Amendment 4 Revisions 05.15.2020.pdf
PDF 1 MB Posted
- Attached to
- Forest Lodge - Main Lodge & Machine Shed, Bayfield County, WI Chequamegon-Nicolet National Forest
- Solicitation number
- 12569R20Q0014
- Issued by
-
Department of Agriculture Forest Service
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers.pdf | ||
| Amendment 4 - Solicitation12569R20Q0014.docx | DOCX document | |
| Amendment 4 SF30.pdf | ||
| Amendment 3-SF30.pdf | ||
| Amendment 2-SF30.pdf | ||
| Solicitation12569R20Q0014-Amendment2.docx | DOCX document | |
| Solicitation12569R20Q0014-Amendment1.docx | DOCX document | |
| Attachment 4 - Section 08 3613 Sectional Doors.pdf | ||
| Amendment 1-SF30.pdf | ||
| Att.1 - Specifications.pdf | ||
| Att.2 - Plans.pdf | ||
| Att.3 - WageDetermination.pdf | ||
| Solicitation12569R20Q0014.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT 4
ISSUE DATE: May 15, 2020
RE: Forest Lodge Three Building Historic Rehabilitation
CHANGES TO THE SPECIFICATIONS:
1. SECTION 02 8716.13 – EXCREMENT REMOVAL
a. Article 3.2 add paragraph D as follows:
“Remove bird excrement from Machine Shed and Main Lodge interior roof structure and any exterior Main Lodge structure requiring work.”
2. Add New SECTION 07 41113.13 – EXPOSED FASTENER PREFORMED ROOF PANELS
3. SECTION 07 7200 THERMAL INSULATION
a. 2.8.B: Add approved manufacturer/product “Demilec Heatlok HFO Pro.”
4. Add New SECTION 07 7253 - SNOW GUARDS
5. Section 26 43 05 SURGE SUPPRESSION
1. 2.01 SERVICE ENTRANCE, Replace G., 3., b. with the following:
b. 120/240 800 800 800.
CHANGES TO DRAWINGS:
1. SHEETS MS-A1.1 MACHINE SHED FLOOR PLAN and MS-A2.1 - MACHINE SHED EXTERIOR
ELEVATIONS generally includes:
a. Replaces existing painted metal roofing with new; makes miscellaneous exterior revisions and clarifications.
b. Changes overhead door size.
c. Changes attic insulation system
d. Revises attic access.
e. Adds snow guards to elevations.
2. SHEET ML-S1.1 – MAIN LODGE FRAMING PLAN
a. New beams to have smooth finish with stain to closely match existing structure.
3. SHEET ML-S1.1 – MAIN LODGE FRAMING
a. Various revisions.
4. SHEET MS-S1.1 – MACHINE SHED FRAMING PLAN
a. Attic access door framing.
b. Finish new and repaired exterior wood with one coat of Cabot Semi-Transparent #300 Series Oil-
Based Stain.
5. SHEET S0.1 – GENERAL STRUCTURAL NOTES
a. STRUCTURAL SHEET INDEX updated.
6. SHEET E2.2 - ELECTRICAL SCHEDULES
a. Light Fixture Type F4 shall be equal to a 4’ lensed strip light by Columbia #CSL4-4040.
Forest Lodge Three Building Historic Rehabilitation May 15, 2020 Amendment 4 Page 2
ATTACHMENTS:
Specifications Section: 07 41113.13 – EXPOSED FASTENER PREFORMED ROOF PANELS Section: 07 7253 - SNOW GUARDS.
Drawing Sheets:
MS-A1.1, MS-A2.1
ML-S1.1, MS-S1.1, S0.1
END OF ADDENDUM
Dimension IV – Madison, LLC 6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719
FOREST LODGE THREE BUILDING HISTORIC REHABILITATION PREFORMED ROOF PANELS
Project No. 19042 07 4113.13 -1
SECTION 074113.13 - EXPOSED FASTENER PREFORMED ROOF PANELS
PART 1 - GENERAL
1.1 SUMMARY
A. This section covers the pre-finished, pre-fabricated exposed fastener metal roof system. All metal trim, accessories, fasteners, insulation and sealants indicated on the drawings as part of this section.
B. Drawings and general provisions of the Contract, including general and Supplementary Conditions and Division 01 Specifications, apply to this section.
1.2 DEFINITIONS
A. Metal Roof/Wall Panel Assembly: Metal roof/ panels, attachment system components, miscellaneous metal framing, thermal, and accessories necessary for a complete weathertight roofing system.
B. References:
1. American Society for Testing and Materials (ASTM)
a. ASTM A 653: Steel Sheet, Zinc Coated by the Hot Dip Process
b. ASTM A 792: Steel Sheet, Aluminum-Zinc Alloy Coated by the Hot Dip Process
c. ASTM B 209: Aluminum and Aluminum Alloy Sheet and Plate
d. ASTM B370 Standard Specification for Copper Sheet and Strip for Building Construction
2. Sheet Metal and Air Conditioning Contractors National Association (SMACNA)
a. SMACNA Architectural Sheet Metal Manual, 1993 edition
3. American Iron and Steel Institute (AISI)
a. AISI Cold Formed Steel Design Manual
4. Aluminum Association
a. Aluminum Design Manual
5. Metal Construction Association
a. Preformed Metal Wall Guidelines
6. Code References
a. ASCE, Minimum Loads for Buildings and Other Structures
b. BOCA National Building Codes
c. UBC Uniform Building Code
d. SBC Standard Building Code
1.4 QUALITY ASSURANCE
A. Petersen Aluminum Corp, Elk Grove Village, IL, 800-323-1960 products establish a minimum of quality required.
B. Manufacturer and erector shall demonstrate experience of a minimum of five (5) years in this type of project.
C. Panels shall be factory-produced only. No portable, installer-owned or installer-rented machines will be permitted.
1.5 SUBSTITUTIONS
A. The material, products and equipment specified in this section establish a standard for required function, dimension, appearance and quality to be met by any proposed substitution.
B. Manufacturers listed in this section are prequalified manufacturers. Substitution of manufacturer's products for those specified shall not be allowed at any time during construction.
1.6 SYSTEM DESCRIPTION
A. Material to comply with:
1. ASTM A 653 Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated by the Hot-Dip Process
Project No. 19042 07 4113.13 -2
1.7 ROOF SYSTEM PERFORMANCE TESTING
A. General Performance: Metal roof/wall panels shall comply with performance requirements without failure due to defective manufacture, fabrication, installation or other defects in construction.
B. Roof System shall be designed to meet Standard Building Code Wind Load requirements.
C. Panels to meet:
1. Roof/Wall System shall be designed to meet applicable Local Building Code and the System shall have tested by the Manufacturer per ASTM E-1592 and have the applicable Load Tables published from this testing for loads.
1.8 WARRANTIES
A. Finish warranty: Manufacturer's standard form in which manufacturer agrees to repair finish or replace standing seam metal roof panels that show evidence of deterioration of factory-applied finish within specified warranty period.
1. Exposed Panels Finish - deterioration includes the following:
a. Color fading more than 5 hunter units when tested according to ASTM D 2244
b. Chalking in excess of a No. 8 rating when tested according to ASTM D 4214
c. Cracking, checking, peeling or failure of a paint to adhere to a bare metal.
2. Warranty Period: 20 Years from the date of substantial completion B. Applicator shall furnish written warranty for a two (2) year period from date of substantial completion of building covering repairs required to maintain roof and flashings in watertight condition.
1.9 SUBMITTALS
A. Furnish detailed drawings showing profile and gauge of exterior sheets, location and type of fasteners, location, gauges, shape and method of attachment of all trim locations and types of sealants, and any other details as may be required for a weather-tight installation.
B. Provide finish samples of all colors specified.
C. Shop drawings: Show fabrication and installation layouts of metal roof panels, metal wall panels or metal soffit panels, details of edge conditions, side-seam joints, panel profiles, corners, anchorages, trim, flashings, closures and accessories, and special details. Distinguish between factory and field-assembled work
D. Coordination Drawings: Roof plans, drawn to scale, on which the following are shown and coordinated with each other, based on input from installer of the items involved:
1. Roof panels and attachments
2. Wood framing, bracings and supports
3. Roof-mounted items including snow guards.
1.10 DELIVERY, STORAGE AND HANDLING
A. Ordering: Comply with manufacturer's ordering instruction and lead time requirements to avoid construction delays.
B. Deliver components, sheets, metal roof/wall panels and other manufactured items so as not to be damaged or deformed. Package metal roof/wall panels for protection during transportation and handling.
C. Unload, store and erect metal roof/wall panels in a manner to prevent bending, warping, twisting and surface damage.
D. Stack metal roof panels on platforms or pallets, covered with suitable weathertight and ventilated covering. Store metal roof/wall panels to ensure dryness. Do not store metal roof panels in contact with other materials that might cause staining, denting or other surface damage.
E. Protect strippable protective coating on any metal coated product from exposure to sunlight and high humidity, except to the extent necessary for material installation.
1.11 PROJECT CONDITIONS
A. Weather Limitations: proceed with installation only when existing and forecasted weather conditions permit metal roof panel work to be performed.
Project No. 19042 07 4113.13 -3
B. Field Measurements: Verify actual dimensions of construction contiguous with metal roof panels by field measurements before fabrication.
1.12 COORDINATION
A. Coordinate sizes and locations of roof curbs, equipment supports and roof penetrations with actual equipment provided.
