Attachment_A.2.1_Work_Order_History.pdf

PDF 25 MB Posted

Attached to
Operations and Maintenance Support Services for the Eastern Regional Research Center
Solicitation number
1232SC18R0015
Issued by

About this file

Attachment A.2.1, Work Order History

View the file

Other files

File Type Posted
Sol_1232SC18R0015_Amd_0002.pdf PDF
PH_21_PWS.pdf PDF
Copy_of_Schedule_B_06112018.xls XLS spreadsheet
1232SC18R0015.pdf PDF
Attachment_A.2.2.2_Preventive_maintenance_schedule_in_the_existing_preve.._.pdf PDF
Craft_Codes.pdf PDF
PH_13_Questions_and_Answers.pdf PDF
1232SC18R0015_Amendment_01.pdf PDF
Attachment_A.7.1_Key_Request_Form.pdf PDF
Attachment_A.1.2_List_of_known_Confined_Spaces.pdf PDF
Attachment_A.7.3.4_Housekeeping_Matrix.pdf PDF
Attachment_A.7.3.4.2_schedule_of_flooring_surfaces.pdf PDF
Attachment_A.6.6.10_Special_Environmental_Rooms.pdf PDF
Attachment_A.2.2.1_Historically_maintained_equipment_and_preventative_ma....pdf PDF
Attachment_A.6.6.5_List_of_Pressure_vessels.pdf PDF
Safety_Manual_2012.pdf PDF
QASP.pdf PDF
Directory_of_Occupations.pdf PDF
Attachment_A.6.4_List_of_elevators_and_hoisting_devices.pdf PDF
Attachment_A.1.4.1_Government_Furnished_Services_via_contract.pdf PDF
Attachment_A.1.0_Maps_and_floor_plans_for_the_ERRC.PDF PDF
Attachment_A.2.4_Historical_Pricing_data.pdf PDF
PH_2,1_PWS.pdf PDF
Craft_Codes.pdf PDF
Schedule_B_06112018.xls XLS spreadsheet
PH_2,17_DBA_WD.pdf PDF
1232SC18R0015.pdf PDF
Attachment_A.7.3.1_ARS_45_Annual_Vehicle_Inspection_Checklist.pdf PDF
Attachment_A.3.3_Inventory_of_Government__owned_vehicles.pdf PDF
Attachment_A.1.1_Applicable_Codes,_regulations,_and_resources.pdf PDF
PH_2,17_CBA_WD.pdf PDF
PH_2,17_CBAa.pdf PDF
Attachment_A.3.2.2_REE_NEIS_PII_SHEET[1].pdf PDF
Attachment_A.4.1_Historically_Subcontracted_Work_(Contractor_Subcontract....pdf PDF
PH_2,17_SCA_WD.pdf PDF
Attachment_A.1.3_Available_Government_Property_and_Materials.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EQUIPMENT_NO EMPSYSID WO_TYPE ACT_TIME DESCRIPTION COMMENT

MB 0000 75 SC 0.16

THE DEHUMIDIFIER IN ROOM 0000 IS SOUNDING AN ALARM.

PROBABLY JUST THE USUAL SPRING STARTUP PROBLEM.

THANKS, BILL WILLIAM DAMERT, PHD 215-233-6616

WILLIAM.DAMERT@ARS.USDA.GOV EMPTIED TANK AND PLUGGED UNIT IN. SET TO 50% RH

MB 0213 74 SC 0

WE NEED SOME ASSISTANCE WITH GETTING SOME BOXES

FROM ERRC TO AMERICOLD IN HATFIELD PA. WE HAVE

APPROXIMATELY 60 16X16X16 BOXES TO BE MOVED FROM

0213.E TO: AMERICOLD 2525 BERGEY RD HATFIELD, PA

AMERICOLD IS ABLE TO RECEIVE SHIPMENTS DURING NORMAL

WORKING HOURS ALMOST ANY DAY OF THE WEEK, SO ONCE

WE FIND OUT THE AVAILABILITY OF THE DELIVERY COMPANY, I

CAN SCHEDULE A FIRM DELIVERY DATE. THANKS, BRAD

X6665

CLOSE AT THIS TIME WILL BE OPENED AGAIN WHEN

CUSTOMER IS READY

MB MAIN 74 SC 0

SEND ARC FLASH GLOVES TO BURLINGTON SAFETY LAB FOR

TESTING. THERE ARE 5 PAIRS TOTAL. DONE

MB 1110 67 SC 0.5

A PIECE OF EQUIPMENT WAS RECENTLY MOVED OUT OF LAB

1110. PLEASE CLEAN THIS PART OF THE FLOOR. MAY NEED TO

BE STRIPPED AND WAXED. COMPLETED THE AREA

MB 3116 65 SC 0.25

COULD YOU PLEASE PUT SOME MOUSE TRAPS IN OFFICE 3116,

ONE HAS JUST BEEN SPOTTED. THANK YOU, ANGELA COMPLETE - PUT DOWN TRAP

MB 1004 50 SC 0.5

HI MIKE, CAN YOU DISCONNECT MARJORIE MEDINA'S

NUMBER, HER PHONE IS STILL TAKING MESSAGES. 6436 IS HER

EXTENSION. THANKS, BARBARA HAWKINS P: 215.233.6611,

F: 215.233.6581 PHONE AND VOICEMAIL DELETED, LINE DEACTIVATED

MSB 60 SC 2

HELP STAGE BOXES ON THE 2ND FLOOR OF MSB FOR KAREN

AND LESLIE. ONCE STAGED HELP WITH THE PACKAGING OF

BOXES. SEE LESLIE FOR DETAILS.

4/18 PUSH CART WITH BOXES TPO MSB EXCESS CAGE. .5HRS,

4/24 1.5HRS PACK MOVE BOXES

MB 1208 87 SC 1.75

PLEASE MOVE THE ELECTROSPINNING INSTRUMENT TO THE

TABLE NEXT TO THE HOOD IN LAB 1208. THE

ELECTROSPINNING INSTRUMENT MUST BE PROPERLY

GROUNDED. THE TWO SHAKERS NEAR THE HOOD CAN BE

PLACED ON THE BENCH WHICH THE ELECTROSPINNING

INSTRUMENT WAS ORIGINALLY LOCATED. CONTACT LIN SHU

LIU EXT. 6486 AND ERIC TILMAN EXT. 3776 ABOUT THIS

REQUEST.

MOVED A PIECE OF EQUIPMENT FROM ONE PLACE TO

ANOTHER. ASISTED BY ALLEN MOORE. REPLACED OLD

GRPOUND WIRE FOR SAID EQUIPMENT WITH NEW GROUND

WIRE AFTER RELOCATING IT. USED 5 FEET OF #10 GROUND

WIRE. CUSTOMER SATISFIED AND WILL CONFIRM PROPER

OPERATION.

MB 1202 60 SC 0.25

PLEASE DISPOSE OF A CORNING STIRRING PLATE LOCATED IN

HALLWAY NEXT TO ROOM 1202. SCRAP. TAKEN TO METAL DUMPSTER

MB 2101 61 SC 0.5

HI, COULD SOMEONE HELP ME INSERT HOOKS FOR

ADDITIONAL SHELVES IN A REFRIGERATOR IN LAB 2101? I

DON'T HAVE THE TOOLS NEEDS TO DO THE JOB MYSELF.

THANKS, KIMBERLY SOKORAI PHONE: 215-233-6457 EMAIL:

KIMBERLY.SOKORAI@ARS.USDA.GOV

INSTALLED HOOKS SUPPLLIED BY CUSTOMER INTO LOCATIONS

IDENTIFIED

MB 2121 61 SC 1

THE RECENTLY MOVED FISHER ISOTEMP FREEZER IN ROOM

2121 NEEDS TO LEVELED IT'S ROCKING. THANK YOU.

TERENCE P. STROBAUGH, JR. 215-233-6455 LEVELED FREEZER BY ADJUSTING LEGS

305-BFPRV-002 50 SC 1 REPAIRS TO FEBCO BACKFLOW

ADVANCED CAME TO SITE AND REPAIRED FAULTY BACKFLOW

CHECK. OUTLET VALVE PASSES SO BACKFLOW COULD NOT BE

CHECKED PROPERLY.

HAZOP 59 SC 1.25 FILL LIQUID NITROGEN TANK BY TUESDAY THE 6TH

GROUNDS 61 SC 1.25

I NEED THREE SIGNS HUNG, ONE AT THE LOADING DOCK, ONE

ON THE VEHICLE GATE TO THE COURTYARD AND ONE BY THE

OVERHEAD DOORS AT THE PILOT PLANT. THEY ARE NO IDLING

SIGNS AS REQUIRED BY THE PADEP. THE SIGNS HAVE BEEN

ORDERED AND WILL BE DELIVERED ON THE 6TH OF MAY.

THANKS A MILLION. MARSHALL REED SAFETY &

OCCUPATIONAL HEALTH SPECIALIST OFFICE: 215-836-6932

CELL: 215-356-7223 MARSHALL.REED@ARS.USDA.GOV HUNGALL SIGNS IN DESIGNATED AREAS.

MB 2113 61 SC 0.5

THE MECHANISM FOR THE DOOR HANDLE TO 2113 IS BROKEN.

THE DOOR WILL NOT OPEN WHEN THE HANDLE IS PUSHED

DOWN. LORI

ELECTRIC STRIKE PUT ON BY OTHERS IS CAUSING PROBLEM.

KAREN AND TOM SEEN PROBLEM AND ARE CALLING CRI TO

RECTIFY

MB AW3 50 SC 0.5

TAKE DOWN THE SIGN HANGING FROM THE HALLWAY CEILING

OUTSIDE THE AUDITORIUM REMOVED AS REQUESTED

MB AW1 85 SC 2

HI, I THINK THE WATER FOUNTAIN IN FRONT OF THE CENTER

DIRECTORS OFFICE IS NOT DRAINING PROPERLY. THANKS.

KENDRA MCGUIGAN PHONE (215) 233-6692

KENDRA.MCGUIGAN@ARS.USDA.GOV COFFEE GROUNDS CLOGGED DRAI N

MB 3100 61 SC 1.25

THE SHELVES ATTACHED TO THE WALL CAME OFF IN OFFICE

3100.2, PLEASE COME BY AND FIX IT. THANKS, HELEN REATTACHED SHELF STANDARS WITH MOLLY BOLTS

MSB 61 SC 1

MAKE A KEY FOR KERBY JONES TO ACCESS THE EXCESS CAGE

AREA THIS IS FOR THE DOUBLE DOORS LEADING TO THE

WHOLE AREA

CUT KEY FOR KIRBY JONES. COLLECTED SIGNATURE,

COMPLETED PAPERWORK

MB MAIN 50 SC 0.5

REMOVE MARJORIE MEDINA'S NAME FROM HER OLD

TELEPHONE NUMBER WHICH I BELIEVE WAS 6436

PREVIOUSLY COMPLETED. WORK ORDER WAS PUT IN BY

ANOTHER PERSON

MB 2006 61 SC 4

PLEASE ARRANGE ROOM 2006 FOR CULTURAL DISPLAY BY

MAY 8, 8:00 AM. 1. MOVE FRAMES FROM AUDITORIUM TO

ROOM 2006. 2. ARRANGE LONG TABLES IN ROOM 2006 FOR

DISPLAY ARTIFACTS. 3. HANG PICTURES AND PAINTINGS ON

THE WALLS OF ROOM 2006 4. LOCK THE DOOR OF ROOM

2006 AT 10:00 AM 5. UNLOCK THE DOOR AT 12:00 AM 6.

MOVE FRAMES BACK TO AUDITORIUM AFTER 5:00 PM IF

YOU HAVE ANY QUESTION PLEASE CONTACT DR. MADHAV

YADAV (X3783) C.-K. LIU

SET UP AND BROKE DOWNITEMS USED FOR DISPLAY. HAD TO

MOVE CHAIRS IN ROOM TO ATTIC AND BACK DOWN AGAIN

MB 0100 60 SC 1

PLEASE REMOVE 1 LAPTOP AND 4 COMPUTERS TO SCRAP

PLEASE REMOVE 4 SWITCH BOXES TO EXCESS ALL ARE

LOCATED IN ROOM 0100 THANK YOU! TAKE TO SCRAP, SWITCH BOXES TO EXCESS CAGE

MB 0215 60 SC 0.5

PLEASE REMOVE FROM ROOM 0215 FOR SCRAP 1) VACUUM

PUMP 2)

MOISTURE ANALYZER TAKE TO SCRAP

MB 2100 60 SC 0.25

THERE IS AN OLD COMPUTER PRINTER WHICH IS SITTING

OUTSIDE RM. 2100. THIS PRINTER IS NO LONGER BEING USED

AND NEEDS TO BE EXCESSED. ANITA PARAMESWARAN XTN.

