This federal contract opportunity solicitation requests selective demolition services at the Ouachita Job Corps Center. The scope of work includes demolishing and removing 30 buildings and structures, grading and stabilizing disturbed areas, and potentially abating hazardous materials. Bidders must provide all labor, tools, equipment and materials. Key dates include the question deadline of September 10th, bid submission deadline of September 15th, and 180 day completion period after notice to proceed. The solicitation will be posted to SAM.gov on August 5th with no hard copies distributed. The contract is set aside for small businesses below $16.5M in size for NAICS 238910. The magnitude is between $250,000 to $500,000. The issuing agency is the US Department of Agriculture Forest Service.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared for:

United States Forest Service 1700 Bypass Road Winchester, KY 40391

OUACHITA JOB CORPS

HAZARDOUS MATERIALS

SURVEY REPORT

September 2021

Prepared by:

Harbor 5800 Evergreen Drive Little Rock, AR 72205

P: 501.663.8800 F: 501.588.0123 www.harborenv.com

Engineering ǀ Compliance ǀ Sustainability

Page Intentionally Blank i

Harbor was retained to perform a hazardous materials survey which includes the following:

asbestos-containing materials (ACM), lead-based paint, fluorescent light ballasts containing polychlorinated biphenyl (PCBs), and any other potential hazardous materials or substances. The survey was performed on twenty-eight (28) structures or areas at the Ouachita Civilian Conservation Center Job Corps in Royal, AR. The purpose of the survey was to identify suspect ACM, LBP, PCBs and other hazardous materials in the buildings/structures determined to be demolished at the Job Corps facility. Mr. Michael Dollar (AR Inspector No. 017385) and Mrs. Leslie Davis (AR Inspector 013151) of Harbor performed the asbestos sampling. Mr. David Fields and Mr.

Caleb Gourley were on-site to provide support for the inspectors. Samples were collected August 16th to 17th. Harbor is an ADEQ-licensed asbestos consultant (No. 000477). Inspector and company credentials are presented as Attachment B.

All concrete slabs, concrete debris and sidewalks set for demolition were inspected and found to contain no hazardous materials on or around the structures. This includes the concrete slab and sidewalk north of Building 10, the concrete slabs southeast of Building 15, the concrete debris east/northeast of Building 57, the concrete slabs by the Amphitheater, the sign and concrete north of Building 13, the concrete slabs and storage bin by Buildings 43 and 53A, the storage bin and area southeast of Building 63, and the concrete slabs near Building 5B.

Thank you for the opportunity to work with you on this asbestos survey. Should you have any questions or require additional information, please do not hesitate to contact us at 501.663.8800.

Sincerely, HARBOR ENVIRONMENTAL AND SAFETY

Michael Dollar Leslie Davis, Project Manager Principal Asbestos Inspector #017385 Asbestos Inspector #013151

United States Forest Service Hazardous Materials Survey ii

Table of Contents Section A: Hazardous Substance Containing Materials Summary Asbestos Containing Materials 3 Polychlorinated Biphenyls 5 Lead-based Paint 5

Section B: Hazardous Materials Survey: All Materials Building 2: Men’s Dormitory 11 Building 5: Healthcare 29 Building 6C: Gym Storage 49 Building 6D: Gym Storage 53 Building 6E: Gym Storage 57 Gym Dumpster Pad 61 Building 8A: Paint Storage 69 Building 8B: Maintenance Storage 85 Building 8C: Carpentry Storage 96 Building 8D: Vocational Storage 107 Storage Racks by Building 8D 118 Building 12: Vocational Education 128 Reservoir and Pump House 165 Building 15B: Dining Storage 169 Building 15C: Dining Storage 173 Building 21: Laundry/Canteen 177 Storage Bin by Building 29 200 Building 29: Vocational Storage 208 Building 29A: Vocational Storage 220 Building 30: Vocation Storage 224 Building 30A: Oil Storage 233 Building 31: Vocational Storage 249 Building 43: Vocational Storage 263 Building 53A: Masonry Storage 275 Building 55A: Dormitory Storage 286 Building 57: Gazebo 294 Building 59: Gazebo 302 Building 60: Gazebo 308 Building 61: Gazebo 317 iii

Building 62: Gazebo 326 Building 63: Storage 330 Building 63A: Vocational Storage 342 Building 63B: Vocational Storage 346 Concrete Storage Bins by Building 63 349 Carport 354

List of Attachments Attachment A: Asbestos-Containing Material Quantity Summary Attachment B: Key Plans Attachment C: Inspector and Company Credentials

Section A:

Hazardous Substance Containing

Materials Summary

1.0 Asbestos Inspection Methodology

The asbestos survey was conducted to supplement a previous inspection report conducted in 1992. The previous report excluded some interior materials and the exterior building materials.

Homogeneous areas were identified and suspect materials within each area were categorized as surfacing, thermal system insulation, or miscellaneous. Homogeneous materials are those building materials that, by visual and manual inspection, are similar in texture, color, composition, and use in the building. The condition of each suspect material was assessed in the field by the inspector.

The condition of the materials was classified as good, damaged, or significantly damaged. A Sampling Location Key Plan is included as Attachment A for building and area sample location reference numbers for the survey. Each structure/area section of this report contains respective sample location maps for the structure/area sampled.

Federal and state regulatory agencies define ACM as any building material that contains greater than 1% asbestos. The presence and percentage of asbestos can only be determined by laboratory analysis. Asbestos samples were sent to EMSL Analytical, Inc. (EMSL) in Houston, Texas. EMSL participates in the National Institutes for Standards and Testing (NIST) National Voluntary Laboratory Accreditation Program (NVLAP) proficiency testing program (NVLAP No. 101587-0).

Samples were analyzed by Polarized Light Microscopy (PLM) by EPA method 600/R/R-93/116. All percentages reported for composition are based on visual estimation or gravimetric determinations. Laboratory reports are provided with each building and area sampled throughout the report. Asbestos containing materials summary is provided in Table 1-1 below. An ACM Quantity Summary is provided as Attachment A of this Report.