B. Coordinate metal roof panels with rain drainage work, flashing, trim and construction of decks, parapet walls and other adjoining work to provide a leakproof, secure and noncorrosive installation.
PART 2 - PRODUCTS
2.1 PANEL DESIGN
A. General: Provide factory-formed, prefinished, lappable exposed fastener, structural ribbed metal roof/wall panel system, that has been pretested and certified by manufacturer to comply with specified requirements under installed conditions.
B. Roof panels shall be exposed fastener R-36 Panels with 1 1/4" deep profile ribs, 12" on center, total coverage of Roof/Wall panels when installed shall be 36" coverage.
C. Structural Requirements: Engineer panels for structural properties in accordance with latest edition of American Iron and Steel Institute's Cold Formed Steel Design Manual using effective width concept and Aluminum Associations Aluminum Design Manual.
D. Forming: Use continuous end rolling method. No end laps on panels. No portable roll-forming machines will be permitted on this project, no installer-owned or installer-rented machines will be permitted. It is the intent of the Architect to provide Factory-Manufactured panel systems only for this project.
E. Panels shall be directly fastened to the substrate.
F. The panel shall have an overlapping sidelap feature.
2.2 ACCEPTABLE MANUFACTURERS
A. This project is detailed around the roofing product of Petersen Aluminum Corporation Petersen Aluminum Corp, Elk Grove Village, IL, 800-323-1960, R-36 Panel.
B. Equivalent products by:
1. AEP SPAN; A Bluescope Steel Company
2. Berridge Manufacturing Corporation.
3. Firestone Metal Products
4. Metal Sales Manufacturing Corporation.
2.3 MATERIALS AND FINISHES
A. Preformed roofing panels shall be fabricated of 22 GA Steel
B. Color to be selected by COR from standard color palette.
C. Texture: Panel shall be smooth.
D. Finish shall be Kynar 500 or Hylar 5000 Fluorocarbon coating with a top side film thickness of 0.70 to 0.90 mil over a
0.25 to 0.3 mil prime coat to provide a total dry film thickness of 0.95 to 1.25 mil, to meet AAMA 621. Bottom side shall be coated with a primer with a dry film thickness of 0.25 mil. Finish shall conform to all tests for adhesions, flexibility and longevity as specified by Kynar 500 or Hylar 5000 finish supplier.
E. If Strippable coating to be applied on the pre-finished panels to the top side to protect the finish during fabrication, shipping and handling, film shall be removed before installation.
F. Trim: Trim shall be fabricated of the same material and finish to match the profile, and will be press broken in lengths of 10 to 12 feet. Trim shall be formed only by the manufacturer of their approved dealer. Trim to be erected in overlapped condition. Use lap strips only as indicated on drawings. Miter conditions shall be factory welded material to match the sheeting. Trim to be fabricated in accordance with standard SMACNA procedure and details.
Project No. 19042 07 4113.13 -4
G. Closures: shall be pre-molded polyethylene to match the profile of the exposed fastener panel and shall be in lengths as supplied by the panel manufacturer.
H. Accessories/Fasteners: Fasteners shall be of type, material, size, corrosion resistance, holding power and other properties required to fasten miscellaneous framing members to substrates. Accessories and their fasteners shall be capable of resisting the specified design wind uplift forces and shall allow for thermal movement of the roof panel system. Exposed fasteners shall not restrict free movement of the roof panel system resulting from thermal forces, except at designed points of roof panel fixity
1. Fasteners shall have combination steel and EPDM washers
2. Screws for panel to girt/purlins shall be sufficient to penetrate the supporting member by 1". All fasteners shall be applied in accordance with the fastening schedule as provided by panel manufacturer.
3. Screws for flashings and sidelaps shall be #14 HHA x 3/4" sheet metal stitch screws. All accessories, flashings and sidelaps shall be fastened 12" OC.
I. Substrate shall be wood purlins J. Caulking: Shall be a polyurethane where it is exposed and there is no thermal movement. All caulking and sealing shall be done in a neat manner with excess caulking or sealant removed from exposed surfaces.
K. Caulking shall be non-skinning, non-hardening gun grade butyl sealant or butyl sealant tape with a minimum thickness of 1/4" where it is concealed and where thermal movement must be accommodated. All caulking or sealing shall be done in a neat manner with excess caulking or sealant removed from exposed surfaces.
2.4 FABRICATION
A. Comply with dimensions, profile limitations, gauges and fabrication details shown and if not shown, provide manufacturer's standard product fabrication.
B. Fabricate components of the system in factory, ready for field assembly.
C. Fabricate components and assemble units to comply with fire performance requirements specified.
D. Apply specified finishes in conformance with manufacturer's standard, and according to manufacturer's instructions.
E. Panels are lappable. It is recommended that individual aluminum roof panels not exceed 16' in length and steel roof panels not exceed 32' in length for thermal movement reasons.
F. Panels shall be roll formed on a stationary industrial type rolling mill to gradually shape the sheet metal. Portable roll-formers rented or owned by the installer, are not acceptable.
PART 3 - EXECUTION
3.1 INSPECTION
A. Examine alignment of structural steel and related supports, primary and secondary roof framing, solid roof sheathing, prior to installation. Components should comply with shop drawings and be smooth, even, sound and free of depressions.
B. For the record, prepare written report, endorsed by installer, listing conditions detrimental to performance of the Work.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 FASTENERS
A. Secure units to supports B. Place fasteners as indicated in manufacturer's standards.
3.3 INSTALLATION
A. Panels shall be installed plumb and true in a proper alignment and in relation to the structural framing. The erector must have at least five years successful experience with similar applications.
B. Install metal panels, fasteners, trim and related sealants in accordance with approved shop drawings and as may be required for a weather-tight installation. Conform to standards set forth in SMACNA architectural sheet metal manuals and approved shop drawings for this project.
C. Remove all strippable coating and provide a dry-wipe down cleaning of the panels as they are erected.
Project No. 19042 07 4113.13 -5
D. Install panel system so it is watertight, without waves, warps, buckles or distortions, and allow for thermal movement considerations.
E. Abrasive devices shall not be used to cut on or near roof or wall panel system.
F. Apply sealant tape or caulking as necessary at flashing and panel joints to prevent water penetration.
G. Remove any strippable film immediately upon exposure to direct sunlight.
A. Upon determination of responsibility, repair or replace damaged metal panels and trim to the satisfaction of the
Architect and Owner.
END OF SECTION
FOREST LODGE THREE BUILDING HISTORIC REHABILIATION SNOW GUARDS
Project No. 19042 07 7253 - 1
SECTION 07 7253 – SNOW GUARDS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Snow guards for mechanical mounting.
1.2 DELIVERY, STORAGE AND HANDLING
A. Inspect materials at the time of receipt. Damaged goods once delivered are the responsibility of the Contractor and Owner.
B. Store products in manufacturer’s unopened packaging or in a covered facility protected from the elements until ready for installation.
1.3 WARRANTY
A. The following warranty is made in lieu of all other warranties expressed or implied. Sno Shield warrants that the products it manufactures shall be free from material defects. Any goods proven to be defective due to materials will be replaced or purchase price refunded. In no event shall Sno Shiled Inc. be liable for incidental or consequential damages or misapplication of the product. The customer shall determine the suitability of the product for its intended use and assumes all risks of its use or handling, including proper installation of the product. A two (2) year workmanship warranty is to be provided by the Installer. Because the manufacturer has no control of workmanship, there is no warranty on screws, tapes, sealants, or adhesives sold or recommended.
There is no warranty on the installation or application of any Sno Shield, Inc. products. Any Sno Shield product warranty claim is limited solely to Sno Shield, Inc.
PART 2 - PRODUCTS
2.1 PRODUCTS
A. Basis-of-Design Product: Sno Shield™ S.S. Snow Rail and Deck Mount Brackets, manufactured by Sno Shield Inc.; 3968 E. Sunnyside Road, Building 3, Ammon, Idaho; (P) 888-976-6744; Email: info@snoshield.com ; Web-site: www.snoshield.com ; or approved equal.
2.2 SNOW FENCE/RAIL COMPONENTS
A. Steel (Powder Coated).
2.3 SYSTEM COMPONENTS
A. S.S. Sno Rail Deep Deck Double Rail
1. Dimensions: (W-Face x H-Face x L-Base): 1.4” x 6.25” x 3.6”. Deep Deck Double Rail Track
2. Dimensions: (Steel Thickness): .1875”, Deep Deck Double Rail.
3. Hole Diamater: (Width of hole for railing): .875”, Standard.
B. Accessories: Manufacturer’s standard mounting brackets, pipe collars and end caps.
C. Railing:
1. Material: (Steel) Standard.
mailto:info@snoshield.com http://www.snoshield.com/
FOREST LODGE THREE BUILDING HISTORIC REHABILIATION SNOW GUARDS
Project No. 19042 07 7253 - 2
2. Finish: Powder Coated.
3. O.D. Dimensions (.875”) Standard.
4. Material Thickness (Schedule 40): Standard.
PART 3 - EXECUTION
3.1 PREPARATION
A. Prior to installation, inspect conditions to verify that surfaces are suitable for installation of S. S. Sno Rail and clean all surfaces to achieve best result.
B. Be careful in staging materials to not overload roof surfaces, always maintain a safe work zone as approved by OSHA or prevailing work safety standards.
C. Clean the designated area with isopropyl alcohol (direct fastener application only) and allow to dry completely before installation.