6563 ANITA.PARAMESWARAN@ARS.USDA.GOV TAKE TO SCRAP

MB CAF� 85 SC 0.5

PLEASE CHECK AND REMOVE AND REPLACE THE SILICONE

AROUND THE FAUCET IN THE CAFETERIA.

MB 0105 85 SC 1 CHECK FOR THE SOURCE OF ODOR IN ALBERTO'S AREA

DISINFECTED ALL DRAINS SURROUNDING AREA WITH

SPECTRUM HBV. CANT FIND CAUSE OF ODER. USED 1/2 GALL

OF SPECTRUM HBV

MB 1104 50 SC 1

I NEED A WORK ORDER TO REPAIR OVERHEAD LIGHTS IN ROOM

1104. DENNIS STEINBERG DAIRY AND FUNCTIONAL FOODS

RESEARCH UNIT 215-233-6498

DENNIS.STEINBERG@ARS.USDA.GOV

LAMPS REPLACED IN 3 FIXTURES PLUS 1 IN HALL. 13 F32CW

ECO

MB 0201 87 SC 0

WE'D LIKE TO HAVE SOMEONE SEE IF THEY CAN REPLACE THE

POWER CORD TO ONE OF OUR STIRRING HOTPLATES IN ROOM

0201. BRAD X6665 CANCELLED BY REQUESTER

MB 3113 61 SC 0.5

THE DOOR TO LAB 3113 IS NOT CLOSING PROPERLY. I AM NOT

SURE IF IT IS DUE TO THE INSTALLATION OF THE CARD READERS

OR AIR PRESSURE ISSUES. CAN SOMEONE PLEASE COME AND

TAKE A LOOK AT THE DOOR? THANK YOU! JANYSHA S.

TAYLOR, B.S, MLAS BIOLOGICAL SCIENCE LAB TECHNICIAN

OFFICE: 215-233-6419 ADJUSTED SPEED ON CLOSER

MB 0217 61 SC 0.75

PLEASE FIX DOOR IN CHALLENGE LAB THAT LEADS INTO THE

COURTYARD, IT DOES NOT LATCH PROPERLY. THANKS - CRIS-

OI5

REMOVED EXTRA WEATHER STRIPPNG. ALSO ADJUSTED CATCH

ON LEG OF DOOR FRAME

MB 3202 61 SC 0.75

FIX THE BASE PLATES ON THE MODULAR FURNITURE RIGHT

OUTSIDE 3202.1. THEY ARE FALLING OFF. THANKS

PUT BASE PLATES BACK TO ORIGINAL POSITION. ALSO

RECONNECTED END CAP

MB 1107 85 SC 0

GOOD AFTERNOON: WE WOULD LIKE TO HAVE AN

AUTOCLAVE INSTALLED IN ROOM 1107. THIS REQUEST IS TO

HAVE THE APPROPRIATE UTILITIES (PRIMARILY STEAM SUPPLY)

PUT INTO ROOM 1107. THERE APPEARS TO BE AN

APPROPRIATE FLOOR DRAIN ALREADY IN THE ROOM. THANK

YOU, GEORGE PAOLI CANCELLED

MB 1026 87 SC 0.5

GOOD AFTERNOON, LIGHT IN ROOM 1026 ABOVE MY DESK

JUST WENT OUT. THANK YOU, CONNIE A. FRANKLIN

PHONE: (215) 233-6604 EMAIL:

CONNIE.FRANKLIN@ARS.USDA.GOV BALLAST CHANGE, BALLAST #B3321UNVHP-A

MB AW3 85 SC 0.5 3RD FLOOR MENS ROOM TOILET IS LOOSE REPLACED NUTS & WASHERS ON BOTTOM OF TOILET

VSB 59 SF 2

REMOVE SALT AND HEAVY ITEMS FROM MEZZANINE. TAKE

DOWN ALL HEAVY ITEMS THAT EXCEED THE RATED WEIGHT

LIMIT. STORE SALT IN A DRY LOCATION OR COVER WITH

PLASTIC. MIKE O. 1 HR. LARRY 1 HR

MB 0124 66 SC 1.5

AFTER ITEMS ARE REMOVED FROM 0124 STRIP AND WAX

FLOOR AND COORDINATE WITH JONATHON MARTIN AT 6628

SB 57 SC 4.5

CLEAN AREA AROUND AIR COMPRESSORS. WIPE DOWN ALL

PARTS OF THE COMPRESSORS AND PIPING. CLEAN UNDER AND

BEHIND COMPRESSORS. SWEEP AND CLEAN FLOOR. PAY

ATTENTION TO CORNERS AND TIGHT AREAS.

MB 0000 53 SC 0.5

THE ALARM IS GOING OFF AGAIN ON THE DEHUMIDIFIER.

AGAIN THE PUMP IS NOT STARTING. PROBABLY JUST NEEDS

DRAINING. THANKS WILLIAM DAMERT, PHD 215-233-6616

WILLIAM.DAMERT@ARS.USDA.GOV NO PROBLEM. RESET AND CLOSED DOOR

HAZOP 50 SC 1.5

EXPOSED WIRING ON HAZOP 2ND FLOOR. THERE IS AN OPEN

JUNCTION BOX ON THE CEILING WITH EXPOSED WIRES. THERE

IS ALSOA SMALL WIRE ON BACK WALL THAT IS EXPOSED

(PHONELINE?) THERE MAY BE OTHER PROBLEMS. IDENTIFY

AND ADDRESS ALL ISSUES FOUND.

1 1900 BOX, 1 1900 BLANK, 1 4 ROUND BLANK, 2 3/4

LOCKNUTS, 8 YELLOW WIRENUTS. LB REMOVED & REPLACED

W/1900 & BLANK. WIRES SAFETIED, COVER INSTALLED ON BOX

MISSING COVER

VSB 87 SC 2

REPLACE FLOURESCENT LIGHT COVERS IN VSB. TWO LIGHT

FIXTURES ON THE MEZZANINE LEVEL HAVE UNPROTECTED

LAMPS THAT ARE BELOW 7 FEET CLEARANCE. LOCATE AND

REPLACE THE COVERS. CLEANED FIXTURES AND LENSES AND RWEPLACED COVERS

MB CAF� 85 SC 1

CLEAN THE FLOORS UNDER THE VENDING MACHINES AFTER

THEY ARE REMOVED AND PRIOR TO THE NEW MACHINES

BEING INSTALLED. THE TWO VENDING COMPANIES ARE

TRYING TO COORDINATE THE MOVE WITH THE MACHINES

BEING REMOVED AROUND 9AM AND THE NEW MACHINES

BEING INSTALLED AROUND NOON ON THURSDAY MAY 15

MB 0217 60 SC 2

HI KAREN-CAN YOU PLEASE HELP US BY MOVING THE KOCH

INJECTOR FROM THE CHALLENGE LAB TO THE MSB AND BY

MOVING THE SPRAY CABINET FROM THE MSB TO THE

CHALLENGE LAB? SEE BRAD FOR THE DETAILS. MANY THANKS -

JOHN FOR CRIS -015

TAKE LARGER ITEM TO 2ND FLOOR MSB FROM PATH. AND

REPLACE WITH PIECE FROM MSB

MB 2110 60 SC 0.25

HI, WE HAVE AN EXCESS INCUBATOR. IT IS LOCATED IN THE

HALL OUTSIDE OF LAB 2110. THANKS, BRYAN COTTRELL

X3751 ROOM 2112 TYAKE TO METAL DUMPSTER

MB 2110 60 SC 1

HI, WE NEED TO MOVE AN INCUBATOR THAT IS HEAVY FROM

ONE LAB BENCH TO ANOTHER IN LAB 2110. I REMEMBER IN

THE PAST THERE WAS AN ORANGE LIFT CART THAT WOULD BE

STURDY ENOUGH TO MOVE A HEAVY ITEM. WE ALSO HAVE A

ROLLING LAB TABLE THAT IS THE SAME HEIGHT AS THE LAB

BENCHES THAT MIGHT HELP WITH MOVING IT BUT LET US

KNOW IF YOU WANT TO USE THAT BECAUSE WE WILL HAVE TO

CLEAR THINGS OFF OF IT FIRST. THANKS, BRYAN

TAKE ORANGE JACKING TABLE TO LAB. MOVE HEAVY

INCUBATOR ACROSS LAB TO BACK BENCH

MB 1116 60 SC 0.25

HELLO, CAN WE HAVE SOMEONE DISPOSE OF AN OFFICE

CHAIR LOCATED IN THE HALLWAY OF 1116. IT HAS ALREADY

BEEN SIGNED OFF BY TOM NIEDERRITER. THANKS! LY X3759 SCRAP CHAIR IN METAL DUMPSTER

115-FANEX-017 87 UN 0

115-FANEX-017 87 UN 0

115-FANEX-017 87 UN 0

MB 1207 87 SC 0

REQUEST THE INSTALLATION OF A 6-20 RECEPTACLE IN ROOM

1207 UNDER WINDOW NEAR PC ON BENCH THANK YOU,

KENNETH TODD ROOM 3024 PH: 215-836-3771

WO CLOSED PER NEIL GOLDBERG. WORK BEING DONE ON

WORK ORDER #5363.

320-PMPSM-009 50 UN 0

804-ENVCB-006 53 SC 1.45 FAN BLADE BROKEN REPLACED BROKEN FAN BLADE ON COLD BOX #4

GROUNDS 59 SC 4

AT THE USDA MONUMENT AT THE ENTRANCE TO THE FRONT

CIRCLE, REMOVE THE BUSHES NEXT TO IT BACK AND FRONT,

SAVE THE TREE, PRESSURE WASH THE MONUMENT, AND

MULCH THE AREA. IF THE PLANTING PLAN CALLS FOR LOW

FLOWERS BEING PLANTED, THAT IS OK BEHIND THE

MONUMENT.

A.MOORE AND L.BYERS COMPLETED. REMOVED SHRUBS, CUT,

AND MULCHED BED. POWER WASHED THE MONUMENT

133-CHILR-002 54 SC 32

CLEAN CHILLER ROOM #3. WIPE DOWN ALL PARTS OF CHILLER,

PUMPS, AND PIPE THAT ARE ACCESSIBLE. CLEAN FLOOR

THOROUGHLY. SWEEP UNDER AND AROUND ALL EQUIPMENT.

PUT AWAY ANY ITEMS THAT ARE LAYING AROUND. CLEAN THE CHILLER NAD ALSO THE CHILLER PUMPS AND LINES.

