AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES

1 5

2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)

02 3-1-2018 848465

6. ISSUED BY 7. ADMINISTRATED BY (If other than Item 6)

USDA Forest Service Mt. Baker-Snoqualmie National Forest Attn: Brian A. Johnson, CO 2930 Wetmore Ave., Suite 3A Everett, WA 98201

Same as Block 6

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) 9A. AMENDMENT OF SOLICITATION NO.

1205G118R0011

9B. DATED (SEE ITEM 11)

1-29-2018

10A. MODIFICATION OF CONTRACT/ORDER NO.

*TO BE COMPLETED BY VENDOR IF NOT COMPLETE 10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended is not extended.

NOTE: If offers are handcarried, additional time should be allowed to access the depository facility due to heightened security requirements.

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing Item 8 and 15, and returning 1 copies of the amendment; (b) acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hours and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required) N/A

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS, IT MODIFIES THE CONTRACT/ORDER NO.

AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT/ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return Zero (0) copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

1. The purpose of Amendment 02 is to:

a. Replace Specification Section 28 13 00, Paragraph 2.04 (in its entirety); and

b. Modify Specification Section 28 13 00, Paragraph 2.25 (A. and C. only).

(Continued…)

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

Brian A. Johnson 15B. CONTRACTOR/OFFEROR 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED

BY

(Signature of person authorized to sign)

BY

(Signature of Contracting Officer) 3-1-2018

RFP No. 1205G118R0011, Amendment 02 Building #2002 Colville SO, Entrance Security Page 1 of 5

SECTION 28 13 00

INTELLIGENT SYSTEM CONTROLLER

(SECTION 2.04 UPDATED 02/28/2018)

1. 2.04 – INTELLIGENT SYSTEM CONTROLLER

2.041 INTELLIGENT SYSTEM CONTROLLER

A. Provide Lenel Advanced dual reader intelligent system controller model LNL-4420 B. Controller must be compatible and supported by USDA ePACS central server software using current Onguard software and compatible with Linc Pass government issued PIV cards..

C. General: Intelligent System Controller communicates to the host computer in a single or dual path configuration of Ethernet, dial-up or direct connection RS-485 communication.

D. Enables connection to up to 64 devices.

E. Description:

1. The LNL-4420 is an Advanced Dual Reader Controller by Lenel that provides a single-board solution for interfacing up to 64 doors, plus auxiliary inputs and outputs, to an OnGuard® system.

2. The LNL-4420 controller enables Ethernet connection directly from an entry location to the OnGuard server. The controller is scalable for most access control applications.

In addition, other I/O and reader interface modules can be added on the controller’s two downstream ports, further expanding its capabilities. In the event of communication loss, the LNL-4420 controller can maintain most of its local functionality until the server connection is restored.

3. The LNL-4420 controller can act as in interface to building automation systems via the ASHRAE BACnet™ protocol. Through the OnGuard software, up to 63 total BACnet points can be defined. These can be a mix of physical inputs connected to the board and virtual outputs. Virtual outputs can be set and read from a connected BACnet client, allowing two-way state exchange with a variety of building control systems. This information can be used by both OnGuard and the external system for status reporting, and as inputs to control logic.

4. Utilizing its 32-bit processor and a multiple-application operating system, the LNL- 4420 controller can communicate upstream to the host computer through its Ethernet port. The LNL-4420 controller can store more than 1,000,000 cardholders in non-volatile flash memory (depending on configuration), and supports selective download for larger cardholder databases. The two downstream RS-485 two-wire ports can be used to connect up to 64 devices (64 doors) in many combinations of LNL- 1100, LNL-1200, LNL- 1300, LNL-1320, LNL-500B, LNL-500W, Schlage® PIM-400 wireless interface, or Assa Abloy Aperio® wireless devices

5. Each LNL-4420 controller supports up to 16 different card formats. The LNL-4420 controller also includes eight inputs — four designated for door interface support and four for general-purpose inputs.

F. Features and Functionality:

1. BACnet protocol support via up to 63 total inputs and virtual outputs

RFP No. 1205G118R0011, Amendment 02 Building #2002 Colville SO, Entrance Security Page 2 of 5

(Refer to Pages 170/171 of the original RFP) bajohnson03 Highlight

2. Support for DHCP and fixed IP addressing

3. DNS device naming through DHCP extended commands

4. Provide 96 MB of available on-board, non-volatile flash memory for badge data, plus dedicated storage for future apps and extensions

5. Battery-backed, non-volatile storage of 50,000 events

6. Firmware stored in flash memory, background download of firmware updates supported

7. Support for up to 16 different formats

8. Biometric template storage support for Bioscrypt® and ANSI/ INCITS 378 templates

9. Advanced anti-pass back capabilities

10. Up to 32,000 access level permissions total (255 per badge)

11. Elevator control support for up to 128 floors

12. Individual extended held open and strike times (ADA required)

13. A dedicated input for cabinet tamper and power failure status

14. Advanced Encryption Standard (AES) 128-bit algorithm for communications to downstream reader and I/O interfaces

15. AES128 or TLS1.2 (with AES256) communication to OnGuard

16. Reader Interface Functionality

a. Support for Data1/Data0, Clock/Data, Unsupervised F2F and OSDP™-compatible RS-485 readers and keypads, including OSDP

b. Secure Channel (SC) encrypted communications

17. Extended Functionality

a. Optional onboard HID® pivCLASS® or Technology Industries

b. Entry Point™ FIPS-201 Embedded Authentication (consult Lenel for OnGuard and third party requirements G. Power Supply

