This federal contract opportunity solicitation seeks demolition and salvage services at the Ouachita Job Corps Center in Arkansas. The scope of work includes demolishing and removing 30 buildings and structures, grading areas, and stabilizing soils. Offerors must provide all labor, tools, equipment and materials. Key dates include the IFB issuance on August 5, 2021, a pre-bid conference on August 13, 2021, the question deadline on September 10, 2021 and bid submission due by September 15, 2021. The contract type is firm-fixed-price awarded to the lowest priced responsive and responsible bidder. The project value is between $250,000 to $500,000. The solicitation and documents will be available for download at SAM.gov on or after August 5, 2021. The solicitation is 100% set aside for small businesses with a size standard of $16.5M NAICS 238910. The contracting agency is the USDA Forest Service.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OUACHITA
Civilian Conservation Center Royal, AR
Facility Planning Report Volume II
Supporting Data
Final June 2015
Department of Labor/ Office of Job Corps
OUACHITA
Civilian Conservation Center Royal, AR
Facility Planning Report Volume II
Supporting Data
Final June 2015
Lodge Building 18
VOLUME I - PLANNING STRATEGY
Acronyms and Abbreviations Defi nition of Terms Executive Summary Existing Site Plan Center Statistics Facility Survey Assessment Results and Recommendations
1.0 INTRODUCTION
• Objective and Scope
• Report Contents
2.0 EXISTING CONDITIONS
• Background
• Ownership
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Facility Assessment by Function
• Environmental Management
• Resource Use/Conservation
• Sustainability
• Accessibility Standards
• Completed and Current Projects
• Health and Life Safety Issues
• Defi ciency Summary
3.0 PLANNING ANALYSIS
• Space Utilization Analysis
• Federal Real Property Asset Management
• Defi ciency Analysis
• Facility Condition Summary
• Building Condition by Function
• Planning Analysis Results and Conclusions
4.0 RECOMMENDATIONS
• Status of Previous Plan
• Proposed Plan
• Funded Not Corrected (FNC) Defi ciencies
• Summary of Proposed Plan
• Proposed Site Plan
• Implementation Plan
• Summary Lists of National Projects
• Project Data Sheets
Appendix A. Energy and Water Evaluation Report
VOLUME II - SUPPORTING DATA
Acronyms and Abbreviations Defi nition of Terms Executive Summary
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Mintues
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Appendix E.
• FRPC Performance Measures Matrix
Acronyms and Abbreviations
ACRONYMS AND ABBREVIATIONS
A Amperage ABAAS Architectural Barriers Act Accessibility Standard ACM Asbestos-Containing Materials AFUE Annual Fuel Utilization Efficiency AHU Air Handling Unit ANSI American National Standards Institute ARRA American Recovery and Reinvestment Act of 2009 BTU British Thermal Units\ CAA Clean Air Act CCF Hundred Cubic Feet CCTV Closed Circuit Television CDC Child Development Center CDC Centers for Disease Control and Prevention CDP Career Development Period CDSS Career Development Service System CFL Compact Fluorescent Light Bulbs CFM Cubic Feet per Minute CIS Center Information System CMA Certified Medical Assistant CMMS Computerized Maintenance Management System CMU Concrete Masonry Unit CAN Certified Nursing Assistant CO Carbon Monoxide CO Contracting Officer COR Contracting Officer’s Representative CPP Career Preparation Period CRA Construction, Rehabilitation, and Acquisition CTP Career Transition Period CTS Career Transition Services
CTST Career Technical Skills Training (formerly Vocational Skills Training [VST])
CW Cold Water CWA Clean Water Act DDC Direct Digital Controls DFAM Division of Facilities and Asset Management DOL Department of Labor EISA Energy Independence and Security Act of 2007 EMT Emergency Medical Technician
EMT Electrical Metal Tubing (Conduit) EO Executive Order EPA U.S. Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act (1986) EPMD Ethylene Propylene Diene Terpolymer ESC Engineering Support Contractor ESCIS Engineering Support Contractor Information System ESL English as a Second Language oF Degrees Fahrenheit FACP Fire Alarm Control/Annunciator Panel fc Foot Candle FNC Funded Not Corrected FOP Financial Operating Plan FRPC Federal Real Property Council FY Fiscal Year GAO General Accounting Office GED General Educational Development GFCI Ground Fault Circuit Interrupter gph Gallons per Hour GSA General Services Administration GSF Gross Square Feet HID High Intensity Discharge HP Horsepower HSD High School Diploma HTW Hazard and Toxic Waste HVAC Heating, Ventilating, and Air Conditioning HW Hot Water IBC International Building Code IMC International Mechanical Code ION Inventory of Needs IPC International Plumbing code KBTU Thousand British Thermal Unit/Gross Square Foot/Year kV Kilovolt kVA Kilovolt-Amps kw Kilowatt JCC Job Corps Center JCDC Job Corps Data Center JCH Job Corps Handbook kWh Kilowatt Hours LAN Local Area Network LED Light Emitting Diode LF Linear Feet MBH Thousand BTUs per Hour MBTU Thousand British Thermal Unit MWH Megawatt Hour MC Mission Critical MCF Million Cubic Feet MDNC Mission Dependent, Not Critical MDP Main Distribution Panel MLO Main Lug Only m/s Meters/Second MTS Manual Transfer Switch NEC National Electric Code NEMA National Electrical Manufacturers Association NEPA National Environmental Protection Act NFPA National Fire Protection Association NMD Not Mission Dependent NSF Net Square Feet OA Outreach and Admissions OBS On Board Strength OCM Office of Contract Management OIG Office of Inspector General O&M Operations and Maintenance OSHA Occupational Safety and Health Administration PA Public Address pCi Picocurie PV Photovoltaic PVC Polyvinyl Chloride RCRA Resource Conservation and Recovery Act RTU Rooftop Unit SGA Student Government Association SHPO State Historic Preservation Office SF Square Feet SPCC Spill Prevention, Control and Countermeasure SST Social Skills Training T5 Fluorescent Lighting Designation (High Efficiency)