3.2 INSTALLATION
A. Install system in accordance with manufacturer's installation instructions and approved architectural drawings.
B. Install brackets two feet O.C. or as close as ribbing will allow within the specified layout. Fasten brackets to wood roof purlins below the metal roofing. Use a non-hardening roofing sealant (polyurethane or equal) to seal penetrations. It is easiest to place bracket in a generous bead of caulking sealant (try to match roof color when possible, or defer to clear when no color match is available).
END OF SECTION 07 7253
8x14 DF
8x14 DF
8x14 DF
8x14 DF 8x14 DF
8x14 DF
8x14 DF
8x14 DF 8x14 DF
8x14 DF
8x14 DF
8x14 DF 8x14 DF
8x14 DF
8x14 DF
8x14 DF 8x14 DF
8x14 DF
8x14 DF
8x14 DF 8x14 DF
8x14 DF
8x14 DF
8x14 DF
TYP
TYP
TYP
TYP
TYP 9
9 TYP
TYP
ML-S1.1
TYP
5' -0
4'
-9
1" 4'
-9
5' -0
PORCH FRAMING NOTES:
1) FIELD VERIFY ALL DIMENSIONS
2) ALL NEW COLUMNS HSS 3x3x1/4.
3) HSS BEAMS AND COLUMNS TO RECEIVE HIGH PERFORMANCE PRIMER:
PREP: SSPC-SP6/NACE 3 COMMERCIAL BLAST CLEANING WITH A MINIMUM ANGULAR ANCHOR PROFILE OF 1.5 MILS.
PRIMER AROMATIC URETHANE ZINC- RICH WITH A MINIMUM ZINC LOAD OF 83% AT 2.5-3.5 MILS DFT - TNEMEC OR
APPROVED EQUAL. APPLY PER MNFR'S RECOMMENDATIONS. TOUCH OP PRIMER AFTER FIELD WELDING PER
MNFR'S RECOMMENDATIONS
4) USE SIMPSON CPTZ66 COLUMN BASE TO TOP OF PLANTER WALL. MILL TOP OF WALL FLAT AT BEARING. CONFIRM SOUND WOOD AT BEARING LOCATIONS. REMOVE AND REPLACE LEAD LINING OF PLANTERS BETWEEN COLUMN LOCATIONS, AND INSTALL NEW LEAD FLASHING BETWEEN COLUMN AND BED TO MAINTAIN WATER TIGHT PLANTER BED.
5) CONFIRM INTEGRITY OF EXISTING ROOF SHEATHING AND RE-USE OR REPLACE AS NECESSARY. IF BOARD
SHEATHING IS USED, PROVIDE 1/2" CDX PLYWOOD OVER BOARD SHEATHING FOR DIAPHRAGM.
6) REMOVE AND RE-BUILD PORCH SCREEN WALLS WITH MATERIALS SIM TO EXISTING.
FV
7'-4"
FV
6'-4"
FV
7'-4"
2'-10" FV
CENTER TO CENTER WALL
21'-0" FV
2'-10" FV
F V
2' -8
F V
9' -4
/2
8" F
V
ML-S1.1
HSS4X4X1/4
HSS6X6X3/8
HS
S5
X3 X3
/1
HS
S5
X3 X3
/1
HSS6X6X3/8
HSS5X5X5/16
HSS5X4X3/16
ML-S1.1
EXISTING ROOF
ML-S1.1
9 9
1. SEE SHEETS S0.1 AND S0.2 FOR GENERAL NOTES.
2. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS, MEMBER SIZES, MEMBER MATERIALS, AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL MEMBER
SIZES AND DIMENSIONS SHOWN ON THE CONTRACT STRUCTURAL DRAWINGS ARE INTENDED AS
GUIDELINES ONLY AND MUST BE VERIFIED BY THE CONTRACTOR.
3. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF ANY CONDIITONS THAT
DIFFER FROM THOSE INDICATED ON THE STRUCTURAL DRAWINGS.
4. BEFORE PROCEEDING WITH ANY WORK WITHIN OR ADJACENT TO THE EXISTING STRUCTURE, THE
CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS. DURING THE PROCESS OF
CONSTRUCTION, IT SHALL BE THE CONTRACTOR'S RESPONSIBLITY TO MAINTAIN THE INTEGRITY
OF THE EXISTING STRUCTURE WHERE THE EXISTING STRUCTURE WHERE THE EXISTING
STRUCTURE IS MODIFIED TO ACCOMODATE NEW CONSTRUCTION AND TO PROTECT FROM
DAMAGE THOSE PORTIONS OF THE EXISTING STRUCTURE WHICH ARE TO REMAIN.
5. CONTRACTOR SHALL NOT CUT, CORE, DRILL, OR OTHERWISE ALTER THE EXISTING STRUCTURAL
ELEMENTS OTHER THAN THE MODIFICATIONS SHOWN IN THE CONTRACT STRUCTURAL DRAWINGS
WITHOUT PRIOR APPROVAL OF THE ENGINEER OF RECORD.
6. EXISTING RAFTERS MAY HAVE LONGITUDINAL CRACKS (PARALLEL TO THE RAFTER LENGTH) WITH
NO REMEDIAL ACTION REQUIRED. NOTIFY THE CONTRACTING OFFICER, ARCHITECT AND
STRUCTURAL ENGINEER OF ANY CRACKS IN MEMBERS PERPINDICULAR TO THEIR LENGTH.
EXISITNG WOOD FRAMING PLAN NOTES
SEE PLAN SEE PLAN SEE PLAN SEE PLAN
EXISTING RIDGE BEAM
EXISTING RAFTER
NEW SUPPORT BEAMS,
SEE PLAN
EXISTING LOG WALL
EXISTING ROOF
NOTCH WALL FOR NEW BEAM TO
LAND ON OR RUN THROUGH WALL. PROVIDE
CHINKING TO MATCH EXISTING AROUND OPENING
S3.1
FIELD CUT BIRDSMOUTH
IN NEW BEAMSS CONFORMING
TO RAFTER SHAPE
1' -2
2" M
A X
EXISTING RAFTER
EXISTING BEAM FV EXISTING BEAM FV EXISTING BEAM FV APPROX 2.5'" FV
APPROX 4' FV APPROX 9' FV
EXISTING ROOF
AND ROOF BEAMS
NEW HSS BEAM
SEE PLAN
1x CEDAR TRIM
HORIZ BOTTOM FACE OF HSS, TYP
13'-0" FV
REMOVE EXISTING
BEAM AT EXTERIOR WALL
AND REPLACE WITH HSS
SEE PLAN
EXISTING
LODGE ROOF
OVERHANG
EXISTING
LODGE WALL
2x CEDAR TRIM VERTICAL
FACE OF HSS TYP
NOTE: CEDAR TRIM FOR HSS BEAMS AND COLUMNS
STANDARD AND BETTER GRADE.
FASTEN WITH STAINLESS STEEL TRIM HEAD SCREWS
SIMPSON ABW66Z COL BASE, TYPICAL
FASTEN PER SIMPSON RECOMMENDATIONS
CUT FLOORING TO PLACE POST BASE
DIRECTLY ON LOG BEAM. FLATTEN BEAM
TOP TO INSTALL POST BASE AND BEAM BOTTOM
TO BEAR ON POST BELOW.
NEW COLUMN POST
SEE PLAN
NEW FOOTING SEE PLAN
EXISTING FLOOR AND
JOISTS
EXISTING LOG BEAM. REPLACE DETERIORIATED
LOGS WITH (2) 2X10 AT > 8 FT SPAN AND (2) 2X8 AT <
8 FT SPAN
SIMPSON SDWC 15600 EACH FACE
OF POST TO LOG BEAM
CENTER OF WALL ( NOT SHOWN )
SEE PLAN
CUT FLOORING TO PLACE POST BASE
DIRECTLY ON POST BELOW.
(2) 2X REPLACEMENT BEAM WHERE
EXISTING LOG BEAM IS DETERIORATED
SUPPORT FROM POST W/ SIMPSON HUS28-2
INSTALL PER MFR RECOMMENDATIONS
A
A
SECTION A-A AT REPLACEMENT BEAM
6x6 SPF POST
CENTER OF COLUMN
SEE PLAN
12D TOENAIL NEW BEAM TO PLATE
AT 12" O.C. BOTH SIDES
1/4 3
TYP MAIN BEAM TO
EDGE BEAM
EXISTING ROOF
NEW EDGE BEAM
SEE PLAN
EXISTING
EDGE BEAM
NEW CEDAR
TRIM
MAIN ROOF BEAM
SEE PLAN
1/4STEEL BEAM
SEE PLAN
STEEL COLUMN
SEE PLAN
SHIP 6" LONG
FIELD CUT TO FIT
SECTION A-A
A
A
EXIST. ROOF NOT SHOWN
1/2" x 6" x 6"
BASE PLATE
W/ (4) 5/16" DIA
HOLES FOR
(4) SIMPSON
SDS25300
STAINLESS
SCREWS
1/4
EXISTING
PLANTER WALL
PROJECT #
DATE OF ISSUE:
6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719 p608.829.4444 f608.829.4445 dimensionivmadison.com
C
U s e rs
\M ik e \D o c u m e n ts
\1
S T
R
F o re s t
L o d g e m le if e rm a n .r v t
/2
/2
:1
:5
A
M
FOREST LODGE
THREE BUILDING
HISTORIC
REHABILITATION
22230 GARMISCH ROAD,
CABLE, WI 54821
ML−S1.1
MAIN LODGE
FRAMING PLAN
190147
01/17/2020
SHEET KEYNOTES
2 FIELD VERIFY MINIMUM 4 1/2" DIA RAFTERS
4 EXISTING LOG RIDGE BEAM
8 NOTCH EXISTING LOG WALL FOR NEW RIDGE BEAM BEARING.
9 MIN (1) 6X6 SPF POST UNDER BEAM TYPICAL AT NON-LOG WALL. REMOVE AND RE-INSTALL
PANELING. REPLACE DAMAGED PANELING TO MATCH EXISTING. INSTALL MINIMUM 2'x 2' X
12" UNREINFORCED FOOTING DIRECTLY UNDER NEW COLUMNS WHICH ARE NOT
SUPPORTED BY EXISTING CONCRETE WALLS, AND PROVIDE 6X6 SPF POST AS INDICATED
BETWEEN FLOOR BEAM AND FOOTING IN CRAWLSPACE.
