This document appears to be a set of technical specifications related to a federal contract opportunity for the Pagosa Ranger District Security Upgrade project. The specifications cover various construction and security-related work, including selective demolition, rough carpentry, thermal insulation, applied fire protection, hollow metal doors and frames, access control, and security camera installation.

The key objectives of the project are to redesign the office lobby by installing a new wall and doors to separate the main lobby from the rest of the building, build a small conference room in the existing lobby, and install several security cameras and other security features for the US Forest Service employees. The technical specifications provide detailed requirements for the materials, installation, and performance of the various building components and security systems required for this project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Forest Service Specifications Pagosa RD Security Upgrade Project

San Juan National Forest

Pagosa Springs, CO

Table of Contents

SECTION 024119 - SELECTIVE DEMOLITION

SECTION 061000 - ROUGH CARPENTRY

SECTION 072100 - THERMAL INSULATION

SECTION 078100 - APPLIED FIRE PROTECTION

SECTION 081113 - HOLLOW METAL DOORS AND FRAMES

SECTION 083113.53 - SECURITY ACCESS DOORS AND FRAMES

SECTION 085113 - ALUMINUM WINDOWS

SECTION 087100 - DOOR HARDWARE

SECTION 092900 - GYPSUM BOARD

SECTION 096543 - LINOLEUM FLOORING

SECTION 099123 - INTERIOR PAINTING

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION 280010 – SUPPLEMENTAL REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 281000 - ACCESS CONTROL

SECTION 281300 - ACCESS CONTROL SOFTWARE AND DATABASE MANAGEMENT

SECTION 281400 - ACCESS CONTROL SYSTEM HARDWARE

SECTION 281500 - INTEGRATED ACCESS CONTROL HARDWARE DEVICES

SECTION 281511 - INTEGRATED CREDENTIAL READERS AND ENTRY MANAGEMENT

SECTION 024119 - SELECTIVE DEMOLITION

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Demolition and removal of selected portions of building or structure.

2. Demolition and removal of selected site elements.

3. Salvage of existing items to be reused or recycled.

B. Related Requirements:

1. Section 011000 "Summary" for restrictions on use of the premises, Owner-occupancy requirements, and phasing requirements.

2. Section 015639 "Temporary Tree and Plant Protection" for temporary protection of existing trees and plants that are affected by selective demolition.

3. Section 017300 "Execution" for cutting and patching procedures.

4. Section 013516 "Alteration Project Procedures" for general protection and work procedures for alteration projects.

5. Section 311000 "Site Clearing" for site clearing and removal of above- and below-grade improvements not part of selective demolition.

1.2 DEFINITIONS

A. Remove: Detach items from existing construction and dispose of them off-site unless indicated to be salvaged or reinstalled.

B. Remove and Salvage: Detach items from existing construction, in a manner to prevent damage, and deliver to Owner ready for reuse.

C. Remove and Reinstall: Detach items from existing construction, in a manner to prevent damage, prepare for reuse, and reinstall where indicated.

D. Existing to Remain: Leave existing items that are not to be removed and that are not otherwise indicated to be salvaged or reinstalled.

E. Dismantle: To remove by disassembling or detaching an item from a surface, using gentle methods and equipment to prevent damage to the item and surfaces; disposing of items unless indicated to be salvaged or reinstalled.

1.3 MATERIALS OWNERSHIP

A. Unless otherwise indicated, demolition waste becomes property of Contractor.

B. Historic items, relics, antiques, and similar objects including, but not limited to, cornerstones and their contents, commemorative plaques and tablets, and other items of interest or value to Owner that may be uncovered during demolition remain the property of Owner.

1. Carefully salvage in a manner to prevent damage and promptly return to Owner.

1.4 PREINSTALLATION MEETINGS

A. Predemolition Conference: Conduct conference at Project Site. See SOW for details.

1. Inspect and discuss condition of construction to be selectively demolished.

2. Review structural load limitations of existing structure.

3. Review and finalize selective demolition schedule and verify availability of materials, demolition personnel, equipment, and facilities needed to make progress and avoid delays.

4. Review requirements of work performed by other trades that rely on substrates exposed by selective demolition operations.

5. Review areas where existing construction is to remain and requires protection.

1.5 INFORMATIONAL SUBMITTALS

C. Proposed Protection Measures: Submit report, including Drawings, that indicates the measures proposed for protecting individuals and property for noise control. Indicate proposed locations and construction of barriers.

D. Schedule of Selective Demolition Activities: Indicate the following:

1. Detailed sequence of selective demolition and removal work, with starting and ending dates for each activity. Ensure Owner's building manager’s on-site operations are uninterrupted.

2. Interruption of utility services. Indicate how long utility services will be interrupted.

3. Coordination for shutoff, capping, and continuation of utility services.

4. Use of elevator and stairs.

5. Coordination of Owner's continuing occupancy of portions of existing building and of

Owner's partial occupancy of completed Work.

E. Predemolition Photographs or Video: Show existing conditions of adjoining construction, including finish surfaces, that might be misconstrued as damage caused by salvage and demolition operations. Comply with Section 013233 "Photographic Documentation." Submit before Work begins.

G. Warranties: Documentation indicating that existing warranties are still in effect after completion of selective demolition.

1.6 CLOSEOUT SUBMITTALS

A. Inventory: Submit a list of items that have been removed and salvaged.

1.8 FIELD CONDITIONS

A. Owner will occupy portions of building immediately adjacent to selective demolition area.

Conduct selective demolition so Owner's operations will not be disrupted.