T8 Fluorescent Lighting Designation T12 Fluorescent Lighting Designation (Low Efficiency TSCA Toxic Substances Control Act of 1976 TV Television TVSS Transient Voltage Surge Suppression UEV Unevaluated UFAS Uniform Federal Accessibility Standards UL Underwriters Laboratories USDA U. S. Department of Agriculture V Volt VCR Video Cassette Recorder VST Vocational Skills Training W Watt WAN Wide Area Network WBL Work-Based Learning WIA Workforce Investment Act WIB Workforce Investment Board
Defi nition of Terms
DEFINITION OF TERMS
Accessibility: The degree to which a product, device, service, or environment is available to as many people as possible. Accessibility can be viewed as the "ability to access" and benefit from some system or entity. The Federal Government is required to comply with published law (Architectural Barriers Act (ABA) of 1968 , American Disabilities Act of 1990), regulations and related standards. Accessibility laws and standards have evolved over the past 12 years. DOL now follows ABA Accessibility Standards for Federal Facilities (ABAAS) adopted by the General Services Administration.
Annual Operating Cost: This FRPC performance measure reflects the cost to operate each used asset and consists of lease costs as well as costs related to recurring maintenance, utilities, janitorial, and roads and grounds expenses (Source: FRPC 2012).
Building: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a building includes an enclosure for human occupancy that serves a variety of functions (food service, education, recreation, medical/dental, storage, administration) and is likely to have full utility services (heating, cooling, etc.). A building typically is over 400 square feet.
Building Condition Rating by Function: Each building is assigned a building condition based on the physical condition of the building and the impact on the functional use of the facility. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required.
Building/Structure Ratings: Each building is rated according to three ratings (good, fair, and poor) based on evaluations of the structure, exterior, interior, mechanical, and electrical elements. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required
Construction Type: The International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type II and III. Any type of construction where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
Contract Strength: The authorized number of students at a Center in accordance with the contract between the Region and Center Operator.
Deficiency: A deficiency at a Center represents the spectrum of conditions related to the Center’s mission and/or its physical, functional, or operational features do not meet related goals, standards, codes, or other measures of acceptability. Each deficiency at a JCC or CCC initially is categorized as one of the following three deficiencies: Program, Site, or Building:
Program: Program deficiencies address issues such as square footage shortages or the omission of amenities required or standard for the proper operation of a particular Job Corps function.
Site: Site deficiencies indicate adverse site and infrastructure conditions which negatively impact operations and environment (e.g., site lighting, sidewalks, roads, etc.)
Building: Building deficiencies indicate adverse conditions at the building level.
This element includes the substructure, shell, interior, services (plumbing, HVAC, fire protection, and electrical), and equipment and furnishings.
Deficiency Classifications (I to IV): Deficiency classifications are defined as follows:
Class IA - Deficiencies which address imminent life safety and health hazards.
Class II - Deficiencies which address code violations, however, do not represent imminent life safety and health hazards.
A - Deficiencies which violate code (Federal, State or Local) and may result in an interruption of center operations if not corrected.
B - Deficiencies which violate code (Federal, State or Local) and have no immediate impact on center operations if not corrected.
C- Deficiencies which are not in compliance for accessibility in accordance with the Architectural Barriers Act (ABA), Americans with Disabilities Act (ADA), Uniform Federal Accessibility Standards (UFAS), or other applicable standards.
Class III - Deficiencies which address facility repair, replacement or maintenance.
A - Deficiencies which if not corrected may result in an interruption of center operations.
B - Deficiencies which if not corrected will have minimal impact on center operations or can be mitigated through temporary measures until the deficiency is corrected.
Class IV – Deficiencies which address programmatic needs.
A - Deficiencies which if corrected produce substantial improvements in the quality of the learning and living environment.
B - Deficiencies which if corrected are desirable enhancements.
Deficiency Funding Status: The status of the deficiency included the following categories:
Funded deficiencies report indicates the funding year for funded Regional projects, which have dollar amounts shown, or deficiencies assigned to funded National and Regional projects without dollar amounts. Major Regional projects are equivalent to National projects but assigned to the Federal agency (e.g., U.S.