1. Primary Power: 12 or 24 VDC ± 10%. 500 mA maximum (reader current not included)

2. Memory and Clock: Backup Battery 3 V lithium, type BR2325, BR2330, CR2330 H. Communication Ports

1. Host Communications Ethernet Port, 10/100Base-TX

2. SIO Downstream Ports Two each, 2-wire RS-485, 9600 to 38.4 Kbps async

I. Inputs

1. Tamper and Power Fail Monitors Unsupervised, dedicated

2. Door position, REX 4, each programmable as normally open or normally closed, supervised or unsupervised circuits

3. AUX: 4 each programmable as normally open or normally closed, supervised or unsupervised circuits J. Outputs

1. Relay Outputs Four Form-C 5A@30 VDC, resistive, relay outputs: two for strike, two for auxiliary outputs

K. Reader Interface

RFP No. 1205G118R0011, Amendment 02 Building #2002 Colville SO, Entrance Security Page 3 of 5

1. Reader Power:(Jumper Selectable):

a. DC output: 12 VDC, +/- 10% regulated, current limited to 150mA for each reader

b. 12 to 24 VDC, +/- 10% (input voltage pass through) current limited to 150 mA for each reader L. Data Inputs

1. TTL: Wiegand Data1/Data0, Magnetic Clock/Data, Unsupervised F2F single-wire protocol (Note: Supervised F2F supported on connected door controllers but not for the two onboard ports)

2. RS-485: 9600 baud, Bioscrypt RS-485 or OSDP (Open Supervised Device Protocol);

OSDP Secure Channel, Transparent Mode and biometric templates supported

M. Building Automation Interface Supports:

1. ASHRAE BACnet™ protocol

N. Environmental

1. Operating Temperature 32° to 158° F (0° to +70° C)

2. Storage Temperature -67° to +185° F (-55° to +85° C)

3. Humidity 0 to 95% Relative Humidity, Non-Condensing (RHNC)

O. Mechanical

1. Dimensions 6.0" x 8.0" x 1.0" (152mm x 203mm x 25mm)

2. Weight 10.65 oz. (302g) nominal

END OF SECTION

RFP No. 1205G118R0011, Amendment 02 Building #2002 Colville SO, Entrance Security Page 4 of 5

2.21 PULL AND JUNCTION BOXES

A. Provide steel pressed steel junctions boxes for all sensors and junctions boxes in accordance with Section 26 00 50.

2.22 CONDUCTORS

A. Supply all conductors per manufacture’s specification recommendations.

B. Verify with all devices, length from panel, load to size conductors.

C. Provide conductors of type and size required for devices required.

D. Provide voltage drop calculations to verify size of conductors to be provided.

E. Provide conductors rated for outdoor submerged use if installed in underground conduit.

2.23 POWER SUPPLY FOR CONTROL BOARDS

A. Power supply for control boards, and field devices card readers, door position sensors.

B. Manufacturer: Lenel: LNL-AL600ULX-4CB6 or approved equal.

C. Input 115 VAC 50/60 Hz, 1.9 amp. Provide a larger power supply if needed for loads.

D. Thermal overload protection Short circuit protection E. Primary plug-able connector for incoming 115 VAC F. Output Power 12 VDC, 4-port power limited outputs G. Maximum 6 amps continuous supply current at 12 VDC H. Four individual circuit breaker outputs rated @ 2.5 amps each I. 100 mV peak output voltage ripple J. UL Approve and RoHS compliant K. Provide power supply sizing calculations L. Provide spare 25% in power supply rating above calculated loads.

M. Provide a front panel mounted LED indicating light that power supply is energized.

2.24 POWER SUPPLY FOR DOOR ELECTRIC STRIKES

A. Provide a separate power supply for all door electric strikes or other devices that are not sensors. Do not use control board power supply to power door electric strikes.

B. Provide 12 or 24 VDC for door locks. Provide power supply to operate system with

25% spare capacity.

C. Provide a front panel mounted LED indicating light that door power supply is energized.

2.25 BATTERY BACKUP & POWER SUPPLY

A. Provide a 24-hour battery back-up for both systems, control boards power supply and door strike power supply, separate from UPS battery.

B. Provide a sealed lead acid batteries with charger.

C. Provide separate battery calculations for each systems. The UPS battery shall not be used to provide 24-hour back-up time.

2.26 TRANSFORMERS

A. NFPA 70, Class II control transformers, NRTL listed. Transformers for access control system if required, these shall not be shared with any other system. Provide 25% spare capacity in all transformers.

