1 41 C 42 933
3096 3224 2580 SUM PER PHASE (VA) LEFT SIDE SUM PER PHASE (VA) RIGHT SIDE 14133 13453 14633
17229 16677 17213 SUM PER PHASE (VA) PANEL
3% LOAD BALANCE
144 LARGEST PHASE LOAD
MINIMUM FEEDER RATING
NOTES:
1 - LOAD ANALYSIS IS BASED ON USER INPUT THAT NO MORE THAN TWO WELDERS WILL BE IN USE AT ANY TIME.
2 - BID OPTION
Panel Name:6A MLO OR MCB:MCB Panel Location:BLDG 6 SURFACE OR FLUSH:SURFACE
Voltage 277/480V FRAME AMPS:225A Phase/Wire:3PH/4W GROUNDING:EQUIPMENT GROUND
Min Interrupt Rating:22,000A SECTIONS:ONE SECTION - 54X New/Existing:EXISTING NEMA RATING:NEMA 1
LOAD VA BRANCH LOAD DATA BREAKER # PH # BREAKER BRANCH LOAD DATA LOAD VA
A B C TRIP POLE TRIP POLE A B C
EXIST 6LA
(EXISTING) 100 1
1 A 2
125 3 PANEL 7LA
(NEW)
17229
EXIST 3 B 4 16677
EXIST 5 C 6 17213
0 0 0 SUM PER PHASE (VA) LEFT SIDE SUM PER PHASE (VA) RIGHT SIDE 17229 16677 17213
17229 16677 17213 SUM PER PHASE (VA) PANEL
3% LOAD BALANCE
62.19975933 LARGEST PHASE LOAD
MINIMUM FEEDER RATING
SCALE:
SITE ELECTRICAL PLAN
1" = 20'
E001
UNDERGROUND SERVICE FROM
EXISTING PANEL 6A TO NEW PANEL 7A.
2" (4)1/0, #6(G)
1"C FOR FIRE ALARM SIGNALING
PATHWAY. INTEGRATE NEW FIRE ALARM
COMPONENTS INTO EXISTING FIRE
ALARM LOCATED IN BUILDING 1.
1. BASIS OF DESIGN SHOWN TO ESTABLISH A STANDARD
OF QUALITY AND PERFORMANCE, NOT TO LIMIT
COMPETITION. EQUIVALENT EQUIPMENT FROM OTHER
MANUFACTURERS SHALL BE ACCEPTABLE.
2. EQUIPMENT SHOWN MAY NOT BE MANUFACTURED IN
THE USA, HOWEVER, ALL EQUIPMENT FURNISHED FOR
THIS PROJECT MUST COMPLY WITH THE "BUY
AMERICAN ACT".
GENERAL NOTES
1. NEW UNDERGROUND SERVICE FROM EXISTING SHOP
BUILDING 6.
2. PROVIDE NEW INITIATION AND ANNUNCIATION
DEVICES AND INTEGRATE INTO EXISTING FIRE ALARM.
REFER TO E104.
KEYED NOTESX
T75
XFMR
XFMR
225A
MLO
208V
7LA
SCALE:
SINGLE LINE DIAGRAM
N.T.S.
E001
250A
MLO
480V
6A
THREE PHASE DRY-TYPE TRANSFORMER SCHEDULE
TAG
PRIMARY SECONDARY
GROUNDING
ELECTRODE
NOTES
ELECTRICAL
CHARACTERISTICS FEEDER ELECTRICAL CHARACTERISTICS FEEDER
kVA VOLTS FLA OCP KEY VOLTS FLA IMPED-
ANCE
Available
SSC OCP KEY KEY
T75 75 480∆ 90 125A 125A3G 208Y/120V 208 3.00% 6,939 225A 225A4BJ 2GEC
GENERAL REQUIREMENTS:
A SUBMITTALS SHALL INCLUDE (AS A MINIMUM): RATED NAMEPLATE DATA, CAPACITIES, WEIGHTS, DIMENSIONS, WIRING DIAGRAMS, HEAT OUTPUT, MINIMUM
CLEARANCES, INSTALLED DEVICES AND FEATURES, AND PERFORMANCE FOR EACH TYPE AND SIZE OF TRANSFORMER INDICATED.
B OPERATION AND MAINTENANCE MANUALS SHALL INCLUDE (AS A MINIMUM): OPERATING AND MAINTENANCE PROCEDURES, COMPLETE SET OF MANUFACTURER'S
DRAWINGS AND PRODUCT DATA, AND DATA SHEETS UPDATED TO REFLECT FIELD INSTALLATION CONDITIONS.
E TRANSFORMERS SHALL COMPLY WITH IEEE C57.12.91.
F WHERE FLOOR MOUNTED, COORDINATE SIZE AND LOCATION OF 4 INCH HIGH CONCRETE BASE WITH ACTUAL TRANSFORMER PROVIDED. CAST ANCHOR BOLT
INSERTS INTO BASES.
H TRANSFORMER ENCLOSURES SHALL BE VENTILATED NEMA 2 OR OTHERWISE NOTED.
L WINDINGS CONNECTIONS SHALL BE BRAZED OR PRESSURE TYPE AND MATERIAL SHALL BE COPPER.
N THE MAXIMUM SOUND LEVEL RATING SHALL BE AS FOLLOWS: 0 TO 9 KVA - 40 DBA, 10 TO 50 KVA - 45 DBA, 51 TO 150 KVA - 50 DBA, 151 TO 300 KVA - 55 DBA, 301 TO
500 KVA - 60 DBA. AFTER INSTALLATION, TRANSFORMERS SHALL EXHIBIT NO OBJECTIONABLE NOISE AS JUDGED BY THE ARCHITECT OR ENGINEER.
