Vendor RFI 260304.docx

DOCX document 17 KB Posted

Attached to
WMF Andro and Saco HVAC Repair Federal contract opportunity
Solicitation number
12445526Q0006
Issued by
Department of Agriculture Forest Service

About this file

This is a Request for Information (RFI) document containing vendor questions and government responses related to HVAC repair and replacement work at two White Mountain National Forest ranger stations in New Hampshire.

Androscoggin Ranger Station (Gorham, NH): The scope includes full replacement of four exterior air conditioning units with new pads, disconnects, and refrigerant line sets; installation of a new air handler in limited mechanical room space; reuse of existing ductwork unless field modifications are necessary; reuse of compatible condensate piping; replacement of corroded plumbing at boiler connection points only; verification that current electrical service is adequate for replacement equipment; and retention of existing controls and thermostats. No Building Automation System exists at this facility. The government confirmed that existing electrical service and panel capacity are adequate and that all work must comply with applicable federal, state, and local laws and regulations, though federal jurisdiction applies.

Saco Ranger Station (Conway, NH): The scope includes replacement of a Rheem RHERGEDYB120ACG22BAA unit (or approved equivalent) with determination needed regarding curb adapter requirements; reuse of existing condensate piping; verification that existing electrical service and disconnect are adequate; integration of new equipment with existing controls without upgrades required; and compliance with all applicable laws and regulations. The government estimated the project magnitude at under $150,000. Both projects are covered under solicitation 12445526Q0006, a Total Small Business Set-Aside with a $19 Million size standard, issued by the USDA Forest Service under NAICS 238220. Site visits were scheduled for February 18-19, 2026, with contact information provided for the Contracting Officer Representative.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

We have the following RFI’s question for the subject project, please advise:

RFI’s Questions - Androscoggin Ranger Station

1. Please confirm that all four (4) exterior air conditioning units are to be fully replaced, including replacement of pads, disconnects, and refrigerant line sets if existing components are not compatible with new equipment.

This is correct.

1. Please confirm required service and maintenance clearances for the new air handler within the limited mechanical room space.

1. Please confirm that existing ductwork may be reused and reconnected to the new air handler unless field conditions require modification.

This is Correct.

1. Please confirm whether existing condensate piping is to be reused or replaced as part of this scope.

Condensate piping may be reused if it is compatible with new equipment.

1. The SOW indicates replacement of corroded plumbing at boiler connection points. Please confirm whether replacement is limited to the immediate near-boiler connections or extends further into the main distribution piping.

The corrosion exists at the connection points and these are the only portions to be replaced.

1. Please confirm that existing electrical service and panel capacity are adequate for the replacement air conditioning units and air handler.

Current electrical connections are adequate for the replacement.

1. Please confirm whether new thermostats and control components are included in the scope, or if existing controls are to remain.

Existing controls are to remain in place.

1. Please confirm if any permits are required prior to construction. If federal jurisdiction applies, confirm no local AHJ permits or inspections are required.

This is a federal facility, but please act in accordance with all applicable laws and regulations.

1. What is the estimated magnitude of the project.

RFI’s Questions - Saco Ranger Station

1. Please confirm whether a curb adapter will be required for the replacement unit or if the existing mounting base is to remain.

Unknown

1. Please confirm whether condensate piping modifications are anticipated or if existing piping may be reused.

Existing piping may be reused.

1. Please confirm that existing electrical service and disconnect are adequate for the replacement Rheem RHERGEDYB120ACG22BAA (or approved equivalent) unit.

Existing service and disconnect are assumed to be adequate.

1. Please confirm that the replacement unit shall integrate with existing controls, and clarify whether any control upgrades are required.

All new equipment is to be integrated with existing controls.

1. Please confirm if any permits are required prior to construction. If federal jurisdiction applies, confirm no local AHJ permits or inspections are required.

This is a federal facility, but please act in accordance with all applicable laws and regulations.

General question:

1. Please confirm the estimated government magnitude of construction for this project. Under 150,000

RFI’s Questions:

1. Is there an existing Building Automation System (BAS) at the Androscoggin Ranger Station?

No

1. Are the replacement air conditioning units and new air handler required to integrate into the existing BAS?

N/A