12505B22R0028 – Steam Meter Replacements, Ames, IA Questions and Answers through 8/23/22
1. Can you answer the following:
a. Line Size: 6in Yes it is 6”
b. Connection: 6in (316ss cl 300 RF Flange schedule 80????) Schedule 80 black iron, not stainless
c. Process Temp: Min/Opp/Max -40 to +500 Deg F
d. Ambient Temp: Min/Opp/Max -40 to +176 Deg F
e. Measurement Type: Volumetric/Mass, Mass Flow
f. Process Pressure: PN40, Class 300, 20K
g. Expected Flow Rate: 0-1,374 lb/min
h. Media: Saturated or Super Heated Steam??? Saturated
i. Area Classification: GP/XP/IS Not familiar with what they are asking, but these are standard mechanical rooms with NO explosion proof required. No clean room standard. Approval is Non- Hazardous Area.
END