1/8" = 1'-0"ML-S1.1
1 ROOF FRAMING PLAN
3/8" = 1'-0"ML-S1.1
2 NEW BEAMS MAIN LODGE
100% - BID SET
1 AMENDMENT 4 05/15/2020
1/2" = 1'-0"ML-S1.1
4 SECTION AT PORCH ROOF
1" = 1'-0"ML-S1.1
5 COLUMN BEARING AT LODGE FLOOR
1 1/2" = 1'-0"ML-S1.1
3 SECTION AT PORCH EAVE
1" = 1'-0"ML-S1.1
6 HSS BEAM TO HSS COLUMN
T/ CONCRETE
1. SEE SHEETS S0.1 AND S0.2 FOR GENERAL NOTES.
2. THIS DRAWING IS FOR REINFORCING OF AN EXISTING WOOD FRAME POLE BUILDING.
3. SEE DETAILS FOR TYPICAL WOOD SHEAR WALLS.
MS-S1.1
WOOD FRAMING PLAN NOTES
HL10-3
1 2
A
B
W6U1
WOOD FRAMING LEGEND
WOOD FRAMING
WOOD
STUD WALL
GRID LINE
(CENTERLINE OF
STUD)
(FACE OF STUD OR
SHEATHING)
HEADER MARK,
SEE SCHED
WOOD SHEAR WALL,
SEE SCHED
H8-3
G7B2
P
SHEAR WALL
MARK,SEE
SCHED
SHEAR WALL,
SEE SCHED
PERFORATED SHEAR WALL REQD,
SEE ELEVATION AND SCHED
A T
S T
3.
(2
C S
TENSION STRAP
OR
ANCHOR TIEDOWN
SYSTEM, EACH
END OF SHEAR
WALL
SHEATHING
PANEL EDGE FASTENING
BLOCKED / UNBLOCKED
NUMBER OF SIDES SHEATHED
FTAO FORCE TRANSFER AROUND
OPENING SHEAR WALL
REQD, SEE ELEVATION AND
SCHED
# OF PLIES
NOMINAL DEPTH
LVL (IF SHOWN)
TYPICAL ALL 2X4 RAFTERS
EXTEND PAST SUPPORT MIN 12"
MS-S1.1
INSTALL TRIPLE 2X6
TO SUPPORT NEW AND
EXISTING TRUSSES BEARING
ON HEADERS, TYP
ANCHOR TO SLAB W/
SIMPSON DTT2Z AND
TITEN 12350HMG 1/2 X 3 1/2
CONCRETE SCREW
NEW 5/8" PLYWOOD INTERIOR
SHEATHING.
SEE ARCH FOR FIRE TREATMENT
23'-7"
7' -1
1/
4" 5'
-1
1/ 2"
9' -1
1/
2" 7'
-1
1/ 2"
7' -1
1/
4"
FIELD VERIFY ALL DIMENSIONS
PROVIDE (4) NEW PRESS PLATE ROOF TRUSSES
CAPABLE OF SUPPORTING
ENTIRE SPECIFIED DEAD AND SNOW LOADS
FOR THE SPANS AND SPACING
INDICATED.
ANCHOR TRUSS TO SUPPORT WITH
SIMPSON H6 ANCHOR EACH END
FRAME OUT ATTIC
ACCESS HATCH
W/ 2X6. SEE ARCH
FOR SIZE AND LOCATION
N O
R
TH
TYPICAL 6x6 WOOD PERIMETER
COLUMN
PANEL EDGE @ 6" OC AND
FIELD @ 12" OC
MIN 0.113 DIA x 2
HOT DIP GALVANIZED
5/8" WALL
SHEATHING,
SEE WALL
SHEATHING NOTES
EXISTING ENDWALL
FRAMING
EXISTING TRUSS
SUPPORTED BY
NOTCHED 6X6 COLUMN
NEW TRUSS
SISTER TO EXISTING
2x6 TRUSS SUPPORT JACK
NAILED TO COLUMN TO
SUPPORT NEW TRUSS, RUN TO
GROUND, MUST PROVIDE FULL
BEARING FOR NEW TRUSS, TYP
MS-S1.1
MS-S1.1
NEW 2x6 STUDS AT 16" OC
TYP
2'-0"
APPROX 24'-0" FIELD VERIFY
V
IF
.2
2X6 SPF #1/2 CEILING JOIST @ 24" OC,
W/ SIMPSON LUS26 TYPICAL
5/8" GYPSUM CEILING
NEW PRESS PLATE TRUSS.
SISTER TO EXISTING.
NEW TRUSS TO SUPPORT ALL
INDICATED LOADING NEGLECTING EXISTING
PLYWOOD GUSSET TRUSS CAPACITY
SISTER NEW 2X4 ATTACH EACH DOUBLE 2X4 TO
NEW TRUSS AND EXISTING ENDWALL
FRAMING WITH SIMPSON H2.5A
NAIL PLIES TOGETHER W/ 0.113" DIA x 3" @ 12" O.C.
ALTERNATE SIDES NAILS ARE FASTENED THROUGH
PROVIDE MINIMUM (1) 2X6 TO SUPPORT EACH TRUSS PLY
EXISTING METAL ROOF
FASTEN CHORD AND WEB MEMBERS OF
EXISTING TO NEW W/ SIMPSON
WSNTL3S AT 12" O.C. AT BOTTOM CHORD,
24 OC REMAINDER. FILL GAP BETWEEN EXISTING
PLYWOOD GUSSETS OSB OR PLYWOODNEW PLYWOOD SHEATHING
TOP PLATE
NEW WALL
STUDS REMOVE AND REINSTALL
EXISTING CONTINUOUS 2x
AT TOP OF POSTS IF NECESSARY
TO INSTALL WALL STUDS
EXISTING 2x6 WALL GIRTS
EXISTING METAL SIDING
NEW 2x6 STUDS AT 16" OC
ATTACH TO EXISTING 2X6 GIRTS
W/10d TOENAILS EACH GIRT
NEW PLYWOOD INTERIOR
SHEATHING SEE ARCH FOR FIRE
TREATMENT
REQUIREMENTSEXISTING 6x6 POST
NEW 2x6 JACK AT
NEW TRUSS LOCATIONS
FASTEN TO EXISTING 6x6 W/ (2) 12d NAILS AT 16" O.C.
NEW DOUBLE 2x6 AT
GARAGE DOOR
EXISTING 6x6 POST BEYOND
NEW INTERIOR PLYWOOD
SHEATHING
NEW 2X6 SPF #1/2 STUD FRAMING
NEW PRESERVATIVE TREATED
2X6 BOTTOM PLATE FULL
LENGTH BETWEEN 6x6 POSTS
EXISTING 2x6 GIRTS
EXISTING METAL SIDING
EXISTING THICKENED EDGE SLAB
ON GRADE
SIMPSON THD37350HMG AT 24" OC
W/ SIMPSON BPS-6 BEARING PLATE
PROJECT #
DATE OF ISSUE:
6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719 p608.829.4444 f608.829.4445 dimensionivmadison.com
C
U s e rs
\M ik e \D o c u m e n ts
\1
S T
R
F o re s t
L o d g e m le if e rm a n .r v t
/1
/2
:4
:4
P
M
FOREST LODGE
THREE BUILDING
HISTORIC
REHABILITATION
22230 GARMISCH ROAD,
CABLE, WI 54821
MS−S1.1
MACHINE SHED
FRAMING PLAN
190147
01/17/2020
SHEET KEYNOTES
3 SISTER NEW WOOD ROOF TRUSS TO EXISTING WOOD TRUSSES.
11 SISTER 2x4'S TO EXISTING WOOD PURLINS.
1/4" = 1'-0"MS-S1.1
1 ROOF FRAMING PLAN
3/8" = 1'-0"MS-S1.1
4 WALL ELEVATION FROM INSIDE OF MACHINE SHED
1/2" = 1'-0"MS-S1.1
2 MACHINE SHED TRUSS
1 1/2" = 1'-0"MS-S1.1
5 MACHINE SHED WALL CONSTRUCTION
1 1/2" = 1'-0"MS-S1.1
3 MACHINE SHED WALL BASE
100% - BID SET
1 AMENDMENT 4 05/15/2020
FD
24' - 2" VIF
V
IF
23' - 8" VIF
7' - 2" VIF5 1/2"7' - 6" VIF5 1/2"7' - 1" VIF
7'
V
IF
1/
2" 7'
V
IF
1/ 2"
9'
V
IF
1/
2" 5'
V
IF
1/ 2"
7'
V
IF
7' - 2" VIF5 1/2"7' - 6" VIF5 1/2"7' - 1" VIF
7'
V
IF
1/
2" 5'
V
IF
1/ 2"
9'
V
IF
1/
2"
7'
V
IF
1/
2" 7'
V
IF
MS-A2.1 A
MS-A2.1
C
MS-A2.1D
MS-A2.1
B
MACHINE SHED
STORAGE
100d
6U
TYP.
