Attachment 4 - Section 08 3613 Sectional Doors.pdf
PDF 99 KB Posted
- Attached to
- Forest Lodge - Main Lodge & Machine Shed, Bayfield County, WI Chequamegon-Nicolet National Forest
- Solicitation number
- 12569R20Q0014
- Issued by
-
Department of Agriculture Forest Service
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers.pdf | ||
| Amendment 4 Revisions 05.15.2020.pdf | ||
| Amendment 4 - Solicitation12569R20Q0014.docx | DOCX document | |
| Amendment 4 SF30.pdf | ||
| Amendment 3-SF30.pdf | ||
| Amendment 2-SF30.pdf | ||
| Solicitation12569R20Q0014-Amendment2.docx | DOCX document | |
| Solicitation12569R20Q0014-Amendment1.docx | DOCX document | |
| Amendment 1-SF30.pdf | ||
| Att.1 - Specifications.pdf | ||
| Att.2 - Plans.pdf | ||
| Att.3 - WageDetermination.pdf | ||
| Solicitation12569R20Q0014.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOREST LODGE THREE BUILDING HISTORIC REHABILITATION SECTIONAL DOORS
Project No. 19042 08 3613 - 1
SECTION 08 3613 – SECTIONAL DOORS
PART 1 – GENERAL
1.1 SUMMARY
A. Section includes electrically operated sectional, exterior doors.
B. Related Section:
1. Division 05 Section "Metal Fabrications" for miscellaneous steel supports.
1.2 PERFORMANCE REQUIREMENTS
A. General Performance: Sectional doors shall meet performance requirements specified without failure due to defective manufacture, fabrication, installation, or other defects in construction and without requiring temporary installation of reinforcing components.
B. Structural Performance: Exterior sectional doors shall withstand the effects of gravity loads, and the following loads and stresses within limits and under conditions indicated according to ASCE/SEI 7.
1. Wind Loads: Uniform pressure (velocity pressure) of 20 lbf/sq. ft. (960 Pa), acting inward and outward.
1.3 SUBMITTALS
A. Product Data: For each type and size of sectional door and accessory.
B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data. Include plans, elevations, sections, details, and attachments to other work.
C. Samples: For each exposed product and for each color and texture specified.
D. Maintenance Data.
E. Warranties: Sample of special warranties.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for both installation and maintenance of units required for this Project.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. Standard for Sectional Doors: Fabricate sectional doors to comply with DASMA 102 unless otherwise indicated.
1.5 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of sectional doors that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Two years from date of Substantial Completion.
B. Special Finish Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components that show evidence of deterioration of factory-applied finishes within specified warranty period.
FOREST LODGE THREE BUILDING HISTORIC REHABILITATION SECTIONAL DOORS
Project No. 19042 08 3613 - 2
1. Warranty Period: 10 years from date of Substantial Completion.
PART 2 – PRODUCTS
2.1 STEEL DOOR SECTIONS
A. Exterior Section Faces and Frames: Fabricate from manufacturer's standard zinc-coated (galvanized), cold-rolled, steel sheet.
1. Roll horizontal meeting edges to a continuous, interlocking, keyed, rabbeted, shiplap, or tongue-in-groove weather tight seal, with a reinforcing flange return.
2. For insulated doors, provide sections with continuous thermal-break construction, separating the exterior and interior faces of door.
B. Section Ends and Intermediate Stiles: Enclose open ends of sections with channel end stiles formed from galvanized-steel sheet welded to door section. Provide intermediate stiles formed from galvanized-steel sheet, cut to door section profile, and welded in place. Space stiles not more than 48 inches apart.
C. Reinforce bottom section with a continuous channel or angle conforming to bottom-section profile and allowing installation of astragal.
D. Reinforce sections with continuous horizontal and diagonal reinforcement, as required to stiffen door and for wind loading. Provide galvanized-steel bars, struts, trusses, or strip steel, formed to depth and bolted or welded in place.