Department of Agriculture) that acts as the Center operator. All operations and maintenance (O&M) deficiencies are treated as funded through the Center Operators O&M contract within the Region.
Proposed deficiencies have been assigned to a proposed future National project.
Unfunded deficiencies are Regional projects unless or until they are assigned to a National project.
Deficiency Status: The deficiency status is tracked and updated during the three-year facility survey cycle, or as such deficiencies are corrected and reported. The status includes:
Uncorrected: Once a deficiency is identified, documented, reported, and assigned for correction, the deficiency remains uncorrected until such time that the deficiency is corrected, reported, and verified.
Corrected: A corrected deficiency is one that has been assigned, funded, corrected, reported, and verified. Typically, the ESC verifies completion of the deficiency through the facility survey or site visit. The Center also may report completion and provide verifiable evidence of the correction, subject to review by the ESC.
Funded Not Corrected: A deficiency that has been approved and authorized as a regional project through the CRA budget, emergency or supplemental funding, or the Life Safety Memo. Note: the funding may not have reached the Center yet as the first steps are a FOP allocation by the National Office and a contract modification by the Region.
No Longer Needed: A no longer needed deficiency is one that has been approved and funded as a Regional project, but due to subsequent circumstances, has been reported by the Center as no longer being required to be accomplished. This type of deficiency is verified and confirmed by the ESC and removed from the Funded Not Corrected deficiency category. The Center should take action with its Region to return the funds.
Facility Condition Index: This performance measure reflects the condition of each asset by comparing the current repair needs to the replacement value of the asset. The index is expressed as a percentage, with 100% being a facility with no repair needs.
Gross Square Foot: The sum of all areas on all floors of a building included within the outside faces of its exterior walls, including all vertical penetration areas, for circulation and shaft areas that connect one floor to another. Gross Area is computed by physically measuring or scaling measurements from the outside faces of exterior walls, disregarding cornices, pilasters, buttresses, etc., that extend beyond the wall faces. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Measured in terms of Gross Square Feet (GSF): GSF = Net Usable Area + Structural Space (Source: http://nces.ed.gov/pubs2006/ficm/).
Mission Dependency: The value an asset brings to the performance of the mission as determined by the governing agency. Specific elements of this category include (FRPC 2012):
Mission Critical - – Without constructed asset or parcel of land, mission is compromised.
Mission Dependent, Not critical (MDNC) - Does not fit into Mission Critical or Not Mission Dependent categories.
Not Mission Dependent (NMD) – Mission unaffected
Ownership (Owned vs Leased): If the property is owned, the Federal Government has fee simple interest for the real property asset. If the property is leased, the rights to use the asset are assigned to the Federal Government by a private entity or a non-Federal Government entity for a defined period of time in return for rental payments (FRPC 2012).
National Project: Generally large and complex projects that require professionally prepared drawings and specifications that are time phased (design and construction) and contracted by the DOL National Office.
Net Square Foot: The sum of all areas on all floors of a building assigned to, or available for assignment to, an occupant or specific use. This value is computed by physically measuring or scaling measurements from the inside faces of surfaces that form the boundaries of the designated areas. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Included should be major space use categories for assignable space (e.g., dormitories, education, recreation, etc.) that are used to accomplish the institution’s mission. Net Square foot: NASF = Sum of Areas Designated by the Major Space Use Categories (Source: http://nces.ed.gov/pubs2006/ficm/).
On Board Strength (OBS): The actual number of students on Center on a day to day basis.
Preventive Maintenance: The care and servicing by personnel for the purpose of maintaining equipment and facilities in satisfactory operating condition by providing for systematic inspection, detection, and correction of incipient failures either before they occur or before they develop into major defects (Source: Dictionary of Military and Associated Terms, US DOD 2005).
Property Type: Indicates the asset as one of the following categories of real property:
land, building, structure.
Property Use: Since the elements defined by the FRPC do not match the space use codes employed in ESCIS, a mapping procedure will be created to align the definitions.
In the report, the Federal Real Property Council (FRPC) classifications will be printed for display. The information is available through the property registration field of Engineering Support Contractor Information System (ESCIS), and the current ESCIS designations will be correlated to the FRPC designations as follows:
ESCIS FRPC
Dormitory Dormitories/Barracks Food Service Other Institutional Uses Education School Recreation Other Institutional Uses Medical/Dental Other Institutional Uses Storage Warehouse Administration Office Structure * Storage, Service, Utility
Systems, or Other Land Institutional
* Each structure will be entered manually from the ESCIS database into one of four FRPC categories listed opposite the term “structure”.
Replacement Value: The cost of replacing the existing constructed asset at today’s building standards. It is the amount required to construct an asset of similar size and in the same location at today’s construction standards. The replacement value reported must be greater than zero (FRPC 2012).
Regional Office Project: Generally smaller projects where the funds will be transferred to the region for center execution.
Structure: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a structure serves to provide storage, service, utility systems and is not likely to have full utilities (heating, cooling, etc.). A structure typically is less than 400 square feet.