TYP.6
TYP.6
CATCH BASIN WITH
SEALED COVER, SEE MEP
A
MS-A1.1
100a
100b 100c
30" x 30" PRIMED STEEL
INSULATED ATTIC
ACCESS PANEL
6W
6W
6W
6W
SEE STRUCTURAL
FOR FRAMING
EXISTING RAFTERS AND TRUSSES WITH
NEW SISTER TRUSSES, SEE STRUCTURAL
MACHINE SHED
GYPSUM CEILING ON NEW JOISTS SHOWN
ON STRUCTURAL DRAWINGS
BLOWN INSULATION OVER 12" BATT = R 49
EXISTING
OVERHEAD DOOR TRACK AND OPENER
INSULATION BAFFLE
INSULATION BAFFLE
VENTED PAINTED
ALUMINUM SOFFIT -
PROVIDE END CLOSURES
VENTED PAINTED ALUMINUM
SOFFIT - PROVIDE END
CLOSURES
MACHINE SHED FIRST FLOOR
100' - 0"
MACHINE SHED TRUSS
BEARING
109' - 4 1/2"
NEW GYPSUM CEILING AT
BOTTOM OF TRUSS
EXISTING EXTERIOR WALL
SIDING TO REMAIN
NEW OVERHEAD DOOR TRACK AND OPENER
NEW EXTERIOR DOOR, SEE DOOR SCHEDULE
6U
EXISTING RAFTERS AND TRUSSES WITH
NEW SISTER TRUSSES, SEE STRUCTURAL
PROVIDE ROOFING MANUFACTURER'S STANDARD
MATCHING TRIM, CLOSURE STRIPS, RIDGE VENT AND
ACCESSORIES FOR A COMPLETE INSTALLATION.
5 1/2"5/8"
R = 106W
(MINIMUM R-10) CLOSED CELL
SPRAY FOAM INSULATION
SIDING FASTENED PER
MANUFACTURER
EXISTING 2x6 HORIZONTAL FURRING
(1) LAYER 5/8" PLYWOOD
SHEATHING, SEE STRUCTURAL
5/8"5 1/2"5/8"
6U
5/8" PLYWOOD
2x6 WOOD STUDS
AT 16" O.C.
CORRUGATED METAL SIDING
EXISTING 6x6 WOOD POSTS & NEW 6x6 WOOD FRAMING, SEE STRUCTURAL
(MINIMUM R-15) HIGH DENSITY
BATT INSULATION
FLOOR PLAN GENERAL NOTES
A. PROVIDE VERTICAL CONTROL JOINTS (CJ'S) WHERE STRUCTURAL
SYSTEMS CHANGE, LOCATIONS THAT ARE PRONE TO CRACKING
AND AS REQUIRED BY MANUFACTURES INSTALLATION
RECOMMENDATIONS.
B. VERIFY SIZE AND LOCATIONS OF ALL MECHANICAL OPENINGS.
GENERAL CONTRACTOR TO PAINT AND SEAL LOUVER PERIMETER,
TYPICAL.
C. GENERAL CONTRACTOR TO PROVIDE CONCRETE EQUIPMENT
PADS/CURBS AS REQUIRED FOR MECHANICAL/ELECTRICAL
EQUIPMENT. VERIFY SIZE/PROFILE/LOCATION WITH
PLUMBING/MECHANICAL/ELECTRICAL.
D. VERIFY ALL ACTUAL CHASE DIMENSIONS WITH HVAC CONTRACTOR.
E. ABA CLEARANCE CIRCLES AND BOXES SHOWN ON PLAN ARE FOR
INFORMATION PURPOSES ONLY.
F. DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD UNLESS
NOTED OTHERWISE.
G. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS SHOWN AND SHALL REPORT ALL DISCREPANCIES TO
THE ARCHITECT PRIOR TO COMMENCING WORK.
FLOOR PLAN KEYNOTES
1. LUMBER RACK TO BE REMOVED. COORDINATE SALVAGE WITH
OWNER.
2. NEW WALL TO BE PLACED WHERE EXISTING FRAMING STANDS.
REMOVE EXISTING FRAMING AND BUILD NEW WALL TO DECK.
3. REPLACE EXISTING DOOR, FRAME, AND HARDWARE. SEE DOOR
SCHEDULE.
4. EXISTING ROOF STRUCTURE TO REMAIN, TYP. SEE STRUCTURAL
DRAWINGS FOR REINFORCEMENT PLAN.
5. PATCH AND REPAIR EXISTING CONCRETE FLOOR AS NEEDED.
6. EXISTING COLUMNS TO REMAIN.
7. EXISTING FIRE EXTINGUISHER CABINET TO REMAIN.
8. REMOVE EXISTING ELECTRICAL PANEL. ADD NEW PANEL ON NEW
WALL FACE IN LOCATION INDICATED ONCE FURR WALL HAS BEEN
BUILT. SEE ELECTRICAL DRAWINGS.
9. REMOVE PORTION OF WALL AS INDICATED ON PLAN AT HEIGHT
REQUIRED FOR NEW HEADER WHERE APPLICABLE.
10. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. SALVAGE
SIDING FROM DOOR FOR PATCH WORK. COORDINATE REMAINING
SALVAGE WITH COR.
11. REMOVE PORTION OF WALL AROUND EXISTING OPENING TO
ACCOMODATE NEW OVERHEAD DOOR AND HEADER, SEE DOOR
SCHEDULE.
12. EXISTING ELECTRICAL BOX. SEE ELECTRICAL DRAWINGS.
13. INFILL/PATCH OPENING WITH SALVAGED SIDING.
24' - 2" VIF
8'
9'
/4
V
IF
3'
4'
/4
V
IF
8'
V
IF
0"
V
IF
V
IF
23' - 8" VIF
7' - 2" VIF5 1/2"7' - 6" VIF5 1/2"7' - 1" VIF
7'
V
IF
1/
2" 7'
V
IF
1/ 2"
9'
V
IF
1/
2" 5'
V
IF
1/ 2"
7'
V
IF
7' - 2" VIF5 1/2"7' - 6" VIF5 1/2"7' - 1" VIF
7'
V
IF
1/
2" 5'
V
IF
1/ 2"
9'
V
IF
1/
2" 7'
V
IF
1/ 2"
7'
V
IF
MACHINE SHED
E100c
E100e
1/
2"
E100a
MACHINE SHED FIRST FLOOR
100' - 0"
SEE PLAN FOR WALL TYPES
GYPSUM WALLBOARD CEILING AT BOTTOM
OF TRUSS
EXISTING AND NEW SISTER TRUSSES, SEE
STRUCTURAL
REPLACE BASE STRUCTURAL MEMBER WITH
TREATED LUMBER WHERE SIGNS OF ROT ARE
PRESENT
ADD METAL CLOSURE STRIP TO MATCH
EXISTING SIDING PROFILE AROUND PERIMETER
SPRAY ON GREAT STUFF PESTBLOCK OR EQUAL
TO FILL ANY REMAINING GAPS AT BASE OF WALL
NEW WOOD JOISTS - SEE STRUCTURAL
REPLACE EXISTING METAL ROOF
VENTED PAINTED ALUMINUM
SOFFIT - PROVIDE END CLOSURES
BLOWN INSULATION OVER 12" BATT = R 49
INSULATION BAFFLE
METAL TRIM
NEW PRESSURE TREATED PLATE BOLTED
TO SLAB
RIDGE VENT
RIB METAL ROOFPUMBLING VENT
PROJECT #
DATE OF ISSUE:
6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719 p608.829.4444 f608.829.4445 dimensionivmadison.com
100% − BID SET
C
U s e rs
\m z h o u \D o c u m e n ts
\1
F o re s t
L o d g e m z h o u Y
Z T
B J .r v t
/2
/2
:3 :5
P
M
FOREST LODGE −
THREE BUILDING
HISTORIC
REHABILITATION
22230 GARMISCH ROAD,
CABLE, WI 54821
MS−A1.1
MACHINE SHED
FLOOR PLAN
19042
05/15/2020
3/16" = 1'-0"
FIRST FLOOR PLAN
1/4" = 1'-0"
BB
MACHINE SHED SECTION
PROJECT
NORTH
N0' 1' 2' 4'
0' 1' 2' 4'
1/4" = 1'-0"
AA
MACHINE SHED SECTION
0' 1' 2' 4'
1 1/2" = 1'-0"
TYPE 6 WALL TYPES - WOOD
4" 8"2"0'
3/16" = 1'-0"
DEMOLITION PLAN
PROJECT
NORTH
N0' 1' 2' 4'
3/4" = 1'-0" A
TYPICAL WALL SECTION
3/16" = 1'-0"
MACHINE SHED ROOF PLAN
PROJECT
NORTH
N0' 1' 2' 4'
3 Amendment 4 Date 3
3 AMENDMENT 4 05/15/2020
MACHINE SHED FIRST FLOOR
100' - 0"
MACHINE SHED TRUSS
BEARING
109' - 4 1/2"
EXISTING FEC TO REMAIN
DEMOLISH EXISTING WALL, DOOR, FRAME, ETC. TO ACCOMODATE NEW
DOOR, FRAME, AND HEADER. SALVAGE AND REUSE SIDING & ROOFING
AND REPLACE IN KIND AS NECESSARY. PATCH AND REPAINT AS
NEEDED.