B. Conditions existing at time of inspection for bidding purpose will be maintained by Owner as far as practical.

1. Before selective demolition, Owner will remove the following items:

a. None. All items must be removed by the Contractor.

C. Notify Architect of discrepancies between existing conditions and Drawings before proceeding with selective demolition.

D. Hazardous Materials: It is not expected that hazardous materials will be encountered in the Work.

1. Hazardous materials will be removed by Owner before start of the Work.

2. If suspected hazardous materials are encountered, do not disturb; immediately notify

Architect and Owner. Hazardous materials will be removed by Owner under a separate contract.

E. Hazardous Materials: Present in buildings and structures to be selectively demolished. A report on the presence of hazardous materials is on file for review and use. Examine report to become aware of locations where hazardous materials are present.

1. Hazardous material remediation is specified elsewhere in the Contract Documents.

2. Do not disturb hazardous materials or items suspected of containing hazardous materials except under procedures specified elsewhere in the Contract Documents.

3. Owner will provide material safety data sheets for suspected hazardous materials that are known to be present in buildings and structures to be selectively demolished because of building operations or processes performed there.

F. Historic Areas: Demolition and hauling equipment and other materials shall be of sizes that clear surfaces within historic spaces, areas, rooms, and openings, including temporary protection, by

[12 inches] or more.

G. Storage or sale of removed items or materials on-site is not permitted.

H. Utility Service: Maintain existing utilities indicated to remain in service and protect them against damage during selective demolition operations.

1. Maintain fire-protection facilities in service during selective demolition operations.

1.9 WARRANTY

A. Existing Warranties: Remove, replace, patch, and repair materials and surfaces cut or damaged during selective demolition, by methods and with materials and using approved contractors so as not to void existing warranties. Notify warrantor before proceeding.

B. Notify warrantor on completion of selective demolition, and obtain documentation verifying that existing system has been inspected and warranty remains in effect. Submit documentation at

Project closeout.

1.10 COORDINATION

A. Arrange selective demolition schedule so as not to interfere with Owner's operations.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Regulatory Requirements: Comply with governing EPA notification regulations before beginning selective demolition. Comply with hauling and disposal regulations of authorities having jurisdiction.

B. Standards: Comply with ANSI/ASSP A10.6 and NFPA 241.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verify that utilities have been disconnected and capped before starting selective demolition operations.

B. Review Project Record Documents of existing construction or other existing condition and hazardous material information provided by Owner. Owner does not guarantee that existing conditions are same as those indicated in Project Record Documents.

C. Perform an engineering survey of condition of building to determine whether removing any element might result in structural deficiency or unplanned collapse of any portion of structure or adjacent structures during selective building demolition operations.

1. Perform surveys as the Work progresses to detect hazards resulting from selective demolition activities.

D. Steel Tendons: Locate tensioned steel tendons and include recommendations for de-tensioning.

E. Verify that hazardous materials have been remediated before proceeding with building demolition operations.

F. Survey of Existing Conditions: Record existing conditions by use of preconstruction photographs and Drawings.

1. Inventory and record the condition of items to be removed and salvaged.

2. Before selective demolition or removal of existing building elements that will be reproduced or duplicated in final Work, make permanent record of measurements, materials, and construction details required to make exact reproduction.

3.2 PREPARATION

A. Refrigerant: Before starting demolition, remove refrigerant from mechanical equipment according to 40 CFR 82 and regulations of authorities having jurisdiction.

3.3 UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS

A. Existing Services/Systems to Remain: Maintain services/systems indicated to remain and protect them against damage.

B. Existing Services/Systems to Be Removed, Relocated, or Abandoned: Locate, identify, disconnect, and seal or cap off utility services and mechanical/electrical systems serving areas to be selectively demolished.

1. Owner will arrange to shut off indicated services/systems when requested by Contractor.

2. Arrange to shut off utilities with utility companies.

3. If services/systems are required to be removed, relocated, or abandoned, provide temporary services/systems that bypass area of selective demolition and that maintain continuity of services/systems to other parts of building.

4. Disconnect, demolish, and remove fire-suppression systems, plumbing, and HVAC systems, equipment, and components indicated on Drawings to be removed.

a. Piping to Be Removed: Remove portion of piping indicated to be removed and cap or plug remaining piping with same or compatible piping material.

b. Piping to Be Abandoned in Place: Drain piping and cap or plug piping with same or compatible piping material and leave in place.

c. Equipment to Be Removed: Disconnect and cap services and remove equipment.

d. Equipment to Be Removed and Reinstalled: Disconnect and cap services and remove, clean, and store equipment; when appropriate, reinstall, reconnect, and make equipment operational.

e. Equipment to Be Removed and Salvaged: Disconnect and cap services and remove equipment and deliver to Owner.

f. Ducts to Be Removed: Remove portion of ducts indicated to be removed and plug remaining ducts with same or compatible ductwork material.

g. Ducts to Be Abandoned in Place: Cap or plug ducts with same or compatible ductwork material and leave in place.

3.4 PROTECTION

A. Temporary Protection: Provide temporary barricades and other protection required to prevent injury to people and damage to adjacent buildings and facilities to remain.

1. Provide protection to ensure safe passage of people around selective demolition area and to and from occupied portions of building.

2. Provide temporary weather protection, during interval between selective demolition of existing construction on exterior surfaces and new construction, to prevent water leakage and damage to structure and interior areas.

3. Protect walls, ceilings, floors, and other existing finish work that are to remain or that are exposed during selective demolition operations.

4. Cover and protect furniture, furnishings, and equipment that have not been removed.

5. Comply with requirements for temporary enclosures, dust control, heating, and cooling specified in Section 015000 "Temporary Facilities and Controls."

