FA_18-0924_4507_KTN_bunkhouse.pdf

PDF 1 MB Posted

Attached to
TNF Fire Alarm Annual Inspection Federal contract opportunity
Solicitation number
12010919Q0068
Issued by
Department of Agriculture Forest Service R10-Alaska Region

About this file

Ketchikan Bunkhouse

View the file

Other files for this federal contract opportunity

Other files attached to TNF Fire Alarm Annual Inspection, newest first.
File Type Posted
FA_18-0924_4506_KTN_whse.pdf PDF
FA_18-0925_4523_WRG_office.pdf PDF
FA_18-0926_4530_TNB_office.pdf PDF
FA_18-0927_4534_CRG_office.pdf PDF
FA_18-0919_4480_JNU_office.pdf PDF
FA_18-0925_4524_WRG_whse.pdf PDF
FA_18-0926_4531_TNB_whse.pdf PDF
FA_18-0924_4515_SEADC.PDF PDF
FA_18-0919_4475_JNU_bunkhouse.pdf PDF
FA_18-0924_4505_KTN_office.pdf PDF
FA_18-0815_4396_Sitka_office.pdf PDF
SKM_C45819062319260.pdf PDF
FA_18-0919_4470_MGVC.PDF PDF
FA_18-0917_4461_JNU_FSL.PDF PDF
FA_18-0918_4463_HNH_office.pdf PDF
wage_determination.pdf PDF
12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service - Tongass Ketchikan Bunkhouse

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com

Fire Alarm Inspection Report Status

Status

Date 09/24/2018

Time 12:07

Owner /Client / Contracting Agency

Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2

City Sitka State

AK

Zip 99835

Representative

LOGAN WILD

Telephone

Fax None Email None

Property Name (User)

Name Ketchikan Bunkhouse Address 1 504 9th Street Address 2

City Ketchikan State

AK

Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

Zip 99901

Monitoring Entity

Contact / Agency

LJ ALARM

Telephone 907-789-7940

Monitoring Account Ref. No.

Approving Agency

Contact

USDA

Telephone

Service

Service Annually

Other (Specify)

Prior To Any Testing Notifications Are

Made To Other (Specify) Yes/No Who Time

Monitoring Entity Yes LJ ALARM 12:09

Type Transmission

Type Transmission Digital

Other (Specify)

Control Panel

Control Panel Manufacturer

SILENT KNIGHT

Control Panel Model

Control Panel Location

ENTRY WAY

Is Panel in "normal" conditions upon arrival?

Yes Circuit Styles

IDC

Number of Circuits

Software Rev.

N/A Last Date System Had Any Service Performed

PREVIOUS ANNUAL INSPECTION

Last Date that Any Software or Configuration Was Revised None

Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

Printer Model None Location

Did Printer Function Properly

Is Printer Supervised?

Alarm-Initiating Devices and Circuit Information Description If Other

(Specify) Quantity of

Devices Installed

Quantity of Devices Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Manual Fire Alarm Boxes

4 4 4 0 CLASS B

Smoke Detectors 8 8 8 0 CLASS B Heat Detectors SPOT TYPE 4 4 4 0 CLASS B

Alarm Verification

Alarm Verification feature is Disabled

Alarm Notification Appliances & Circuit Info Description If Other

(Specify) Quantity of Appliances

Installed

Quantity of Appliances

Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Horns 1 1 1 0 CLASS B Horn/Strobes 2 2 2 0 CLASS B Strobes 4 4 4 0 CLASS B Decibel Levels

Location Description Ambient Level Alarm Level

ENTIRE BUILDING 59 101-110

Alarm Notification Circuits

No. of alarm notification appliance circuits

Are circuits monitored for integrity?

Yes

Initiating Device Circuit

Quantity

Style(s)

CLASS B

Signaling Line Circuits

Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity

Style(s)

CLASS B

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

System Primary Power Supply

(a) Primary (Main) Location (of Primary Supply Panelboard)

BOILER RM

Nominal Voltage 120/208

Amps Overcurrent Protection Type

BREAKER

Overcurrent Protection Amps

Disconnecting Means Location

AB 34

Secondary (standby) Power Supply Type Location Battery

Dated:

Storage Battery:

Amp Hour Rating

Battery Type

Other Battery

Type

Calculated capacity in Amp-Hours to operate system for 24 hours.