E. Provide reinforcement for hardware attachment.
2.2 TRACKS, SUPPORTS, AND ACCESSORIES
A. Tracks: Manufacturer's low headroom, galvanized-steel track system of configuration indicated, sized for door size and weight, designed for lift type indicated and clearances shown on Drawings. Provide complete track assembly including brackets, bracing, and reinforcement for rigid support of ball-bearing roller guides for required door type and size. Slot vertical sections of track spaced 2 inches (51 mm) apart for door-drop safety device. Slope tracks at proper angle from vertical or design tracks to ensure tight closure at jambs when door unit is closed.
B. Track Reinforcement and Supports: Galvanized-steel track reinforcement and support members. Secure, reinforce, and support tracks as required for door size and weight to provide strength and rigidity without sag, sway, and vibration during opening and closing of doors.
C. Weatherseals: Replaceable, adjustable, continuous, compressible weather-stripping gaskets of flexible vinyl, rubber, or neoprene fitted to bottom and top of sectional door unless otherwise indicated.
2.3 HARDWARE
A. General: Provide heavy-duty, corrosion-resistant hardware, with hot-dip galvanized, stainless steel, or other corrosion-resistant fasteners, to suit door type.
B. Hinges: Heavy-duty, galvanized-steel hinges at each end stile and at each intermediate stile, according to manufacturer's written recommendations for door size. Attach hinges to door sections through stiles and rails.
C. Rollers: Heavy-duty rollers with steel ball-bearings in case-hardened steel races, mounted with varying projections to suit slope of track. Provide 3-inch- (76-mm-) diameter roller tires for 3-inch- (76-mm-) wide track and 2-inch- (51-mm-) diameter roller tires for 2-inch- (51-mm-) wide track.
FOREST LODGE THREE BUILDING HISTORIC REHABILITATION SECTIONAL DOORS
Project No. 19042 08 3613 - 3
2.4 LOCKING DEVICES
A. Safety Interlock Switch: Equip power-operated doors with safety interlock switch to disengage power supply when door is locked.
2.5 COUNTERBALANCE MECHANISM
A. Torsion Spring: Counterbalance mechanism consisting of adjustable-tension torsion springs mounted on torsion shaft made of steel tube or solid steel. Provide springs designed for number of operation cycles indicated.
B. Cable Drums and Shaft for Doors: Cast-aluminum or gray-iron casting cable drums mounted on torsion shaft and grooved to receive door-lifting cables as door is raised. Mount counterbalance mechanism with manufacturer's standard ball-bearing brackets at each end of torsion shaft.
C. Cables: Galvanized-steel lifting cables.
D. Cable Safety Device: Include, on each side-edge of door, a device designed to automatically stop door if either lifting cable breaks.
E. Bracket: Provide anchor support bracket as required to connect stationary end of spring to the wall and to level the shaft and prevent sag.
F. Provide a spring bumper at each horizontal track to cushion door at end of opening operation.
2.6 ELECTRIC DOOR OPERATORS
A. General: Electric door operator assembly of size and capacity recommended and provided by door manufacturer for door and "operation cycles" requirement specified, with electric motor and factory-prewired motor controls, starter, gear-reduction unit, solenoid-operated brake, clutch, remote-control stations, control devices, integral gearing for locking door, and accessories required for proper operation.
B. Usage Classification: Electric operator and components capable of operating for not less than number of cycles per hour indicated for each door.
C. Door Operator Type: Unit of type indicated, consisting of electric motor, gears, pulleys, belts, sprockets, chains, and controls needed to operate door and meet required usage classification.
D. Electric Motors: Comply with NEMA designation, temperature ratings, service factor, enclosure type, and efficiency requirements specified in Division 11 Section “Common Motor Requirements for Equipment” unless otherwise indicated.
1. Electrical Characteristics:
a. Phase Polyphase.
b. Volts 208 V.
c. Hertz: 60.Motor Type and Controller: Reversible motor and controller (disconnect switch) for motor exposure indicated.
3. Motor Size: Minimum size as indicated. If not indicated, large enough to start, accelerate, and operate door in either direction from any position, at a speed not less than 8 in./sec. (203 mm/s) and not more than 12 in./sec.
(305 mm/s), without exceeding nameplate ratings or service factor.
4. Operating Controls: Controllers (Disconnect Switches), Wiring Devices, and Wiring: Manufacturer’s standard unless otherwise indicated.