B. Temporary Shoring: Design, provide, and maintain shoring, bracing, and structural supports as required to preserve stability and prevent movement, settlement, or collapse of construction and finishes to remain, and to prevent unexpected or uncontrolled movement or collapse of construction being demolished.

1. Strengthen or add new supports when required during progress of selective demolition.

C. Remove temporary barricades and protections where hazards no longer exist.

3.5 SELECTIVE DEMOLITION, GENERAL

A. General: Demolish and remove existing construction only to the extent required by new construction and as indicated. Use methods required to complete the Work within limitations of governing regulations and as follows:

1. Proceed with selective demolition systematically, from higher to lower level. Complete selective demolition operations above each floor or tier before disturbing supporting members on the next lower level.

2. Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting methods least likely to damage construction to remain or adjoining construction. Use hand tools or small power tools designed for sawing or grinding, not hammering and chopping.

Temporarily cover openings to remain.

3. Cut or drill from the exposed or finished side into concealed surfaces to avoid marring existing finished surfaces.

4. Do not use cutting torches until work area is cleared of flammable materials. At concealed spaces, such as duct and pipe interiors, verify condition and contents of hidden space before starting flame-cutting operations. Maintain portable fire-suppression devices during flame-cutting operations.

5. Maintain fire watch during and for at least 2 hours after flame-cutting operations.

6. Maintain adequate ventilation when using cutting torches.

7. Remove decayed, vermin-infested, or otherwise dangerous or unsuitable materials and promptly dispose of off-site.

8. Remove structural framing members and lower to ground by method suitable to avoid free fall and to prevent ground impact or dust generation.

9. Locate selective demolition equipment and remove debris and materials so as not to impose excessive loads on supporting walls, floors, or framing.

10. Dispose of demolished items and materials promptly.

B. Site Access and Temporary Controls: Conduct selective demolition and debris-removal operations to ensure minimum interference with roads, streets, walks, walkways, and other adjacent occupied and used facilities.

C. Work in Historic Areas: Selective demolition may be performed only in areas of Project that are not designated as historic. In historic spaces, areas, and rooms, or on historic surfaces, the terms

"demolish" or "remove" shall mean historic "removal" or "dismantling" as specified in

Section 024296 "Historic Removal and Dismantling."

D. Removed and Salvaged Items:

1. Clean salvaged items.

2. Pack or crate items after cleaning. Identify contents of containers.

3. Store items in a secure area until delivery to Owner.

4. Transport items to Owner's storage area indicated on Drawings.

5. Protect items from damage during transport and storage.

E. Removed and Reinstalled Items:

1. Clean and repair items to functional condition adequate for intended reuse.

2. Pack or crate items after cleaning and repairing. Identify contents of containers.

3. Protect items from damage during transport and storage.

4. Reinstall items in locations indicated. Comply with installation requirements for new materials and equipment. Provide connections, supports, and miscellaneous materials necessary to make item functional for use indicated.

F. Existing Items to Remain: Protect construction indicated to remain against damage and soiling during selective demolition. When permitted by Architect, items may be removed to a suitable, protected storage location during selective demolition[ and cleaned] and reinstalled in their original locations after selective demolition operations are complete.

3.6 SELECTIVE DEMOLITION PROCEDURES FOR SPECIFIC MATERIALS

A. Concrete: Demolish in small sections. Using power-driven saw, cut concrete to a depth of at least

3/4 inch at junctures with construction to remain. Dislodge concrete from reinforcement at perimeter of areas being demolished, cut reinforcement, and then remove remainder of concrete.

Neatly trim openings to dimensions indicated.

B. Concrete: Demolish in sections. Cut concrete full depth at junctures with construction to remain and at regular intervals using power-driven saw, and then remove concrete between saw cuts.

C. Masonry: Demolish in small sections. Cut masonry at junctures with construction to remain, using power-driven saw, and then remove masonry between saw cuts.

D. Concrete Slabs-on-Grade: Saw-cut perimeter of area to be demolished, and then break up and remove.

E. Resilient Floor Coverings: Remove floor coverings and adhesive according to recommendations in RFCI's "Recommended Work Practices for the Removal of Resilient Floor Coverings."

F. Roofing: Remove no more existing roofing than what can be covered in one day by new roofing and so that building interior remains watertight and weathertight.

1. Remove existing roof membrane, flashings, copings, and roof accessories.

2. Remove existing roofing system down to substrate.

3.7 DISPOSAL OF DEMOLISHED MATERIALS

A. Remove demolition waste materials from Project site and dispose of them in an EPA-approved construction and demolition waste landfill acceptable to authorities having jurisdiction.

1. Do not allow demolished materials to accumulate on-site.

2. Remove and transport debris in a manner that will prevent spillage on adjacent surfaces and areas.

3. Remove debris from elevated portions of building by chute, hoist, or other device that will convey debris to grade level in a controlled descent.

4. Comply with requirements specified in Section 017419 "Construction Waste Management and Disposal."

B. Burning: Do not burn demolished materials.

3.8 CLEANING

A. Clean adjacent structures and improvements of dust, dirt, and debris caused by selective demolition operations. Return adjacent areas to condition existing before selective demolition operations began.

