7- Questions-Answers 001.pdf
PDF 137 KB Posted
- Solicitation number
- 1240LU24Q0005
- Issued by
-
Department of Agriculture Forest Service
About this file
This document provides the questions and answers from a pre-proposal conference for solicitation number 1240LU24Q0005 from the United States Department of Agriculture Forest Service. The solicitation involves a combined office and conference room remodel for the Deputy Regional Forester located in Missoula, Montana.
The remodel includes partitioning an area of the existing secretary's office to create an additional private office, matching all finishes and ensuring full functionality of both resulting offices. The conference room will have all existing furniture removed and stored. A new wall will be built to isolate individual offices, and the room will be remodeled as a dual purpose conference and hoteling/training area. Electrical, communication, and data lines will be installed in new walls and tracked in the floor to allow movable furniture. The conference will utilize a set-aside for small businesses and is due by January 11, 2024. Bonds of 100% of the contract price are required for offers over $35,000, with payment bonds over $250,000.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of Agriculture
Forest Service
Northern Region Acquisition Management
24 Fort Missoula Rd.
Missoula, MT 59804
America’s Working Forests – Caring Every Day in Every Way Printed on Recycled Paper
Date: January 11, 2024 To: All interested parties
Subject: Solicitation - 1240LU24Q0005, Forest Service, Region 1 - DRF Office Conference Room Remodel; Questions – Answers 001.
1. Q - Is the post in the new wall?
a. A - No. A101.
2. Q - Does the base stay?
a. A - If wall intersects base, cut base to abut wall fittingly.
3. Q - How high is drop ceiling above the floor?
a. A - About 10’ from ceiling to floor and 21” above drop ceiling.
4. HVAC units
a. Q - HVAC unit, above waiting room portion – does this stay?
i. A – No change. M101.
b. Q - HVAC unit above secretary’s office – does this move?
i. A –As shown on M101.
5. Q - Can we look at the electrical room?
a. A – Yes, as shown in the site visit.
6. Q - Can we look into the ceiling?
a. A – Yes, as shown in the site visit.
7. Q - Where is the trunk line for the HVAC?
a. A – As shown on M101.
8. Q - Does page A102 exist?
a. A – No. Sheet index A000.
9. Q - Is there a door schedule?
a. A – No.
10. Q - A101 – Does the wall in the conference room fire rated like the reference diamond with an i in it?
a. A – Same construction as wall in Office – A103. See picture below.
b. Furniture will be moved to the 14th and Catlin location.
11. Q - Asked where the fire alarm control panel was located?
a. A – Shown, below the tele-com room in the basement.
12. Q - Is there only one IT room?
a. A - There is one per floor – shown.
13. Q - Why is the core drilling spec in the contract?
a. A - Core drilling is not anticipated but is there if applicable. A103.
14. Q - Pointing to the middle section – is that the ceiling?
a. A – It is plaster – drawing added labeled “From prior remodel - Electrical_Compiled_Part2 - Page 1”.
15. Q - Will it be demolished to access the canned lights?
a. A – If needed but not anticipated.
16. Q - Wanted to check access through the hall back to the electrical panel
I did not see any route or feasible access to panel R1A on floor 1 to run new conference room circuits 65, 67, 69, 71, 73, 75, 77, 81 and office circuits 61, 63.
The demo plans show existing available furniture circuits in the conference room 54,56,58,60,62,64 and existing office circuits 45,47.
My question is will it be sufficient to use the existing local circuits noted to complete the job?
If not, what is the plan on gaining access to panel R1A with the hard lid in the way?
Is it okay to run all the Data drops down a floor into the basement and use the existing wire rack to the small server room?
a. A - It is anticipated to primarily use existing circuits.
b. A - Conference room – Existing data lines to the existing cubicles will be utilized and routed through the tracked floor as will the power. As needed, additional power for the TVs can be tracked in through the basement.
c. A - Office - Either can be dropped through the floor and run in the trays in the basement.
17. Q - When was the building remodeled?
a. A - About 10 years ago or so.
18. Q - Will the new wall get the chair rail like the existing walls?
a. A – yes. A103, A101.
19. Q - How much will be the Bid bond for this work?
a. A - C.4 BONDING Bonding: In accordance with FAR Part 28.102-1, Performance Bonds, for 100% of the contract price. are required for offers over $35,000. In addition, Payment Bonds are required for offers over $250,000. Bonds shall be provided within 10 days of award.
20. Q - When will the Q&A from the Pre-proposal conference be published?
a. All Q&A’s will be posted in SAM no later than January 11, 2024, by 04:PM
MST.
21. Q - Where is location of condenser unit?
a. A – Outside behind the secretary window, South.
22. Q – What refrigerant do the units contain?
a. A – Glycol.
23. Q – Are multiple indoor ductless units tied together with single condenser units?
(Does one outdoor condenser serve more than one indoor evaporator)
a. A – Yes.
24. Q – What are the size of the acoustic panels to be used?
a. A – 2’x4’.
25. Q – Can we run multiple parallel tracks? This might be to avoid using “T”s, or to add capacity in the track?
a. A – Yes, provided they don’t make a ripple effect in the floor, i.e. peaks and valleys in close proximity.
Also, tracks can be placed adjacent to each other to increase capacity as needed.
Moreover, parallel tracks that are not adjacent, but close, can forego the transition ramps altogether. This can be done by using a uniform, equally durable, filler of the same height between them such as plywood, backerboard, or floating the floor. This will prevent ripples and provide a flat surface, which is overall preferable.