Sustainability: Formally known as the World Commission on Environment and Development, the Brundtland Commission's mission in the 1980s was to unite countries to pursue sustainable development. The Commission defined sustainability as the “development which meets the needs of current generations without compromising the ability of future generations to meet their own needs".
Sustainability also is defined as the creation or enhancement of environmental, economic, and social-cultural balance, as realized through business activities, individual actions, and community engagement. Sustainability addresses approaches, methods and practices that optimize the use of energy, water, and materials while reducing greenhouse gas emissions.”
Utilization: This performance measure assesses the degree to which each asset is utilized and is expressed as a percentage. It is calculated on a square footage basis, comparing the square footage used to the “design square footage” based on contract strength (Source: FRPC 2012).
Executive Summary
The facility survey for the Ouachita Civilian Conservation Center was completed November 3, 2014 – November 7, 2014. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
OUACHITA
JOB CORPS CENTER
ROYAL, ARKANSAS
OUACHITA JCC
10 MI50
2.0 - Descriptions
2.0 DESCRIPTIONS
In this section, the following information on the Center and its buildings and structures is presented in tabular format:
Building and Structures – This table indicates the building type, asset number, name, use group, gross square footage (GSF), construction year, number of floors, number of sleeping room and number of beds, construction type (noted as numerical values instead of code-specified Roman numerals), status (active or closed), and overall condition. The possible International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type III. This type of construction is where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces. Fire-retardant-treated wood framing complying with IBC section 2303.2 shall be permitted within exterior wall construction with a 2-hour rating or less.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
The overall building/structure condition is rated in one of three categories: good, fair, or poor.
Space Utilization by Function - This table compares the DOL recommended net square footage per enrollee and for the total function (e.g., housing, education, food service, recreation, medical/dental, administration, storage/support) to the actual values.
Net Square Footage by Building - This table compares the DOL recommended net square footage for the buildings with the function (e.g., housing, education, food service, recreation, medical/dental, storage/support) to the actual values and presents a percentage difference in the two values. In some instances, a recommended value is not available for sub-elements of a function; therefore, the recommended value is shown as “0”.
Environmental Management Report – This table summarizes regulatory related solid and hazardous waste information in accordance with the Resource Conservation and Recovery Act (RCRA) and the presence or absence of hazardous material storage facilities in accordance with Emergency Planning and Community Right-to-Know Act of
1986 (EPCRA). An inventory of petroleum storage tanks is noted as well as asbestos and polychlorinated biphenyls (PCBs) in accordance with the Clean Water Act (CWA) and Toxic Substance Control Act (TSCA), respectively. In addition, this report statuses air quality as required under the Clean Air Act (CAA).Any radon testing of buildings also is documented.
Site Descriptions – Tabular information is documented for the site. Among the data presented are the topography; total number of buildings and structures; roads, parking and sidewalks; fencing; site utilities; storage tanks; accessibility; historic preservation;
natural hazards; and sustainability. The overall condition of the site is rated in one of three categories: good, fair, or poor.
Building Descriptions – Tabular information, as well as photographs and floor plan drawings, are provided for each building or structure, as appropriate, in the following categories: real estate; accessibility; building envelope; interior finishes; vertical circulation; heating, ventilation and air conditioning (HVAC); plumbing; fire protection;
electrical services; fire alarms; carbon monoxide detection; communication; and building metering. The overall condition of the building and its five key subsystems (structure, exterior, interior, mechanical, and electrical) are rated in one of three categories: good, fair, or poor. If applicable, recommendations for renovation or demolition are provided.
BUILDINGS AND STRUCTURES
00616 OUACHITA 06/04/2015
1Page: of Date:
0001 - ADMINISTRATION
0002 - MEN'S DORMITORY I (VACANT)
0003 - MEN'S DORMITORY II
0004 - MEN'S DORMITORY III
0005 - HEALTH CARE
0006 - GYMNASIUM
0007 - OEP/VOCATIONAL
0009 - VOCATIONAL
0010 - VOCATIONAL
OFFICE/WAREHOUSE
0012 - VOCATIONAL
0013 - RESIDENTIAL WORKER OFFICE
0014 - EDUCATION
0015 - DINING HALL
0018 - LODGE
0021 - LAUNDRY/STUDENT CANTEEN
0028 - LUMBER STORAGE
0029 - VOCATIONAL STORAGE
0031 - VOCATIONAL STORAGE
0043 - VOCATIONAL STORAGE
0047 - WELDING
0048 - FEMALE DORMITORY IV
0049 - SEWAGE TREATMENT PLANT LAB
0052 - IT OFFICE
0053 - CEMENT/PLASTER SHOP
0005A - MEDICAL STORAGE (8Ft x 10Ft) 0005B - FLAMMABLE STORAGE (12Ft x 24Ft) 0006A- SWIMMING POOL STORAGE (6Ft x 8Ft) 0006B- SWIM POOL MECH EQUIP (7Ft x 11Ft) 0006C - GYMNASIUM STORAGE (12.5Ft x 17Ft) 0006D - GYMNASIUM STORAGE (12.5Ft x 17Ft) 0006E - GYMNASIUM STORAGE (12.5Ft x 17Ft) 0008A- PAINT STORAGE (15Ft x 23Ft) 0008B- MAINTENANCE STORAGE (12Ft x 16.5Ft) 0008C- CARPENTRY STORAGE (12Ft x 18Ft) 0008D - VOCATION STORAGE (7Ft x 10Ft) 0015A - DINING HALL FREEZER (15Ft x 25Ft) 0015B - DINING STORAGE (12Ft x 15Ft) 0015C - DINING STORAGE (12Ft x 15Ft) 0029A - VOCATION STORAGE (10Ft x 16Ft) 0030 - OIL STORAGE (17Ft x 25Ft)
Name GSF
2,880 6,254 7,200 7,200 3,480
12,000 3,350
10,330 4,540
4,900 1,600 6,600 6,360 6,550 1,900 2,495 1,770 1,680
4,640
14,900
6,230
Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active
Active
Active
Active
Active Active
Active
Active Active
Active Active Active
Active
StatusType
Building Building Building Building Building Building Building Building Building
Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure
Structure
Structure
Structure
Structure
Structure
Structure Structure
Structure
Structure Structure
Structure Structure Structure
Structure
Use Group Built Flrs Const
Business Residential Residential Residential Business Assembly Business Business Storage
Business Business Business Assembly Business Utility/Misc.