Table 1-1 Asbestos Containing Materials Sample Number Location & Description Condition

Friable/Non-Friable Asbestos

Type RACM Survey

Building 2: Men’s Dormitory

2SR-2-

Texture Sheetrock Ceiling Sheetrock W Dorm Good

Friable 2% Chrysotile (A) ’21 Survey

2SR-3-

Texture Sheetrock Ceiling Tile W Dorm Good

Friable Positive Stop

(Not Analyzed) (A) ’21 Survey

2SR-4-

Texture Sheetrock Ceiling Tile E Dorm S Side Good

Friable Positive Stop

(Not Analyzed) (A) ’21 Survey

Building 5: Health Care

*16-1 Linoleum Floor, Light Green, Light Brown Grey Patterned, Lab

Good Non-Friable

20-25% Chrysotile

(E) ’92 Survey

*16-2 Grey, Light Brown Off-white Small Patterned Linoleum, Utility Room

Good Non-Friable

20-25% Chrysotile

(E) ’92 Survey

Building 9: Vocational

9-3 12”x 12” Vinyl Floor Tile, Grey w/ Light Green, Dark & White Streaks

Good Non- Friable

1-5% Chrysotile (E) ’92 Survey

Sample Number Location & Description Condition

Friable/Non-Friable Asbestos

Type RACM Survey

Building 10: Vocational Office / Warehouse

10-1 12” x 12” Vinyl Floor Tile, Off-White w/ Brown Specks1 and Mastic2

Good Non- Friable

1-5% Chrysotile

(E)1 (F)2 ’92 Survey

Building 12: Vocational Education

12VM-1

Vent Mastic - Northeast Corner of Main Building Roof

Good Non-Friable

10% Chrysotile (D) ’21 Survey

12VM-2

Vent Mastic - Northeast Corner of Main Building Roof

Good Non-Friable

Positive Stop (Not Analyzed) (D) ’21 Survey

12RM-1

Roof Pipe Mastic - Northwest Area of Main Building Roof

Good Non-Friable

10% Chrysotile (D) ’21 Survey

12RM-2

Roof Pipe Mastic - Northwest Area of Main Building

Good Non-Friable

Positive Stop (Not Analyzed) (D) ’21 Survey

12LRM-1

Lower Roof Pipe Mastic – Near Southwest Area of Roof

Good Non-Friable

10% Chrysotile (D) ’21 Survey

12LRM-2

Lower Roof Pipe Mastic – Near Southwest Area of Roof

Good Non-Friable

Positive Stop (Not Analyzed) (D) ’21 Survey

12-3 12”x 12” Vinyl Floor Tile, Off-White w/ Brown Streaks

Good Non-Friable

1-5% Chrysotile (E) ‘92 Survey

12”x 12” Vinyl Floor Tile, Off-White w/ Brown Streaks (same as 12-3 above) – Cement Masonry (Safe Room) and stairway entrance landing.

Good Non-Friable Assumed (E) -

12-4 12”x 12” Vinyl Floor Tile, Off-White w/ Light Green Streaks (Mastic is ACM)

Good Non-Friable

1-5% Chrysotile (F) ‘92 Survey

12-4QC

12”x 12” Vinyl Floor Tile, Off-White w/ Light Green Streaks (Mastic is ACM)

Good Non-Friable 1% Chrysotile (F) ‘92 Survey

Regulation 21 as revised by the Commission as of January 2014 defines Regulated Asbestos- Containing Material (RACM) as:

(A) Friable asbestos material;

(B) Category I non-friable ACM that has become friable;

(C) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading;

(D) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by this regulation;

(E) Category I non-friable resilient floor covering which contains ACM that will be or has been removed by sanding, grinding, cutting, or abrading; or

(F) Category II mastic which contains ACM that will be removed by sanding, grinding, cutting, or abrading.)

Harbor recommends following ADEQ regulations which require notice of demolition of these structures. A project design will be required, along with appropriately certified workers and contracting company. A notice of intent (NOI), along with a copy of the asbestos survey, is required to be filed with ADEQ a minimum of 10 days prior to beginning work.

2.0 PCB Inspection Methodology

The PCB portion of the survey consisted of inspecting the capacitors in the light ballasts in the buildings proposed for demolition. Capacitors in which the label did not state “No PCBs” are assumed to contain PCBs and are listed in Table 2-1 below.

Table 2-1 PCBs Building 5: Healthcare

Description and Location Qty

Old fluorescent light capacitors throughout the building with two (2) ballasts, observed on the walls, were found to contain PCBs. 14

Pole-mounted transformer south of Carport 1

According to 40 Code of Federal Regulations (CFR) § 761.60(b)(2) any person may dispose of PCB small capacitors as municipal solid waste.

Harbor recommends following disposal methods for PCB transformers according 40 CFR 760.60(b)(1)(i)(A) or (B). Option A includes disposing of transformer in an incinerator in compliance with 40 CFR761.70. Option B includes disposing of the transformer in a chemical waste landfill approved under 40 CFR 761.75; provided that all free-flowing liquid is removed from the transformer. See regulations for more detail disposal information.

3.0 Lead-based Paint Sampling

The lead inspection procedures consisted of collection of discrete paint samples of visible paint material in the planned renovation area. Positive lead-based paint sample results are provided in Table 3-1 below. Federal and state regulatory agencies define a lead-based paint as containing 0.5% lead by weight.

Table 3-1 Positive Lead-based Paints

CPP-1 exceeded the Federal Agencies definition of a lead-based paint at 0.5% with a result of 1.23%. The brown/green paint on the carport overhang was peeling at the time of the site visit.

There are no regulations that require removal of LBP prior to renovation activities. However, OSHA does require that workers be protected from potential exposure to lead during the project.

Therefore, Harbor recommends that the Forest Service inform the renovation contractors of the lead-based paint discovered.

Carport Sample Number

Description and Location Total Lead

(mg/kg) Weight %

CPP-1 Brown/Green Paint from Carport Overhang 12,300 1.23% Positive

Section B:

Hazardous Materials Survey:

All Materials

Building 2: Men's Dormitory

Building 2: Men’s Dormitory See Map HA1 for Sample Locations

Building 2 is located southeast of Building 3 near the middle of the Job Corps facility. The building is constructed on a block and pier foundation, wood-framed walls with stucco exterior, and a pitched, asphalt-shingled roof. Building 2 is approximately 6,254 square feet. The building was inspected for suspect ACM, LBP, and other potentially hazardous materials. The sampled/observed materials and corresponding laboratory results, if applicable, are provided in Table 2-1, 2-2, and 2-3 below. Photographs of sampled/potentially hazardous materials from the 2021 HazMat Survey are included in Attachment A. Laboratory results are presented as Attachment B. This building was not sampled during the 1992 asbestos survey conducted by Asbestos Abatement Services, Inc.