RFP No. 1205G118R0011, Amendment 02 Building #2002 Colville SO, Entrance Security Page 5 of 5

(Replace Page 178 of the original RFP with this page) bajohnson03 Highlight bajohnson03 Highlight bajohnson03 Highlight

Spec Section 28 13 00 (Updated).pdf
1. 2.04 – intelligent system controller
2.041 intelligent system controller
A. Provide Lenel Advanced dual reader intelligent system controller model LNL-4420
B. Controller must be compatible and supported by USDA ePACS central server software using current Onguard software and compatible with Linc Pass government issued PIV cards..
C. General: Intelligent System Controller communicates to the host computer in a single or dual path configuration of Ethernet, dial-up or direct connection RS-485 communication.
D. Enables connection to up to 64 devices.
E. Description:
1. The LNL-4420 is an Advanced Dual Reader Controller by Lenel that provides a single-board solution for interfacing up to 64 doors, plus auxiliary inputs and outputs, to an OnGuard® system.
2. The LNL-4420 controller enables Ethernet connection directly from an entry location to the OnGuard server. The controller is scalable for most access control applications. In addition, other I/O and reader interface modules can be added on the cont...
3. The LNL-4420 controller can act as in interface to building automation systems via the ASHRAE BACnet™ protocol. Through the OnGuard software, up to 63 total BACnet points can be defined. These can be a mix of physical inputs connected to the board ...
4. Utilizing its 32-bit processor and a multiple-application operating system, the LNL-4420 controller can communicate upstream to the host computer through its Ethernet port. The LNL-4420 controller can store more than 1,000,000 cardholders in non-vo...
5. Each LNL-4420 controller supports up to 16 different card formats. The LNL-4420 controller also includes eight inputs — four designated for door interface support and four for general-purpose inputs.
F. Features and Functionality:
1. BACnet protocol support via up to 63 total inputs and virtual outputs
2. Support for DHCP and fixed IP addressing
3. DNS device naming through DHCP extended commands
4. Provide 96 MB of available on-board, non-volatile flash memory for badge data, plus dedicated storage for future apps and extensions
5. Battery-backed, non-volatile storage of 50,000 events
6. Firmware stored in flash memory, background download of firmware updates supported
7. Support for up to 16 different formats
8. Biometric template storage support for Bioscrypt® and ANSI/ INCITS 378 templates
9. Advanced anti-pass back capabilities
10. Up to 32,000 access level permissions total (255 per badge)
11. Elevator control support for up to 128 floors
12. Individual extended held open and strike times (ADA required)
13. A dedicated input for cabinet tamper and power failure status
14. Advanced Encryption Standard (AES) 128-bit algorithm for communications to downstream reader and I/O interfaces
15. AES128 or TLS1.2 (with AES256) communication to OnGuard
16. Reader Interface Functionality
a. Support for Data1/Data0, Clock/Data, Unsupervised F2F and OSDP™-compatible RS-485 readers and keypads, including OSDP
b. Secure Channel (SC) encrypted communications
17. Extended Functionality
a. Optional onboard HID® pivCLASS® or Technology Industries
b. Entry Point™ FIPS-201 Embedded Authentication (consult Lenel for OnGuard and third party requirements
G. Power Supply
1. Primary Power: 12 or 24 VDC ± 10%. 500 mA maximum (reader current not included)
2. Memory and Clock: Backup Battery 3 V lithium, type BR2325, BR2330, CR2330
H. Communication Ports
1. Host Communications Ethernet Port, 10/100Base-TX
2. SIO Downstream Ports Two each, 2-wire RS-485, 9600 to 38.4 Kbps async
I. Inputs
1. Tamper and Power Fail Monitors Unsupervised, dedicated
2. Door position, REX 4, each programmable as normally open or normally closed, supervised or unsupervised circuits
3. AUX: 4 each programmable as normally open or normally closed, supervised or unsupervised circuits
J. Outputs
1. Relay Outputs Four Form-C 5A@30 VDC, resistive, relay outputs: two for strike, two for auxiliary outputs
K. Reader Interface
1. Reader Power:(Jumper Selectable):
a. DC output: 12 VDC, +/- 10% regulated, current limited to 150mA for each reader
b. 12 to 24 VDC, +/- 10% (input voltage pass through) current limited to 150 mA for each reader
L. Data Inputs
1. TTL: Wiegand Data1/Data0, Magnetic Clock/Data, Unsupervised F2F single-wire protocol (Note: Supervised F2F supported on connected door controllers but not for the two onboard ports)
2. RS-485: 9600 baud, Bioscrypt RS-485 or OSDP (Open Supervised Device Protocol); OSDP Secure Channel, Transparent Mode and biometric templates supported
M. Building Automation Interface Supports:
1. ASHRAE BACnet™ protocol
N. Environmental
1. Operating Temperature 32 to 158 F (0 to +70 C)
2. Storage Temperature -67 to +185 F (-55 to +85 C)
3. Humidity 0 to 95% Relative Humidity, Non-Condensing (RHNC)
O. Mechanical
1. Dimensions 6.0" x 8.0" x 1.0" (152mm x 203mm x 25mm)
2. Weight 10.65 oz. (302g) nominal