FA_18-0925_4523_WRG_office.pdf
PDF 1 MB Posted
- Attached to
- TNF Fire Alarm Annual Inspection Federal contract opportunity
- Solicitation number
- 12010919Q0068
About this file
Wrangell Office
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0924_4506_KTN_whse.pdf | ||
| FA_18-0919_4480_JNU_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0926_4530_TNB_office.pdf | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4507_KTN_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0919_4470_MGVC.PDF | ||
| FA_18-0917_4461_JNU_FSL.PDF | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf | ||
| wage_determination.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass Wrangell Office
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/25/2018
Time 11:11
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
LOGAN WILD
Telephone
Fax None Email None
Property Name (User)
Name Wrangell Office Address 1 525 Bennett Street Address 2
City Wrangell State
AK
Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Zip 99929
Monitoring Entity
Contact / Agency
LJ ALARM
Telephone 789-7940
Monitoring Account Ref. No.
Approving Agency
Contact
USDA
Telephone
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 11:12
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
ESL
Control Panel Model
Control Panel Location Boiler room
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
IDC
Number of Circuits
Software Rev.
N/A Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised None
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
2 2 2 0 CLASS B
Smoke Detectors 17 17 17 0 CLASS B
Alarm Verification
Alarm Verification feature is Disabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horn/Strobes 13 13 13 0 CLASS B Bells 1 1 1 0 CLASS B Horns 1 1 1 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level Entire Building 56 85
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
Elevator Recall 2 2 2 0
Initiating Device Circuit
Quantity
Style(s)
CLASS B
Signaling Line Circuits http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
CLASS B
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard)
NEXT TO PANEL
Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location
DID NOT CONFIRM
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel IN PANEL 2010 DUE
FOR
REPLACEMENT
STATUS 2
12/7 Sealed Lead- Acid
N/A N/A N/A
Dialer In dialer 2010 DUE
FOR
REPLACEMENT
STATUS 2
12/7 x1 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Same 120 20 BREAKER 20 Same Same 120 20 BREAKER 20 Same
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
None
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
System Tests And Inspections Type Visual Functional Comments
Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring
Secondary Power Type Visual Functional Comments
Battery Condition DUE FOR REPLACEMENT Load Voltage LOW Discharge Test BORDER LINE Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Notification Appliances Notification Appliances Visual Functional Comments
Audible Audible/Visual Combination Visible
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
PULLS HALLS
ENTRY AND
EXITS
Pass
SMOKES CEILINGS
LOCATED
THROUGH
OUT
COMPLEX
Pass NOTICED
SMOKES
APPEAR TO
BE DUE FOR
SENSITIVITY
TESTING THE
LED TEST
FUNCTION
ON
MAJORITY
OF SMOKES
WERE
FLASHING 8
TIMES
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Device Type
Loc. & S/N Visual Check
Functional Test
Factory Setting
Measured Setting
Pass/Fail Comments
INDICATING
HIGHER
THEN
NORMAL
SENSITIVITY
Emergency Communications Equipment Type Visual Functional Comments
Call-in Signal
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 10:58 Alarm Restoration Yes 10:59 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ ALARM 11:58
Deficiencies and Issues
The following did not operate correctly
** BATTERIES DUE FOR REPLACEMENT IN THE MAIN
FACP AND DIALER THIS IS A STATUS 2 REQUIREMENT IT
WAS NOTED THAT THE PANEL AND DIALER KEEP GOING
IN AND OUT OF TROUBLE WHICH THIS MAY BE THE
FIRST OLSCE TO REMEDY THAT ISSUE, IF DIALER IS
GOING IN AND OUT OF TROUBLE IT IS POSSIBLE THE
PHONE LINES MAY BE AN ISSUE AND OR IF FREQUENT
BROWN OUTS HAPPEN THIS WILL ALSO CAUSE THE
DIALER TO GO INTO TROUBLE INDICATING A AC
FAILURE AND PHYSICAL ACKNOWLEDGEMENT OF THE
PANEL VIA TROUBLE SILENCE BUTTON OS REQUIRED
TO SILENCE THIS TROUBLE PIEZO, IF PERSISTENT
RECOMMEND UPGRADING PANEL WITH AN ONBOARD
DIALER WHICH MAY HELP WITH THIS ISSUE, AND ALSO
LOG THE TROUBLE SIGNALS TO REVIEW AT A LATER
DATE TO HELP TROUBLE SHOOT THE PROBLEM.
** DETECTORS APPEAR TO BE DUE FOR SENSITIVITY
TESTING IT WAS NOTED THAT THE DETECTORS ON SITE
HAVE A FEATURE WHIH ALLOWS THE TECHNICIAN TO
NOTE THE NUMBER OF FLASHES ON THE LEDS
INDICATING HIGH SENSITIVITY.
System restored to normal operation
Date 09/25/2018 Time 13:58 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Pictures
Photo 1
Photo 1 Description Account info
Photo 2
Photo 2 Description Panel info and conductor integrity
Photo 3
Photo 3 Description Dialer info and conductor integrity
Photo 4
Photo 4 Description Horns and smokes tested on site
Photo 5
Photo 5 Description Audibles tested on battery backup
Photo 6
Photo 6 Description Elevator recalls on second floor smoke and equipment room only
Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Photo 7 Description Ambient Db
Photo 8 Description Alarm Db
Photo 9 Description Bell tested on battery backup
Notes and Recommendations
Notes and Recommendations
** NONE
Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/25/2018 Time 15:12 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04523 www.gocanvas.com 3748F474-5031-4233-A110-BF4CBB4BAA26
Inspector Signature
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
LOGAN WILD
Date 09/25/2018
Time 15:12
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link