SECTION 061000 - ROUGH CARPENTRY

1.1 SUMMARY

A. Section Includes:

1. Wood products.

2. Wood-preservative-treated lumber.

3. Fire-retardant-treated lumber.

4. Dimension lumber framing.

5. Miscellaneous lumber.

6. Plywood backing panels.

B. Related Requirements:

1. Section 061533 "Wood Patio Decking" for elevated decks, including support framing.

2. Section 061600 "Sheathing" for sheathing, subflooring, and underlayment.

3. Section 061753 "Shop-Fabricated Wood Trusses" for wood trusses made from dimension lumber.

4. Section 064013 "Exterior Architectural Woodwork" for exterior wood stairs and railings.

5. Section 064023 "Interior Architectural Woodwork" for interior wood stairs and railings.

6. Section 313116 "Termite Control" for site application of borate treatment to wood framing.

1.2 DEFINITIONS

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension.

B. Dimension Lumber: Lumber of 2 inches nominal size or greater but less than 5 inches nominal size in least dimension.

C. Exposed Framing: Framing not concealed by other construction.

D. Lumber grading agencies, and abbreviations used to reference them, include the following:

1. NeLMA: Northeastern Lumber Manufacturers' Association.

2. NLGA: National Lumber Grades Authority.

3. SPIB: The Southern Pine Inspection Bureau.

4. WCLIB: West Coast Lumber Inspection Bureau.

5. WWPA: Western Wood Products Association.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.

1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.

2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified independent testing agency.

3. For fire-retardant treatments, include physical properties of treated lumber both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency in accordance with ASTM D5664.

4. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.

1.4 INFORMATIONAL SUBMITTALS

A. Material Certificates:

1. For dimension lumber specified to comply with minimum allowable unit stresses. Indicate species and grade selected for each use and design values approved by the ALSC Board of

Review.

2. For preservative-treated wood products. Indicate type of preservative used and net amount of preservative retained.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Stack wood products flat with spacers beneath and between each bundle to provide air circulation.

Protect wood products from weather by covering with waterproof sheeting, securely anchored.

Provide for air circulation around stacks and under coverings.

PART 2 - PRODUCTS

2.1 WOOD PRODUCTS

B. Lumber: Comply with DOC PS 20 and applicable rules of grading agencies indicated. If no grading agency is indicated, comply with the applicable rules of any rules-writing agency certified by the ALSC Board of Review. Grade lumber by an agency certified by the ALSC Board of

Review to inspect and grade lumber under the rules indicated.

1. Factory mark each piece of lumber with grade stamp of grading agency.

2. For exposed lumber indicated to receive a stained or natural finish, mark grade stamp on end or back of each piece.

3. Where nominal sizes are indicated, provide actual sizes required by DOC PS 20 for moisture content specified. Where actual sizes are indicated, they are minimum dressed sizes for dry wood products.

4. Dress lumber, S4S, unless otherwise indicated.

C. Maximum Moisture Content:

1. Boards: 15 percent.

2. Dimension Lumber: 15 percent for 2-inch nominal thickness or less; no limit for more than

2-inch nominal thickness unless otherwise indicated.

2.2 WOOD-PRESERVATIVE-TREATED LUMBER

A. Preservative Treatment by Pressure Process: AWPA U1, Use categories as follows:

1. UC1: Interior construction not in contact with ground or subject to moisture. Include all rough carpentry.

a. Wood sills, sleepers, blocking, furring, and similar concealed members in contact with masonry or concrete.

b. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.

c. Wood floor plates that are installed over concrete slabs-on-grade.

d. Wood furniture.

e. Wood millwork.

2. UC2: Interior construction not in contact with ground but may be subject to moisture.

Include all rough carpentry.

a. Wood sills, sleepers, blocking, furring, and similar concealed members in contact with masonry or concrete.

b. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.

c. Wood floor plates that are installed over concrete slabs-on-grade.

d. Wood millwork.

e. Wood flooring.

3. UC3A (Commodity Specification A): Coated sawn products in exterior construction not in contact with ground but exposed to all weather cycles including intermittent wetting.

Include all rough carpentry.

a. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

b. Wood framing members that are less than 18 inches above the ground in crawlspaces or unexcavated areas.

c. Wood siding and trim.

4. UC3A (All Other Commodity Specifications): Coated products excluding sawn products in exterior construction not in contact with ground, exposed to all weather cycles but protected from liquid water. Include all rough carpentry.

a. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

b. Wood framing members that are less than 18 inches above the ground in crawlspaces or unexcavated areas.

c. Wood floor plates that are installed over concrete slabs-on-grade.

d. Wood siding and trim.

e. Wood sheathing.

5. UC3B (Commodity Specification A): Uncoated sawn products in exterior construction not in contact with ground, exposed to all weather cycles including intermittent wetting but with sufficient air circulation for wood to dry. Excludes sawn products not in contact with ground but with ground contact-type hazards. Include [all rough carpentry.]

a. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

b. Wood framing members that are less than 18 inches above the ground in crawlspaces or unexcavated areas.

c. Wood decking, railings, and joists and beams for decks that are not critical to the performance and safety of the entire system/construction and that are in locations easily accessible for maintenance, repair, or replacement.

6. UC3B (All Other Commodity Specifications): Uncoated products excluding sawn products in exterior construction not in contact with ground, exposed to all weather cycles including prolonged wetting. Include [all rough carpentry.]

a. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

b. Wood framing members that are less than 18 inches above the ground in crawlspaces or unexcavated areas.

7. UC4A (Commodity Specification A): Non-critical sawn products in contact with ground and exposed to all weather cycles including continuous or prolonged wetting, and sawn products not in contact with ground but with ground contact-type hazards or that are critical or hard to replace. Include [all rough carpentry.]

a. Wood framing members that are less than 6 inches above the ground.

b. Joists and beams when they are difficult to maintain, repair, or replace and are critical to the performance and safety of the entire system/construction.

8. UC4A (All Other Commodity Specifications): Non-critical products excluding sawn products in contact with ground and exposed to all weather cycles, normal exposure conditions. Include [all rough carpentry.]