Table 2-1: Asbestos Inspection Findings Building 2: Men’s Dormitory

2021 HazMat Survey Asbestos Samples Sample Number Description and Location Condition

Friable/Non-Friable Asbestos Type

2SR-1 Sheetrock Repaired Sheetrock W End of Hall Good Friable None Detected

2SR-2-

Sheetrock Sheetrock Ceiling Sheetrock W Dorm Good

Friable None Detected

2SR-2-

Texture Sheetrock Ceiling Sheetrock W Dorm Good

Friable 2% Chrysotile

2SR-3-

Sheetrock Sheetrock Ceiling Tile W Dorm Good

Friable None Detected

2SR-3-

Texture Sheetrock Ceiling Tile W Dorm Good

Friable Positive Stop

(Not Analyzed)

2SR-4-

Sheetrock Sheetrock Ceiling Tile E Dorm S Side Good Friable None Detected

2SR-4-

Texture Sheetrock Ceiling Tile E Dorm S Side Good

Friable Positive Stop

(Not Analyzed)

2WC-1 Caulk on Awning Plate Glass Window Front Left Good Non-Friable None Detected

2WC-2 Caulk on Awning Plate Glass Window Front Right Good Non-Friable None Detected

2PL-1 Interior Wall Plaster Interior Wall Office West Good Friable None Detected

2PL-2 Interior Wall Plaster Interior Wall Dorm West Good Friable None Detected

2PL-3 Interior Wall Plaster Interior Wall Dorm East Good Friable None Detected

2PL-4 Interior Wall Plaster Interior Wall Office East Good Friable None Detected

2CM-1 Carpet Mastic Yellow Carpet Mastic Foyer Good Non-Friable None Detected

Number Description and Location Condition

Friable/Non-Friable Asbestos Type

2CM-2 Carpet Mastic Yellow Carpet Mastic Dorm West Good Non-Friable None Detected

2ES-1-

Stucco Exterior Stucco West Wall Good

Friable None Detected

2ES-1-

Insulation Exterior Stucco West Wall Good

Friable None Detected

2ES-2-

Stucco Exterior Stucco North Wall Good

Friable None Detected

2ES-2-

Insulation Exterior Stucco North Wall Good

Friable None Detected

2ES-3-

Stucco Exterior Stucco East Wall Good

Friable None Detected

2ES-3-

Insulation Exterior Stucco East Wall Good

Friable None Detected

2ES-4-

Stucco Exterior Stucco South Wall Good

Friable None Detected

2ES-4-

Insulation Exterior Stucco South Wall Good

Friable None Detected

2DP-1-

Duct Paper HVAC Duct Paper NE Corner Good

Non-Friable None Detected

2DP-1-

Insulation HVAC Duct Paper NE Corner Good

Non-Friable None Detected

2DP-2 HVAC Duct Paper South Side Good Non-Friable None Detected

2WC2-1 White Window Caulk Front Glass to Right Good Non-Friable None Detected

2WC2-2 White Window Caulk Front Glass to Left Good Non-Friable None Detected

2UR-1-

Shingle 1 Asphalt Roofing Upper Roof Center Good

Non-Friable None Detected

2UR-1-

Shingle 2 Asphalt Roofing Upper Roof Center Good

Non-Friable None Detected

2UR-1-

Shingle 3 Asphalt Roofing Upper Roof Center Good

Non-Friable None Detected

2UR-1-

Felt Asphalt Roofing Upper Roof Center Good

Non-Friable None Detected

2UR-2-

Shingle 1 Asphalt Roofing Upper Roof West End Good

Non-Friable None Detected

2UR-2-

Shingle 2 Asphalt Roofing Upper Roof West End Good

Non-Friable None Detected

2UR-2-

Felt Asphalt Roofing Upper Roof West End Good

Non-Friable None Detected

2LR-1-

Shingle 1 Asphalt Roofing Lower Roof East Good

Number Description and Location Condition

Friable/Non-Friable Asbestos Type

2LR-1-

Shingle 2 Asphalt Roofing Lower Roof East Good

Non-Friable None Detected

2LR-2-

Shingle 1 Asphalt Roofing Lower Roof West Good

Non-Friable None Detected

2LR-2-

Shingle 2 Asphalt Roofing Lower Roof West Good

Non-Friable None Detected

2LR-2-

Felt Asphalt Roofing Lower Roof West Good

Non-Friable None Detected

2UWC-1 Upper Window Caulk Center Windows Good Non-Friable None Detected

2VWC-2 Upper Window Caulk West End Windows Good Non-Friable None Detected

Table 2-2: Lead-based Paint Inspection Findings

Table 2-3: Miscellaneous Hazardous Materials Inspection Findings

Building 2: Men’s Dormitory Sample Number

Description and Location Total Lead

(mg/kg) Weight %

Significantly peeling paint was not observed on the structure. - -

Building 2: Men’s Dormitory

Description and Location Qty

The fluorescent light ballast capacitors did not contain PCBs. 56

D ra fte r

D at e

Sc al e A

ES

8-

-2

1" =1

6'REVISION DESCRIPTION DATENO

XX X-X-XASBESTOS/LEAD SURVEY

BLDG #2 MEN'S DORM, USFS-21488

570 JOB CORPS ROAD

ROYAL, AR 71968 HA

IN

SP

EC

TO

R

IN

SP

EC

TO

R N

O

C O

N

SU

LT

A

N T

N O

:0

Harbor

A

SB

ES

TO

S/

LE

A D

N

EG

A

TI

VE

A

SB

ES

TO

S/

LE

A

D P

O

SI

TI

VE

LE

G

EN

D

N O

TE

S:

1)

FE

D

ER

A L

A N

D S

TA

TE

R

EG

U

LA

TO

R

Y A

G

EN

C

IE

S D

EF

IN

E A

N A

SB

ES

TO

S-

C O

N

TA

IN

IN

G M

A

TE

R

IA

L (A

C M

) A S

A N

Y B

U

IL

D

IN

G M

A

TE

R

IA

L

TH

A T

C O

N

TA

IN

S

G R

EA

TE

R T

H A

N

.0

A

SB

ES

TO

S.

2)

FE

D

ER

A

L A

N D

S

TA

TE

R

EG

U

LA

TO

R Y

A G

EN

C

IE

S

D

EF

IN

E

A L

EA

D

-B A

SE

D

P A

IN

T

A S

A P

A

IN

T C

O N

TA

IN

IN

G

G R

EA

TE

R T

H A

N

.5

L

EA

D B

Y W

EI

G

H T.

E ve rg ree n D riv e Li ttl e R oc k, AR

Ph (5

)6

-8

Fa x

(5

)5

-0 ww w.

ha rb or en v.

co m

M

IC

H A

EL

D

O

LL

A R

2S R

-1

2S R

-2

2S R

-3

2S R

-4

2W C

-1

2W C

-2

2P L-

1 2P L-

2P L-

2P L-

2C M

-1

2C M

-2

2E S-

2E S-

2E S-

2E S-

2D P-

1 2D P-

2U W

C -1

2U W

C -2

2U R

-2

2U R

-1

2C R

-1 2C

R -2

2W C

2-

2W C

2-

ATTACHMENT A

Building 2 Photographs

A T T A C H M E N T A

P HOTOGRAP HS

Photograph 1: Sheetrock.

Sample Nos. 2SR-1, -2, -3, -4 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

Photograph 2: Caulk on awning plate glass window.

Sample Nos. 2WC-1, -2, and 2WC2-1, -2 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

2WC-1, -2

2WC2-1, -2

Photograph 3: Interior wall plaster.

Sample Nos. 2PL-1, -2, -3, -4 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

Photograph 4: Carpet mastic.