Calculated capacity in Amp-Hours to operate system for 60 hours.

Control Panel In panel 7-16 12/7 Sealed Lead- Acid

N/A N/A N/A

Secondary (standby) Power Primary Power Supply Location of

Primary Power Supply

(Distribution Panel)

Nominal Voltage of Primary Power

Supply

Amps of Primary Power Supply

Overcurrent Protection Type

Overcurrent Protection Amps

Disconnecting Means Location

Same 120 20 BREAKER 20 Same

Generator System

Engine-driven generator dedicated to fire alarm system.

None

Location of fuel storage:

Other Backup

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

None

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

System Tests And Inspections Type Visual Functional Comments

Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

Type Visual Functional Comments Disconnect Switches Ground-Fault Monitoring

Secondary Power Type Visual Functional Comments

Battery Condition Load Voltage Discharge Test Charger Test

Transient Suppressors

Transient Suppressors Visual

Comments

Notification Appliances Notification Appliances Visual Functional Comments

Audible Visible Audible/Visual Combination

Initiating & Supervisory Device Tests & Inspection Device

Type Loc. & S/N Visual

Check Functional

Test Factory Setting

Measured Setting

Pass/Fail Comments

PULLS Entry and exit ways

Pass

SMOKES LOCATED

THROUGH

OUT ON

CEILINGS IN

HALLWAY

Pass

HEATS MECHANICAL

AND

ORDINARY

HAZARD

AREAS

Pass

Emergency Communications Equipment Type Visual Functional Comments

Call-in Signal

Central Station Monitoring Type of Signal Yes/No Time Comments

Alarm Signal Yes 12:32 DURING TESTING THE

ALARM SIGNALS WERE

COMING INTO LJ ALARM AS

INVALID ENTRY AND HAD

JEN PROGRAM THEM AS

ALARM SIGNALS FOLLOW

UP MAY BE REQUIRED TO

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

Type of Signal Yes/No Time Comments

CONFIRM THESE HAVE

BEEN REMEDIES

Alarm Restoration Yes 12:33 Trouble Signal Yes 12:34 Trouble Signal Restoration Yes 12:35 Notifications That Testing is Complete Notification Given

To Other (Specify) Yes/No Who Time

Monitoring Agency Yes LJ ALARM 12:34

Deficiencies and Issues

The following did not operate correctly

** HEAT DETECTORS ARE DUE TO BE TESTED OR

REPLACED AS THEY APPEAR TONBE OVER FIFTEEN

YEARS OLD

** UNCLEAR LAST TIME SMOKES WERE SENSITIVITY

TESTED NO TAGS ON SITE RECOMMEND SENSITIVITY

TESTING

System restored to normal operation

Date 09/24/2018 Time 12:34 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

Pictures

Photo 1

Photo 1 Description

DEVICE MAP

Photo 2

Photo 2 Description Power supply

Photo 3

Photo 3 Description Smoke detectors on site

Photo 4

Photo 4 Description Heats on site

Photo 5

Photo 5 Description Horn strobes on site

Photo 6

Photo 6 Description Pull stations on site

Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

Photo 7 Description Ambient Db

Photo 8 Description Heats tested on site

Photo 9 Description Horn on site

Photo 10

Photo 10 Description Alarm Db

Notes and Recommendations

Notes and Recommendations http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04507 www.gocanvas.com 384DC3EC-9530-4D4F-A927-246ED6D6CDDF

None Plan of Corrective Action:

**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A

Corrective Action and Date Taken:

**NONE TAKEN AT THIS TIME

Inspector Information

This testing was performed in accordance with (Standard/Edition)

CURRENT NFPA 72 STANDARDS

Name of Inspector

ALEXANDER MARTINEZ

License Number 10-009

Date 09/24/2018 Time 12:41

Inspector Signature

Inspector Signature

Owner or Representative Information

Name of Owner or Representative

LOGAN WILD

Date 09/24/2018

Time 12:41

Owner or Representative Signature

Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link