9. UC4B (Commodity Specification A): Critical or difficult-to-replace sawn products in contact with ground and exposed to all weather cycles including continuous or prolonged wetting, high decay potential, and salt water splash. Include [all rough carpentry.]

a. Wood foundations.

10. UC4B (All Other Commodity Specifications): Critical or difficult-to-replace products excluding sawn products in contact with ground and exposed to all weather cycles including high decay potential and salt water splash. Include [all rough carpentry.]

11. UC4C (Commodity Specification A): Critical structural sawn products in contact with ground and exposed to all weather cycles including continuous or prolonged wetting, severe environments, and extreme decay potential. Include [all rough carpentry.]

a. Wood foundation piling.

12. UC4C (All Other Commodity Specifications): Critical structural products excluding sawn products in contact with ground and exposed to all weather cycles including severe environments and extreme decay potential. Include [all rough carpentry.]

a. Wood foundation piling.

13. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium.[ Do not use inorganic boron (SBX) for sill plates.]

14. For exposed items indicated to receive a stained or natural finish, chemical formulations are not to require incising, contain colorants, bleed through, or otherwise adversely affect finishes.

15. After treatment, redry [boards] to 19 percent maximum moisture content.

B. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Do not use material that is warped or that does not comply with requirements for untreated material.

C. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review.

1. For exposed lumber indicated to receive a stained or natural finish, [mark end or back of each piece]

D. Application: Treat [all rough carpentry unless otherwise indicated.]

1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

2. Wood sills, sleepers, blocking, [furring,] and similar concealed members in contact with masonry or concrete.

3. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.

4. Wood framing members that are less than 18 inches above the ground in crawlspaces or unexcavated areas.

5. Wood floor plates that are installed over concrete slabs-on-grade.

2.3 FIRE-RETARDANT-TREATED LUMBER

A. General: Where fire-retardant-treated materials are indicated, materials are to comply with requirements in this article, that are acceptable to authorities having jurisdiction, and with fire-test-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency.

B. Fire-Retardant-Treated Lumber and Plywood by Pressure Process: Products with a flame-spread index of 25 or less when tested in accordance with ASTM E84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet beyond the centerline of the burners at any time during the test.

1. Treatment is not to promote corrosion of metal fasteners.

2. Exterior Type: Treated materials are to comply with requirements specified above for fire-retardant-treated lumber and plywood by pressure process after being subjected to accelerated weathering in accordance with ASTM D2898. Use for exterior locations and where indicated.

3. Interior Type A: Treated materials are to have a moisture content of 28 percent or less when tested in accordance with ASTM D3201/D3201M at 92 percent relative humidity. Use where exterior type is not indicated.

4. Design Value Adjustment Factors: Treated lumber is to be tested according to

ASTM D5664 and design value adjustment factors are to be calculated according to

ASTM D6841.[ For enclosed roof framing, framing in attic spaces, and where high temperature fire-retardant treatment is indicated, provide material with adjustment factors of not less than 0.85 modulus of elasticity and 0.75 for extreme fiber in bending for Project's climatological zone.]

C. Kiln-dry lumber after treatment to maximum moisture content of 19 percent.[ Kiln-dry plywood after treatment to maximum moisture content of 15 percent.]

D. Identify fire-retardant-treated wood with appropriate classification marking of qualified testing agency and other information required by authorities having jurisdiction.

1. For exposed lumber indicated to receive a stained or natural finish, [mark end or back of each piece]

E. For exposed items indicated to receive a stained or natural finish, chemical formulations are not to bleed through, contain colorants, or otherwise adversely affect finishes.

F. Application: Treat [all rough carpentry unless otherwise indicated.]

1. Framing for raised platforms.

2. Framing for stages.

3. Concealed blocking.

4. Framing for non-load-bearing partitions.

5. Framing for non-load-bearing exterior walls.

6. Wood cants, nailers, curbs, equipment support bases, blocking, and similar members in connection with roofing.

7. Plywood backing panels.

2.4 DIMENSION LUMBER FRAMING

A. Non-Load-Bearing Interior Partitions by Grade: [Construction, Stud, or No. 3] grade.

1. Application: [Interior partitions not indicated as load bearing].

2. Species:

a. Hem-fir (north); NLGA.

b. Southern pine or mixed southern pine; SPIB.

c. Spruce-pine-fir; NLGA.

d. Hem-fir; WCLIB, or WWPA.

e. Spruce-pine-fir (south); NeLMA, WCLIB, or WWPA.

f. Northern species; NLGA.

g. Eastern softwoods; NeLMA.

h. Western woods; WCLIB or WWPA.

B. Load-Bearing Partitions by Grade: [Construction, Stud, or No. 3] grade.

1. Application: [Exterior walls] [and] [interior load-bearing partitions].

2. Species:

a. Hem-fir (north); NLGA.

b. Southern pine; SPIB.

c. Douglas fir-larch; WCLIB or WWPA.

d. Southern pine or mixed southern pine; SPIB.

e. Spruce-pine-fir; NLGA.

f. Douglas fir-south; WWPA.

g. Hem-fir; WCLIB or WWPA.

h. Douglas fir-larch (north); NLGA.

i. Spruce-pine-fir (south); NeLMA, WCLIB, or WWPA.

C. Machine Stress-Rated (MSR) Lumber Partitions: Any species of MSR dimension lumber with a grade of not less than [2100f-1.8E]

1. Application: [Exterior walls] [and] [interior load-bearing partitions].

D. Load-Bearing Partitions by Performance: Any species and grade with a modulus of elasticity of at least [1,100,000 psi] and an extreme fiber stress in bending of at least [700 psi] for 2-inch nominal thickness and 12-inch nominal width for single-member use.