Sample Nos. 2CM-1, -2 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

Photograph 5: Exterior stucco.

Sample Nos. 2ES-1, -2, -3, -4 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

Photograph 6: HVAC duct paper.

Sample Nos. 2DP-1, -2 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

Photograph 7: Upper roof (asphalt roof shingles).

Sample Nos. 2UR-1, -2 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

Photograph 8: Lower roof (asphalt roof shingles and upper window caulk).

Sample Nos. 2LR-1, -2, and 2UWC-1, -2 Date: August 16, 2021 Taken by: Leslie Davis, Inspector No. 013151

2UR-1, -2

Photograph 9: Close up of capacitor in fluorescent light.

Photograph 10: Close up of capacitor in fluorescent light.

Photograph 11: Close up of capacitor in fluorescent light.

Photograph 12: Close up of capacitor in fluorescent light.

ATTACHMENT B

Laboratory Analysis Results

EMSL Analytical, Inc.

5950 Fairbanks N. Houston Rd. Houston, TX 77040

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106462EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Attention: Phone:Michael Dollar (501) 663-8800

Fax:Harbor Environmental & Safety (501) 588-0123

Received Date:5800 Evergreen Drive 08/23/2021 10:00 AM

Analysis Date:Little Rock, AR 72205 08/24/2021

Collected Date: 08/16/2021

Project: USFS-21488

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

2SR-1

152106462-0001

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Sheetrock Repaired

Sheetrock W End of

Hall

2SR-2-Sheetrock

152106462-0002

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%White

Fibrous

Homogeneous

Sheetrock Ceiling

Sheetrock W Dorm

2SR-2-Texture

152106462-0002A

2% ChrysotileCa Carbonate

Non-fibrous (Other)

20%

78%

White

Non-Fibrous

Heterogeneous

Sheetrock Ceiling

Sheetrock W Dorm

Inseparable paint / coating layer included in analysis

2SR-3-Sheetrock

152106462-0003

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Sheetrock Ceiling Tile

W Dorm

2SR-3-Texture

152106462-0003A

Positive Stop (Not Analyzed)Sheetrock Ceiling Tile

W Dorm

2SR-4-Sheetrock

152106462-0004

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Sheetrock Ceiling Tile

E Dorm S Side

2SR-4-Texture

152106462-0004A

Positive Stop (Not Analyzed)Sheetrock Ceiling Tile

E Dorm S Side

2WC-1

152106462-0005

None DetectedNon-fibrous (Other)100%Black/Beige

Non-Fibrous

Heterogeneous

Caulk on Away Plate

Glass Window Front

Left

Inseparable paint / coating layer included in analysis

2WC-2

152106462-0006

None DetectedNon-fibrous (Other)100%Black/Beige

Non-Fibrous

Heterogeneous

Caulk on Away Plate

Glass Window Front

Right

Inseparable paint / coating layer included in analysis

2PL-1

152106462-0007

None DetectedCa Carbonate

Non-fibrous (Other)

10%

90%

Gray

Non-Fibrous

Heterogeneous

Interior Wall Plaster

Interior Wall Office

West

Inseparable paint / coating layer included in analysis

2PL-2

152106462-0008

None DetectedCa Carbonate

Non-fibrous (Other)

10%

90%

Gray

Non-Fibrous

Heterogeneous

Interior Wall Plaster

Interior Wall Dorm

West

2PL-3

152106462-0009

None DetectedCa Carbonate

Non-fibrous (Other)

10%

90%

Gray

Non-Fibrous

Heterogeneous

Interior Wall Plaster

Interior Wall Dorm

East

Inseparable paint / coating layer included in analysis

2PL-4

152106462-0010

None DetectedCa Carbonate

Non-fibrous (Other)

10%

90%

Gray

Non-Fibrous

Heterogeneous

Interior Wall Plaster

Interior Wall Office

East

Inseparable paint / coating layer included in analysis

2CM-1

152106462-0011

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Carpet Mastic Yellow

Carpet Mastic Foyer

Initial report from: 08/24/2021 17:12:02

Page 1 of 3ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 4:12 PM

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106462EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

2CM-2

152106462-0012

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Carpet Mastic Yellow

Carpet Mastic Dorm

West

2ES-1-Stucco

152106462-0013

None DetectedCa Carbonate

Non-fibrous (Other)

15%

70%

Glass15%Gray/Blue/Beige

Fibrous

Heterogeneous

Exterior Stucco West

Wall

Inseparable paint / coating layer included in analysis

2ES-1-Insulation

152106462-0013A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Exterior Stucco West

Wall

2ES-2-Stucco

152106462-0014

None DetectedCa Carbonate

Non-fibrous (Other)

15%

70%

Glass15%Gray/Blue/Beige

Fibrous

Heterogeneous

Exterior Stucco North

Wall

Inseparable paint / coating layer included in analysis

2ES-2-Insulation

152106462-0014A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Exterior Stucco North

Wall

2ES-3-Stucco

152106462-0015

None DetectedCa Carbonate

Non-fibrous (Other)

15%

70%

Glass15%Gray/Blue/Beige

Fibrous

Heterogeneous

Exterior Stucco East

Wall

Inseparable paint / coating layer included in analysis

2ES-3-Insulation

152106462-0015A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Exterior Stucco East

Wall

2ES-4-Stucco

152106462-0016

None DetectedCa Carbonate

Non-fibrous (Other)

15%

70%

Glass15%Gray/Blue/Beige

Fibrous

Heterogeneous

Exterior Stucco South

Wall

Inseparable paint / coating layer included in analysis

2ES-4-Insulation

152106462-0016A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Exterior Stucco South

Wall

2DP-1-Duct Paper

152106462-0017

None DetectedNon-fibrous (Other)15%Cellulose

Glass

80%

5%

Brown/Silver

Fibrous

Homogeneous

HVAC Duct Paper NE

Corner

2DP-1-Insulation

152106462-0017A

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

HVAC Duct Paper NE

Corner

2DP-2

152106462-0018

None DetectedNon-fibrous (Other)15%Cellulose

Glass

80%

5%

Brown/Silver

Fibrous

Homogeneous

HVAC Duct Paper

South Side

2WC2-1

152106462-0019

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Window Caulk

Front Glass to Right

2WC2-2

152106462-0020

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Window Caulk

Front Glass to Left

2UR-1-Shingle 1

152106462-0021

None DetectedNon-fibrous (Other)90%Glass10%Various/Black

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof Center

2UR-1-Shingle 2

152106462-0021A

None DetectedNon-fibrous (Other)90%Glass10%Brown/Various/Blac k

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof Center

2UR-1-Shingle 3

152106462-0021B

None DetectedNon-fibrous (Other)90%Glass10%Tan/Black

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof Center

Initial report from: 08/24/2021 17:12:02

Page 2 of 3ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 4:12 PM

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106462EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