Business Business Business Business Factory/Ind.
Residential Utility/Misc.
Business Factory/Ind.
Storage Storage
Business
Business
Storage
Storage
Storage
Business Business
Business
Storage Storage
Storage Storage Storage
Storage
Good Fair
Good Good Good Good Good Good Good
Poor Good Good Good Good Poor Good Good Good Poor Good Good Good Good Good Good Good
Good
Good
Good
Good
Good
Good Good
Good
Good Good
Good Good Good
Good
ConditionAsset Number
0061600002 0061600003 0061600004 0061600005 0061600015 0061600006 0061600007 0061600008 0061600009
0061600011 0061600012 0061600013 0061600014 0061600016 0061600019 0061600021 0061600010 0061600032 0061600022 0061600030 0061600031 0061600035 0061608049 0061608050 0061608062 0061608063
0061600020
0061600028
0061608065
0061608066
0061608064
0061600026 0061600033
0061600034
0061608067 0061608068
0061608069 0061608070 0061608071
0061600027
BUILDINGS AND STRUCTURES
00616 OUACHITA 06/04/2015
2Page: of Date:
0030A - VOCATION STORAGE (9Ft x 13Ft) 0048A - BLEACHERS (16Ft x 17Ft) 0048B - BLEACHERS (16Ft x 17Ft) 0049A - WWTP SHED (3.5Ft x 14Ft) 0049B - GRAVEL STORAGE (10Ft x 14Ft) 0049C - WWTP STORAGE (3.5Ft x 4Ft) 0050 - PAVILION (48Ft x 82Ft) 0053A - MASONRY STORAGE (6Ft x 10Ft) 0055 - STORAGE (17Ft x 25Ft) 0055A - DORM STORAGE (8Ft x 12.3Ft) 0056 - DORM STORAGE (16Ft x 32Ft) 0057 - GAZEBO (12Ft DIAMETER) 0058 - PAVILION (15Ft x 20Ft) 0059 - GAZEBO (12Ft DIAMETIER) 0060 - GAZEBO (12Ft DIAMETER) 0061 - GAZEBO (12Ft DIAMETER) 0062 - GAZEBO (12Ft DIAMETER) 0063 - STORAGE (20Ft x 34.5Ft) 0063A - RESIDENTIAL STORAGE (12.5Ft x 17Ft) 0063B - RESIDENTIAL STORAGE (12.5Ft x 17Ft) 0063C - RESIDENTIAL STORAGE (12.5Ft x 17Ft)
Name GSF
3,940
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active
StatusType
Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Structure
Structure
Use Group Built Flrs Const
Storage Assembly Assembly Utility/Misc.
Storage Utility/Misc.