NEW WORK NEW WORK EXISTING TO REMAINEXISTING NEW WORK EXISTING
DEMOLISH EXISTING WALL, DOOR, HEADER, AND
FRAME. SALVAGE AND REUSE SIDING & ROOFING
AND REPLACE IN KIND AS NECESSARY. PATCH WALL
AND REPAINT.
D O
O R
8'
EXISTING SLIDING DOOR
TRACK REMAINS.
RIDGE VENT
SNOW RAIL - EXTEND 1' BEYOND
DOOR OPENING
EXISTING SIDING ABOVE
DOOR CAN REMAIN
EXTEND SNOW RAIL 1'
BEYOND FIRE EXTINGUISHER
1/ 4"
/1 6"
EXISTING TO REMAIN
CONTINUOS RIDGE VENT
MACHINE SHED FIRST FLOOR
100' - 0"
MACHINE SHED TRUSS
BEARING
109' - 4 1/2"
EXISTING FIRE EXTINGUISHER
CABINET TO REMAIN
EXISTING TO REMAIN
CONTINUOS RIDGE VENT
EXISTING TO REMAINNEW WORKEXISTING TO REMAIN
INFILL OPENING WITH SALVAGED
SIDING/ROOFING
ROOFING MANUFACTURER'S
STANDARD RIDGE VENTREMOVE EXISTING METAL ROOF AND INSTALL NEW
SIMILAR METAL ROOF. SALVAGE GOOD EXISTING
PANELS FOR WALL INFILL AND PATCHING
D O
O R
8'
EXISTING SLIDING DOOR
TRACK REMAINS.
SNOW RAIL - EXTEND 1' BEYOND DOOR
OPENING IN EACH DIRECTON
EXISTING SIDING ABOVE
DOOR CAN REMAIN
ELEVATION LEGEND & NOTES
GENERAL NOTES
A. GENERAL CONTRACTOR TO COORDINATE ALL COLORS WITH
ARCHITECT AND OWNER.
SIDING
PM PRE-FINISHED METAL SIDING COLOR TO MATCH EXISTING
LEGEND
DEMOLISH TO REMOVE OR INSTALL NEW DOOR. SALVAGE AND
REINSTALL SIDING. PATCH, REPAIR, AND REPAINT TO MATCH
ADJACENT.
DOOR SCHEDULE GENERAL NOTES
A. HOLLOW METAL FRAME HEADS TO BE 2", U.N.O.
B. ALL SWING DOORS TO RECEIVE 1-1/2 PAIR OF HINGES (3 HINGES
TOTAL), U.N.O.
C. PROVIDE LEVER HANDLE LOCK/LATCH SETS AT ALL DOORS, U.N.O.
D. ALL FIRE DOORS ARE TO BE RATED ASSEMBLIES (DOOR AND
FRAME TOGETHER). PROVIDE ALL REQUIRED HARDWARE, SMOKE
SEALS, AND ACCESSORIES.
E. MEANS OF EGRESS DOORS: LATCHES DO NOT REQUIRE MORE
THAN 15 lbf TO RELEASE THE LATCH. LOCKS DO NOT REQUIRE USE
OF A KEY, TOOL OR SPECIAL KNOWLEDGE FOR OPERATION.
F. PROVIDE WEATHER STRIPPING FOR ALL NEW INTERIOR AND
EXTERIOR DOORS.
DOOR SCHEDULE LEGEND
SYMBOL ITEM DESCRIPTION
INS INSULATED
HM HOLLOW METAL
A
SINGLE
B
DOUBLE
PER DOOR SIZEPER DOOR SIZE
F
FLUSH
OH
SECTIONAL OVERHEAD
NG
NARROW GLAZED
8"
8"
1' - 0"
3'
PROJECT #
DATE OF ISSUE:
6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719 p608.829.4444 f608.829.4445 dimensionivmadison.com
100% − BID SET
C
U s e rs
\m z h o u \D o c u m e n ts
\1
F o re s t
L o d g e m z h o u Y
Z T
B J .r v t
/2
/2
:3 :5
P
M
FOREST LODGE −
THREE BUILDING
HISTORIC
REHABILITATION
22230 GARMISCH ROAD,
CABLE, WI 54821
MS−A2.1
MACHINE SHED
EXTERIOR
ELEVATIONS
19042
05/15/2020
1/4" = 1'-0" A
MACHINE SHED WEST ELEVATION
1/4" = 1'-0"
B
MACHINE SHED SOUTH ELEVATION
1/4" = 1'-0" C
MACHINE SHED NORTH ELEVATION
1/4" = 1'-0"
D
MACHINE SHED EAST ELEVATION
0' 1' 2' 4'0' 1' 2' 4'
0' 1' 2' 4'0' 1' 2' 4'
MACHINE SHED DOOR SCHEDULE
DOOR
NO.
ROOM
NAME TYPE
DOOR FRAME
HARDWARE COMMENTSW H T ELEV MATERIAL ELEV MATERIAL HEAD JAMB SILL
MACHINE SHED FIRST FLOOR
100a MACHINE SHED Single 3' - 0" 6' - 8" 1 3/4" NG HM, INS A HM, INS PAINT TO MATCH EXISTING, COORDINATE ALL COLORS WITH CONTRACTING OFFICER. PROVIDE
WEATHERSTRIPPING, THRESHOLD, ETC.
100b MACHINE SHED Overhead 9' - 0" 8' - 0" 2" OH HM, INS HM, INS PAINT TO MATCH EXISTING, COORDINATE ALL COLORS WITH CONTRACTING OFFICER. PROVIDE
WEATHERSTRIPPING.
100c MACHINE SHED Overhead 9' - 0" 8' - 0" 2" OH HM, INS HM, INS PAINT TO MATCH EXISTING, COORDINATE ALL COLORS WITH CONTRACTING OFFICER. PROVIDE
WEATHERSTRIPPING.
100d MACHINE SHED Double 6' - 0" 6' - 8" 1 1/2" F HM, INS B HM, INS PAINT TO MATCH EXISTING, COORDINATE ALL COLORS WITH CONTRACTING OFFICER. PROVIDE
WEATHERSTRIPPING, THRESHOLD, ETC.
1/4" = 1'-0"
MACHINE SHED DOOR FRAME & TYPE ELEVATIONS
3 Amendment 4 Date 3
AMENDMENT 4 05/15/2020
GENERAL NOTES
1. THE CONTRACTOR IS RESPONSIBLE FOR JOB SITE SAFETY REQUIREMENTS, PROGRAMS AND PRECAUTIONS.
2. THE ENGINEER OF RECORD HAS NO CONTROL OVER, OR CHARGE OF, AND SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, PROCEDURES, TECHNIQUES OF CONSTRUCTION NOR ANY RIGHT OR POWER TO STOP THE
WORK.
3. THE BUILDING STRUCTURE IS DESIGNED TO FUNCTION AS A COMPLETE SYSTEM, AND HAS NOT BEEN ANALYZED NOR DESIGNED FOR STABILITY DURING CONSTRUCTION. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DESIGN AND PROVIDE ADEQUATE TEMPORARY BRACING TO INSURE STABILITY DURING THE CONSTRUCTION PROCESS. ADDITIONALLY, THE CONTRACTOR IS RESPONSIBLE TO INSURE THAT
CONSTRUCTION LOADS DO NOT EXCEED THE DESIGN CAPACITY OF THE FRAMING ELEMENTS.
4. THE CONTRACTOR IS REQUIRED TO COORDINATE THE STRUCTURAL DRAWINGS WITH THE ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS, AND TO BRING ANY DISCREPANCIES, INTERFERENCES, DIMENSIONAL INCONSISTENCIES, OR CONCERNS ASSOCIATED WITH THIS COORDINATION
TO THE ARCHITECT AND ENGINEERS IMMEDIATELY.
5. DO NOT SCALE THE DRAWINGS.
6. DETAILS, SECTION CUTS AND NOTES INDICATED ON THESE DRAWINGS APPLY TO ALL SIMILAR CONDITIONS, WHETHER REPEATED OR NOT THROUGHOUT THE DRAWINGS.
7. INFORMATION CONTAINED ON THE STRUCTURAL DRAWINGS IS, IN ITSELF, INCOMPLETE AND VOID UNLESS USED IN CONJUNCTION WITH ALL OF THE CONTRACT DOCUMENTS AND ALL SPECIFICATIONS, TRADE PRACTICES, APPLICABLE STANDARDS AND CODES INCORPORATED THEREIN BY REFERENCE.
8. THE USE OF THESE DRAWINGS AND SPECIFICATIONS SHALL BE RESTRICTED AND LIMITED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED. ALL REPRODUCTION OR DISTRIBUTION IS EXPRESSLY LIMITED TO SUCH USE. ANY OTHER REPRODUCTION OR REUSE, IN WHOLE OR IN PART, FOR ANY OTHER PURPOSE IS PROHIBITED.
DESIGN LOADS
APPLICABLE DESIGN CODE AND REFERENCES
THE CODES AND STANDARDS LISTED HAVE BEEN USED FOR THE DESIGN OF THIS PROJECT.