126-PMPVS-001 56 SC 1

WIPE DOWN ALL PARTS OF VACUUM PUMPS, AND PIPE THAT

ARE ACCESSIBLE. CLEAN FLOOR THOROUGHLY. SWEEP UNDER

AND AROUND ALL EQUIPMENT. PUT AWAY ANY ITEMS THAT

ARE LAYING AROUND.

702-DRELC-013 50 SC 3

VSB ROLL-UP DOOR PROBLEM. BAY 5 DOOR HAS A BAD UP

LIMIT SWITCH

PO IN ON 5/13- /21 SWITCH REPLACED AND LIMITS RESET.

SUGGEST CABLES BE REPLACED. THEY ARE IN PRETTY BAD

SHAPE.

MB 0020 66 SC 1 CLEAN DARK SPOTS FROM CARPET IN ROOM 0020.

MB 0201 53 SC 1.25

WE HAVE AN INCUBATOR THAT FROZE UP SOMETIME IN THE

LAST FEW DAYS. IT IS THE BOTTOM INNOVA 44 UNIT IN ROOM

0201. IT IS SET AT 7C, AND THE DISPLAY HAS ALWAYS READ 7C

BUT WHEN I OPENED IT TODAY, THE INSIDE WAS ABOUT 15C

AND THE ENTIRE RIGHT INTERIOR WALL IS FROZEN OVER, EVEN

THOUGH IT READ 7C. I POWERED DOWN THE UNIT AND LEFT IT

OPEN TO DEFROST. BRAD X6665

INCUBATOR 808-INCUB-121. THE UNNIT WAS RUNNING FINE.

DID NOT FIND ANY PRIBLEMS. SOMEBODY DID NOT SHUT THE

DOOR ALL THE WAY.

MB AW2 61 SC 1.25

JANITORIAL CLOSET HAS NO LOCK CYLINDER. 2ND FLOOR NEAR

LADIES ROOM ADMIN HALLWAY. INSTALL CYLINDER

RETRIEVED 407 CYLINDER FROM STORAGE IN MSB. PLACED

CYLINDER IN DOOR.

MB 3111.3 61 SC 0.5 DRAWER LOCK STUCK IN THE CLOSED POSITION. ADJUSTED LOCKING ARM MECHANISM

VSB 59 SC 2

ORDER FILTERS AND LEVEL GAUGE FOR EQUIPMENT THIS IS

FOR THE ZERO TURN AND TRACTOR TIME INCLUDES GETTING THEM

MB 3008 61 SC 1.25

A PODIUM WAS RECEIVED IN SHIPPING/RECEIVING. IT NEEDS

TO BE UNCRATED AND PLACED IN THE FRONT OF CONFERENCE

ROOM 3008. I DON'T BELIEVE IT NEEDS ANY ASSEMBLY.

UNPACKED AND PUT 2 FINISH PANELS ON THE PODIUM.

MOVED TO ROOM 3008. CLEANED UP ALL TRASH FROM

PODIUM PACKAGING.

MB 0212 66 SC 0.08

THE TRASH IN 0212 IS OVERFLOWING AND NEEDS TO BE

PICKED UP TRASH WAS OVERFLOWING. REMOVED AND REPLACED BAG.

MB 2105 52 SC 0.5

OUR BIOHOOD HAS 4 GAS ACCESS PORTS THAT ARE NOT

NEEDED. CAN I HAVE THEM REMOVED AND THE HOLES

SEALED? NOTHING IS HOOKED UP TO ACTUAL GAS LINES. THE

HOOD IS IN LAB 2105. LET ME KNOW BEFORE YOU COME SO I

CAN DECON THE HOOD. THANKS, KIM

HOOD WAS DECONTAMINATED WHEN I GOT THERE.

REMOVED ALL 4 VALVES FROM HOOD.

MB 0008 61 SC 1

REMOVE MIAL DROP BOX FROM OUTSIDE OF THE MAILROOM

AND ATTACH TO THE WALL OUTSIDE OF THE PROJECT OFFICE.

REMOVED BOX FROM OLD AREA. TOOK DOWN BULLETIN

BOARD AND PUT IN DIFFERENT PLACE. THEN PUT MAILBOX IN

DESIGNATED AREA.

108-HNDLR-008 53 SC 1 MSB AHU-1 NEEDS NEW BELT. BX-45

MB 1219 50 SC 0.5

THERE IS A NEW INTERN THAT IS SITTING AT MIKE K.'S OLD

DESK. THERE IS A PHONE ALREADY THERE. PLEASE SET UP THE

PHONE (EXT IS 6451) FOR THE INTERN. NUMBER AND VM BLANKED AND REPROGRAMMED

MB 1CHW 60 SC 0.5

REMOVE SCRAP ITEMS- PLEASE REMOVE 9 SCRAP ITEMS.

PLEASE EXCESS BLACK TABLE THE ITEMS ARE RESTING ON.

EVERYTHING IS LOCATED IN THE HALL OUTSIDE OF 1122.

THERE ARE ALSO 3-4 BOXES MARKED AS TRASH FOR DISPOSAL.

THANK YOU. ROBYN MOTEN X6510, RM 1125 TAKEN TO THE SCRAP DUMPSTER

MSB 60 SC 1.5

LAB BENCH MOVED FROM MSB- I WOULD LIKE A LAB

TABLE/BENCH THAT IS CURRENTLY IN THE MSB DELIVERED TO

ROOM 1105. TOM NIEDERRITER PROVIDED THE ATTACHED

PHOTOGRAPH WHICH WAS TAKEN ON MAY 15. THANK YOU,

GEORGE PAOLI AL, THERE IS A REFRIGERATOR THAT WILL

HAVE TO BE MOVED TO MAKE ROOM FOR THIS TABLE. CHECK

WITH GEORGE BEFORE HAND.

MOVE REFRIGERATOR FROM 1123 TO HALL CLOSET 1107.

BROUGHT TABLE UP FROM MSB 2ND FLOOR TO 1105. MOVED

TABLE WITH EQUIPMENT FROM 1105 TO 1123.

MB 2105 61 SC 1.25

I HAVE A PLASTIC SHEET THAT I NEED CUT IN HALF AND AN 1

INCH HOLE PUT INTO ONE HALF. THE MATERIAL IS IN LAB 2105.

LET ME KNOW WHEN SOMEONE CAN LOOK AT IT AND I WILL

GET IT READY. THANKS, KIM

RETRIEVED PLASTIC FROM KIM. CUT AND DRILLED HOLE TO

HER SPECIFICATIONS. DELIVERED PLASTIC TO KIM.

MB 3116 50 SC 0.5

BREANNA TYRELL IS A NEW STUDENT SITTING AT ZAC

WILLIAMS OLD DESK. THE PHONE IS BLINKING RED. CAN YOU

PLEASE CLEAR THE MESSAGES FROM ZAC AND THEN SET UP

BREANNA WITH A NEW VOICEMAIL. PROGRAMMING CHANGES MADE AS REQUESTED

501-VHCLE-015 59 SC 1

PLEASE CHECK THE TIRE PRESSURE ON THE SILVER PICKUP.

DAVE DOUDS INDICATED THAT THE TIRE PRESSURE LIGHT IS ON

FOR A LOW TIRE MESSGAE. HE DID NOT BELIEVE THAT

ANYTHING WAS WRONG WITH THE VEHICLE AND NO TIRES

APPEAR TO BE FLAT. THE DRIVER'S SIDE REAR TIRE WAS LOW. ADDED AIR.

MB AUDITORIUM 50 SC 0.5

TELECONFERENCING PHONE SETUP- COULD YOU PLEASE SET

UP THE TELECONFERENCING PHONE IN THE AUDITORIUM FOR

A WEBINAR TO BEGIN AT 10:00 AM AND WILL RUN TIL 5:00 PM

THANKS BILL DAMERT WILLIAM DAMERT, PHD ERRC-ARS-

USDA 600 EAST MERMAID LANE WYNDMOOR, PA 19038 215-

233-6616 WILLIAM.DAMERT@ARS.USDA.GOV

MB 0201 61 SC 0.75

WE NEED ONE OF THE FIRE EXTINGUISHER CABINETS IN 0201

MOVED. NEAR THE DOOR FARTHEST FROM THE CAFETERIA WE

HAVE A FIRE EXTINGUISHER THAT IS SORT OF BLOCKED FROM

VIEW BY A LARGE INCUBATOR. IDEALLY, WE'D LIKE THE

CABINET MOVED CLOSER TO THE DOOR, UNDER THE

EMERGENCY STOP BUTTON. AS AN ASIDE, THE CONTRACTORS

INSTALLING THE NEW DOOR LOCKS SAID THAT IF THAT WAS

MOVED SOONER RATHER THAN LATER, IT WOULD MAKE THEIR

INSTALLATION MUCH EASIER, BUT I HAVE NO IDEA WHAT

THEIR TIME FRAME IS. I CAN SERVE AS A CONTACT FOR ANY

QUESTIONS ABOUT THIS PROJECT. BRAD X6665

PUT NEW EXTINGUISHER HANGER WHERE DESIGNATED BY

CUSTOMER. REHUNG EXTINGUISHER

MB 1025 50 SC 0.5

AUDIO PHONE SETUP- COULD I HAVE AN AUDIO PHONE SET

UP IN ROOM 1025 ON THURSDAY, 5/22 @10:30. THANKS.

JOANNE F. MURPHY PROGRAM SUPPORT ASSISTANT FOOD

SAFETY AND INTERVENTION TECHNOLOGIES UNIT UNITED

STATES DEPARTMENT OF AGRICULTURE EASTERN REGIONAL

RESEARCH CENTER 215 233-6582 OFFICE 215-233-6406 FAX

JOANNE.MURPHY@ARS.USDA.GOV

MB 3CHW 61 SC 1

PROVIDE/MAKE A KEY FOR THE HALL CLOSET OUTSIDE OF 3103

FOR KAREN WAGNER IN ORDER TO STORE SUPPLIES.

PROVIDED KEY TO KAREN WAGNER. HAS APPROPRIATE

PAPERWORK FILLED OUT

MB 0131 61 SC 0.5

ADJUST THE DOOR CLOSER TO THE BIO WASTE ROOM #0131.

DOOR DOESN'T CLOSE ALL THE WAY AT TIMES

ADJUSTED LATCH AND SWING SPEED ON DOOR. IT IS MY

THOUGHT THAT IF SLIDING DOORS ARE OPEN THIS DOOR WILL

NOT SHUT ALL OF THE WAY. ADDITIONAL TASK- SPRAYED

WD40 ON LATCH PLATE CONTACT POINTS TO ALLOW

SMOOTHER ACTION.

MB 3122 61 SC 2

THERE IS A LEAK IN 3122 THAT APPEARS TO BE COMING FROM

THE ROOF. CALLED OUT AS A TROUBLE CALL ON 5/16/14

PUT PLASTIC OVER LAN EQUIPMENT. IN CRAWL SPACE IN

ATTIC I PLACED BUCKETS TO CATCH DRIPPING. REMOVED

PLASTIC FROM LAB EQUIPMENT.

MB 2004 87 SC 0.5 REPLACE SWITCH PLATE AT ENTRANCE TO ROOM 2004 COMP

MB 2006 61 SC 0.5

EITHER THE DOOR CLOSER OR THE HINGES NEED LUBRICATION

AS THEY ARE VERY NOISY. OILED UP HINGES AND CLOSEER ARM PIVOT PIN.

CAMPUS 50 SC 7

COLLECT EQUIPMENT INFORMATION. DOCUMENT ANY AND

ALL INFORMATION ON EACH AIR COMPRESSOR ON SITE. PUT

ALL INFORMATION ON 4 X 8 NOTE CARD PROVIDED.