CORRECTIONS SHALL BE MADE TO THE SATISFACTION OF THE ARCHITECT OR ENGINEER.
O TRANSFORMERS SHALL HAVE IDENTIFICATION LABELS PER THE SPECIFICATIONS AND NAMEPLATE DETAIL.
P INSTALL TRANSFORMERS TO MAINTAIN CLEARANCES PER THE NATIONAL ELECTRICAL CODE AND MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q GROUND/BOND SECONDARY PER SPECIFICATIONS WITH A MAXIMUM OF 5 OHM GROUND RESISTANCE.
R INSTALL TRANSFORMERS ON CONCRETE BASE ON FLOOR, SUSPEND, OR WALL MOUNT AS REQUIRED ON KORFUND 'ELASTORIB" RESILIENT VIBRATION ISOLATING
MATERIAL OF SUFFICIENT QUANTITY TO NOT EXCEED MANUFACTURER'S RECOMMENDED POUNDS PER SQUARE INCH RATING.
S AFTER INSTALLATION, VACUUM (DO NOT USE COMPRESSED AIR) THE INTERIOR AND EXTERIOR OF ALL DIRT AND DEBRIS.
T ADJUST TAPS ARE REQUIRED TO PRODUCE THE SCHEDULED VOLTAGE UNDER LOAD.
U AVAILABLE SHORT CIRCUIT CURRENT IN AMPERES (AvailSSC) AT THE TRANSFORMER SECONDARY IS BASED ON: INFINITE SOURCE AND 80 DEGREES CELSIUS
COPPER WINDINGS TRANSFORMER.
V FEEDER KEYS SHALL BE USED UNLESS INDICATED DIFFERENTLY ELSEWHERE.
W REFER TO SPECIFICATIONS FOR TESTING AND COMMISSIONING REQUIREMENTS.
COPPER FEEDER SCHEDULE
KEY
QTY.
OF
RUNS
CONDUCTORS C
(IN)
125A3G 1 3#1/0,1#6G 2
225A4BJ 1 4#4/0,1#2BJ 2-1/2
2GEC 1 1#2GEC 3/4
REFER TO NATIONAL ELECTRICAL CODE FOR
INSTALLATION OF CONDUIT TYPE.
ALL CONDUCTORS ARE COPPER.
FEEDER MARK LEGEND
PANEL
PANEL
SIZE PER NEC
0 -
SEE SCHEDULE
FOR CONDUCTOR
SIZE AND CONDUIT
CONFIGURATION.
3,4 OR 5 IS 3-PHASE. 5-WIRE
INDICATES 200% NEUTRAL
BUS, PROVIDE ADDITIONAL
NEUTRAL CONDUCTOR. 2
WIRE IS 1-PHASE.
IF NO SIZE IS INDICATED THEN
REFER TO TRANSFORMER AND
PANEL SCHEDULES.
X7A
125/3 L
'7A' NEMA 3R
125A-480Δ
3PHASE, 3WIRE
22kAIC
SE RATED
EXISTING DIRECT BURIED CABLE TO
IRRIGATION PUMP TO REMAIN.
EXISTING TELECOMMUNICATIONS DUCT
SYSTEM. SYSTEM TERMINATES AT
BUILDING 1 TELEPHONE ROOM IN
PROXIMITY OF FACILITY FACP.
04/25
1 04/2025 BSN PPI CLARIFICATIONS
FARM STORAGE
FARM STORAGE
FARM STORAGE
X-7A
U
D A
S
KIMBERLY, ID
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
SCALE:
FIRE ALARM PLAN
1/4" = 1'-0"
E104
GENERAL NOTES
A. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
AND EXISTING CONDITIONS PRIOR TO PERFORMING ANY
WORK OR FABRICATION OR PURCHASE OF EQUIPMENT,
MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION
FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
B. PROVIDE NEW DEVICES AND INTEGRATE INTO EXISTING
FACILITY FIRE ALARM AND NOTIFICATION SYSTEM. REFER
TO DETAIL 1/E001. EXISTING FIRE ALARM CONTRACTOR
CONTACT IS "JOHNSON CONTROLS SECURITY SOLUTION
LLC, 1-800-274-3932".
C. EXISTING SYSTEM IS "UNIMODE 9600" LOCATED IN
TELEPHONE ROOM OF BUILDING 1 WITH EXISTING DEVICE
LOOPS IN BUILDING 5 AND BUILDING 6.
E104
FIRE ALARM PLANBSN
PANEL 7A
FA
CP
T
F
F
F
M
M
M
M
T
T
T
T
T
1 04/2025 BSN PPI CLARIFICATIONS
04/25
| PEMB CIVIL_REV1-C101 |
| Sheets and Views |
| C101 |
| PEMB CIVIL_REV1-C102 |
| Sheets and Views |
| C102 |
| PEMB CIVIL_REV1-C103 |
| Sheets and Views |
| C103 |
| PEMB_REV1-S001 |
| Sheets and Views |
| S001 |
| Farm Storage A101-A301 FARM STOR. |
| Sheets and Views |
| A301 FARM STOR. |
| Farm Storage A101-A501 FARM STOR. |
| Sheets and Views |
| A501 FARM STOR. |
| Farm Storage A101-A301 FARM STOR..pdf |
| Sheets and Views |
| A301 FARM STOR. |
| Farm Storage A101-A501 FARM STOR..pdf |
| Sheets and Views |
| A501 FARM STOR. |
| Farm Storage Rev 1 4.25 elec.pdf |
| E001r1 |
| Sheets and Views |
| E-001 |
| E104r1 |
| Sheets and Views |
| E-104 |
File details come from the government source that posted it. Updated .