2UR-1-Felt

152106462-0021C

None DetectedNon-fibrous (Other)30%Cellulose70%Brown/Black

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof Center

2VR-2-Shingle 1

152106462-0022

None DetectedNon-fibrous (Other)90%Glass10%Brown/Various/Blac k

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof West End

2VR-2-Shingle 2

152106462-0022A

None DetectedNon-fibrous (Other)90%Glass10%Black

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof West End

2VR-2-Felt

152106462-0022B

None DetectedNon-fibrous (Other)30%Cellulose70%Black

Fibrous

Homogeneous

Asphalt Roofing

Upper Roof West End

2LR-1-Shingle 1

152106462-0023

None DetectedNon-fibrous (Other)90%Glass10%Various/Black

Fibrous

Homogeneous

Asphalt Roofing

Lower Roof East

2LR-1-Shingle 2

152106462-0023A

None DetectedNon-fibrous (Other)90%Glass10%Gray/Various/Black

Fibrous

Homogeneous

Asphalt Roofing

Lower Roof East

2LR-2-Shingle 1

152106462-0024

None DetectedNon-fibrous (Other)90%Glass10%Various/Black

Fibrous

Homogeneous

Asphalt Roofing

Lower Roof West

2LR-2-Shingle 2

152106462-0024A

None DetectedNon-fibrous (Other)90%Glass10%Gray/Various/Black

Fibrous

Homogeneous

Asphalt Roofing

Lower Roof West

2LR-2-Felt

152106462-0024B

None DetectedNon-fibrous (Other)30%Cellulose70%Black

Fibrous

Homogeneous

Asphalt Roofing

Lower Roof West

2UWC-1

152106462-0025

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Upper Window Caulk

Center Windows

2VWC-2

152106462-0026

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Upper Window Caulk

West End Windows

Analyst(s)

Jenny Drapela (15)

Rushing Leika (25)

Michelle Leggett, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Houston, TX NVLAP Lab Code 102106-0, AZ 0925, CO AL-15355, LA 04126, TX 300159

Initial report from: 08/24/2021 17:12:02

Page 3 of 3ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 4:12 PM

OrderID: 152106462

OrderID: 152106462

Building 5: Healthcare

Building 5: Healthcare See Map HA2 for Sample Locations

The Healthcare building is located just south/southwest of the gate on the west side of the Job Corp facility. The building is constructed on a concrete slab with wood-framed walls and a stucco exterior with a pitched, asphalt-shingled roof. The building consists of dental offices, exam rooms, restrooms, a waiting area, bed wards, a storage closet, dark room, and medical lab rooms. Building 5 is approximately 3,480 square feet. The building was inspected for suspect ACM and LBP, and other potentially hazardous materials. The sampled/observed materials and corresponding laboratory results, if applicable, are provided in Table 5-1, 5-2, and 5-3 below. Photographs of sampled/potentially hazardous materials from the 2021 HazMat Survey are included in Attachment A. Laboratory results are presented as Attachment B. This table is supplemented with sample results from the 1992 Asbestos Evaluation Report prepared by Asbestos Abatement Services, Inc.

Table 5-1: Asbestos Inspection Findings

Building 5: Healthcare 2021 HazMat Survey Asbestos Samples

Sample Number Description and Location Condition

Friable/Non-Friable Asbestos Type

5-SR-1-

Sheetrock

Sheetrock, South Dental Office Good Friable None Detected

5-SR-1-

Joint

Compound Sheetrock, South Dental Office

Good Friable None Detected

5-SR-1-

Texture Sheetrock, South Dental Office

Good Friable None Detected

5-SR-2-

Sheetrock

Sheetrock, North Dental Office Good Friable None Detected

5-SR-2-

Joint

Compound Sheetrock, North Dental Office

Good Friable None Detected

5-SR-2-

Texture Sheetrock, North Dental Office

Good Friable None Detected

5-SR-3-

Sheetrock

Sheetrock, Sick Room Good Friable None Detected

5-SR-3-

Joint

Compound Sheetrock, Sick Room

Good Friable None Detected

5-SR-3-

Texture Sheetrock, Sick Room

Good Friable None Detected

5-FT-1-

Floor Tile 12”x 12” White w/Blue Flecks, Dental Office

Good

Number Description and Location Condition

Friable/Non-Friable Asbestos Type

5-FT-1-

Mastic 12”x 12” White w/Blue Flecks, Dental Office

Good Non-Friable None Detected

5-FT-2-

Floor Tile 12”x 12” White w/Blue Flecks, Dental Office Good

Non-Friable None Detected

5-FT-2-

Mastic 12”x 12” White w/Blue Flecks, Dental Office

Good Non-Friable None Detected

5-FT-3-

Floor Tile 12”x 12” White w/Blue Flecks, Dental Office

Good Non-Friable None Detected

5-FT-3-

Mastic 12”x 12” White w/Blue Flecks, Dental Office

Good Non-Friable None Detected

5-L1-1- Linoleum Gray Linoleum, Entrance Foyer Good

Non-Friable None Detected

5-L1-1- Mastic Gray Linoleum, Entrance Foyer Good

Non-Friable None Detected

5-L1-2- Linoleum Gray Linoleum, Outside Office by Exit Good

Non-Friable None Detected

5-L1-2- Mastic Gray Linoleum, Outside Office by Exit Good

Non-Friable None Detected

5-C-1- Sheetrock

Popcorn Ceiling, Dental Lab (South) Good Friable None Detected

5-C-1- Texture Popcorn Ceiling, Dental Lab (South) Good

Friable None Detected

5-C-2- Sheetrock

Popcorn Ceiling, Dental Lab (North) Good Friable None Detected

5-C-2- Texture Popcorn Ceiling, Dental Lab (North) Good

Friable None Detected

5-C-3- Sheetrock

Popcorn Ceiling, Dental Lab Female Sick Room

Good Friable None Detected

5-C-3- Texture

Popcorn Ceiling, Dental Lab Female Sick Room

Good Friable None Detected

5-RS-1-

Shingle Roof Shingles & Paper, East Side of Roof Good

Friable None Detected

5-RS-1-Felt Paper Roof Shingles & Paper, East Side of Roof Good

Friable None Detected

5-RS-2-

Shingle 1 Roof Shingles & Paper, West Side of Roof Good

Friable None Detected

5-RS-2-

Shingle 2 Roof Shingles & Paper, West Side of Roof Good

*Building 5 was labeled Building 16 in the 1992 Evaluation Report.