MANUFACTURER, MODEL, SIZE, DATE INSTALLED, MOTOR SIZE

POWER REQUIREMENTS, FRAME # AND HP. , FILTER SIZES &

QUANTITY. VOLTAGE, CONNECTED PIPING/TUBING/ LINE SIZES.

ANY AND ALL INFORMATION IS PERTINENT. COULD NOT FIND INFORMATION ON BOILER AIR COMPRESSOR

MB 2023 66 SC 0.5

STAIN ON CARPET- HELLO IN ROOM 2023-IN FRONT OF

BONNIE DISALVO'S CUBICLE-THERE IS A STAIN OF CHOCOLATE

SHAKE- I WIPED IT UP BUT STAIN NEEDS TO BE TREATED I

MARKED THE SPOT WITH TAPE BONNIE

133-CHILR-003 58 SC 6

CLEAN CHILLER ROOM #2. WIPE DOWN ALL PARTS OF CHILLER,

PUMPS, AND PIPE THAT ARE ACCESSIBLE. CLEAN FLOOR

THOROUGHLY. SWEEP UNDER AND AROUND ALL EQUIPMENT.

PUT AWAY ANY ITEMS THAT ARE LAYING AROUND.

WIPED DOWN #2 CHILLER, ALL PUMPS, AIR COMPRESSOR, AND

ALL ACCESSIBLE PIPING. SWEPT AND VACED FLAT SURFACES

AND FLOOR.

VSB 60 SC 2.5

GROUNDS EQUIPMENT CLEANING AND MAINTENANCE. CHECK

EQUIPMENT USED DURING THE WEEK FOR GROUNDS WORK.

ENSURE EQUIPMENT IS CLEANED AND LUBRICATED AS

NEEDED. TIGHTEN BELTS, NUTS AND BOLTS TO ENSURE SAFETY

OF EQUIPMENT AND PERSONNEL. SHARPEN BLADES, REPLACE

NUTS AND BOLTS FOUND MISSING. CLEANED EQUIPMENT AND GARAGE DAILY

MB 0124 60 SC 0.5

SCRAP EQUIPMENT- PLEASE REMOVE THE FOLLOWING

TAGGED ITEMS FROM THE CENTER BENCH IN LAB 0124: ONE

VACUUM PUMP WITH METAL PAN A SECOND VACUUM PUMP

A COLLECTION OF 4 PRESSURE REGULATORS FOR GAS

CYLINDERS THANKS YOU, DAVE DOUDS X6421

TOOK 2 PUMPS TO THE METAL DUMPSTER AND 4

REGULATORS TO THE EXCESS CAGE

MB 2113 60 SC 0.25

PLEASE REMOVE 2 SMALL PIECES OF EQUIPMENT OUTSIDE OF

ROOM 2113. TOOK TO THE METAL DUMPSTER

CAMPUS 85 SC 4

COLLECT AND DOCUMENT ALL AUTOCLAVE INFORMATION

AND RECORD IT ON 4 X 8 NOTE CARDS PROVIDED. RECORD

EQUIPMENT #, LOCATION, MANUFACTURER, POWER

REQUIREMENTS, ALL CONNECTED PIPING/TUBING/LINE SIZES.

INSTALLATION/MANUFACTERED DATE. ANY AND ALL

INFORMATION IS PERTINENT

CAMPUS 60 SC 17

WEEKLY GROUNDS WORK. CUT GRASS, TRIM, EDGE AS

REQUIRED. CLEAN UP AREAS AS NEEDED

5/20/14- MOWED AND TRIMMED FRONT CIRCLE, BLEW CURBS

AND SIDEWALKS 1.5 HRS MOWED 1ST ISLAND, 2ND ISLAND,

GAZEBO AREA, TRIMED, EDGED, BLEW 1.5 HRS MOWED VSB,

HAZOPS, TRIMMED, EDGED, AND BLEW 2 HRS 5/21/14-

MOWED SOUTH LAWN, TRIMMED, BLEW 2.5 HRS MOWED

HILL TO MSB ISLAND, TRIMMED- 1 HR MOWED NORTH LAWN,

TRIMMED, BLEW, EDGED- 3 HRS 5/22/14- MOWED LRB AND

MPL, TRIMMED, EDGED, BLEW- 2 HRS 5/23/14- MOWED

MSB, COOLING TOWER AREA, HAZOPS BEHIND GATE.

TRIMMED, EDGED, BLEW- 3.5 HRS

MB 0008 62 SC 0.5

BIND PLEASE OR THREE HOLE PUNCH AND PUT IN 2 BINDER.

THANKS - NO RUSH - BY NEXT FRIDAY IS FINE! COMPLETED AS REQUESTED

MB 0017 53 SC 0.5

REPLACE FILTER ON SMALL DAYTON SHOP VAC. VACUUM USED

FOR PM'S COMP

CAMPUS 59 SC 28

WEEKLY GROUNDS WORK. CUT GRASS, TRIM AND EDGE AS

REQUIRED. CLEAN UP AREAS AS NEEDED. CLEANING, MOWING, WEEDING, ETC

VSB 59 SC 35

GROUNDS EQUIPMENT CLEANING AND MAINTENANCE. CHECK

EQUIPMENT USED DURING THE WEEK FOR GROUNDS WORK.

ENSURE EQUIPMENT IS CLEANED AND LUBRICATED AS

NEEDED. TIGHTEN BELTS, NUTS AND BOLTS TO ENSURE SAFETY

OF EQUIPMENT AND PERSONNEL. SHARPEN BLADES, REPLACE

NUTS AND BOLTS FOUND MISSING. THIS INCLUDES CLEANING AND WORKING ON THE EQUIPMENT

CAMPUS 52 SC 16

COLLECT EQUIPMENT INFORMATION. DOCUMENT ANY AND

ALL INFORMATION ON EACH AIR HANDLER ON SITE. PUT ALL

INFORMATION ON 4 X 8 NOTE CARD PROVIDED.

MANUFACTURER, MODEL, SIZE, DATE INSTALLED, MOTOR

VOLTAGE, FRAME SIZE AND HP, FILTER SIZES & QUANTITY,

CONNECTED PIPE/TUBING/LINE SIZES. ANY AND ALL

INFORMATION IS PERTINENT.

MB 2104 50 SC 0.5

A NEW STUDENT WILL BE IN SUITE 2104 (FIRST RIGHT CORNER)

AND USE THE PHONE (215-836-6938). PLEASE CLEAN THE OLD

MESSAGE AND CLEAN THE PERSONAL CODE SETUP. THANKS.

TONY X6904 VOICEMAIL RESET FOR NEW USER AS REQUESTED

MB 3CHW 61 SC 1

CHANGE OUT THE CEILING TILE IN THE THIRD FLOOR

KITCHENETTE AREA. THIS LEAK IS EITHER FROM ATTIC OR PIPE.

IF POSSIBLE DETERMINE CAUSE - IF NOT JUST REPLACE.

KAREN

WENT TO THE ROOF TO INSPECT FOR LEAK. I BELIEVE THAT IS

WHER THE LEAK IS COMING FROM. SILICONED EXPANSION

JOINT AND CHANGED OUT 2 CEILING TILES. CLEANED UP

AREA.

MSB 61 SC 1

THE KNOB ON THE DOOR THAT LEADS INTO THE 2ND FLOOR OF

MSB IS COMING COMING. ITS THE KNOB ON THE DOOR THAT

FACES INSIDE OF THE HALL. ADJUSTED AND TIGHTENED KNOB ON DOOR HANDLE

GH 50 SC 0.5

PLEASE LOOK AT THE RADIO IN THE GUARD BOOTH.

ARHMAND HAS IDENTIFIED THAT THERE IS A PROBLEM.

COUND NOT FIND AN ISSUE WITH THE RADIO, BUT REPLACED

WITH A SPARE- WILL CONTINUE TO USE

MB BAHW 61 SC 1.5

MAKE UP AND HANG IN THE HALL OUTSIDE OF 0008 A

SUGGESTION BOX. PROVIDE 2 KEYS TO THE PROJECT OFFICE

FOR THE BOX. ONE TO LESLIE AND ONE TO KAREN.

PROVIDED BOX. DRILLED OUT SLOT FOR SUGGESTION SLIPS.

WROTE OUT PO FOR HASP. HUNG BOX ON WALL AND

ATTACHED HASP. USED A PADLOCK FROM STOCK.

CAMPUS 85 SC 3

COLLECT WATER FOUNTAIN INFORMATION AND DOCUMENT

FOR RECORDS. INSTALL DATE, ID NUMBER, MANUFACTURER,

MODEL, LOCATION, SUPPLY LINE SIZE, FILTER TYPE, MODEL #

AND LOCATION. ANY INFORMATION AVAILABLE IS NEEDED.

MB 2006 66 SC 0.5 SET UP METAL EASEL (NO BOARD) IN 2006 BY 11:00AM

MB AUDITORIUM 66 SC 0.5

SETUP FOR APANA VIDEO- TWO TABLES FOR REFRESHMENT

AND CHAIRS FOR THE VIDEO EXHIBIT ON MAY 28 (WED) FROM

12:00 NOON-1:30 PM.

MB AUDITORIUM 50 SC 0.25

SETUP FOR APANA VIDEO- VIDEO, AND AUDIO FOR THE VIDEO

EXHIBIT ON MAY 28 (WED) FROM 12:00 NOON-1:30 PM. REQUESTOR HAD SET UP VIDEO PRIOR TO MY ARIVAL

MB 1118 85 SC 0.75

THERE IS A SEWAGE SMELL IN LABS 1118/1122- CALLED OUT

AS A TROUBLE CALL ON 5/27/14 DISINFECTED ALL DRAINS IN THE LAB

MB 2002 50 SC 0.5

UNTANGLE THE WIRES TO THE PODIUM IN 2002 SIMILAR TO

HOW THE WIRES LOOK IN 2006.

MSB - CARPENTER

SHOP 61 SC 0.75 NEED MORE ARMSTRONG #770 CEILING TILE FOR STOCK

804-ENVCB-001 53 SC 1 EVAPORATOR FAN BLADE NEEDS TO BE CHANGED IN 0213 REPLACE FAN BROKEN BLADE

MB 3116 87 SC 0.25

THERE ARE LIGHTS OUT ABOVE A DESK IN 3116.1- CALLED OUT

AS A TROUBLE CALL ON 5/28/14 COMPLETED ON MONTHLY SUPPORT

804-ENVCB-015 53 SC 2.25

ORGANIZE CONTROLS ON 2121B & A BOXES PLEASE

DISCONNECT, REMOVE AND BLANK OFF CONTROLS THAT DO

NOT WORK PLEASE VERIFY THAT THE CHART AND THE

CONTROL REMAINING ARE IN SYNC PLEASE LABEL ALL

REMAINING CONTROLS CORRECTLY TO THE ASSOCIATED

ENVIRONMENTAL COLD BOX.

1. WALK IN BOX 2121A CIRCUIT BOARD NOT WORKING. HAS

TO BE REMVED FROM PANEL CONTROL BECAUSE IT WAS

BURNED. RELOCATED TEMPERATURE CONTROL FOR 2121A. 2.

FLOR WALK IN BOX 2121B- FIXED TEMPERATURE PROBE.

RELOCATED SNESOR INSIDE BOX BECAUSE IT WAS NOT

READING ACCURATELY.