1. Application: [Exterior walls] [and] [interior load-bearing partitions].

E. Ceiling Joists: [Standard, Stud, or No. 3] grade.

1. Species:

a. Hem-fir (north); NLGA.

b. Southern pine; SPIB.

c. Douglas fir-larch; WCLIB or WWPA.

d. Douglas fir-larch (north); NLGA.

e. Southern pine or mixed southern pine; SPIB.

f. Spruce-pine-fir; NLGA.

g. Hem-fir; WCLIB or WWPA.

h. Douglas fir-south; WWPA.

i. Spruce-pine-fir (south); NeLMA, WCLIB, or WWPA.

j. Northern species; NLGA.

k. Eastern softwoods; NeLMA.

l. Western woods; WCLIB or WWPA.

F. Joists, Rafters, and Other Framing by Grade: [Construction, Stud, or No. 3] grade.

1. Species:

a. Hem-fir (north); NLGA.

b. Southern pine; SPIB.

c. Douglas fir-larch; WCLIB or WWPA.

d. Southern pine or mixed southern pine; SPIB.

e. Spruce-pine-fir; NLGA.

f. Douglas fir-south; WWPA.

g. Hem-fir; WCLIB or WWPA.

h. Douglas fir-larch (north); NLGA.

i. Spruce-pine-fir (south); NeLMA, WCLIB, or WWPA.

G. Joists, Rafters, and Other Framing by Performance: Any species and grade with a modulus of elasticity of at least [1,100,000 psi] and an extreme fiber stress in bending of at least [700 psi] for

2-inch nominal thickness and 12-inch nominal width for single-member use.

H. Exposed Framing: Hand-select material[ indicated to receive a stained or natural finish] for uniformity of appearance and freedom from characteristics, on exposed surfaces and edges, that would impair finish appearance, including decay, honeycomb, knot-holes, shake, splits, torn grain, and wane.

1. Species and Grade:

a. As indicated above for load-bearing construction of same type.

b. Hem-fir (north); [No. 1] grade; NLGA.

c. Southern pine; [No. 1] grade; SPIB.

d. Douglas fir-larch; [No. 1] grade; WCLIB or WWPA.

e. Mixed southern pine; [No. 1] grade; SPIB.

f. Spruce-pine-fir; [No. 1] grade; NLGA.

g. Douglas fir-south; [No. 1] grade; WWPA.

h. Hem-fir; [No. 1] grade; WCLIB or WWPA.

i. Douglas fir-larch (north); [No. 1] grade; NLGA.

j. Spruce-pine-fir (south); [No. 1] grade; NeLMA, WCLIB, or WWPA.

k. Eastern hemlock-balsam fir or eastern hemlock-tamarack; [No. 1] grade; NeLMA.

l. Beech-birch-hickory; [No. 1] grade; NeLMA.

m. Northern red oak; [No. 1] grade; NeLMA.

n. Redwood; No. 1] grade; RIS.

o. Mixed oak; [No. 1] grade; NeLMA.

p. Mixed maple; [No. 1] grade; NeLMA.

q. Western cedars; [No. 1] grade; WCLIB or WWPA.

2.5 MISCELLANEOUS LUMBER

A. Provide miscellaneous lumber indicated and lumber for support or attachment of other construction, including the following:

1. Blocking.

2. Nailers.

3. Rooftop equipment bases and support curbs.

4. Cants.

5. Furring.

6. Grounds.

7. Utility shelving.

B. Dimension Lumber Items: [Construction or No. 2] [the following species:]

1. Hem-fir (north); NLGA.

2. Mixed southern pine or southern pine; SPIB.

3. Spruce-pine-fir; NLGA.

4. Hem-fir; WCLIB or WWPA.

5. Spruce-pine-fir (south); NeLMA, WCLIB, or WWPA.

6. Western woods; WCLIB or WWPA.

7. Northern species; NLGA.

8. Eastern softwoods; NeLMA.

C. Utility Shelving: Lumber with [15] percent maximum moisture content of [any of the following] species and grades:

1. Eastern white pine, Idaho white, lodgepole, ponderosa, or sugar pine; [Premium or

No. 2 Common (Sterling)] grade; NeLMA, NLGA, WCLIB, or WWPA.

2. Mixed southern pine or southern pine; No. [2] grade; SPIB.

3. Hem-fir or hem-fir (north); [Select Merchantable or No. 1 Common] grade; NLGA, WCLIB, or WWPA.

4. Spruce-pine-fir (south) or spruce-pine-fir; [Select Merchantable or No. 1 Common] grade; NeLMA, NLGA, WCLIB, or WWPA.

D. Concealed Boards: [19] percent maximum moisture content and [any of ]the following species and grades:

1. Mixed southern pine or southern pine; No. [2] grade; SPIB.

2. Hem-fir or hem-fir (north); [Construction or No. 2 Common] grade; NLGA, WCLIB, or

WWPA.

3. Spruce-pine-fir (south) or spruce-pine-fir; [Construction or No. 2 Common] grade;

NeLMA, NLGA, WCLIB, or WWPA.

4. Eastern softwoods; No. [2] Common grade; NeLMA.

5. Northern species; No. [2] Common grade; NLGA.

6. Western woods; [Construction or No. 2 Common] grade; WCLIB or WWPA.

E. Roofing Nailers: Structural- or No. 2-grade lumber or better; kiln-dried Douglas fir, southern pine, or wood having similar decay-resistant properties.