Sample Number Description and Location Condition

Friable/Non-Friable Asbestos Type

5-RS-2-Felt Paper Roof Shingles & Paper, West Side of Roof Good

Non-Friable None Detected

5-ES-1-

Stucco 1 Ext Stucco Bottom, East End of Bldg. Good

Friable None Detected

5-ES-1-

Foam Ext Stucco Bottom, East End of Bldg. Good

Friable None Detected

5-ES-1-

Stucco 2 Ext Stucco Bottom, East End of Bldg. Good

Friable None Detected

5-ES-2-

Stucco Ext Stucco Bottom, East End of Bldg. Good

Friable None Detected

5-ES-2-

Foam Ext Stucco Bottom, East End of Bldg. Good

Friable None Detected

5-PW-1-

Wrap Pipe Wrap, Bldg. HVAC, Attic

Good Non-Friable None Detected

5-PW-1-

Insulation Pipe Wrap, Bldg. HVAC, Attic

Good Non-Friable None Detected

5-PW-2-

Wrap Pipe Wrap, Bldg. HVAC, Attic

Good Non-Friable None Detected

5-PW-2-

Insulation Pipe Wrap, Bldg. HVAC, Attic

Good Non-Friable None Detected

5-PI-1 Pipe Insulation, Bldg. HVAC, Attic Good

Non-Friable None Detected

5-PI-2 Pipe Insulation, Bldg. d HVAC, Attic Good

Non-Friable None Detected

5-HVAC-

PW-1-Wrap

HVAC Duct Wrap, West End of Bld,, Crawl Space

Good Non-Friable None Detected

5-HVAC-

PW-1-

Insulation

HVAC Duct Wrap, West End of Bld,, Crawl Space

Good Non-Friable None Detected

5-HVAC-

PW-2-Wrap

HVAC Duct Wrap, East End of Bld Good Friable None Detected

5-HVAC-

PW-2-

Insulation HVAC Duct Wrap, East End of Bld

Good Friable None Detected

1992 Asbestos Samples

*16-1 Linoleum Floor, Light Green, Light Brown Grey Patterned, Lab

Good Non-Friable

20-25% Chrysotile

*16-2 Grey, Light Brown Off-white Small Patterned Linoleum, Utility Room

Good Non-Friable

20-25% Chrysotile

Table 5-2: Lead-based Paint Inspection Findings

Table 5-2: Miscellaneous Inspection Findings

Building 5: Healthcare

Description and Location Qty

Significantly peeling paint was not observed on the structure. -

Building 5: Healthcare

Description and Location Qty

Old fluorescent lights throughout the building with two (2) ballasts, observed on the walls, were found to contain PCBs. 14

Newer light ballasts on the ceiling were found to not contain PCBs 23

BLDG #5 WELLNESS CENTER, USFS-21488

570 JOB CORPS ROAD

ROYAL, AR 71968

D ra fte r

D at e

Sc al e A

ES

8-

-2

1" =1

0'REVISION DESCRIPTION DATENO

XX X-X-XASBESTOS/LEAD SURVEY

HA

IN

SP

EC

TO

R

IN

SP

EC

TO

R N

O

C O

N

SU

LT

A

N T

N O

:0

Harbor

A

SB

ES

TO

S/

LE

A D

N

EG

A

TI

VE

A

SB

ES

TO

S/

LE

A

D P

O

SI

TI

VE

LE

G

EN

D

N O

TE

S:

1)

FE

D

ER

A L

A N

D S

TA

TE

R

EG

U

LA

TO

R

Y A

G

EN

C

IE

S D

EF

IN

E A

N A

SB

ES

TO

S-

C O

N

TA

IN

IN

G M

A

TE

R

IA

L (A

C M

) A S

A N

Y B

U

IL

D

IN

G M

A

TE

R

IA

L

TH

A T

C O

N

TA

IN

S

G R

EA

TE

R T

H A

N

.0

A

SB

ES

TO

S.

2)

FE

D

ER

A

L A

N D

S

TA

TE

R

EG

U

LA

TO

R Y

A G

EN

C

IE

S

D

EF

IN

E

A L

EA

D

-B A

SE

D

P A

IN

T

A S

A P

A

IN

T C

O N

TA

IN

IN

G

G R

EA

TE

R T

H A

N

.5

L

EA

D B

Y W

EI

G

H T.

E ve rg ree n D riv e Li ttl e R oc k, AR

Ph (5

)6

-8

Fa x

(5

)5

-0 ww w.

ha rb or en v.

co m

M

IC

H A

EL

D

O

LL

A R

5-

SR

-1

5-

SR

-2 5-

SR

-3

5-

FT

-1 5-

FT

-2 5-

FT

-3

5-

LI

-1

5-

LI

-2

5- C

-1

5- C

-2

5- C

-3

EN

TR

A N

C E

D

EN

TA

L

D

EN

TA

L

R

ES

TR

O

O M

U

TI

LI

TY

EX

A

M R

O O

M

EX

A M

R O

O M

FE

M

A

LE

S

IC

K R

O O

M

R

ES

TR

O

O M

R

ES

TR

O

O M

M A

LE

S

IC

K

R O

O M

O

FF

IC

E

B

IO

H A

ZA

R

D

ST

O

R M

ED

R

O O

M M

ED

IC

A L

R

EC

O R

D S

5-

ES

-2 5-

ES

-1

5- H

VA

C

PW

-2

5- R

S-

5- R

S-

5- H

VA

C

-P W

-1

5-

PW

-2 , 5

-P I-2

5-

PW

-1 , 5

-P I-1

Building 5 Photographs

A TTA CHMEN T A

Photograph 1: Sheetrock in Dental Offices.

Sample Nos. 5-SR-1, -2, -3 Date: August 16, 2021 Taken by: Michael Dollar, Inspector No. 013151

Photograph 2: 12”x 12” white with blue flecks floor tile in Dental Offices.

Sample Nos. 5-FT-1, -2, -3 Date: August 16, 2021 Taken by: Michael Dollar, Inspector No. 017385

Photograph 3: Gray Linoleum in entrance foyer and surrounding area.

Sample Nos. 5-L1-1, -2 Date: August 16, 2021 Taken by: Michael Dollar, Inspector No. 017385

Photograph 4: Popcorn ceiling (w sheetrock).

Sample Nos. 5-C-1, -2, -3 Date: August 16, 2021 Taken by: Michael Dollar, Inspector No. 017385

Photograph 5: Roof shingles.

Sample Nos. 5-RS-1, -2 Date: August 16, 2021 Taken by: Michael Dollar, Inspector No. 017385

Photograph 6: Exterior stucco.

Sample Nos. 5-ES-1, -2 Date: August 16, 2021 Taken by: Michael Dollar, Inspector No. 017385

Photograph 7: Pipe wrap and insulation from HVAC system in attic.

Sample Nos. 5-PW-1, -2, PI-1, -2, and 5-HVAC-PW-1, -2 Date: August 16, 2021

Taken by: Michael Dollar, Inspector No. 017385

Photograph 8: Wall-mounted fluorescent light ballast with capacitor containing PCBs.

Photograph 9: Close up of capacitor in wall-mounted fluorescent light.

