FA_18-0926_4531_TNB_whse.pdf

PDF 418 KB Posted

Attached to
TNF Fire Alarm Annual Inspection Federal contract opportunity
Solicitation number
12010919Q0068
Issued by
Department of Agriculture Forest Service R10-Alaska Region

About this file

Thorne Bay Warehouse

View the file

Other files for this federal contract opportunity

Other files attached to TNF Fire Alarm Annual Inspection, newest first.
File Type Posted
FA_18-0924_4506_KTN_whse.pdf PDF
FA_18-0925_4523_WRG_office.pdf PDF
FA_18-0926_4530_TNB_office.pdf PDF
FA_18-0927_4534_CRG_office.pdf PDF
FA_18-0919_4480_JNU_office.pdf PDF
FA_18-0925_4524_WRG_whse.pdf PDF
FA_18-0924_4515_SEADC.PDF PDF
FA_18-0919_4475_JNU_bunkhouse.pdf PDF
FA_18-0924_4507_KTN_bunkhouse.pdf PDF
FA_18-0924_4505_KTN_office.pdf PDF
FA_18-0815_4396_Sitka_office.pdf PDF
SKM_C45819062319260.pdf PDF
FA_18-0919_4470_MGVC.PDF PDF
FA_18-0917_4461_JNU_FSL.PDF PDF
FA_18-0918_4463_HNH_office.pdf PDF
wage_determination.pdf PDF
12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service - Tongass Thorne Bay Warehouse

No.

04531 www.gocanvas.com CC634FB0-5A96-4726-882D-01B7DA68243A

725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com

Fire Alarm Inspection Report Status

Status

Date 09/26/2018

Time 16:44

Owner /Client / Contracting Agency

Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2

City Sitka State

AK

Zip 99835

Representative

Telephone

Fax None Email None

Property Name (User)

Name Thorne Bay Warehouse Address 1 1312 Federal Way Address 2

City Thorne Bay State

AK

Contact

Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04531 www.gocanvas.com CC634FB0-5A96-4726-882D-01B7DA68243A

Zip 99919

Monitoring Entity

Contact / Agency None

Monitoring Account Ref. No.

Approving Agency

Contact

Service

Service Annually

Other (Specify)

Type Transmission

Type Transmission Other

Other (Specify)

Control Panel

Control Panel Manufacturer

CEREBERUS PYROTRONICS

Control Panel Model

CP30

Control Panel Location

OFF

Is Panel in "normal" conditions upon arrival?

No Circuit Styles

IDC

Number of Circuits

Software Rev.

N/A Last Date System Had Any Service Performed

PREVIOUS ANNUAL INSPECTION

Last Date that Any Software or Configuration Was Revised None

Printer

Printer Model

Location

Did Printer Function Properly

Is Printer Supervised?

No.

04531 www.gocanvas.com CC634FB0-5A96-4726-882D-01B7DA68243A

Alarm Verification

Alarm Verification feature is Disabled

Alarm Notification Circuits

No. of alarm notification appliance circuits

Are circuits monitored for integrity?

Yes

Initiating Device Circuit

Quantity

Style(s)

CLASS B

Signaling Line Circuits

Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity

Style(s)

CLASS B

System Primary Power Supply

(a) Primary (Main) Location (of Primary Supply Panelboard)

Nominal Voltage 120/208

Amps Overcurrent Protection Type

BREAKER

Overcurrent Protection Amps

Disconnecting Means Location

Generator System

Engine-driven generator dedicated to fire alarm system.

Location of fuel storage:

Other Backup

(c) Emergency or standby system used as a backup to primary power Legally required standby described in NFPA 70, Article 701 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04531 www.gocanvas.com CC634FB0-5A96-4726-882D-01B7DA68243A supply, instead of using a secondary power supply:

None

Emergency system described in NFPA 70, Article 700

Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

Transient Suppressors

Transient Suppressors Visual

Comments

Deficiencies and Issues

The following did not operate correctly

** THIS SYSTEM HAS BEEN TURNED OFF AND REMOVED

FROM SERVICE **

System restored to normal operation

Date 09/26/2018 Time 16:46 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04531 www.gocanvas.com CC634FB0-5A96-4726-882D-01B7DA68243A

Pictures

Photo 1

Photo 1 Description Panel is off

Notes and Recommendations

Notes and Recommendations None Plan of Corrective Action:

**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A

Corrective Action and Date Taken:

**NONE TAKEN AT THIS TIME

Inspector Information

This testing was performed in accordance with (Standard/Edition) Date http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04531 www.gocanvas.com CC634FB0-5A96-4726-882D-01B7DA68243A

CURRENT NFPA 72 STANDARDS

Name of Inspector

ALEXANDER MARTINEZ

License Number 10-009

09/26/2018 Time 16:47

Inspector Signature

Inspector Signature

Owner or Representative Information

Name of Owner or Representative

Date 09/26/2018

Time 16:47

Owner or Representative Signature

Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link