ALL CONSTRUCTION, FABRICATION, AND MATERIALS SHALL CONFORM TO THESE CODES AND STANDARDS.
2015 INTERNATIONAL BUILDING CODE
ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS
ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
ACI 530-13 SPECIFICATION FOR MASONRY STRUCTURES
NDS-2012 AF&PA NATIONAL DESIGN SPEC FOR WOOD CONSTRUCTION
AISC 360-10 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
AISC 341-10 SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS
BUILDING DESIGN CRITERIA
BUILDING RISK CATEGORY: II (SEE ASCE 7-10 TABLE 1.5-1)
BUILDING DESIGN LOADS AND DATA
DEAD LOADS
ROOF 18 PSF COW PALACE
18 PSF MAIN LODGE
12 PSF MACHINE SHED
(6 PSF TOP CHORD, 6 PSF BOTTOM)
LIVE LOADS
FLOORS 40 PSF
ROOF LIVE LOADS
TRIBUTARY. AREA < 200 SF 20 PSF
TRIBUTARY. AREA > 600 SF 12 PSF
ROOF LIVE LOADS FOR A MEMBER WITH TRIBUTARY BETWEEN 200 SF AND 600 SF MAY
BE DETERMINED USING LINEAR INTERPOLATION.
SNOW
GROUND SNOW (Pg) 60.0 PSF
SNOW IMPORTANCE FACTOR, (I) 1.0
EXPOSURE FACTOR (Ce) 1.0 THERMAL FACTOR (Ct) 1.0 COW PALACE AND MAIN LODGE
1.1 MACHINE SHED
FLAT ROOF SNOW (Pf) 42.0 PSF COW PALACE AND MAIN LODGE
46.2 MACHINE SHED
SEE SNOW DRIFT SURCHARGE PLAN FOR ADDITIONAL SNOW LOADS REQUIRED
WIND DESIGN DATA
BASIC WIND SPEED 115 MPH
WIND IMPORTANCE FACTOR 1.0
DIRECTIONALITY FACTOR (Kd) 0.85 TOPOGRAPHY FACTOR (Kzt) 1.0
WIND EXPOSURE B
ENCLOSURE CLASSIFICATION ENCLOSED
INTERNAL PRESSURE COEFFICIENT +/- 0.18
SEISMIC DESIGN DATA
SEISMIC IMPORTANCE FACTOR, Ie 1.0 MAPPED SPECTRAL RESPONSE COEFFICIENT, Ss 0.041
MAPPED SPECTRAL RESPONSE COEFFICIENT, S1 0.018
SITE CLASSIFICATION D
SPECTRAL RESPONSE COEFFICIENT, Sds 0.043 SPECTRAL RESPONSE COEFFICIENT, Sd1 0.028
SEISMIC DESIGN CATEGORY A
SEISMIC BASE SHEAR 0.015W KIPS
RESPONSE COEFFICIENT, Cs 0.015
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
SOIL DESIGN DATA
ALLOWABLE NET SOIL BEARING PRESSURE 1,500 PSF (ASSUMED)
ALLOWABLE DEFLECTION CRITERIA
ROOF L/360 LIVE; L/240 TOTAL
FLOOR L/480 LIVE; L/240 TOTAL
(WOOD TRUSSES OR I-JOISTS)
L/360 LIVE; L/240 OTHER (OTHER MEMBERS)
EXTERIOR WALLS L/240 WIND (WOOD SIDING / STEEL PANEL)
1. SEE SPECIFICATION DIVISION 03 FOR REQUIREMENTS IN ADDITION TO THOSE LISTED BELOW.
2. MATERIAL SPECIFICATIONS
FOOTINGS F’c = 4000 PSI @ 28 DAYS FOUNDATION WALLS F’c = 4000 PSI @ 28 DAYS SLAB ON GRADE F’c = 3000 PSI @ 28 DAYS CONCRETE NOT OTHERWISE NOTED F’c = 4000 PSI @ 28 DAYS MILD REINFORCING STEEL BARS Fy = 60 KSI; ASTM A615
FIBER REINFORCING FOR SLABS ASTM C1116
ANCHOR RODS SEE SCHEDULE
3. SUBMIT CONCRETE MIX DESIGNS, WITH REQUIRED BACKUP DATA, INCLUDING RECENT GRADATIONS FOR EACH AGGREGATE USED, FOR EACH TYPE OF CONCRETE PROPOSED FOR USE, TO THE ARCHITECT AND ENGINEER FOR REVIEW A MINIMUM OF TWO WEEKS PRIOR TO PLACEMENT. SEE SPECIFICATIONS FOR ADDITIONAL MIX DESIGN REQUIREMENTS. CONCRETE MIXES SUBMITTED SHALL BE DESIGNED TO BE PLACABLE FOR THE
TEMPERATURE CONDITIONS AT THE JOBSITE, AND BE ABLE TO BE PLACED AND CONSOLIDATED AROUND THE REINFORCING INDICATED ON THE PLANS. DO NOT USE CALCIUM CHLORIDE IN ANY CONCRETE.
4. PROVIDE AIR-ENTERTAINING IN CONCRETE AS INDICATED IN THE SPECIFICATIONS.
5. ALL CONCRETE SHALL BE NORMAL WEIGHT (APPROX. 145 PCF) UNO.
6. SUBMIT DETAILED SHOP DRAWINGS INDICATING REINFORCEMENT SIZE, SPACING, BENDING, AND PLACEMENT TO THE ARCHITECT AND ENGINEER FOR REVIEW PRIOR TO FABRICATION. INCLUDE DETAILS AND LOCATIONS
OF ALL CURBS, CONSTRUCTION JOINTS, SLAB DEPRESSIONS, SLEEVES, OPENING, ETC.
7. THE MAXIMUM TOTAL AMOUNT OF WATER THAT MAY BE ADDED TO THE MIX AFTER BATCHING IS THE AMOUNT
INDICATED AS BEING WITHHELD ON THE BATCH TICKET FOR THE SPECIFIC BATCH.
8. SUBMIT ELECTRONIC COPIES OF ALL CONCRETE DELIVERY TICKETS WITHIN 5 DAYS OF PLACEMENT, INDICATING
THE FOLLOWING INFORMATION:
TIME AND NUMBER OF CUBIC YARDS BATCHED
THEORETICAL TARGET AND ACTUAL BATCH WEIGHTS OF EACH INGREDIENT
AMOUNT OF WATER WITHHELD
AMOUNT OF WATER ADDED AT JOBSITE
MIX DESIGN NUMBER
STRUCTURE BEING PLACED
LOCATION OF PLACEMENT
NUMBER OF REVOLUTIONS AT MIXING SPEED
TOTAL REVOLUTIONS AT COMPLETION OF DISCHARGE
TIME AT COMPLETION OF DISCHARGE
SLUMP AND AIR CONTENT, IF TESTED
TEMPERATURE OF AIR AND CONCRETE
SAMPLE NUMBERS OF CYLINDERS MADE FROM LOAD
9. DETAIL, FABRICATE, SUPPORT, AND PLACE ALL CONCRETE REINFORCEMENT IN ACCORDANCE WITH ACI 315 “DETAILS AND DETAILING OF CONCRETE REINFORCEMENT” AND ACI 318 “BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE”. FIELD BENDING OF REINFORCING BARS IS NOT PERMITTED EXCEPT WHERE
INDICATED ON THE STRUCTURAL DRAWINGS.
10. COVERAGE FOR REINFORCEMENT SHALL NOT BE NOT LESS THAN:
11. SEE DETAIL FOR CLASS B TENSION CONTACT LAP SPLICE LENGTHS.
STAGGER ADJACENT LAPS 3’ – 0” UNO.
12. PROVIDE (2) # 5 BARS DIAGONAL AT CORNERS OF OPENINGS AND AT RE-ENTRANT CORNERS.
PROVIDE (2) # 5 BARS AROUND THE PERIMETER OF OPENINGS WITH SIDES EXCEEDING 18 INCHES IN LENGTH.
13. WELDING OF GRADE A615 REINFORCING BARS IS NOT PERMITTED.
14. COORDINATE LOCATION OF ALL CONSTRUCTION JOINTS WITH ENGINEER PRIOR TO COMMENCEMENT OF CONCRETE WORK. EXTERIOR BASEMENT WALLS AND RETAINING WALLS SHALL HAVE VERTICAL CONTROL JOINTS SPACED NOT FARTHER THAN 30’-0” ON CENTER. CONSTRUCTION JOINTS SHALL BE LOCATED TO
COINCIDE WITH CONTROL JOINT LOCATIONS.
15. CLEAN AND MOISTEN ALL CONSTRUCTION JOINTS IMMEDIATELY PRIOR TO PLACING FRESH CONCRETE.
16. UNLESS NOTED OTHERWISE, PROVIDE DOWELS TO MATCH MAIN REINFORCEMENT SIZE AND SPACING.
PROVIDE TENSION LAP SPLICE UNLESS NOTED OTHERWISE.
17. REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR CURBS, PADS, DEPRESSIONS, WALL/SLAB OPENINGS, REVEALS, REGLETS, DRIPS, SPECIAL FLOOR FINISHES, AND OTHER
REQUIREMENTS NOT SHOWN ON STRUCTURAL DRAWINGS.
18. ALUMINUM CONDUIT SHALL NOT BE EMBEDDED IN CONCRETE.
20. REFER TO ACI 305 FOR REQUIREMENTS FOR PLACING CONCRETE IN HOT WEATHER AND TO ACI 306 FOR
REQUIREMENTS FOR PLACING CONCRETE IN COLD WEATHER.
