Attachment 6 Geanerator Specs.pdf
PDF 353 KB Posted
- Attached to
- Shell Falls Primary Power
- Solicitation number
- 1240LT26Q0038
About this file
This document is a Final Construction Document (CD) electrical one-line diagram for the Shell Falls Wayside Primary Power project located in the Medicine Wheel Ranger District of the Bighorn National Forest, prepared by the USDA Forest Service Rocky Mountain Region 2. The drawing, dated March 2025 and designated as sheet E3.1, illustrates the electrical infrastructure and power distribution system for the wayside facility.
The one-line diagram depicts a comprehensive electrical system including a 25 kilovolt-amp (kVA) 240/120V single-phase transformer connected to utility service, an existing medium voltage transformer noted as not in use, a 20-kilowatt propane generator rated at 240/120V with 1.6 kilowatt (3W) capacity at 6,500 feet altitude, a minimum 5,000-ampere-hour battery bank, photovoltaic (PV) panels with charge controller, utility building infrastructure with a 200/2P meter, and an isolation disconnect switch. The associated sheet notes and key notes specify critical construction requirements including coordination with existing underground utilities, PVC conduit specifications, grounding requirements (1/2" and 1/6" RMC), cable burial specifications with 3" PVC protective sleeves, removal of existing transformer feeders, a turn-key off-grid photovoltaic system with specified battery duration and operational capacity, NEMA 3R disconnect switches, and a minimum two-day site operation battery system to support loads including 24/7 bathroom lighting operations. Additional requirements address generator operational protocols, alternate underground boring provisions, and neutral-ground bonding disconnections at existing electrical infrastructure.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DWG SHEET NO.
OF
SHEETCHECKEDDESIGNERDATEDRAWING TITLE
United States Department of Agriculture Forest Service
NO. DATEBYREVISION DESCRIPTION
SHELL FALLS WAYSIDE
PRIMARY POWERREGION 2
MEDICINE WHEEL RANGER DISTRICT
BIGHORN NATIONAL FOREST
ROCKY MOUNTAIN
MARCH 2025
F
IN
A L C
O N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
C D
ELECTRICAL
ONE-LINE DIAGRAM
KLC SKB
E3.1
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
KEY NOTES
AutoCAD SHX Text
1. COORDINATE NEW UNDERGROUND WORK WITH EXISTING COORDINATE NEW UNDERGROUND WORK WITH EXISTING UNDERGROUND UTILITIES AND EQUIPMENT.
AutoCAD SHX Text EXISTING MEDIUM VOTLAGE TRANSFORMER. TRANSFORMER IS NOT IN USE. NO UTILITY CONNECTION ON THE SITE. EXISTING 3-500 KCMIL IN 4" PVC CONDUIT AND 4" SPARE PVC CONDUIT WITH PULL STRING. EXISTING (3#2 & 1#8 GND) 1-1/2" RMC CONNECTED VIA WIRE TROUGH. EXISTING (3#1/0 & 1#4 GND) 2" RMC. EXISTING (1#6) 1/2" RMC GROUND CONDUCTOR. EXISTING (1#6) 1/2" RMC GROUND CONDUCTOR BONDED TO GROUND ROD. DO NOT BOND NEUTRAL AND GROUND IN THIS EQUIPMENT. PROVIDE (1#6) 1/2" RMC GROUND CONDUCTOR BONDED TO (1#6) 1/2" RMC GROUND CONDUCTOR BONDED TO GROUND ROD. DISCONNECT AND REMOVE FEEDERS FROM SECONDARY OF UTILITY TRANSFORMER SPLICE BOX DISCONNECTED. PROVIDE 3-#350, 1#1 QUADRUPLEX URD DIRECT BURIAL CABLE VIA EXISTING 6" PCV SLEEVE. PROVIDE 3" PVC TO EXISTING 6" SLEEVE TO ROUTE FROM THE UTILITY BUILDING TO THE RESTROOM BUILDING. FEEDER SIZED FOR VOLTAGE DROP. EXISTING 6" SLEEVE CONTAINS EXISTING 2" GRC AND 1" HDPE. PULL A MANDREL THROUGH SLEEVE TO CONFIRM CLEAR SPACE PRIOR TO PULLING CABLES. SEE KEY NOTE #14 FOR ADDITIONAL INFORMATION. PROVIDE GENERATOR INDICATED. KOHLER 20RESA(L) OR EQUAL. PROVIDE A TURN-KEY, OFF-GRID RATED, PHOTOVOLTAIC (PV) SYSTEM WITH PHOTOVOLTAIC PANELS, CHARGE CONTROLLER/INVERTER, METER, AND BATTERY BANK AS PRIMARY POWER SOURCE. PROVIDE PROPANE GENERATOR AND CONTROLS FOR GENERATOR SUPPLEMENTAL POWER SOURCE