MB 2124 85 SC 0.5

THERE IS A LEAK FROM AN OVERHEAD PIPE THAT IS LEAKING

ONTO THE FLOOR WHEN YOU IMMEDIATELY WALK INTO 2124-

CALLED OUT AS A TROUBLE CALL ON 5/28/14

PIPE WAS LEAKING AT SHUT OFF VAVLE. TIGHTENED PACKING

NUT AND STOPPED LEAK

MB 2AHW 53 SC 3.5

TAKE DOWN AIR VENTS IN BOTH ADMIN BATHROOMS ON 2ND

FLOOR (LADIES AND MEN S) AND CLEAN AND PAINT IF

NECESSARY.

ALL BATHROOMS ARE COMP. CLEANED THE DUCT WORK

EXHAUST AND PAINTED ALL VENTS ON EXHAUST.

HAZOP 54 SC 4

HAZOP BOILER FEED PUMP BINDING UP. THE PUMP IS

STICKING FRTOM DEBRIS AND CORROSION. REMOVE PUMP,

CLEAN IT OUT AND RE-INSTALL IT.

TOOK PUMP AND CLEANED ALL PARTS. REPLACED THE BAD

UNION ON DISCHARGE SIDE OF THE PUMP AND RE-INSTALLED

MB 0016 50 SC 0.25

REPLACE 2 BATTERIES FOR DEWALT SCREWGUN. BOTH

BATTERIES DEAD OR DYING COMP

MB 0213 52 SC 2 SWEEP AND WET MOP FLOOR IN 0213 (COLD BOX ROOM)

SWEPT, VACUUMED CORNERS, AND MOPPED THE FLOOR. THE

FLOOR NEEDS TO BE REPAINTED.

MB 0008 50 SC 0.5 EXTEND THE TECH SUPPORT ON THE EASY CLOCK SYSTEM SUPPORT IN EFFECT

MB CAF� 52 SC 0.5

CAFETERIA IS TOO HOT- CALLED OUT AS A TROUBLE CALL ON

5/28/14 TURNED UNITS FROM WINTER TO SUMMER

CAMPUS 85 SC 0.33 ORDER PM STICKERS FOR STOCK FOR ALL CRAFTS

MB 0000 52 SC 0.5

PLEASE CHECK THE DEHUMIDIFER IN THE PRINTER ROOM. IT

SOUNDS LIKE IT NEEDS TO BE EMPTIED. CALLED OUT AS A

TROUBLE CALL ON 5/29/14 EMPTIED THE DRAIN PAN AND RESET THE PUMP

GROUNDS 61 SC 0.75

PLEASE REMOVE THE DELIVERY SIGN THAT IS ON THE STOP

SIGN IN THE PARKING LOT BY THE GUARD BOOTH. IT IS THE

ONE WITH THE RED TAPE THAT IS PEELING AWAY. REMOVED SIGN ADN STORED IN MSB CARPENTERS SHOP

VSB 59 SC 4 TUNE UP ENGINE ON LITTLE WONDER EDGER

CAMPUS 59 SC 3

GROUNDS EQUIPMENT CLEANING AND MAINTENANCE. CHECK

EQUIPMENT USED FOR GROUNDS WORK DURING THE WEEK.

ENSURE EQUIPMENT IS CLEANED AND LUBRICATED AS

NEEDED. TIGHTEN BELTS, NUTS AND BOLTS TO ENSURE SAFETY

OF EQUIPMENT AND PERSONNEL. SHARPEN BLADES, REPLACE

MISSING HARDWARE.

HAZOP 59 SC 1

LIQUID NITROGEN FILL FOR HAZOPS FOR WEDNESDAY

MORNING- 5/28

CAMPUS 59 SC 26

WEEKLY GROUNDS WORK. CUT GRASS, TRIM, EDGE AS

REQUIRED. CLEN UP AS NECESSARY WEED, MOWING, CLEANING, FLOWER PLANTING, ETC

MB 1207 60 SC 1.5

EQUIPMENT MOVE- I HAVE AN OVEN THAT IS ON THE

SHIPPING AREA THAT NEED TO BE MOVED TO LAB 1207 JOHN

MULHERIN X6502

UNPACKED, TRASH PACKING. TAKEN TO SHIPPING FOR TAGS.

DELIVERED TO LAB. LIFTED ONTO WORK BENCH

CAMPUS 60 SC 2

GROUNDS EQUIPMENT CLEANING AND MAINTENANCE. CHECK

EQUIPMENT USED FOR GROUNDS WORK DURING THE WEEK.

ENSURE EQUIPMENT IS CLEANED AND LUBRICATED AS

NEEDED. TIGHTEN BELTS, NUTS AND BOLTS TO ENSURE SAFETY

OF EQUIPMENT AND PERSONNEL. SHARPEN BLADES, REPLACE

MISSING HARDWARE. 5/27- .5 HR 5/28- .5 HR 5/29- .5 HR 5/20- .5 HR

CAMPUS 60 SC 12

WEEKLY GROUNDS WORK. CUT GRASS, TRIM, EDGE, AS

REQUIRED. CLEAN UP AREAS AS NECESSARY

5/27- MOWED, TRIMMED, BLEW, EDGED FRONT CIRCLE- 3

HRS. MOWED COOLING TOWER AREA- 1 HR 5/28- MOWED,

TRIMMED, BLEW HAZPS AND SURROUNDING ISLANDS- 2 HRS

5/29- MOWED AL REMAINING ISLAND AND BLEW NAD

TRIMMED- 2.5 HRS. MOWED SOUTH LAWN, TRIMMED, AND

BLEW- 2.5 HRS MOWED ENTRANCE WAY, TRIMMED, AND

BLEW- 1 HR

CAMPUS 59 SC 2

LAWN SPRINKLER SYSTEM BACKFLOW BROKEN. IRRIGATION

SYSTEM AT FRONT OF BUILDING . CANOPY AND BONNET

CRACKED

MB 0022 53 SC 1.33

THERE SEEMS TO BE A LEAK COMING FROM THE AIR HANDLER

IN THE MAILROOM- PLEASE LOOK AT IT.

LEAK SEEMS TO BE COMING FROM THE AIR HANDLER.

INSPECTED AND FOUND THE PROBLEM ON TEH DRAIN PAN.

TINY LEAK DUE TO OLD SILICONE WAS REMOVED. FIXED THE

LEAK AND PAINTED THE TILE BECAUSE THERE WAS RUST.

MB 0127 61 SC 0.75

IN ROOM 0217, THE FIRST COLD BOX ON THE RIGHT HAS TWO

SHARP EDGES ON THE CORNER OF THE BOX. THESE NEED TO

BE FLATTENED.

BANGE MATERIAL BACK INTO SHAPE. PATCHED WITH METAL

TAPE

MB 3119 61 SC 2

CAN SOMEONE PLEASE CHECK THE LOCK ON THE FLAMMABLE

CABINET IN LAB 3119? WE CANNOT LOCK IT WITH THE KEYS

SINCE IT LOOKS LIKE THE HANDLE IS LOOSE.

TOOK CABINET DOOR APART TO GET TO HANDLE. TIGHTENED

HANDLE AND ALSO RETROFITTED LOCKING MECHANISM

GUIDE. PUT BACK TOGETHER.

HAZOP 60 SC 2

AT THE MAIN ENTRANCE OF THE HAZOPS BUILDING PLACE

SOME TYPE OF SCREENING ON THE CONDUIT ABOVE THE

DOOR TO KEEP THE BIRDS FROM SITTING THERE AND

DUMPING ON THE DOOR AND THRESHOLD. CLEAN THE DOOR

AND THRESHOLD WHEN THE SCREENING IS COMPLETE.

PRESSURE WASHED DOORS AND LANDING. USED A SCRUB

PAD NAD SUPPROX D. TOOK CHICKEN WIRE AND STRAPPED A

PILE OF IT ON TOP OF THE CONDUIT. SECURED WITH ZIP TIES

MB 3201 53 SC 1.25

THERE IS A STRONG SMELL IN LAB 3201/3203- CALLED OUT AS

A TROUBLE CALL ON 5/23/14

INPSECTED TO MAKE SURE THERE WAS NOT A SPILL OR ANY

CHEMICALS ON THE FLOOR INSIDE THE CABINETS. DID NOT

FIND ANY. CHECKED THE DRAIN TO THE EYE WASH. FLUSHED

FOR 10 MINUTES WITH WATER. BELIEVE THIS WAS THE

PROBLEM.

MB 3124 53 SC 1.16

NEED TO CHANGE THE DIAPHRAGM ON THE EXHAUST EVAV

DAMPER

CHANGED THE DIAPHRAGM ON THE EXHAUST EVAV DAMPER

AFTER FOUND TO BE BROKEN. USED TRANE VARIABLE

VOLUME UNIT THAT WE HAD I STOCK. ITEM # CS1329755

FROM CAPP USA

MB 2124 53 SC 1 NEED TO CHANGE THE DIAPHRAGM ON SUPPLY EVAV DAMPER

CHANGED DIAPHRAGM WITH ONE THAT WAS IN STOCK. CAPP

USE ITEM# CS1329755

MB COURTYARD 74 SC 0.5 MAY ODOMETER READINGS

CHECKED ALL ODOMETER READINGS AND RECORDED.

COUNTED DAYS USED. CHANGED THE INFORMATION ON 2

VEHICLES BECAUSE THE LP #S WERE SWITCHED AND PRINTED

UP NEW SHEETS. SENT THE INFORMATION TO MARCIA

HENSON AND GAVE A PAPER COPY TO KAREN CASEY.

MB PP2 58 SC 4

I AM REQUESTING HIGH PRESSURE STEAM SERVICE FOR THE

2ND FLOOR PLANT FOR 9AM TO 1 PM FOR TOMORROW

MB 2203 61 SC 0.5

WE NEED A CLOCK HUNG ON THE WALL IN 2203. THE CLOCK IS

SITTING NEAR SPOT WHERE IT SHOULD BE INSTALLED, WHICH

IS MARKED WITH A PIECE OF TAPE. HUNG CLOCK ON WALL W/ ANCHORS PROVIDED WITH ITEM

MB 2124 61 SC 1.5 PLEASE LOOK AT THE SHELVING UNIT IN LAB 2124

LOOKED AT SHELVES TRIED VARIOUS WAS OF INSTALLING.

KAREN NOW WORKING WITH CUSTOMER FOR RESOLUTION.

320-PMPSM-008 50 SC 9

SB BASEMENT SUMP PUMP #1 TRIPPED BREAKER. PULL PUMP

AND CLEAN DEBRIS FROM INSIDE. CHECK BEARINGS, CHECK

MOTOR.

6/3 4 HRS AND 6/4 5 HRS. PUMP REMOVED NAD BROKEN

DOWN. BUILD UP REMOVED AND PUMP REASSEMBLED AND

INSTALLED.

MB 0206 50 SC 3 REPLACE SEAL ON CONDENSATE PUMP

MSB 61 SC 1

REMOVE LOTO BOARD IN MSB OFFICE AREA. TRASH BOARD.

PUT LOCKOUT DEVICE IN A BOX FOR DISTRIBUTON LATER.