Photograph 10: Ceiling-mounted fluorescent light ballast.

Photograph 11: Close up of capacitor in ceiling-mounted fluorescent light ballast.

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106465EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Attention: Phone:Michael Dollar (501) 663-8800

Fax:Harbor Environmental & Safety (501) 588-0123

Received Date:5800 Evergreen Drive 08/23/2021 10:00 AM

Analysis Date:Little Rock, AR 72205 08/24/2021

Collected Date: 08/16/2021

Project: USFS-21488

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

5-SR-1-Sheetrock

152106465-0001

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Sheetrock South

Dental Office

5-SR-1-Joint Compound

152106465-0001A

None DetectedCa Carbonate

Non-fibrous (Other)

30%

70%

White

Non-Fibrous

Homogeneous

Sheetrock South

Dental Office

5-SR-1-Texture

152106465-0001B

None DetectedCa Carbonate

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Heterogeneous

Sheetrock South

Dental Office

Inseparable paint / coating layer included in analysis

5-SR-2-Sheetrock

152106465-0002

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Sheetrock North

Dental Office

5-SR-2-Joint Compound

152106465-0002A

None DetectedCa Carbonate

Non-fibrous (Other)

30%

70%

White

Non-Fibrous

Homogeneous

Sheetrock North

Dental Office

5-SR-2-Texture

152106465-0002B

None DetectedCa Carbonate

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Heterogeneous

Sheetrock North

Dental Office

Inseparable paint / coating layer included in analysis

5-SR-3-Sheetrock

152106465-0003

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Sheetrock Sick Room

5-SR-3-Joint Compound

152106465-0003A

None DetectedCa Carbonate

Non-fibrous (Other)

40%

60%

White

Non-Fibrous

Homogeneous

Sheetrock Sick Room

5-SR-3-Texture

152106465-0003B

None DetectedCa Carbonate

Non-fibrous (Other)

20%

80%

White/Beige

Non-Fibrous

Heterogeneous

Sheetrock Sick Room

Inseparable paint / coating layer included in analysis

5-FT-1-Floor Tile

152106465-0004

None DetectedNon-fibrous (Other)100%White/Blue

Non-Fibrous

Homogeneous

12x12 White w/Blue

Flecks Dental Office

5-FT-1-Mastic

152106465-0004A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

12x12 White w/Blue

Flecks Dental Office

5-FT-2-Floor Tile

152106465-0005

None DetectedNon-fibrous (Other)100%White/Blue

Non-Fibrous

Homogeneous

12x12 White w/Blue

Flecks Dental Office

5-FT-2-Mastic

152106465-0005A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

12x12 White w/Blue

Flecks Dental Office

5-FT-3-Floor Tile

152106465-0006

None DetectedNon-fibrous (Other)100%White/Blue

Non-Fibrous

Homogeneous

12x12 White w/Blue

Flecks Dental Office

5-FT-3-Mastic

152106465-0006A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

12x12 White w/Blue

Flecks Dental Office

Initial report from: 08/24/2021 13:30:37

Page 1 of 4ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 12:30 PM

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106465EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

5-L1-1-Linoleum

152106465-0007

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Gray Linoleum

Entrance Foyer

Outside Restroom

5-L1-1-Mastic

152106465-0007A

None DetectedNon-fibrous (Other)100%Black/Yellow

Non-Fibrous

Homogeneous

Gray Linoleum

Entrance Foyer

Outside Restroom

5-L1-2-Linoleum

152106465-0008

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Gray Linoleum

Outside Office by Exit

5-L1-2-Mastic

152106465-0008A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Gray Linoleum

Outside Office by Exit

5-C-1-Sheetrock

152106465-0009

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Popcorn Ceiling

Dental Lab (South)

5-C-1-Texture

152106465-0009A

None DetectedCa Carbonate

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Heterogeneous

Popcorn Ceiling

Dental Lab (South)

Inseparable paint / coating layer included in analysis

5-C-2-Sheetrock

152106465-0010

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Popcorn Ceiling

Dental Lab (North)

5-C-2-Texture

152106465-0010A

None DetectedCa Carbonate

Non-fibrous (Other)

5%

95%

White

Non-Fibrous

Heterogeneous

Popcorn Ceiling

Dental Lab (North)

Inseparable paint / coating layer included in analysis

5-C-3-Sheetrock

152106465-0011

None DetectedGypsum

Non-fibrous (Other)

60%

30%

Cellulose10%Brown/White

Fibrous

Homogeneous

Popcorn Ceiling

Dental Lab Female

Sick Room Bathroom

5-C-3-Texture

152106465-0011A

None DetectedCa Carbonate

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Heterogeneous

Popcorn Ceiling

Dental Lab Female

Sick Room Bathroom

Inseparable paint / coating layer included in analysis

5-RS-1-Shingle

152106465-0012

None DetectedNon-fibrous (Other)90%Glass10%Black

Fibrous

Homogeneous

Roof Shingles &

Paper East Side of

Roof

5-RS-1-Felt Paper

152106465-0012A

None DetectedNon-fibrous (Other)30%Cellulose70%Black

Fibrous

Homogeneous

Roof Shingles &

Paper East Side of

Roof

5-RS-2-Shingle 1

152106465-0013

None DetectedNon-fibrous (Other)90%Glass10%Black

Fibrous

Homogeneous

Roof Shingles &

Paper West Side of

Roof

5-RS-2-Shingle 2

152106465-0013A

None DetectedNon-fibrous (Other)90%Glass10%Brown/Gray/Black

Fibrous

Homogeneous

Roof Shingles &

Paper West Side of

Roof

5-RS-2-Felt Paper

152106465-0013B

None DetectedNon-fibrous (Other)30%Cellulose70%Black

Fibrous

Homogeneous

Roof Shingles &

Paper West Side of

Roof

5-ES-1-Stucco 1

152106465-0014

None DetectedCa Carbonate

Non-fibrous (Other)

5%

85%

Glass10%Tan/Blue/Beige

Fibrous

Heterogeneous

Ext Stucco Bottom

East End of Bld

Inseparable paint / coating layer included in analysis

5-ES-1-Foam

152106465-0014A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Ext Stucco Bottom

East End of Bld

Initial report from: 08/24/2021 13:30:37

Page 2 of 4ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 12:30 PM

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106465EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

5-ES-1-Stucco 2

152106465-0014B

None DetectedCa Carbonate

Non-fibrous (Other)

5%

85%

Glass10%Tan

Fibrous

Homogeneous

Ext Stucco Bottom

East End of Bld

5-ES-2-Stucco

152106465-0015

None DetectedCa Carbonate

Non-fibrous (Other)

10%

80%

Glass10%Tan/Blue/Beige

Fibrous

Heterogeneous

Ext Stucco Bottom

East End of Bld

Inseparable paint / coating layer included in analysis

5-ES-2-Foam

152106465-0015A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Ext Stucco Bottom