F. For blocking not used for attachment of other construction, Utility, Stud, or No. 3 grade lumber of any species may be used provided that it is cut and selected to eliminate defects that will interfere with its attachment and purpose.

G. For furring strips for installing plywood or hardboard paneling, select boards with no knots capable of producing bent-over nails and damage to paneling.

2.6 PLYWOOD BACKING PANELS

A. Equipment Backing Panels: Plywood, DOC PS 1, [fire-retardant treated,] in thickness indicated or, if not indicated, not less than [1/2-inch] nominal thickness.

2.7 FASTENERS

A. General: Fasteners are to be of size and type indicated and comply with requirements specified in this article for material and manufacture. Provide nails or screws, in sufficient length, to penetrate not less than 1-1/2 inches into wood substrate.

1. Where rough carpentry is exposed to weather, in ground contact, pressure-preservative treated, or in area of high relative humidity, provide fasteners[ with hot-dip zinc coating complying with ASTM A153/A153M or ASTM F2329]

2. For redwood, use [hot-dip galvanized-steel] fasteners.

B. Nails, Brads, and Staples: ASTM F1667.

C. Power-Driven Fasteners: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on ICC-ES AC70.

D. Post-Installed Anchors: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on [ICC-ES AC01] as appropriate for the substrate.

2.8 METAL FRAMING ANCHORS

B. Post Bases: Adjustable-socket type for bolting in place with standoff plate to raise post 1 inch above base and with 2-inch- minimum side cover, socket 0.062 inch thick, and standoff and adjustment plates 0.108 inch thick.

C. Joist Ties: Flat straps, with holes for fasteners, for tying joists together over supports.

1. Width: [3/4 inch]

2. Thickness: [0.050 inch]

3. Length: [As indicated].

D. Rafter Tie-Downs: Bent strap tie for fastening rafters or roof trusses to wall studs below, 1-1/2 inches wide by 0.050 inch thick.[ Tie fastens to side of rafter or truss, face of top plates, and side of stud below.]

E. Rafter Tie-Downs (Hurricane or Seismic Ties): Bent strap tie for fastening rafters or roof trusses to wall studs below, 2-1/4 inches wide by 0.062 inch thick. Tie fits over top of rafter or truss and fastens to both sides of rafter or truss, face of top plates, and side of stud below.

F. Floor-to-Floor Ties: Flat straps, with holes for fasteners, for tying upper floor wall studs to band joists and lower floor studs, 1-1/4 inches wide by 0.050 inch thick by 36 inches long.

G. Hold-Downs: Brackets for bolting to wall studs and securing to foundation walls with anchor bolts or to other hold-downs with threaded rods and designed with first of two bolts placed seven bolt diameters from reinforced base.

1. Bolt Diameter: [5/8 inch]

2. Width: [2-1/2 inches]

3. Body Thickness: [0.108 inch]

4. Base Reinforcement Thickness: [0.108 inch]

H. Wall Bracing:

1. T-shaped bracing made for letting into studs in saw kerf, 1-1/8 inches wide by 9/16 inch deep by 0.034 inch thick with hemmed edges.

2. Angle bracing made for letting into studs in saw kerf, 15/16 by 15/16 by 0.040 inch thick with hemmed edges.

I. Materials: Unless otherwise indicated, fabricate from the following materials:

1. Galvanized-Steel Sheet: Hot-dip, zinc-coated steel sheet complying with

ASTM A653/A653M, G60 coating designation.

a. Use for interior locations unless otherwise indicated.

2. Heavy-Galvanized-Steel Sheet: Hot-dip, zinc-coated steel sheet complying with

ASTM A653/A653M; structural steel (SS), high-strength low-alloy steel Type A (HSLAS

Type A), or high-strength low-alloy steel Type B (HSLAS Type B); G185 coating designation; and not less than 0.036 inch thick.

a. Use for wood-preservative-treated lumber and where indicated.

3. Stainless steel bars and shapes complying with ASTM A276/A276M, [Type 304]

a. Use for exterior locations and where indicated.

2.9 MISCELLANEOUS MATERIALS

A. Sill-Sealer Gaskets:

1. Glass-fiber-resilient insulation, fabricated in strip form, for use as a sill sealer; 1-inch nominal thickness, compressible to 1/32 inch; selected from manufacturer's standard widths to suit width of sill members indicated.

2. Closed-cell neoprene foam, 1/4 inch thick, selected from manufacturer's standard widths to suit width of sill members indicated.

3. Self-adhering sheet consisting of 64 mils of rubberized asphalt laminated on one side to a

4-mil- thick, polyethylene-film reinforcement, and with release liner on adhesive side[; formulated for application with primer or surface conditioner that complies with VOC limits of authorities having jurisdiction].

B. Flexible Flashing: Composite, self-adhesive, flashing product consisting of a pliable, [butyl rubber] [or] [rubberized-asphalt] compound, bonded to a high-density polyethylene film, aluminum foil, or spunbonded polyolefin to produce an overall thickness of not less than

0.025 inch.

C. Adhesives for Gluing Furring and Sleepers to Concrete or Masonry: Formulation complying with

ASTM D3498 that is approved for use indicated by adhesive manufacturer.

D. Water-Repellent Preservative: NWWDA-tested and -accepted formulation containing 3-iodo-2-propynyl butyl carbamate, combined with an insecticide containing chloropyrifos as its active ingredient.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Framing Standard: Comply with AF&PA's WCD 1, "Details for Conventional Wood Frame

Construction," unless otherwise indicated.

B. Set work to required levels and lines, with members plumb, true to line, cut, and fitted. Fit rough carpentry accurately to other construction. Locate [furring, ]nailers, blocking, [grounds, ]and similar supports to comply with requirements for attaching other construction.

