FA_18-0925_4523_WRG_office.pdf

PDF 1 MB Posted

Attached to
TNF Fire Alarm Annual Inspection Federal contract opportunity
Solicitation number
12010919Q0068
Issued by
Department of Agriculture Forest Service R10-Alaska Region

About this file

Wrangell Office

View the file

Other files for this federal contract opportunity

Other files attached to TNF Fire Alarm Annual Inspection, newest first.
File Type Posted
FA_18-0924_4506_KTN_whse.pdf PDF
FA_18-0919_4480_JNU_office.pdf PDF
FA_18-0925_4524_WRG_whse.pdf PDF
FA_18-0926_4531_TNB_whse.pdf PDF
FA_18-0924_4515_SEADC.PDF PDF
FA_18-0926_4530_TNB_office.pdf PDF
FA_18-0927_4534_CRG_office.pdf PDF
FA_18-0919_4475_JNU_bunkhouse.pdf PDF
FA_18-0924_4507_KTN_bunkhouse.pdf PDF
FA_18-0924_4505_KTN_office.pdf PDF
FA_18-0815_4396_Sitka_office.pdf PDF
SKM_C45819062319260.pdf PDF
FA_18-0919_4470_MGVC.PDF PDF
FA_18-0917_4461_JNU_FSL.PDF PDF
FA_18-0918_4463_HNH_office.pdf PDF
12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf PDF
wage_determination.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service - Tongass Wrangell Office

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com

Fire Alarm Inspection Report Status

Status

Date 09/25/2018

Time 11:11

Owner /Client / Contracting Agency

Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2

City Sitka State

AK

Zip 99835

Representative

LOGAN WILD

Telephone

Fax None Email None

Property Name (User)

Name Wrangell Office Address 1 525 Bennett Street Address 2

City Wrangell State

AK

Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Zip 99929

Monitoring Entity

Contact / Agency

LJ ALARM

Telephone 789-7940

Monitoring Account Ref. No.

Approving Agency

Contact

USDA

Telephone

Service

Service Annually

Other (Specify)

Prior To Any Testing Notifications Are

Made To Other (Specify) Yes/No Who Time

Monitoring Entity Yes LJ ALARM 11:12

Type Transmission

Type Transmission Digital

Other (Specify)

Control Panel

Control Panel Manufacturer

ESL

Control Panel Model

Control Panel Location Boiler room

Is Panel in "normal" conditions upon arrival?

Yes Circuit Styles

IDC

Number of Circuits

Software Rev.

N/A Last Date System Had Any Service Performed

PREVIOUS ANNUAL INSPECTION

Last Date that Any Software or Configuration Was Revised None

Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Printer Model None Location

Did Printer Function Properly

Is Printer Supervised?

Alarm-Initiating Devices and Circuit Information Description If Other

(Specify) Quantity of

Devices Installed

Quantity of Devices Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Manual Fire Alarm Boxes

2 2 2 0 CLASS B

Smoke Detectors 17 17 17 0 CLASS B

Alarm Verification

Alarm Verification feature is Disabled

Alarm Notification Appliances & Circuit Info Description If Other

(Specify) Quantity of Appliances

Installed

Quantity of Appliances

Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Horn/Strobes 13 13 13 0 CLASS B Bells 1 1 1 0 CLASS B Horns 1 1 1 0 CLASS B Decibel Levels

Location Description Ambient Level Alarm Level Entire Building 56 85

Alarm Notification Circuits

No. of alarm notification appliance circuits

Are circuits monitored for integrity?

Yes

Control Equipment Description of

Equipment If Other (Specify)

Quantity Installed

Quantity Tested Quantity Passed Quantity Failed

Elevator Recall 2 2 2 0

Initiating Device Circuit

Quantity

Style(s)

CLASS B

Signaling Line Circuits http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity

Style(s)

CLASS B

System Primary Power Supply

(a) Primary (Main) Location (of Primary Supply Panelboard)

NEXT TO PANEL

Nominal Voltage 120/208

Amps Overcurrent Protection Type

BREAKER

Overcurrent Protection Amps

Disconnecting Means Location

DID NOT CONFIRM

Secondary (standby) Power Supply Type Location Battery

Dated:

Storage Battery:

Amp Hour Rating

Battery Type

Other Battery

Type

Calculated capacity in Amp-Hours to operate system for 24 hours.

Calculated capacity in Amp-Hours to operate system for 60 hours.

Control Panel IN PANEL 2010 DUE

FOR

REPLACEMENT

STATUS 2

12/7 Sealed Lead- Acid

N/A N/A N/A

Dialer In dialer 2010 DUE

FOR

REPLACEMENT

STATUS 2

12/7 x1 Sealed Lead- Acid

N/A N/A N/A

Secondary (standby) Power Primary Power Supply Location of

Primary Power Supply

(Distribution Panel)

Nominal Voltage of Primary Power

Supply

Amps of Primary Power Supply

Overcurrent Protection Type

Overcurrent Protection Amps

Disconnecting Means Location

Same 120 20 BREAKER 20 Same Same 120 20 BREAKER 20 Same

Generator System

Engine-driven generator dedicated to fire alarm system.