Assembly Storage Business Storage Storage Assembly Assembly Assembly Assembly Assembly Assembly Storage Storage
Storage
Storage
Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good
Good
Good
ConditionAsset Number
0061608072 0061608073 0061608074 0061608080 0061608079 0061608083 0061600036 0061608075 0061608052 0061608082 0061608061 0061608054 0061608055 0061608056 0061608057 0061608058 0061608059 0061608060 0061608076
0061608077
0061608078
24 118,219
37 11,375
61 129,594
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/04/2015
Space Utilization By Function 00616 Ouachita Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 164 Non Residents 0
164Total Students
(164)
(164)
(164)
DIFFERENCE
17,712
15,510
2,952
21,320
33,870
5,485
Lounge Other Shower/Toilet Sleeping excl. SPD(32 rooms; 192 beds) Storage
Academic (164) Non-Academic
20 -- Bricklayer + 40 -- Carpentry + 30 -- Office Administration 20 -- Painting + 24 -- Urban Forestry + 24 -- Welding +
Vocational Theory (128)
Dining (2 Servings) Food Preparation Food Storage
3,995 1,375 3,040
12,720
2,145 6,734
6,579 6,703
2,045 2,595 3,910
2,184
2,980 1,400 1,105
1,640 1,312 1,968
11,808
1,640 1,640
1,500 3,000 1,350 1,500 1,800 1,800
1,280
1,312
2,355
1,072 -794
5,094
5,079 3,703
-375
2,110
1,668
Vocations
3,608
18,360
2,533
06/04/2015
Space Utilization By Function 00616 Ouachita Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 319.38 52,379 93,656
(164)
(164)
(164)
(164)
(0)
DIFFERENCE
118,219
0.79
TOTAL GSF
NET TO GROSS RATIO
8,200
1,445
3,280
13,291
1,520
2,948
6,581
8,641
Arts & Crafts Assembly Hall Gymnasium Meeting Room Miscellaneous Recreation Pool Hall Recreation Office Recreation Storage Student Store
Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
8.81
1,413 7,000
1,455
1,520
2,948
2,871 3,710
8,641
1,445
1,312 1,968
1,413 7,000
1,455
-332
1,559 1,742
8,641
RESIDENT
NON-RESIDENT
(164)
(0) 15
50 8,200
5,091
-332
3,301
8,641
41,277
Net Square Footage By Building Date: 06/04/2015 Page: 1
Center: OUACHITA (00616) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
4,800 3,960 3,960
2,500
1,720
0048 - FEMALE DORMITORY IV
0003 - MEN'S DORMITORY II
0004 - MEN'S DORMITORY III
0048 - FEMALE DORMITORY IV
0003 - MEN'S DORMITORY II
0004 - MEN'S DORMITORY III
0048 - FEMALE DORMITORY IV
0003 - MEN'S DORMITORY II
0048 - FEMALE DORMITORY IV
0004 - MEN'S DORMITORY III
0002 - MEN'S DORMITORY I (VACANT)
0004 - MEN'S DORMITORY III
0013 - RESIDENTIAL WORKER OFFICE
0048 - FEMALE DORMITORY IV
0003 - MEN'S DORMITORY II
Bldg Name Actual NSF Difference
12,720
3,995
3,040
1,375
Sub Total: 21,320
11,808
1,640
1,968
1,312
17,712
2,355
-794
1,072
( 164
3,608
16 rooms; 64 beds 8 rooms; 64 beds 8 rooms; 64 beds
Page: 2
Center: OUACHITA (00616) of 4
EDUCATION
Academic
Vocational Theory (128)
Carpentry
Welding
Painting
Bricklayer
Non-Academic
Office Administration
Urban Forestry
Function Suggested
NSF
1,340
4,578
3,910
2,045
5,089 1,490
1,020
1,845
0014 - EDUCATION
0014 - EDUCATION
0014 - EDUCATION
0014 - EDUCATION
0012 - VOCATIONAL
0053 - CEMENT/PLASTER SHOP
0047 - WELDING
0007 - OEP/VOCATIONAL
0009 - VOCATIONAL
0029 - VOCATIONAL STORAGE
0028 - LUMBER STORAGE
0009 - VOCATIONAL
0047 - WELDING
0012 - VOCATIONAL
0053 - CEMENT/PLASTER SHOP
0031 - VOCATIONAL STORAGE
0014 - EDUCATION
0013 - RESIDENTIAL WORKER OFFICE
0014 - EDUCATION
0014 - EDUCATION
0018 - LODGE
0018 - LODGE
0010 - VOCATIONAL OFFICE/WAREHOUSE
0009 - VOCATIONAL
0005 - HEALTH CARE
0018 - LODGE
0018 - LODGE
0014 - EDUCATION
0013 - RESIDENTIAL WORKER OFFICE
0007 - OEP/VOCATIONAL
0007 - OEP/VOCATIONAL
0028 - LUMBER STORAGE
Bldg Name Actual NSF Difference
2,145
2,184
6,703
3,910
2,045
6,579
6,734
2,595
Sub Total: 33,870
1,640
1,280
3,000
1,800
1,500
1,500
1,640
1,350
1,800
15,510
3,703
2,110
5,079
5,094
-375
( 164
18,360
Page: 3
Center: OUACHITA (00616) of 4
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Dining (2 Servings)
Food Preparation
Food Storage
Arts & Crafts
Gymnasium
Student Store
Miscellaneous Recreation
Pool Hall
Assembly Hall
Meeting Room
Recreation Storage
Recreation Office
Medical/Dental
Function Suggested
NSF
2,980
1,400
1,105
7,000
1,455
1,413
1,520
0015 - DINING HALL
0015 - DINING HALL
0015 - DINING HALL
0006 - GYMNASIUM
0006 - GYMNASIUM
0021 - LAUNDRY/STUDENT CANTEEN
0006 - GYMNASIUM
0006 - GYMNASIUM
0018 - LODGE
0013 - RESIDENTIAL WORKER OFFICE
0029 - VOCATIONAL STORAGE
0006 - GYMNASIUM
0006 - GYMNASIUM
0005 - HEALTH CARE
Bldg Name Actual NSF Difference
2,980
1,400
1,105
7,000
1,455
1,413
1,520
Sub Total:
Sub Total:
Sub Total:
5,485
13,291
1,520
1,312
1,445
2,952
8,200
1,445
1,668
2,533
5,091
Page: 4
Center: OUACHITA (00616) of 4
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
2,035
3,710
1,696
1,956 2,185 3,895
0052 - IT OFFICE
0001 - ADMINISTRATION
