12445526Q0005 WMF Saco RD Electrical Panel RFI 260219.docx

DOCX document 2 MB Posted

Attached to
WMF Saco RD Electrical Panel
Solicitation number
12445526Q0005
Issued by

About this file

This is a Request for Information (RFI) document providing clarifications and responses to bidder questions regarding the White Mountain National Forest Saco RD Electrical Panel RFQ (Solicitation 12445526Q0005). The RFI addresses technical specifications and scope questions for electrical panel upgrades at two locations: Saco, NH and Campton, NH.

At the Saco location, the project involves replacement of both the current transformer cabinet and main service board (MSB), which currently contains one 150A main breaker, three 100A breakers, and thirty 20A breakers. A sub-panel with fifteen 20A breakers, one 100A breaker, one 30A breaker, and one 50A breaker also requires replacement. The existing Federal Pacific equipment does not comply with National Electric Code (NEC) or NFPA standards and must be replaced with NEC-compliant hardware. Existing wiring and conduit sizes reach maximum 4/0 and 4-inch conduit. All pricing for repairs to damaged wiring, breakers, or grounding discovered during assessment must be included in base quotes. At the Campton location, the project includes installation of a 400A step-down transformer; however, specification details regarding 240V output configuration and whether the 400A rating applies to input or output remain unknown and require vendor clarification. Permits for both locations must be obtained in accordance with local regulations. All damaged components and replacements are to be included in base pricing rather than handled as modifications.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12445526Q0005 WMF Saco RD Electrical Panel RFI

1. In the SOW, what is meant by the “CT cabinet”? Please confirm whether this involves only the current transformer cabinet or replacement of the MSB/main switchboard?

Both the current transformer cabinet and the main service panel need to be replaced.

1. From the attached photos, can you confirm the total breaker count and all the sizes (20A, 40A, 60A, etc.)?

Sub panel: (15) 20A, (1) 100A, (1) 30A, (1) 50A MSB: (1) 150A Main Breaker

(3) 100A, (30) 20A

1. If damaged wiring, breakers, or grounding are found during assessment, should those replacements be handled by modification, or included in the base quote?

All pricing should be included in the base quote.

1. Can I get each amperage of the circuit breakers in the MSB?

MSB: (1) 150A Main Breaker

(3) 100A, (30) 20A

1. Do you have an idea what were the wires/conduits sizes used in the existing set up?

Max size is 4/0 and 4” Conduit

· Saco location

1. Upgrade - 400A Breaker

0. Are we replacing in kind? Is mounting hardware also required?

This is to be replaced with hardware that conforms to National Electric Code. The existing equipment is Federal Pacific and does not comply with NFPA OR NEC Standards

0. Is this to be upgraded in Switchboard MSB, or Panelboard BHDP?

Panelboard.

1. Upgrade - 400A Panel

1. Is this Panel BHDP?

This panel is a Federal Pacific

1. I can make out the branch breakers from the photo.

1. Can you advise on the "spare" and "heated warehouse" breaker Size and Pole.

See Attached Photos

1. Upgrade - 24 Circuit Load Center

2. Can you confirm this is UWHR-1.

Can NOT confirm

1. Do we need to obtain any permits prior to execution of this project? Please advise.

All permits will need to be obtained in accordance with local regulation.

· Campton location

1. Install - 400A Step Down Transformer

0. Is the 240V Output in the Q&A - 240V Delta? Unknown

0. Is the 400A rating for the Input or Output - If output we will quote a 175kVA Unknown

1. Do we need to obtain any permits prior to execution of this project? Please advise.

Permits will be obtained in accordance with local regulations.