REMOVED LOTO BOARD NA DPUT CONTENTS IN A BOX. PUT

EVERYTHING IN THE CARPENTERS SHOP

MB PP2 66 SC 0.5

FOR TUESDAY PROGRAM I NEED 2 EASELS AND 1 BOARD PUT

IN THE SECOND FLOOR PILOT PLANT - REAR FOR THE DFFRU

PRESENTATION. PLEASE PROVIDE BY MONDAY AFTERNOON -

NO LATER THAN 2 PM. THANK YOU. BERNADETTE

USDA,ARS,NAA,ERRC DAIRY AND FUNCTIONAL FOODS

RESEARCH UNIT PROGRAM SUPPORT ASSISTANT BERNADETTE

DIANDREA 600 EAST MERMAID LANE ROOM 3032

WYNDMOOR, PA 19038-8598 PHONE (215) 233-6703 FAX

(215) 233-6795 BERNADETTE.DIANDREA@ARS.USDA.GOV

MB 3113 85 SC 0.5

CAN THE BATTERY IN THE LAB FAUCET BE CHANGED- CALLED

OUT AS A TROUBLE CALL ON 6/2/14

MB CAF� 85 SC 1

FIX LEAKING DRAIN ON SINK. ORDER NEW WASHERS FOR ALL

DRAINS FITTINGS THROUGH STEVE BRADY

MB PP3 65 SC 0.25

PLEASE SET UP AN EASEL AND SMALL TABLE IN THE 3RD

FLOOR BALCONY OF THE PILOT PLANT ON TUESDAY, JUNE 3, 9

AM TO NOON GEORGE ASSISTED

MB MAIN 85 SC 0.5 ORDER AA BATTERIES FOR STOCK

VSB 59 SC 1 ORDER HERBICIDES

VSB 59 SC 1 ORDER AND APPLY FERTILIZER FOR FLOWERS

MB 2208 85 SC 0.5

THERE IS A LEAK IN LAB 2208- CALLED OUT AS A TROUBLE CALL

AT THE END OF THE DAY ON 6/2/14

COULD NOT DETERMINE WHERE LEAK WAS COMING FROM.

THINK IT IS FROM THE ROOF

HAZOP 50 SC 1 SET UP PORTABLE AC UNIT IN LAB A OF HAZOPS

MB 1122 50 SC 1.5

I NEED TO HAVE REPLACEMENT BATTERIES INSTALLED IN AN

UNINTERRUPTABLE POWER SUPPLY (UPS) LOCATED IN LAB

1122. THEY RECEIVED THE REPLACEMENT BATTERIES ON MAY

30TH. BATTERIES REPLACED WITH USER SUPPLIED

MB 3CHW 61 SC 1

KEY NEEDED- I NEED KEY MADE FOR STORAGE CLOSETS

OUTSIDE LAB #3103 THAT ARE CONSISTENTLY RELOCKED

AFTER BEING UNLOCKED!

MADE KEY (RETRIEVED FROM STOCK). GOT SIGNATURES AND

GAVE KERBY KEY.

MB 3112 50 SC 0.5

COULD YOU PLEASE SET UP A PHONE FOR OUR SUMMER

STUDENT, ROBERT DOWNS? HIS EXTENSION WILL BE 6695 AND

HE IS LOCATED IN ROOM 3112. VOICEMAIL SETUP AS REQUIRED

MSB - HVAC SHOP 50 SC 0.5 PERFORM MAINTENANCE CHECK-UP ON PORTABLE AC UNIT COILS SPRAYED AND UNIT REWIPED DOWN

MB 0100 50 SC 0.75

PLEASE REMOVE THE PLASTIC SHIELD AND ASSOCIATED

HARDWARE ABOVE THE SERVERS IN ROOM 0100A (SERVER

ROOM).

REMOVED AS REQUESTED- 2 18 X8' PIECES OF PLEXIGLASS PUT

ON RACK IN CARPENTER SHOP

VSB 59 SC 3

REPLACE THROTTLE CABLE & STARTER ROPE ON STIHL FS85

TRIMMER

MSB 61 SC 0.75

TAKE DOWN THE SAFETY TOPICS BULLETIN BOARD THAT IS

NEXT TO THE TIME CLOCK ON THE FIRST FLOOR MSB. THIS IS

THE CORKBOARD STYLE BOARD. PLEASE THROW AWAY. REMOVED BOARD FROM WALL AND DISPOSED OF BOARD.

MB BCHW 61 SC 0.5

REPLACE THE TILE ABOVE THE EMERGENCY LIGHT THAT IS

STAINED. IT IS TO THE RIGHT OF ROOM 0117 IN THE

BASEMENT CHEMICAL WING HALLWAY RETRIEVED TILE FROM ATTIC NAD REPLACED STAINED TILE

MB STAIR #5 53 SC 0.5

THE HEATER IN THE BASEMENT IS STILL ON AND BLOWING HOT

AIR- CALLED OUT AS A TROUBLE CALL ON 6/3/14

THE HEATER ON THE BASEMENT WAS INSECTED AND BOTH

HEATING VALVE SUPPLIES AND RETURNED WERE CLOSED

MB BCHW 53 SC 2.17

TAKE DOWN THE VENT BY THE CW EMPLOYEE ENTRANCE (BY

RM 0129) IN THE CW HALLWAY. CLEAN AND PAINT THE VENT

ITSELF. BEFORE PUTTING BACK UP, DUST THE CEILING GRID

AND TILES FROM THE DOUBLE DOORS TO OUTSIDE OF 0127. CLEANED TILES NAD VENTS. PAINTED THE VENTS

CAMPUS 61 SC 3.5 COLLECT SQUARE FOOTAGE OF ALL HALLWAYS

MEASURED AND TOTALLED SQUARE FOOTAGE- BASEMENT:

PILOT- 866 SQ FT ADMIN- 2231 SQ FT CHEM- 25625 SQ FT

CAFE- 990 SQ FT TOTAL= 6649 SQ FT FIRST: PILOT- 2773 SQ

FT ADMIN- 1568 SQ FT CHEM- 2598 SQ FT TERACOTTA- 642

SQ FT TOTAL- 7581 SQ FT SECOND: PILOT- 818 SQ FT ADMIN-

1960 SQ FT CHEM- 2456 SQ FT TOTAL- 5234 SQ FT THIRD:

PILOT- 828 SQ FT ADMIN 1922 SQ FT CHEM- 2684 SQ FT

TOTAL- 5434 SQ FT

MB BCHW 53 SC 2

TAKE DOWN THE VENT BY 0107. CLEAN AND PAINT THE VENT.

BEFORE PUTTING BACK UP, DUST THE CEILING GRID AND TILES

FROM ROOM 0107 TO THE EXIT SIGN BY THE HALLWAY

LEADING TO THE COURTYARD. CLEANED TILES AND VENT

MB 1111.3 53 SC 2.25

THE AIR CONDITIONER IN 1111.3 IS NOT WORKING- CALLED

OUT AS A TROUBLE CALL ON 6/3/14

FOUND THE PROBLEM IN THE COOLING SIEMENS VALVE NOT

ENERGIZING. NEEDED A NEW VALVE. FLUSHED THE SYSTEM

SUPPLY AND RETURN LINE AND MADE SURE THERE WAS NO

AIR IN SYSTEM. CLEANED FAN COIL UNIT AND REMOVED ALL

DUST. ROOM TEMPERATURE AT 73 DEGREES F

MB PP2 54 SC 0.75

HIGH PRESSURE STEAM NEEDED FOR THE 2ND FLOOR PILOT

PLANT 9AM TO 600PM MONDAY , JUNE2 TILL FRIDAY , JUNE 6

PRESSURE RAISED DAILY AT 8:30AM AND DROPPED BACK TO

90 PSI AT 6PM

CAMPUS 50 SC 6 REPLACE DOOR SWITCH ON FRONT LOBBY ELEVATOR

5/2- 2 HR, 5/5 4 HR-- SWITCH REPLACED. WIRING TO

CONECTOR IS BAD- REWIRED FROM CONTROL TO LOWER

LOCK. NEEDED SEPARATE WORK ORDER IN FOR REWIRE

MB 3000 50 SC 0.75

RENOVATION TEMPORARY MOVE- DUE TO

RENOVATION/CONSTRUCTION WORK TO BE PERFORMED IN

ROOM 3004B, NEED NEW COMPUTER SET UP AND PRINTER

MOVED TO OFFICE 3000 TEMPORARILY UNTIL WORK IS

FINISHED.

MOVED PRINTER- MOVED/SWAPPED PHONE #S. PUT TEMP

FLOOR RACEWAY OVER CORDS

CAMPUS 59 SC 24

ORDER AND PLANT ANNUALS FOR THE FRONT OF THE MAIN

BUILDING

HAZOP 59 SC 1

FILL THE LIQUID NITROGEN FOR HAZOPS FOR THURSDAY

MORNING DONE ON ANOHTER WORK ORDER

VSB 59 SC 1 ORDER QUICK PRO

HAZOP 59 SC 1.5 FILL THE NITROGEN FOR HAZOPS FOR TOMORROW MORNING

CAMPUS 59 SC 2

CLEAN MARBLE PLANTING BED IN COURTYARD. PULL WEEDS

AND REPLACE/REPLENISH MARBLE STONE NEAR COURTYARD

RAMP

MB PP2 53 SC 0.5

THE METHANOL CHILLER ON THE 2ND FLOOR PILOT PLANT IS

FREEZING UP- CALLED OUT AS A TROUBLE CALL 6/5/14

INSPECTED AND FOUND PROBLEM ON THE VAPOR SIDE. IT

WAS ALL ICED UP.

MSB 61 SC 0.75

REMOVE THE 4 MONTH PLANNER WHITE BOARD IN THE BACK

OFFICE OF THE MSB OFFICE AREA. THROW AWAY. REMOVE

THE BULLETIN BOARD THAT IS IN THE FRONT MIDDLE OFFICE

ON THE PARTITION WALL THAT IS COMING DOWN. HOLD IN

YOUR SHOP (THIS IS GOING TO BE REHUNG SOMEWHERE

ELSE).

REMOVED ITEMS AND STORED IN DESIGNATED AREA IN

CARPENTER SHOP

MSB- PAINT SHOP 61 SC 3

PLEASE COMPLETE THE FOLLOWING THINGS IN THE PAINT

SHOP IN MSB: 1. PLEASE MOVE THE LARGE TRASHCAN THAT

IS IN FRONT OF THE FIRE EXTINGUISHER. 2. THROW AWAY THE

GATORADE CONTAINER AND ANY OTHER FOOD/DRINK

CONTAINERS. THEY SHOULD NOT BE IN THE ROOM. 3. CLEAN

THE FLOOR AND REPLACE THE 2 MISSING TILES. 4. FIX THE

SECOND FROM THE RIGHT OVERHEAD CABINET DOOR SO IT

CLOSES PROPERLY. 5. IF THEY ARE NOT BEING USED PLEASE

THROW AWAY THE 2 INDEX CARD FILES ON THE DESK. 6. IF

THEY ARE NOT BEING USED PLEASE SCRAP THE SHOPPING

CARTS FROM THE BACK ROOM 7. ORGANIZE THE WINDOW

SCREENS THAT ARE ON TOP OF THE FLAMMABLE CABINETS IN

THE BACK ROOM. MAKE SURE THEY ARE NOT HANGING OVER

THE EDGE OR AT A POTENTIAL TO FALL.

COMPLETED SAID DUTIES AND REPLACED FLOOR TILE WITH

ADHESIVE AND TILE FROM STOCK

MSB 60 SC 0.25

SCRAP THE COMPUTER IN THE OFFICE IN MSB. IT IS ALREADY

MARKED BY TOM. THE AG# IS 0545. TOOK TO ELECTRONIC SCRAP ON THE 2ND FLOOR MSB

MSB 60 SC 1

TRASH THE WOODEN DESK IN THE LEFT OFFICE ON THE FIRST

FLOOR MSB. IT HAS A GLASS TOP. PLEASE BE CAREFUL. I AM

NOT SURE IF THE GLASS IS ATTACHED OR NOT.