0013 - RESIDENTIAL WORKER OFFICE
0018 - LODGE
0010 - VOCATIONAL OFFICE/WAREHOUSE
0009 - VOCATIONAL
0021 - LAUNDRY/STUDENT CANTEEN
0049 - SEWAGE TREATMENT PLANT LAB
0009 - VOCATIONAL
0012 - VOCATIONAL
0002 - MEN'S DORMITORY I (VACANT)
0043 - VOCATIONAL STORAGE
Bldg Name Actual NSF Difference
2,948
3,710
2,871
8,641
Sub Total:
Sub Total:
Sub Total:
2,948
6,581
8,641
3,280
1,968
1,312
3,280
3,280
-332
1,742
1,559
8,641
-332
3,301
8,641
Environmental Management Report
Center: OUACHITA (00616) Page: 1 Date: 06/04/2015 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Municipal Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Buildings 6A, 8A, and 49
Oil based paint (<50 gals), chlorine (10 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Garland County Solid Waste Yes Oil based paint (4 gals/month), organic solvent (4 gals/month)
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service
Crystal Clean, Shreveport, LA
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
09/11/1992 Non-Friable Only Andrew Anthony 03/01/2011 Yes No N/A No Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 06/04/2015Center : Ouachita (00616) Page: 1 of 1
Floor Finishes Floor Finishes
Floor Finishes
Floor Finishes
Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes
Floor Finishes Floor Finishes
Water Utility Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Linoleum, green/brown Linoleum, gray/brown
Linoleum, yellow/gray
12x12 floor tile, gray/green
Mastic beneath 12x12 tile 12x12 floor tile, off-white
12x12 floor tile, off-white Mastic beneath 12x12 tile 12x12 floor tile, white/green
12x12 floor tile, gray/green Mastic beneath 12x12 tile
Pipe fitting gasket 9x9 floor tile, brown
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Exam rooms, lab Utility room
Women's locker room
Carpentry office
Loading dock area Loading dock area
Storage room Hallway Hallway
Food storage hallway Food storage hallway
Meter room 2nd floor hallway
Building :
Building :
Building :
Building :
Building :
Building :
Building :
0005 - HEALTH CARE
0006 - GYMNASIUM
0009 - VOCATIONAL
0010 - VOCATIONAL OFFICE/WAREHOUSE
0012 - VOCATIONAL
0015 - DINING HALL
0018 - LODGE
Radon
Page: 1 of 2
0001 - ADMINISTRATION
0002 - MEN'S DORMITORY I (VACANT)
0003 - MEN'S DORMITORY II
0004 - MEN'S DORMITORY III
0005 - HEALTH CARE
0006 - GYMNASIUM
0007 - OEP/VOCATIONAL
0009 - VOCATIONAL
0010 - VOCATIONAL OFFICE/WAREHOUSE
0012 - VOCATIONAL
0013 - RESIDENTIAL WORKER OFFICE
0014 - EDUCATION
0015 - DINING HALL
0018 - LODGE
0021 - LAUNDRY/STUDENT CANTEEN
0028 - LUMBER STORAGE
0029 - VOCATIONAL STORAGE
0031 - VOCATIONAL STORAGE
0043 - VOCATIONAL STORAGE
0047 - WELDING
0048 - FEMALE DORMITORY IV
0049 - SEWAGE TREATMENT PLANT LAB
0052 - IT OFFICE
0053 - CEMENT/PLASTER SHOP
Bldg Name
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
08/18/1992
08/18/1992
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
03/06/1991
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
No
No
N/A
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
4 - 20 pCi
4 - 20 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
Radon
Page: 2 of 2
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description OUACHITA Civilian Conservation Center
Aerial View of the Center
Page: 1 Date: 06/04/2015 of 4
Comments:
Paving Type for Roads & Parking
There is significant cracking and wear on the roads and sidewalks. There are some gravel roads leading to the vocational storage areas.
Paving Type for Sidewalks
Concrete, Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterHot Springs Municipal Water SystemPublic Water Authority
Source Water Disinfection 0None
The master meter used for billing and the pressure regulator on the main Center supply are owned by the city and are located on city property across the adjacent river.
Comments:
Number of Deficiencies = 1
Number of Deficiencies = 6
Number of Deficiencies = 2SITE FEATURES
UTILITIES
Buildings Structures24 37Gently Sloping
Surrounding
Outdoor Recreation
Forest, Residential
Amphitheater, Basketball, Field, Horseshoe, Pool, Soft/Baseball, Swimming Pool, Volleyball
None
Outdoor HVAC Equipment
Propane Tanks
Recreation Amphitheater
Storage Area
Swimming Pool
Vocations
Vocations
Waste Water Treatment Plant
CMU
Decorative Masonry
CMU
Chain Link
Chain Link
CMU
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Fair
Number of Deficiencies = 2
Fencing
Other Features
Page: 2 Date: 06/04/2015 of 4
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Substandard 0 12None Municipal
The existing fire hydrants are sub-standard sizes (4" diameter or less) and are presumed not to have adequate pressure and flow capacity for fighting a substantial fire. The nearest fire station (volunteer) is about 7 miles away with a response time of about 12 minutes.