C. Install plywood backing panels by fastening to studs; coordinate locations with utilities requiring backing panels.[ Install fire-retardant-treated plywood backing panels with classification marking of testing agency exposed to view.]

D. Install metal framing anchors to comply with manufacturer's written instructions. Install fasteners through each fastener hole.

E. Install sill sealer gasket to form continuous seal between sill plates and foundation walls.

F. Install sill sealer gasket/termite barrier in accordance with manufacturer's written instructions at the underside of wall bottom track or rim track and at the top of foundation wall or slab at stud or joist locations.

G. Do not splice structural members between supports unless otherwise indicated.

H. Provide blocking and framing as indicated and as required to support facing materials, fixtures, specialty items, and trim.

1. Provide metal clips for fastening gypsum board or lath at corners and intersections where framing or blocking does not provide a surface for fastening edges of panels. Space clips not more than 16 inches o.c.

I. Provide fire blocking in furred spaces, stud spaces, and other concealed cavities as indicated and as follows:

1. Fire block furred spaces of walls, at each floor level, at ceiling, and at not more than

96 inches o.c. with solid wood blocking or noncombustible materials accurately fitted to close furred spaces.

2. Fire block concealed spaces of wood-framed walls and partitions at each floor level, at ceiling line of top story, and at not more than 96 inches o.c. Where fire blocking is not inherent in framing system used, provide closely fitted solid wood blocks of same width as framing members and 2-inch nominal thickness.

3. Fire block concealed spaces between floor sleepers with same material as sleepers to limit concealed spaces to not more than 100 sq. ft. and to solidly fill space below partitions.

4. Fire block concealed spaces behind combustible cornices and exterior trim at not more than

20 feet o.c.

J. Sort and select lumber so that natural characteristics do not interfere with installation or with fastening other materials to lumber. Do not use materials with defects that interfere with function of member or pieces that are too small to use with minimum number of joints or optimum joint arrangement.

K. Comply with AWPA M4 for applying field treatment to cut surfaces of preservative-treated lumber.

1. Use inorganic boron for items that are continuously protected from liquid water.

2. Use copper naphthenate for items not continuously protected from liquid water.

L. Where wood-preservative-treated lumber is installed adjacent to metal decking, install continuous flexible flashing separator between wood and metal decking.

M. Securely attach rough carpentry work to substrate by anchoring and fastening as indicated, complying with the following:

1. Table 2304.10.1, "Fastening Schedule," in ICC's International Building Code (IBC).

2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two-

Family Dwellings.

3. ICC-ES evaluation report for fastener.

N. Securely attach roofing nailers to substrates by anchoring and fastening to withstand bending, shear, or other stresses imparted by Project wind loads and fastener-resistance loads as designed in accordance with ASCE/SEI 7.

O. Use steel common nails unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials.

Make tight connections between members. Install fasteners without splitting wood. Drive nails snug but do not countersink nail heads unless otherwise indicated.

3.2 INSTALLATION OF WOOD BLOCKING AND NAILERS

A. Install where indicated and where required for attaching other work. Form to shapes indicated and cut as required for true line and level of attached work. Coordinate locations with other work involved.

B. Attach wood blocking to substrates to support applied loading. Recess bolts and nuts flush with surfaces unless otherwise indicated.

C. Attach wood roofing nailers securely to substrate to resist the designed outward and upward wind loads indicated on Drawings and in accordance with ANSI/SPRI ED-1, Tables A6 and A7.

D. Provide permanent grounds of dressed, pressure-preservative-treated, key-beveled lumber not less than 1-1/2 inches wide and of thickness required to bring face of ground to exact thickness of finish material. Remove temporary grounds when no longer required.

3.3 INSTALLATION OF WOOD FURRING

A. Install level and plumb with closure strips at edges and openings. Shim with wood as required for tolerance of finish work.

B. Furring to Receive Plywood or Hardboard Paneling: Install 1-by-3-inch nominal- size furring

[horizontally] [and] [vertically] at [24 inches] o.c.

C. Furring to Receive Gypsum Board or Plaster Lath: Install 1-by-2-inch nominal- size furring vertically at [16 inches] o.c.

3.4 INSTALLATION OF WALL AND PARTITION FRAMING

A. General: Provide single bottom plate and double top plates using members of 2-inch nominal thickness whose widths equal that of studs, except single top plate may be used for non-load-bearing partitions[ and for load-bearing partitions where framing members bearing on partition are located directly over studs]. Fasten plates to supporting construction unless otherwise indicated.

1. For exterior walls, provide [2-by-6-inch nominal-] size wood studs spaced [16 inches] o.c. unless otherwise indicated.

2. For interior partitions and walls, provide [2-by-6-inch nominal size wood studs spaced

[16 inches] o.c. unless otherwise indicated.

3. Provide continuous horizontal blocking at midheight of partitions more than 96 inches high, using members of 2-inch nominal thickness and of same width as wall or partitions.

B. Construct corners and intersections with three or more studs[, except that two studs may be used for interior non-load-bearing partitions].

C. Frame openings with multiple studs and headers. Provide nailed header members of thickness equal to width of studs. Support headers on jamb studs.

1. For non-load-bearing partitions, provide double-jamb studs and headers not less than 4-inch nominal depth for openings 48 inches and less in width, 6-inch nominal depth for openings 48 to 72 inches in width, 8-inch nominal depth for openings 72 to 120 inches in width, and not less than 10-inch nominal depth for openings 10 to 12 feet in width.

2. For load-bearing walls, provide double-jamb…