None

Location of fuel storage:

Other Backup

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

None

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

System Tests And Inspections Type Visual Functional Comments

Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring

Secondary Power Type Visual Functional Comments

Battery Condition DUE FOR REPLACEMENT Load Voltage LOW Discharge Test BORDER LINE Charger Test

Transient Suppressors

Transient Suppressors Visual

Comments

Notification Appliances Notification Appliances Visual Functional Comments

Audible Audible/Visual Combination Visible

Initiating & Supervisory Device Tests & Inspection Device

Type Loc. & S/N Visual

Check Functional

Test Factory Setting

Measured Setting

Pass/Fail Comments

PULLS HALLS

ENTRY AND

EXITS

Pass

SMOKES CEILINGS

LOCATED

THROUGH

OUT

COMPLEX

Pass NOTICED

SMOKES

APPEAR TO

BE DUE FOR

SENSITIVITY

TESTING THE

LED TEST

FUNCTION

ON

MAJORITY

OF SMOKES

WERE

FLASHING 8

TIMES

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Device Type

Loc. & S/N Visual Check

Functional Test

Factory Setting

Measured Setting

Pass/Fail Comments

INDICATING

HIGHER

THEN

NORMAL

SENSITIVITY

Emergency Communications Equipment Type Visual Functional Comments

Call-in Signal

Central Station Monitoring Type of Signal Yes/No Time Comments

Alarm Signal Yes 10:58 Alarm Restoration Yes 10:59 Notifications That Testing is Complete Notification Given

To Other (Specify) Yes/No Who Time

Monitoring Agency Yes LJ ALARM 11:58

Deficiencies and Issues

The following did not operate correctly

** BATTERIES DUE FOR REPLACEMENT IN THE MAIN

FACP AND DIALER THIS IS A STATUS 2 REQUIREMENT IT

WAS NOTED THAT THE PANEL AND DIALER KEEP GOING

IN AND OUT OF TROUBLE WHICH THIS MAY BE THE

FIRST OLSCE TO REMEDY THAT ISSUE, IF DIALER IS

GOING IN AND OUT OF TROUBLE IT IS POSSIBLE THE

PHONE LINES MAY BE AN ISSUE AND OR IF FREQUENT

BROWN OUTS HAPPEN THIS WILL ALSO CAUSE THE

DIALER TO GO INTO TROUBLE INDICATING A AC

FAILURE AND PHYSICAL ACKNOWLEDGEMENT OF THE

PANEL VIA TROUBLE SILENCE BUTTON OS REQUIRED

TO SILENCE THIS TROUBLE PIEZO, IF PERSISTENT

RECOMMEND UPGRADING PANEL WITH AN ONBOARD

DIALER WHICH MAY HELP WITH THIS ISSUE, AND ALSO

LOG THE TROUBLE SIGNALS TO REVIEW AT A LATER

DATE TO HELP TROUBLE SHOOT THE PROBLEM.

** DETECTORS APPEAR TO BE DUE FOR SENSITIVITY

TESTING IT WAS NOTED THAT THE DETECTORS ON SITE

HAVE A FEATURE WHIH ALLOWS THE TECHNICIAN TO

NOTE THE NUMBER OF FLASHES ON THE LEDS

INDICATING HIGH SENSITIVITY.

System restored to normal operation

Date 09/25/2018 Time 13:58 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Pictures

Photo 1

Photo 1 Description Account info

Photo 2

Photo 2 Description Panel info and conductor integrity

Photo 3

Photo 3 Description Dialer info and conductor integrity

Photo 4

Photo 4 Description Horns and smokes tested on site

Photo 5

Photo 5 Description Audibles tested on battery backup

Photo 6

Photo 6 Description Elevator recalls on second floor smoke and equipment room only

Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Photo 7 Description Ambient Db

Photo 8 Description Alarm Db

Photo 9 Description Bell tested on battery backup

Notes and Recommendations

Notes and Recommendations

** NONE

Plan of Corrective Action:

**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A

Corrective Action and Date Taken:

**NONE TAKEN AT THIS TIME

Inspector Information

This testing was performed in accordance with (Standard/Edition)

CURRENT NFPA 72 STANDARDS

Name of Inspector

ALEXANDER MARTINEZ

License Number 10-009

Date 09/25/2018 Time 15:12 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26

Inspector Signature

Inspector Signature

Owner or Representative Information

Name of Owner or Representative

LOGAN WILD

Date 09/25/2018

Time 15:12

Owner or Representative Signature

Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link