East End of Bld

5-PW-1-Wrap

152106465-0016

None DetectedNon-fibrous (Other)50%Cellulose

Glass

40%

10%

Silver/Beige

Fibrous

Homogeneous

Pipe Wrap Bld HVAC

Attic

5-PW-1-Insulation

152106465-0016A

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

Pipe Wrap Bld HVAC

Attic

5-PW-2-Wrap

152106465-0017

None DetectedNon-fibrous (Other)50%Cellulose

Glass

40%

10%

Silver/Beige

Fibrous

Homogeneous

Pipe Wrap Bld HVAC

Attic

5-PW-2-Insulation

152106465-0017A

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

Pipe Wrap Bld HVAC

Attic

5-PI-1

152106465-0018

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

Pipe Insulation Bld

HVAC Attic

5-PI-2

152106465-0019

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

Pipe Insulation Bld

HVAC Attic

5-HVAC-PW-1-Wrap

152106465-0020

None DetectedNon-fibrous (Other)60%Cellulose

Glass

30%

10%

Tan/Silver

Fibrous

Homogeneous

HVAC Duct Wrap

West End of Bld

Crawl Space

5-HVAC-PW-1-Insulatio n

152106465-0020A

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

HVAC Duct Wrap

West End of Bld

Crawl Space

5-HVAC-PW-2-Wrap

152106465-0021

None DetectedNon-fibrous (Other)60%Cellulose

Glass

30%

10%

Tan/Silver

Fibrous

Homogeneous

HVAC Duct Wrap

East End of Bld

5-HVAC-PW-2-Insulatio n

152106465-0021A

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

HVAC Duct Wrap

East End of Bld

Initial report from: 08/24/2021 13:30:37

Page 3 of 4ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 12:30 PM

Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com

152106465EMSL Order:

Customer ID: HARB78

Customer PO:

Project ID:

Analyst(s)

Jenny Drapela (19)

Michelle Leggett (26)

Michelle Leggett, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Houston, TX NVLAP Lab Code 102106-0, AZ 0925, CO AL-15355, LA 04126, TX 300159

Initial report from: 08/24/2021 13:30:37

Page 4 of 4ASB_PLM_0008_0001 - 1.78 Printed: 8/24/2021 12:30 PM

OrderID: 152106465

OrderID: 152106465

Building 6C: Gym Storage

Building 6C: Gym Storage Building 6C: Gym Storage is located southwest of the Gymnasium (Building 6). The building is constructed with a plywood floor, wood-framed walls, sheet metal exterior and a pitched, sheet metal roof. The shed does not contain any internal structures or equipment. Photographs of the building are presented as Attachment A. The building was inspected for suspect ACM, LBP, and other potentially hazardous materials. The sampled/observed materials and corresponding laboratory results, if applicable, are provided in Table 12-1, 12-2, and 12-3 below. This building was not sampled during the 1992 asbestos survey conducted by Asbestos Abatement Services, Inc.

Table 12-1: Asbestos Inspection Findings Building 6C: Gym Storage

2021 HazMat Survey Asbestos Samples Sample Number Description and Location Condition

Friable/Non-Friable Asbestos Type

- No suspect materials identified. - -

Table 12-2: Lead-based Paint Inspection Findings

Table 12-3: Miscellaneous Hazardous Materials Inspection Findings

Building 6C: Gym Storage Sample Number

Description and Location Total Lead

(mg/kg) Weight %

Significantly peeling paint was not observed on the structure. - -

Building 6C: Gym Storage

Description and Location Qty

There were no other potentially hazardous materials observed in or around the structure. -

Building 6C Photographs

A TTA CHMEN T B

Photograph 1: Building 6C exterior.

Date: August 17, 2021

Photograph 2: Building 6C interior.

Building 6D: Gym Storage

Building 6D: Gym Storage Building 6D: Gym Storage is located southwest of the Gymnasium (Building 6). The building is constructed with a plywood floor, wood-framed walls, sheet metal exterior and a pitched, sheet metal roof. The shed does not contain any internal structures or equipment. Photographs of the building are presented in Attachment A. The building was inspected for suspect ACM, LBP, and other potentially hazardous materials. The building was inspected for suspect ACM, LBP, and other potentially hazardous materials. The sampled/observed materials and corresponding laboratory results, if applicable, are provided in Table 6D-1, 6D-2, and 6D-3 below. This building was not sampled during the 1992 asbestos survey conducted by Asbestos Abatement Services, Inc.

Table 6D-1: Asbestos Inspection Findings Building 6D: Gym Storage

2021 HazMat Survey Asbestos Samples Sample Number Description and Location Condition

Friable/Non-Friable Asbestos Type

- No suspect materials identified. - -

Table 6D-2: Lead-based Paint Inspection Findings

Table 6D-3: Miscellaneous Hazardous Materials Inspection Findings

Building 6D: Gym Storage Sample Number

Description and Location Total Lead

(mg/kg) Weight %

Significantly peeling paint was not observed on the structure. - -

Building 6D: Gym Storage

Description and Location Qty

There were no other potentially hazardous materials observed in or around the

Building 6D Photographs

Photograph 1: Building 6D exterior.

Photograph 2: Building 6D interior.

Building 6E: Gym Storage

Building 6E: Gym Storage Building 6E: Gym Storage is located southwest of the Gymnasium (Building 6). The building is constructed with a plywood floor, wood-framed walls, sheet metal exterior and a pitched, sheet metal roof. The interior of the shed consists of wood shelving. Photographs of the building are presented in Attachment A. The building was inspected for suspect ACM, LBP, and other potentially hazardous materials. The sampled/observed materials and corresponding laboratory results, if applicable, are provided in Table 6E-1, 6E-2, and 6E-3 below. This building was not sampled during the 1992 asbestos survey conducted by Asbestos Abatement Services, Inc.

Table 6E-1: Asbestos Inspection Findings Building 6E: Gym Storage

2021 HazMat Survey Asbestos Samples Sample Number Description and Location Condition

Friable/Non-Friable Asbestos Type

- No suspect materials identified. - -

Table 6E-2: Lead-based Paint Inspection Findings

Table 6E-3: Miscellaneous Hazardous Materials Inspection Findings

Building 6E: Gym Storage Sample Number

Description and Location Total Lead

(mg/kg) Weight %

Significantly peeling paint was not observed on the structure. - -

Building 6E: Gym Storage

Description and Location Qty

There were no other potentially hazardous materials observed in or around the

Building 6E Photographs

Photograph 1: Building 6E exterior.

Photograph 2: Building 6E interior.

Gym Dumpster Pad

Gym Dumpster Pad See Map HA19 for Sample Locations

The gym dumpster pad is located southwest of Building 6 between Buildings 6D and 6E. The structure is constructed on a concrete pad with three cinder block walls.