CAST IN PLACE CONCRETE NOTES
S0.1
CONDITION COVER
CONCRETE CAST AGAINST AND 3"
PERMANENTLY EXPOSED TO EARTH
CONCRETE EXPOSED TO EARTH OR WEATHER
#5 BARS AND SMALLER 1-1/2"
#6 THROUGH #18 BARS 2"
CONCRETE NOT EXPOSED TO WEATHER OR
IN CONTACT WITH GROUND
SLABS, WALLS, & JOISTS
#14 AND #18 BARS 1-1/2"
#11 BARS AND SMALLER 3/4"
BEAMS AND COLUMNS
PRIMARY REINFORCEMENT, TIES, & SPIRALS 1-1/2"
1. THE FOUNDATIONS HAVE BEEN DESIGNED BASED ON AN ASSUMED BEARING CAPACITY. THE
ASSUMED SOIL BEARING CAPACITY SHALL BE CONFIRMED IN THE FIELD PRIOR TO PLACEMENT
OF FOUNDATIONS.
2. GEOTECHNICAL CONSULTANT MUST REVIEW AND APPROVE ALL FINISHED
EXCAVATIONS AND BEARING SUBGRADES BEFORE PLACING CONCRETE. PROVIDE ADDITIONAL
EXCAVATION AS NECESSARY TO ACHIEVE THE REQUIRED BEARING CAPACITY.
3. SEE SITE PLAN FOR ELEVATION DATUM EQUAL TO FIRST FLOOR TOP OF CONCRETE (ELEVATION 100'-0).
4. DO NOT UNDERMINE EITHER NEW OR EXISTING CONSTRUCTION.
5. BEAR ALL FOOTINGS ON UNDISTURBED SOIL OR COMPACTED FILLS HAVING A MINIMUM NET ALLOWABLE
BEARING CAPACITY INDICATED IN SOIL DESIGN DATA.
6. CLEAN REINFORCEMENT IMMEDIATELY PRIOR TO PLACING CONCRETE.
7. DO NOT PLACE CONCRETE IN ANY EXCAVATION CONTAINING FREE WATER, FROST, ICE OR FROZEN MATERIALS. PREVENT FROST OR ICE FROM PENETRATING ANY FOOTING OR SLAB SUBGRADE, BOTH BEFORE AND AFTER CONCRETE PLACEMENT AND UNTIL FOOTINGS OR SUBGRADES ARE FULLY PROTECTED
BY THE PERMANENT BUILDING STRUCTURE.
8. PLACE THE CONCRETE FOR EACH FOOTING IN ONE CONTINUOUS POUR.
9. BRACE FOUNDATION WALLS AND GRADE BEAMS DURING THE OPERATION OF BACKFILLING AND COMPACTION.
FOUNDATION NOTES
COMPONENTS & CLADDING WIND DESIGN PRESSURES
TRIBUTARY AREA = 10 SF NEGATIVE (PSF)
ZONE 1
TRIBUTARY AREA = 100 SF POSITIVE (PSF) NEGATIVE (PSF) R
O
O F
S
TRIBUTARY AREA = 10 SF POSITIVE (PSF) NEGATIVE (PSF)
TRIBUTARY AREA = 500 SF POSITIVE (PSF) NEGATIVE (PSF) W
A
L L
S
POSITIVE (PSF)
-21.816.0
ZONE 2
ZONE 3
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 4
ZONE 5
TRIBUTARY AREA = 10 SF POSITIVE (PSF) NEGATIVE (PSF)
TRIBUTARY AREA = 500 SF POSITIVE (PSF) NEGATIVE (PSF)
O V
E R
H A
N G
S
ZONE 2
ZONE 3
ZONE 2
ZONE 3
-37.916.0
-56.016.0
-19.816.0
-27.816.0
-44.016.0
-25.823.8
-31.923.8
-19.817.7
-19.817.7
-44.416.0
-74.616.0
-44.416.0
-50.416.0
NOTE: ALL PRESSURES ARE ULTIMATE, MULTIPLY BY 0.6 FOR SERVICE
LE
N
G T
H
D E
V E
LO
P
M E
N T
EXTENSION
Ld h
NOTES:
1. TOP BARS ARE DEFINES AT HORIZONTAL BARS WITH MORE THAN 12" OF
CONCRETE BELOW.
2. TABLE VALUES BASED ON 1 1/2" CLEAR COVER AND MINIMUM CENTER TO
CENTER BAR SPACING OF 6".
3. SPLICE LENGTH SHALL BE BASED ON LARGER BAR BEING SPLICED.
4. HOOKED BAR EXTENSION = MIN. BEND DIAMETER + 12db
5. MIN. BEND DIAMETER = 6db FOR #3 - #8 (8db FOR #9 - #11)
6. HOOKED BAR DEVELOPMENT LENGTHS, Ldh, ASSUME
a) SIDE COVER ≥ 2 1/2" AND
b) COVER AT END OF EXTENSION ≥ 2"
BAR SIZE STANDARD TOP BAR
12" 12"
16" 20"
19" 24"
23" 29"
37" 48"
4,000 PSI CONCRETE
61"
75"
91"
109"
6"
7"
9"
10"
12"
14"
15"
17"
19"
#3
#4
#5
#6
#7
#8
#9
#10
#11
STD HOOK
DEVELOPMENT
LENGTH, Ldh
DEVELOPMENT LENGTHS
16" 16"
STANDARD TOP BAR
CLASS "B" TENSION
LAP SPLICE LENGTHS
12"
15"
18"
29"
36"
44"
54"
65"
15"
19"
23"
37"
47"
57"
70"
84"
47"
57"
70"
84"
LE
N
G T
H
LA
P
1. PREPARE SUBGRADE AS INDICATED IN SOIL REPORT. AT A MINIMUM, PROOF ROLL AND REMOVE ALL SOFT AREAS
AND REPLACE WITH COMPATIBLE FILL.
2. SEE SPECIFICATIONS FOR SLAB ON GRADE VAPOR BARRIER, IF REQUIRED.
3. UNDER SLAB GRANULAR FILL PER GEOTECHNICAL REPORT.
4. SAWCUT SLABS ON GRADE AT A MAXIMUM SPACING OF 24 TO 36 TIMES THE SLAB THICKNESS, WITH A PANEL WIDTH TO LENGTH RATIO NOT TO EXCEED 1.5. START SAWCUTTING WITH EARLY ENTRY SAW AS SOON AS THE CONCRETE WILL SUPPORT THE WEIGHT OF THE SAW AND OPERATOR AND NOT RAVEL EDGES OR DISLODGE AGGREGATE, BUT IN NO CASE MORE THAN 6 HOURS AFTER THE SLAB IS PLACED. INSTALLATION OF JOINTS DOES
NOT IMPLY ANY WARRANTY AGAINST THE OCCURRENCE OF SHRINKAGE CRACKS.
5. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND SIZES OF SLAB DEPRESSIONS.
6. SLAB ON GRADE REQUIRES FIBER REINFORCING. SEE SPECIFICATIONS FOR APPROVED MANUFACTURERS AND
MINIMUM QUANTITIES.
7. SLAB ON GRADE THICKNESS, ELEVATION AND FLATNESS / LEVELNESS TOLERANCES:
THICKNESS: PLUS ½ INCHES; MINUS 0 INCHES
ELEVATION: SEE SPECIFICATIONS
FLATNESS / LEVELNESS: SEE SPECIFICATIONS
8. IN AREAS REQUIRING ADHERED FLOORING, DO NOT HARD TROWEL FINISH THE CONCRETE SLAB UNLESS INDICATED ON THE PLANS. CONCRETE IN THESE AREAS SHOULD HAVE AN OPEN PORE STRUCTURE WHEN FINISHED TO FACILITATE SLAB
DRYING, AND FLOORING ADHESION.
9. WET CURE SLAB UNLESS NOTED OTHERWISE ON DRAWINGS.
SLAB ON GRADE NOTES
ANCHORAGE TO CONCRETE & MASONRY
CONCRETE MASONRY
SOLID
CONCRETE
HOLLOW
CORE PLANK
GROUT
FILLED CMU
HOLLOW
CMU
ANCHOR
TYPE
ADHESIVE W/
THREADED
ROD
EXPANSION
ANCHOR
HEAVY DUTY
SCREW
ANCHOR
HILTI-HY 200
W/ HAS-E
THREADED ROD
HILTI-HY 70
W/ HAS-E ROD
& MESH SLEEVE
HILTI-HY 70 W/
HAS-E
THREADED
ROD
HILTI-HY 70 W/
HAS-E ROD IN
HIT-SC SLEEVE
OR HIT-IC INSERT
HILTI KWIK
BOLT TZ N/A N/A
HILTI KWIK
BOLT TZ
SIMPSON
TITEN HD
OR
HILTI KWIK HUS
N/A SIMPSON
TITEN HD
LIGHT DUTY
SCREW
ANCHOR
SIMPSON
TITEN
SIMPSON
TITEN
SIMPSON
TITEN
SIMPSON
TITEN
ADHESIVE
W/ REBAR
HILTI HIT-RE V3
ADHESIVE W/ GR.
60 REBAR
N/A N/A N/A
POWDER
ACTUATED
FASTENERS
SIMPSON PD
OR
HILTI X-U
N/A N/A
NOTES:
1. THE ABOVE CHART INDICATES BASIS…