TOOK TO THE DUMPSTER. DISASSEMBLED TO FIT IN THE

DUMPSTER

MSB 60 SC 0.25

TRASH THE 3 BOXES TO THE LEFT OF THE DESK IN THE BACK

ROOM OF THE MSB OFFICE AREA. THEY ARE NEXT TO THE

DESK WITH THE SIEMENS COMPUTER ON IT. TAKEN TO THE TRAH DUMPSTER

MB 0008 60 SC 0.25

PLEASE TAKE THE BANKERS BOXES FROM 0008 AND 0019 AND

PLACE IN THE O&M CAGE ON THE 2ND FLOOR MSB. TAKEN TO MSB 2ND FLOOR NAD PUT IN CAGE

501-VHCLE-018 60 SC 0.5

SOMEONE SPILLED COFFEE ON THE CARPET OF THE PASSENGER

SIDE OF THE BLUE VAN IN THE FRONT SEAT. PLEASE CLEAN THE

CARPET, AS WELL AS VACUUM, AND THEN WIPE DOWN THE

INSIDE OF THE DOORS/CUP HOLDERS. PLEASE DUST THE

DASHBOARD. IF ADDITIONAL CLEANING TASKS ARE REQUIRED

PLEASE CLEAN THEM AND THEN WRITE AT THE BOTTOM OF

THE WORK ORDER THAT YOU COMPLETED THE TASKS.

VACUUMED. USED CARPET CLEANER FOR STAIN. WIPED

DOWN DASHBOARD

MB 1105 60 SC 1

NEW REFRIGERATOR MOVE- I JUST RECEIVED A NEW FRIDGE

FOR THE LAB. I WOULD LIKE TO PLACE A WORK ORDER TO

MOVE IT FROM SHIPPING AND RECEIVING TO LAB 1105. I WILL

BE OUT OF THE OFFICE STARTING TOMORROW AND

RETURNING ON TUESDAY, JUNE 10. IF THE FRIDGE GETS

MOVED DURING THIS TIME, PLEASE SEE YIPING HE (X6422) AS

THE CONTACT PERSON. BOTH OF US ARE IN OFFICE SUITE

1112/1116. UNPACKED, TAGGED, AND DELIVERED. TRASHED PACKAGING

MB 2CHW 60 SC 0.5

EXCESS LAB EQUIPMENT- WE HAVE SOME EXCESS LAB ITEMS.

THEY ARE LOCATED IN THE HALLWAY OUTSIDE LAB 2110. THEY

WERE ALL IN LONG TERM STORAGE IN THE HALLWAY CLOSET.

THANKS, BRYAN COTTRELL (X3751) OFFICE 2112 SCRAP IN DUMPSTER

MB 2110 60 SC 1.5

LAB EQUIPMENT MOVE- WE HAVE A NEW EPPENDORF -80C

FREEZER THAT NEEDS TO BE MOVED TO LAB 2110. IT IS

CURRENTLY LOCATED NEAR THE FREIGHT ELEVATOR. IT IS

UNDER DR. CHIN-YI CHEN'S NAME. UNPACKED FREEZER. GET TAGS. DELIVERED TO ROOM 2110.

MB 1104 60 SC 1

REMOVE A REFRIGERATOR FROM ROOM 1104. THIS

REFRIGERATOR WILL BE SCRAPPED. DENNIS STEINBERG

DAIRY AND FUNCTIONAL FOODS RESEARCH UNIT USDA-ARS-

NAA-ERRC 600 E. MERMAID LANE WYNDMOOR, PA 19038

215-233-6498 DENNIS.STEINBERG@ARS.USDA.GOV

REMOVE FROM LAB AND TAKE TO HVAC SHOP FOR FREON

REMOVAL.

MB 3125 60 SC 0.25

PLEASE REMOVE 2 EXCESS COMPUTERS FROM 3125. THEY

BOTH HAVE EXCESS PROPERTY TAGS. TAKEN TO SCRAP ON THE 2ND FLOOR OF MSB

HAZOP 61 SC 4

LOFT ACCESS DOORS IN HAZOP SECOND FLOOR DAMAGED.

THE DOORS ARE HANGING LOOSELY AND ONE HAS A

SLIDELOCK THAT IS COMING OFF. THE DOORS APPEAR TO BE

SAGGING AND MAY NEED TO BE SUPPORTED OR REPLACED.

WENT TO STORE FOR PLYWOOD. DEMOLISHED AND THREW

AWAY OLD LOFT DOORS. REPLACED WITH PLYWOOD

(TREATED) AND A 2' X 2' LOUVER FROM STOCK

109-BOILR-004 54 SC 0.5

REPLACE BATTERY ON WATER LEVEL CONTROLLER #4 BLR.

BATTERY MONITOR INDICATES REPLACEMENT IS DUE

SB 54 SC 1

AFTER THE FLOOR CLEANING IS COMPLETED PLEASE USE SPRAY

PAINT (PROVIDED) AND SPRAY THE CRACKS AROUND BOILER

#4 AS DISCUSSED TO SHOW POTENTIAL TRIPPING HAZARDS. PUT BLACK AND YELLOW TAPE DOWN AROUND #4 BOILER

106-SUPFAN-001 52 SC 2

MAINTENANCE NEEDED ON SUPPLY FAN 7. FILTERS NEED TO BE

REPLACED, REPAIR CHICKEN WIRE ON INTAKE SCREEN AND

REMOVE LEAVES

REPAIRED CHICKEN WIRE, REMOVED LEAVES, AND REPLACED

FILTERS

MSB - PIPE SHOP 85 SC 3

CLEAN UP BIG PIPE THREADING MACHINE IN SHOP. GET THE

TRASH AND METAL SHAVINGS OUT OF THE INSIDE. WIPE

DOWN FROM TOP TO BOTTOM AND CLEAN WITH

CLEANER/DEGREASER.

MB BCHW 53 SC 4

PLEASE CLEAN AND PAINT IF NEEDED THE AIR VENTS OUTSIDE

OF 0121 AND 0101 IN HTE CHEMICAL WING BASEMENT

HALLWAY.

REMOVED SUPPLY VENT, CLEANED TILES, CLEANED VENTS,

AND PAINTED.

MB 3119 61 SC 1.5 LAB 3119 FLAMMABLE CABINET STILL CANNOT BE LOCKED

CABINET WAS CLOSED WITH TAB IN LOCKED POSITION.

HANDLE DOES NOT OPERATE PROPERLY. TALKED TO CUSTMER

ON HOW TO LOCK DOOR. LOOKED FOR CABINET IN STOCK.

MB 3CHW 61 SC 1

PLEASE MAKE A KEY FOR A STORAGE CLOSET ON THE 3RD

FLOOR CHEMICAL WING WHERE SUPPLIES ARE STORED

RETRIEVED KEY FROM SOTCK. GOT APPROPRIATE SIGNATURES.

DELIVERED KEY TO CUSTOMER.

MB 2110 87 SC 0.5

CHECKING VOLTAGE- COULD WE FIND OUT IF THE VOLTAGE IN

OUR LAB WILL MATCH THE REQUIRED VOLTAGE FOR THE OUR

NEW FREEZER? THE NEW FREEZER IS - 115V 16.5AMPS 60

HZ ARE OUR OUTLETS OK FOR A 115 VOLT APPLIANCE.

THANKS, BRYAN (X3751) LAB 2110 OFFICE 2112

VERIFIED CIRCUITS TO BE ENERGIZED AND SPOKE WITH BRYAN

CONCERNING VOLTAGES NAD CIRCUITS. CUSTOMER

SATISFIED.

VSB 59 SC 2 REPLACE BLADES ON ZERO TURN MOWER

MB AUDITORIUM 67 SC 0.5

AUDITORIUM SETUP - PLEASE SETUP THE AUDITORIUM AS PER

THE DRAWING GIVEN. GREG JONES HELPED

MB AUDITORIUM 50 SC 0.5

PLEASE SETUP A HANDHELD CORDLESS MICROPHONE FOR AN

EVENT TOMORROW STARTING AT 11:00AM.

MB 0016 50 SC 0.5

ORDER CONSUMMABLE FOR STOCK WHICH INCLUDES FILTERS

AND BAGS FOR SHOP VAC AND ANTI-SEIZE COMPOUND - BAGS

AND FILTERS FROM HOME DEPOT ANTI-SEIZE STILL NEEDED

MB 0008 50 SC 0.5

CLEAN THE COPIER/SCANNER AT LESLIE'S DESK. IT HAS THE

LINES WHEN THEIR ARE SCANS. I CAN NOT FIGURE OUT HOW

TO CLEAN IT SCANNER PLATE CLEANED

MB 3105 61 SC 0.5

HANG PLASTIC DISPENSER FOR GLOVE BOX- I BOUGHT A

PLASTIC DISPENSER THAT HOLDS 3 BOXES OF DISPOSABLE

GLOVES. IT IS SITTING ON A CART INSIDE DOOR TO LAB 3105.

WOULD LIKE IT HUNG ON INSIDE OF DOOR CLOSEST TO

EYEWASH, ORIENTED SO GLOVE BOXES ARE INSERTED INTO

TOP OF DISPENSER. QUESTIONS, SEE KAREN WAGNER IN 3104,

X6518. THANKS! HUNG GLOVE BOX IN SPECIFIED AREA

MB PP2 87 SC 0.25

THE CLOCK ON THE 2ND FLOOR PILOT PLANT OVER THE DESKS

IN THE BACK (ACTUALLY LOCATED ON THE 3RD FLOOR

OVERHANG) IS NOT WORKING. PLEASE CHECK THE BATTERIES

AND REPLACE IF NEEDED. REPLACE WITH A NEW BATTERY

MB 0111.2 61 SC 0.75

THE DOOR KNOB ON THE INSIDE OF THE JANITORIAL CLOSET IS

COMING OFF. PLEASE FIX.

REPLACED SCREWS WITH SOME FROM STOCK. ADJ DOOR

KNOB LENGTH

HAZOP 59 SC 1.25

LIQUID NITROGEN FILL- FILL LIQUID NITROGEN TANK AT HAZ-

OP FOR WEDNESDAY MORNING, 6/11

MB SECOND 67 SC 0.25

SWEEP/VACUUM THE FLOOR GRATES BY THE FIRE DOORS IN

ADMIN WING ON BOTH SIDES LEADING INTO THE CHEMICAL

WING AND PILOT WING

MB THIRD 65 SC 0.25

SWEEP/VACUUM THE FLOOR GRATES BY THE FIRE DOORS IN

ADMIN WING ON BOTH SIDES LEADING INTO THE CHEMICAL

WING AND PILOT WING DID THIS WED /11 AS PER MY SCHEDULE

MB 3CHW 65 SC 0.25

DUST THE TABLE THAT THE COPIER IS ON IN THE FIRE TOWER

AREA

MB 0017 61 SC 2.5

BACK OF 0017 CLEANUP/ORGANIZATION PROJECT- 1.

THROW AWAY ANY ITEMS THAT ARE OLD/OF NO USE 2.

REMOVE ITEMS THAT ARE NOT USED IN THE MAIN BUILDING

AND STORE IN THE CARPENTER SHOP IN MSB 3. TAKE THE

SIGNS THAT ARE IN THE CABINET DOWN TO THE CARPENTER

SHOP AND STORE 4. ORGANIZE THE REMAINING ITEMS ON

THE SHELF IN THE BACK ROOM

STRAIGHTENED OUT, CLEANED, THREW AWAY, AND STORED

ITEMS FROM ROOM

MB 0008 61 SC 1.5 REPAIR WALL ABOVE LESLIES DESK

REMVED VELCRO. SPACKLED AND SANDED WALL. PAINTED

SPOTS AS NEEDED.

MB BCHW 61 SC 1

KEYS FOR HALL STORAGE CLOSET- COULD I GET 4 KEYS FOR THE

SINGLE DOOR STORAGE CLOSET TO THE RIGHT OF ROOM 0117

(FOR ME, ALBERTO, DAVID & GARY) A CURRENT KEY HAS R517

STAMPED ON IT.