D. Obstruction Detection Device: Equip motorized door with indicated external automatic safety sensor capable of protecting full width of door opening. Activation of device immediately stops and reverses downward door travel.
FOREST LODGE THREE BUILDING HISTORIC REHABILITATION SECTIONAL DOORS
Project No. 19042 08 3613 - 4
1. Photoelectric Sensor: Manufacturer's standard system designed to detect an obstruction in door opening without contact between door and obstruction. Provide self-monitoring capability designed to interface with door-operator control circuit to detect damage to or disconnection of sensor device.
2. Sensor Edge: Automatic safety sensor edge, located within astragal or weather stripping mounted to bottom bar.
Contact with sensor activates device. Connect to control circuit using manufacturer's standard take-up reel or self-coiling cable. Provide self-monitoring capability designed to interface with door-operator control circuit to detect damage to or disconnection of sensor device.
F. Remote-Control Station: Momentary-contact, three-button control station with push-button controls labeled "Open,"
"Close," and "Stop."
1. Interior units, full-guarded, surface-mounted, heavy-duty type, with general-purpose NEMA ICS 6, Type 1 enclosure.
2. Exterior units, full-guarded, standard-duty, surface-mounted, weatherproof type, NEMA ICS 6, Type 4 enclosure, key operated.
G. Emergency Manual Operation: Equip each electrically powered door with capability for emergency manual operation.
Design manual mechanism so required force for door operation does not exceed 25 lbf (111 N).
H. Emergency Operation Disconnect Device: Equip operator with hand-operated disconnect mechanism for automatically engaging manual operator and releasing brake for emergency manual operation while disconnecting motor without affecting timing of limit switch. Mount mechanism so it is accessible from floor level. Include interlock device to automatically prevent motor from operating when emergency operator is engaged.
I. Motor Removal: Design operator so motor may be removed without disturbing limit-switch adjustment and without affecting emergency manual operation.
J. Audible and Visual Signals: Audible alarm and visual indicator lights in compliance with regulatory requirements for accessibility.
2.7 DOOR ASSEMBLY
A. Steel Sectional Door: Sectional door formed with hinged sections.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Overhead Door Corporation.
b. Clopay Building Products; a Griffon company.
c. C.H.I. Overhead Doors.
d. Wayne-Dalton Corp.
e. Approved Equal.
B. Operation Cycles: Not less than 50,000.
C. Steel Section: Zinc-coated (galvanized) steel sheet, formed into sections.
1. Exterior-Face Surface: Paneled, embossed.
2. Interior Facing Surface: Zinc-coated (galvanized) steel sheet.
3. Insulated.
D. Track Configuration: Standard clearance-lift track.
E. Weatherseals: Fitted to bottom and top and around entire perimeter of door. Provide combination bottom weatherseal and sensor edge.
G. Electric Door Operator:
FOREST LODGE THREE BUILDING HISTORIC REHABILITATION SECTIONAL DOORS
Project No. 19042 08 3613 - 5
1. Usage Classification: Heavy duty, 60 to 90 cycles per hour.
2. Operator Type: Jackshaft, center mounted.
3. Motor Exposure: Interior, clean, and dry.
4. Emergency Manual Operation: Chain type.
5. Obstruction-Detection Device: Automatic photoelectric sensor.
8. Other Equipment: Audible and visual signals.
I. Door Finish:
1. Factory-Finish: Color as selected by Architect from manufacturer’s standard range.
2. Finish of Interior Facing Material: Match finish of exterior section face.
PART 3 – EXECUTION
3.1 INSTALLATION
A. Install sectional doors and operating equipment complete with necessary hardware, anchors, inserts, hangers, and equipment supports; according to manufacturer's written instructions and as specified.
B. Tracks: Provide sway bracing, diagonal bracing, and reinforcement as required for rigid installation of track and door-operating equipment. Repair galvanized coating on tracks according to ASTM A 780.
C. Adjust hardware and moving parts to function smoothly so that doors operate easily, free of warp, twist, or distortion.
Adjust doors and seals to provide weathertight fit around entire perimeter.
3.2 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain sectional doors.
END OF SECTION 08 3613