FA_18-0924_4506_KTN_whse.pdf
PDF 1 MB Posted
- Attached to
- TNF Fire Alarm Annual Inspection Federal contract opportunity
- Solicitation number
- 12010919Q0068
About this file
Ketchikan Warehouse
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0925_4523_WRG_office.pdf | ||
| FA_18-0919_4480_JNU_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0926_4530_TNB_office.pdf | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4507_KTN_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0919_4470_MGVC.PDF | ||
| FA_18-0917_4461_JNU_FSL.PDF | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf | ||
| wage_determination.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass Ketchikan Warehouse
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/24/2018
Time 11:28
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
LOGAN WILD
Telephone
Fax None Email None
Property Name (User)
Name Ketchikan Warehouse Address 1 3001 Tongass Ave Address 2
City Ketchikan State
AK
Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Zip 99901
Monitoring Entity
Contact / Agency
LJ ALARM
Telephone 907-789-7940
Monitoring Account Ref. No.
Approving Agency
Contact
USDA
Telephone
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 11:30
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
SIMPLEX
Control Panel Model
Control Panel Location
ELECTRICAL RM
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
SLC
Number of Circuits
Software Rev.
N/A Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised Date of install
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
10 10 10 0 CLASS B
Smoke Detectors 2 2 2 0 CLASS B
Alarm Verification
Alarm Verification feature is Disabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horn/Strobes 10 10 10 0 CLASS B Strobes 2 2 2 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level
ENTIRE BUILDING 55 101
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
AHU Shutdown 1 1 1 0
Initiating Device Circuit
Quantity
Style(s)
CLASS B
Signaling Line Circuits
Quantity and style of signaling line circuits connected to Style(s) http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B system (see 2007 NFPA 72, Table 6.6.1) Quantity
CLASS B
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard)
IN ELECTRICAL RM NEXT TO FACP
Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location
LM2 44
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel In FACP Unknown :
BATTERY ID
02174-HK
POWER
SONICS
12/7 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Same 120 20 BREAKER 20 LM2 44
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
None
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
System Tests And Inspections Type Visual Functional Comments
Control Unit http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Type Visual Functional Comments Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring
Secondary Power Type Visual Functional Comments
Battery Condition Load Voltage Discharge Test Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Remote Annunciators Remote Annunciators Location Visual Functional Comments
Remote Annunciator IN MAINT LEAD ART
OFFICE
Notification Appliances Notification Appliances Visual Functional Comments
Visible Audible/Visual Combination
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
PULLS Entry and exit way
Pass
Smokes Above panel and in arts office
Pass
Emergency Communications Equipment Type Visual Functional Comments
Call-in Signal
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 11:39 Alarm Restoration Yes 11:40 Trouble Signal Yes 11:41 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Type of Signal Yes/No Time Comments Trouble Signal Restoration Yes 11:42 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ ALARM 11:40
Deficiencies and Issues
The following did not operate correctly
EVERYTHING OPERATED AND PERFORMED PER NFPA
72 STANDARDS
System restored to normal operation
Date 09/24/2018 Time 11:40 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Pictures
Photo 1
Photo 1 Description Panel conductor integrity
Photo 2
Photo 2 Description Battery info
Photo 3
Photo 3 Description Power supply
Photo 4
Photo 4 Description Pull stations tested
Photo 5
Photo 5 Description Remote annunciator
Photo 6
Photo 6 Description Horn strobes on site
Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Photo 7 Description Strobes tested on site
Photo 8 Description Ambient Db
Photo 9 Description Alarm Db
Photo 10 Photo 11
Photo 10 Description Average alarm Db
Photo 11 Description Panel tagged and in the proper state upon completion http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B
Notes and Recommendations
Notes and Recommendations None Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/24/2018 Time 11:42
Inspector Signature
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
LOGAN WILD
Date 09/24/2018
Time 11:42
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04506 www.gocanvas.com BC655585-4215-4919-929A-BA0F3644E01B http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link