RETRIEVED KEYS FROM STOCK. TALKED TO TOME ABOUT KEYS

OPENING OTHER PEOPLES CLOSETS. HE SAID THAT YOU

CANNOT POLICE EVERYTHING

112-LIEBERT-002 52 SC 2.5

LIEBERT UNIT IS DRIPPING WATER ONTO THE GYM EQUIP-

CALLED OUT AS A TROUBLE CALL 6/12/14

THE AC UNIT WAS TURNED OFF AT THE DISCONNECT SO THE

CONDENSATE PUMP CANT WORK. I CLEANED THE PAN AND

STARTED THE AC UNIT. REPLACED TILE AND CLEANED UP

WATER.

MB 2107 52 SC 2

LEAK FROM REFRIGERATOR- WE HAD A LEAK FROM A

REFRIGERATOR IN LAB 2107 LATE YESTERDAY (DOUBLE DOOR

REFRIGERATOR). MARSHALL SAW IT, TY CLEANED IT UP BUT I

WAS HOPING SOMEONE COULD LOOK AT THE REFRIGERATOR

TO SEE IF THERE IS SOMETHING WRONG WITH IT OR IF

SOMEONE JUST LEFT THE DOOR OPEN TO CAUSE THE WATER.

THE DRIP PAN WAS BROKEN OFF OF THE BOTTOM OF THE

REFRIGERATOR AND THE HEATING ELEMENT NEEDED REPAIR.

BOTH ARE FIXED AT THIS TIME.

CAMPUS 85 SC 0.5 NEED BELL AND GOSSET PUMP OIL FOR PMS.

MB MAIN 85 SC 0.33

TEST THE EYE WASH STATION (ONLY) IN THE SHIPPING AND

RECEVING AREA AND THE JANITORIAL CLOSET. REINSTALLED PULL HANDLE FOR SHOWER CORRECTLY

MB 3PHW 61 SC 0.5

REPLACE STAINED CEILING TILE IN THE PW HALLWAY OUTSIDE

OF 3200C.4 CLOSET

REPLACED STAINED CEILING TILE. THREW AWA DAMAGED

TILE.

MB 1AHW 61 SC 0.5

PLEASE GREASE THE TRASHCAN LID IN THE LADIES ROOM

ADMIN WING SO THAT IT STOPS SQUEAKING GREASED PIVOTING PIN ON TRASHCAN

VSB 61 SC 0.5

FIX DOWNSPOUT- AT THE NW CORNER OF THE VSB, THE

DOWNSPOUT NEEDS REPAIR TO DRAIN ON THE SPLASH BLOCK PUT A SCREW IN DOWN SPOUT TO HOLD IN PLACE

MB 0008 50 SC 2.5

LOOK AT BROTHER PRINTER IN 0008 AND ALSO CONNECT

KONICA TO NETWORK. 1) BROTHER PRINTER HAS PRINT

QUALITY WITH LARGE BLACK BAND ON END OF PAPER 2) WILL

NOT SCAN THRU THE ADF 3) IF HELP IS NEEDED GETTING

ACCESS CODE FOR KONICA - KAREN WILL CALL OFFICE

CONCEPTS TO SEE IF WE CAN BREAK THE CODE.

5/27- .5 BROTHER SCANNER PROBLEM RESOLVED- DRUM

REPLACED 6/-11 2 HR N SCANNER- UNABLE TO GET WORKING

6/13- CLOSE- OFFICE CONCEPTS WORKING ON SCANNER

MB AUDITORIUM 66 SC 0.75

WE WILL BE HOLDING A CONFERENCE IN THE AUDITORIUM ON

JUNE 16TH, 2014 AT 1 PM. WE WOULD APPRECIATE THE ROOM

BE SET UP IN A U CONFIGURATION WITH THREE TABLES ON

EACH SIDE AND TWO ACROSS THE BACK, 30 CHAIRS.

AUDITORIUM SHOULD BE PARTITIONED. THIS WILL RUN UNTIL

COB. THANKS. MARSHALL REED SAFETY & OCCUPATIONAL

HEALTH SPECIALIST USDA, ARS, EASTERN REGIONAL RESEARCH

CENTER 600 EAST MERMAID LANE WYNDMOOR, PA 19038

OFFICE: 215-836-6932 CELL: 215-356-7223 FAX: 215-233-

6720 MARSHALL.REED@ARS.USDA.GOV

MB BASEMENT 66 SC 0.25

SWEEP/VACUUM THE FLOOR GRATES BY THE FIRE DOORS IN

ADMIN WING ON BOTH SIDES LEADING INTO THE CHEMICAL

WING AND PILOT WING

MB BCHW 66 SC 0.75

CLOSET FOR CLEANING- HELLO. COULD THE CLOSET FLOOR TO

THE RIGHT OF ROOM 0117 PLEASE BE CLEANED. WE'RE GOING

TO BE USING IT FOR STORAGE.

MB FIRST 66 SC 0.25

SWEEP/VACUUM THE FLOOR GRATES BY THE FIRE DOORS IN

ADMIN WING ON BOTH SIDES LEADING INTO THE CHEMICAL

WING AND PILOT WING

MB 3028 60 SC 0.25

SCRAP PICKUP- COULD WE GET A SCRAP PRINTER PICKED UP

AND THROWN OUT? IT HAS BEEN LABELED AS SCRAP" BY TOM

NIEDERITTER AND IS IN THE HALLWAY OUTSIDE OFFICE SUITE

3028." TAKEN TO SCRAP

501-VHCLE-015 60 SC 0.5

PLEASE CLEAN THE INSIDE OF THE SILVER PICKUP. PLEASE

VACUUM THE CAB AND WIPE DOWN THE INSIDE OF THE

DOORS AND CUP HOLDERS. DUST THE BASHBOARD. IF

ADDITIONAL CLEANING TASKS ARE REQUIRED WHILE YOU ARE

CLEANING PLEASE COMPLETE THEM AND THEN WRITE AT THE

BOTTOM OF THE WORK ORDER THE ADDITIONAL TASKS.

VACUUMED, WIPED DASHBOARD, DOOR PANELS, CONSOLES,

AND CUP HOLDERS

501-VHCLE-013 60 SC 0.5

PLEASE CLEAN THE INSIDE OF THE GREEN VAN. PLEASE MAKE

SURE THAT THE FOLLOWING ITEMS ARE COMPLETED:

VACUUMING THE ENTIRE VAN INCLUDING THE TRUNK, WIPING

DOWN THE INSIDE OF THE DOORS AND CUP HOLDERS,

DUSTING THE DASHBOARD. IF YOU NOTICE ANY ADDITIONAL

CLEANING TASKS THAT SHOULD BE COMPLETED PLEASE DO

THEM AND WRITE THE ADDITIONAL TASKS AT THE BOTTOM OF

THE WORK ORDER.

VACUUMED, WIPED DASHBOARD, DOOR PANELS, CONSOLES,

CUP HOLDERS

MB 0100 60 SC 0.25

SCRAP COMPUTERS - PLEASE SCRAP 2 TOWERS AND 1 LAPTOP

LOCATED IN ROOM 0100

TOOK 2 COMPUTERS, 1 LAPTOP, AND A BAG OF WIRES TO

SCRAP

MB 0008 60 SC 0.25

THERE IS A SCANNER OUTSIDE OF THE PROJECT OFFICE

MARKED BY TOM FOR SCRAP. PLEASE REMOVE TOOK SCANNER TO SCRAP

MB 2CHW 60 SC 0.25

SCRAP PICKUP- THERE ARE TWO ITEMS READY FOR SCRAP PICK

UP IN THE 2ND FLOOR CHEM WING HALLWAY OUTSIDE THE

2100 OFFICE SUITE. TOOK 2 PIECES TO SCRAP

MB 3002 60 SC 0.25

REMOVE EXCESS PROPERTY- THERE IS A FAX MACHINE IN

ROOM 3002 WHICH NEEDS TO BE REMOVED. IT HAS BEEN

EXCESSED. AN E-MAIL WAS SENT TO SEE IF ANYONE WAS

INTERESTED IN IT AND AS OF NOW NO ONE HAS RESPONDED.

JACQUELINE F. KENNY PROGRAM SUPPORT ASSISTANT

SUSTAINABLE BIOFUELS AND CO-PRODUCTS RESEARCH UNIT

EASTERN REGIONAL RESEARCH CENTER 215-233-6580

(PHONE) 215-233-6406 (FAX)

JACQUELINE.KENNY@ARS.USDA.GOV TOOK FAX MACHINE TO SCRAP

CAMPUS 59 SC 24

WEEKLY GROUNDS WORK INCLUDING GRASS CUTTING,

TRIMMING, CLEAN-UP, EDGING. ALSO TIME SPENT

MAINTAINING AND CLEANING EQUIPMENT MOWING, TRIMMING, WEEDING, ETC

115-FANEX-018 87 SC 2.5

CORRECTIVE MAINTENANCE FOR WORK ORDER #5557-

RESILIENT RING MOUNTS ON THIS MOTOR ARE GOING BAD.

NEED TO REPLACE.

SB 54 SC 0.75

ADD ADDITIONAL TAPE TO THE FLOOR AROUND THE AIR

COMPRESSOR AREA WHERE THE FLOOR IS BROKEN UP.

CLEANED THE FLOOR AROUND THE AIR COMPRESSORS AND

PUT DOWN YELLOW AND BLACK TAPE AROUND THE BROKEN

PART OF THE BOILER ROOM FLOOR.

MB PP2 54 SC 45

HIGH PRESSURE STEAM IS NEEDED IN THE 2ND FLOOR PP

MONDAY JUNE 9- FRIDAY JUNE 13

TOOK THE PLANT STEA PRESSURE TO HIGH STEAM FOR 5 DAYS

FROM 90 LBS STEAM PRESSURE TILL 120 LBS PRESSURE

CAMPUS 60 SC 13

WEEKLY GROUNDS WORK INCLUDING GRASS CUTTING,

TRIMMING, CLEAN-UP, EDGING. ALSO TIME SPENT

MAINTAINING AND CLEANING EQUIPMENT

6/10- 4 HOURS- PULLED WEEDS,BLEW OUT BEDS, TRIMMED

AND BLEW FRONT CIRCLE 6/11- 4 HOURS- MOWED TRIMMED

BLEW NORTH LAWN, MSB AREA 6/12- 5 HOURS- MOWED

TRIMED EDGED BLEW PARKING LOT ISLANDS AND ALL OUT

BUILDINGS

108-HNDLR-020 52 SC 2

REPAIR INSULATION, STOP DRIPS AND REMOVE TRASH CAN

AND TRASH BAG DRIP CHANNEL FROM ABOVE LIGHTING

FIXTURE IN 0025 REINSULATED THE COOLING PIPES IN THE SHIPPING CEILING

115-FANEX-085 50 SC 1.5 REPLACE BELTS ON F85-F86 BELTS WERE FOUND BAD ON PM. REPLACED WITH NEW

MPL 50 SC 5

SHARP METAL AT MPL ENTRY DOOR. A FREEZE PROTECTION

ENCLOSURE FOR THE DOWNSPOUTS ON MPL IS DAMAGED

AND HAS EXPOSED SHARP METAL EDGES. REMOVE OR REPAIR

THE BOX.

5/29- 3 HR HOME DEPOT AND INSTALL, 5/30- 1 HR FOAM, 6/2-

1 HR SEAL

MB BCHW 50 SC 0.75 WIRE PULLED OUT OF INNER CW BASEMENT DOOR

AUTO BAR…