Comments:
Sewage Treatment Flow
Treatment plant is aged, inefficient, and in need of modernization.
Center
On-site Sewage Treatment Plant
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: Generally, each building that utilizes LP gas is provided with a vendor-supplied above-ground propane tank.
Heritage Propane Co.
Number of Deficiencies = 1
Number of Deficiencies = 23. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
2. Fire Protection System
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center No Good
System Capacity Adequate System Condition
Yes Fair
4. Storm Water System Number of Deficiencies = 8
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Gas Company Metering
None
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
6. Central Plant: None
Page: 3 Date: 06/04/2015 of 4
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Entergy Corporation
The primary overhead service is brought to the Center from power lines northwest of the campus along Job Corps Road. The secondary services to buildings on Center are both overhead and underground with individual metering occurring at each building service entrance point. The utility company owns and maintains all pole- and pad-mounted transformers and secondary meters. Dining Hall Building 15 is backed up by a 125 kW diesel engine generator with a 400A automatic transfer switch (ATS) located outside. Similarly, a 50 kW diesel engine generator with a 200A ATS provides backup power to Sewage Treatment Plant Lab Building 49.
Pole and Pad Utility
Utility Utility
No
Comments:
Telephone Company
On-site Line Owner
The telephone service, including the voice over internet protocol (VoIP) long distance phone, is provided and maintained by the Job Corps Data Center (JCDC). Three T1 lines are brought to the computer room located in Administration Building 1. This location is also where the Center server for LAN and WAN networks reside. Fiber optic cables are utilized for network interconnection between the server and buildings. The telephone and network system components are backed up by a 6 kVA portable UPS module. The fire alarm system in buildings on Center is stand-alone except for dormitory buildings which are connected to a central control panel in Residential Worker Office Building 13. Carbon monoxide detectors are installed in most buildings including the dormitories. The security system consists of CCTV cameras in Dormitory I, II and III Building 2, 3, and 4 respectively and Education Building 14, and door alarms in Female Dormitory Building 48. Cable TV is provided in the dormitory, dining, and recreational facilities.
None (JCDC)
Maint. Responsibility
Center Center
CCTV Cameras and Door Alarms in some buildings
13.8 kV, 3-Phase
120/208V, 3-Ph, 4W and 120/240V, 1-Ph, 3WOverhead & Underground
OverheadPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 1
9. Electrical (Communication/Alarm/Security)
7. Electrical (Service)
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Utility, Center Yes Good
Comments: The utility company owns and maintains lights that are mounted on power poles. The Center owns and maintains all other pole-mounted and building-mounted exterior lights.
ATS MTS
Yes No
Number of Deficiencies = 1
Number of Deficiencies = 9
Fire Alarm Security
Metering Individual
Page: 4 Date: 06/04/2015 of 4
ACCESSIBILITY
Yes
UnknownUnknownUnknownNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
01/01/1965CenterActive AbovegroundEach Building
There are twenty 500 - 1000 gallon aboveground propane tanks throughout the site, each of which is located next to the building it serves.
NoPropane
STORAGE TANKS
Comments:
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date
Earthquake Risk
Low Low MediumHigh HighIBC Low
LightningEarthquake Def. Authority
Flooding Tornado Hurricane Forest Fire
ID
Reg.
Number of Deficiencies = 20
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
Roads and sidewalks have cracks and are generally in fair condition. The seawall is damaged and needs to be investigated to determine the proper repair.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Heating & Cooking
Purpose
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
NO
NO
NO
Yes
Yes
Yes
Yes
32 %
Building Descriptions and Structures
BUILDING 1 - ADMINISTRATION
Building Descriptions
Page: 1 of 115
Building: 0001 - ADMINISTRATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Stone Masonry Wood Siding
Wall Roof Batt Batt
Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Business 2,880 2,035 1 Owned 1966 Not Evaluated
Comments: There are concrete stairs at the entrances and no ramps, therefore there is no wheelchair access.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
No
Yes
Yes
Yes
Yes
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The gutters and downspouts on the building are deteriorated and leaking.
Drainage Year Life
Type Area Served
Asphalt Shingles Gutters and Downspouts 2011 15 Gable Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 115
Building: 0001 - ADMINISTRATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile Wood
Ceramic Tile Drywall Stucco Vinyl Wall Covering
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Steps
Comments: Concrete steps are from grade to the north and south entrances.
Fixed - Aluminum Frame; Single Glazing; Sliding - Aluminum Frame; Double Glazing;
Sliding - Wood Frame; Double Glazing;
Gypsum Board
Number of Deficiencies = 4
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The split system heat pump provides heating to the computer room. The condensing unit, ComfortStar model CHH018CD-13(O), R-410A refrigerant, built in 04/2007, provides…