INTEGRATION. PROVIDE START UP AND COMMISSIONING OF THE FULLY INSTALLED SYSTEM. SOLARCRAFT REP TARA EASTER, 303-999-6998. AMERESCO REP KINDLE SCHMIDT, (951)-346-4826. PROVIDE SEQUENCE OF OPERATION FOR FOR PV, BATTERIES, AND GENERATOR POWER OPERATION. PROVIDE NEMA 3R ISOLATION DISCONNECT SWITCH AND WEATHERPROOF SPLICE BOX ADJACENT TO EXISTING WIRE TROUGH FOR CONNECTION AND ISOLATION OF BATTERY, PHOTOVOLTAIC PANELS, AND GENERATOR SYSTEM TO EXISTING DISTRIBUTION SYSTEM. COORDINATE EXACT LOCATION WITH CONTRACTING OFFICER PRIOR TO ROUGH-IN. PROVIDE A UNISTRUT FRAME TO MOUNT THE DISCONNECT SWITCH IF REQUIRED. SIZE SPLICE BOX TO ACCOMMODATE ALL FEEDERS AND CONNECTIONS NOTED. PROVIDE BATTERY SYSTEM TO SUPPORT A MINIMUM OF TWO DAYS SITE OPERATION BASED ON 7.2 KW METERED PEAK DEMAND LOAD, 9 HOURS OF FULL OPERATION, AND 24/7 OPERATION OF BATHROOM LIGHTS. BATTERIES PROVIDED SHALL BE RATED FOR A TEMPERATURE RANGE OF 1°-40° C. BATTERY DURATION CALCULATION SHALL INCLUDE ONLYOPERATION WITHIN THE MANUFACTURER'S RECOMMENDED DEPTH OF DISCHARGE RANGE. PROVIDE DISCONNECT SWITCH IF NOT INTEGRAL TO CHARGE CONTROLLER/INVERTER. ADD ALTERNATE: PROVIDE UNDERGROUND BORING OR DUCT BANK TO SUPPORT CONNECTION FROM UTILITY BUILDING TO EXISTING RESTROOM ELECTRICAL INFRASTRUCTURE. TRENCHING REQUIRES THE SURFACE BE PATCHED TO MATCH EXISTING CONDITIONS SUCH AS ASPHALT, CONCRETE OR VEGETATION. THE GENERATOR IS INTENDED TO OPERATE MINIMALLY. THE PV SYSTEM IS TO BE USED TO CHARGE THE BATTERIES AND SUPPORT THE SITE LOADS. THE GENERATOR IS INTENDED TO OPERATE TO CHARGE THE BATTERIES AND SUPPORT THE SITE LOADS AFTER EXTENDED PERIODS OF POOR WEATHER CONDITIONS PREVENTED PHOTOVOLTAIC POWER GENERATION AND THE BATTERIES ARE DEPLETED. PROVIDE 3-#350, 1#1 QUADRUPLEX URD DIRECT BURIAL CABLE DISCONNECT NEUTRAL-GROUND BOND AT EXISTING WIRE TROUGH AND PANELBOARD DISCONNECTS.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
PARTIAL ONE-LINE DIAGRAM
AutoCAD SHX Text
NONE
AutoCAD SHX Text
AutoCAD SHX Text E3.1
AutoCAD SHX Text
SPLICE BOX
AutoCAD SHX Text
PANEL
AutoCAD SHX Text E
AutoCAD SHX Text
PANEL
AutoCAD SHX Text A
AutoCAD SHX Text
RESTROOM BUILDING 200A/2P(E)
AutoCAD SHX Text
INFORMATION BUILDING 100A/2P(E)
AutoCAD SHX Text
WIRE TROUGH(E)
AutoCAD SHX Text
25 KVA, 2400V-240/120V, SINGLE PHASE TRANSFORMER(E)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
100A/2P 100A FUSES(E)
AutoCAD SHX Text
200A/2P 200A FUSES(E)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING UNLESS NOTED OTHERWISE
AutoCAD SHX Text
EXISTING UNLESS NOTED OTHERWISE
AutoCAD SHX Text
NEW UNLESS NOTED OTHERWISE
AutoCAD SHX Text E
AutoCAD SHX Text
20KW PROPANE GENERATOR 240/120V, 1 , 3WAT ALTITUDE 6,500 FT, 120 DEGREES F
AutoCAD SHX Text 85A2P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CHARGE CONTROLLER/ INVERTER
AutoCAD SHX Text
TO UTILTIY
AutoCAD SHX Text
PULL BOX(E)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COMBINER BOX
AutoCAD SHX Text
GROUND MOUNTED PHOTOVOLTAIC ARRAY
AutoCAD SHX Text
AutoCAD SHX Text
NEW UNLESS NOTED OTHERWISE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PANEL
AutoCAD SHX Text S
AutoCAD SHX Text
UTILITY BUILDING 200A/2P
AutoCAD SHX Text
METER
AutoCAD SHX Text
MINIMUM 5000AH BATTERY BANK
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ISOLATION DISCONNECT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text
CONCRETE ENCASED ELECTRODE
AutoCAD SHX Text
GND ROD
AutoCAD SHX Text
BLDG STEEL
AutoCAD SHX Text
GND BUS
AutoCAD SHX Text #1G
AutoCAD SHX Text #6G
AutoCAD SHX Text #1G
AutoCAD SHX Text #1G
AutoCAD SHX Text
ISC-1,000
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BIDDER QUESTION RESPONSES
AutoCAD SHX Text
AutoCAD SHX Text
KC
AutoCAD SHX Text 4/26
| Sheets and Views |
| Layout1 |
File details come from the government source that posted it. Updated .