12505B22R0028 – Steam Meter Replacements, Ames, IA Questions and Answers through 8/23/22

1. Can you answer the following:

a. Line Size: 6in Yes it is 6”

b. Connection: 6in (316ss cl 300 RF Flange schedule 80????) Schedule 80 black iron, not stainless

c. Process Temp: Min/Opp/Max -40 to +500 Deg F

d. Ambient Temp: Min/Opp/Max -40 to +176 Deg F

e. Measurement Type: Volumetric/Mass, Mass Flow

f. Process Pressure: PN40, Class 300, 20K

g. Expected Flow Rate: 0-1,374 lb/min

h. Media: Saturated or Super Heated Steam??? Saturated

i. Area Classification: GP/XP/IS Not familiar with what they are asking, but these are standard mechanical rooms with NO explosion proof required. No clean room standard. Approval is Non- Hazardous Area.

END