FA_18-0924_4507_KTN_bunkhouse.pdf
PDF 1 MB Posted
- Attached to
- TNF Fire Alarm Annual Inspection Federal contract opportunity
- Solicitation number
- 12010919Q0068
About this file
Ketchikan Bunkhouse
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0924_4506_KTN_whse.pdf | ||
| FA_18-0925_4523_WRG_office.pdf | ||
| FA_18-0926_4530_TNB_office.pdf | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0919_4480_JNU_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0919_4470_MGVC.PDF | ||
| FA_18-0917_4461_JNU_FSL.PDF | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| wage_determination.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass Ketchikan Bunkhouse
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/24/2018
Time 12:07
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
LOGAN WILD
Telephone
Fax None Email None
Property Name (User)
Name Ketchikan Bunkhouse Address 1 504 9th Street Address 2
City Ketchikan State
AK
Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
Zip 99901
Monitoring Entity
Contact / Agency
LJ ALARM
Telephone 907-789-7940
Monitoring Account Ref. No.
Approving Agency
Contact
USDA
Telephone
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 12:09
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
SILENT KNIGHT
Control Panel Model
Control Panel Location
ENTRY WAY
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
IDC
Number of Circuits
Software Rev.
N/A Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised None
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
4 4 4 0 CLASS B
Smoke Detectors 8 8 8 0 CLASS B Heat Detectors SPOT TYPE 4 4 4 0 CLASS B
Alarm Verification
Alarm Verification feature is Disabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horns 1 1 1 0 CLASS B Horn/Strobes 2 2 2 0 CLASS B Strobes 4 4 4 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level
ENTIRE BUILDING 59 101-110
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Initiating Device Circuit
Quantity
Style(s)
CLASS B
Signaling Line Circuits
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
CLASS B
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard)
BOILER RM
Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location
AB 34
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel In panel 7-16 12/7 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Same 120 20 BREAKER 20 Same
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
None
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
System Tests And Inspections Type Visual Functional Comments
Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
Type Visual Functional Comments Disconnect Switches Ground-Fault Monitoring
Secondary Power Type Visual Functional Comments
Battery Condition Load Voltage Discharge Test Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Notification Appliances Notification Appliances Visual Functional Comments
Audible Visible Audible/Visual Combination
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
PULLS Entry and exit ways
Pass
SMOKES LOCATED
THROUGH
OUT ON
CEILINGS IN
HALLWAY
Pass
HEATS MECHANICAL
AND
ORDINARY
HAZARD
AREAS
Pass
Emergency Communications Equipment Type Visual Functional Comments
Call-in Signal
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 12:32 DURING TESTING THE
ALARM SIGNALS WERE
COMING INTO LJ ALARM AS
INVALID ENTRY AND HAD
JEN PROGRAM THEM AS
ALARM SIGNALS FOLLOW
UP MAY BE REQUIRED TO
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
Type of Signal Yes/No Time Comments
CONFIRM THESE HAVE
BEEN REMEDIES
Alarm Restoration Yes 12:33 Trouble Signal Yes 12:34 Trouble Signal Restoration Yes 12:35 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ ALARM 12:34
Deficiencies and Issues
The following did not operate correctly
** HEAT DETECTORS ARE DUE TO BE TESTED OR
REPLACED AS THEY APPEAR TONBE OVER FIFTEEN
YEARS OLD
** UNCLEAR LAST TIME SMOKES WERE SENSITIVITY
TESTED NO TAGS ON SITE RECOMMEND SENSITIVITY
TESTING
System restored to normal operation
Date 09/24/2018 Time 12:34 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
Pictures
Photo 1
Photo 1 Description
DEVICE MAP
Photo 2
Photo 2 Description Power supply
Photo 3
Photo 3 Description Smoke detectors on site
Photo 4
Photo 4 Description Heats on site
Photo 5
Photo 5 Description Horn strobes on site
Photo 6
Photo 6 Description Pull stations on site
Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
Photo 7 Description Ambient Db
Photo 8 Description Heats tested on site
Photo 9 Description Horn on site
Photo 10
Photo 10 Description Alarm Db
Notes and Recommendations
Notes and Recommendations http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF
None Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/24/2018 Time 12:41
Inspector Signature
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
LOGAN WILD
Date 09/24/2018
Time 12:41
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link