FA_18-0917_4461_JNU_FSL.PDF
PDF 2 MB Posted
- Attached to
- TNF Fire Alarm Annual Inspection Federal contract opportunity
- Solicitation number
- 12010919Q0068
About this file
Juneau FSL
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0924_4506_KTN_whse.pdf | ||
| FA_18-0925_4523_WRG_office.pdf | ||
| FA_18-0926_4530_TNB_office.pdf | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0919_4480_JNU_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4507_KTN_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0919_4470_MGVC.PDF | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| wage_determination.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass Juneau Science Lab
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/17/2018
Time 13:04
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
Telephone
Fax None Email None
Property Name (User)
Name Juneau Science Lab Address 1 11175 Auke Lake Way Address 2
City Juneau State
AK
Contact
Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Zip 99801
Monitoring Entity
Contact / Agency
LJ ALARM
Monitoring Account Ref. No.
Approving Agency
Contact
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 11:31
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
SIMPLEX
Control Panel Model
4100EX
Control Panel Location
DOWNSTAIRS ELECTRICAL ROOM
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
SLC
Number of Circuits
Software Rev.
2.2.0 Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised Last annual inspection
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
6 6 6 0 CLASS B
Smoke Detectors 48 48 48 0 CLASS B Heat Detectors ON SLC 10 10 10 0 CLASS B Heat Detectors SPOT TYPE 3 3 3 0 CLASS B Duct Detectors 2 2 2 0 CLASS B
Alarm Verification
Alarm Verification feature is Disabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horn/Strobes 43 43 43 0 CLASS B Strobes 4 4 4 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level Entire building 55-58 89-100
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
Elevator Recall 2 2 2 0 Other SHUNT TRIP 1 1 1 0 AHU Shutdown 2 2 2 0
Initiating Device Circuit
Quantity
Style(s)
CLASS B
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Signaling Line Circuits
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
CLASS B
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard) L1E Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel In facp 3/13 12/33 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Next to facp 120 20 BREAKER 20 Same as above
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
System Tests And Inspections http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Type Visual Functional Comments Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches
Secondary Power Type Visual Functional Comments
Battery Condition Load Voltage Discharge Test Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Remote Annunciators Remote Annunciators Location Visual Functional Comments
Remote Annunciator ENTRY WAY
Notification Appliances Notification Appliances Visual Functional Comments
Audible/Visual Combination Visible
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
PULLS Entry exit ways Pass
SMOKES LOCATED ON
CEILINGS
THROUGH
OUT
COMPLEX
Pass
HEATS MECHANICAL
SPACES
Pass
DUCT
DETECTORS
AHU 1 AND 2 Pass
Emergency Communications Equipment Type Visual Functional Comments
Call-in Signal
Interface Equipment & Special Hazard Systems http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
(Specify) Visual Device Operation
Simulated Operation
Special Procedures
Comments
EPO SHUTDOWN DID NOT TEST
DUE TO TIED INTO
USDA SERVERS
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 11:48 Trouble Signal Yes 18:48 Alarm Restoration Yes 11:49 Trouble Signal Restoration Yes 11:49 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ ALARM 18:49
Deficiencies and Issues
The following did not operate correctly
EVERYTHING OPERATED AND PERFORMED PER NFPA
72 STANDARDS
System restored to normal operation
Date 09/17/2018 Time 18:49 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Pictures
Photo 1
Photo 1 Description Pulls tested
Photo 2
Photo 2 Description Annunciator
Photo 3
Photo 3 Description Horn strobes tested
Photo 4
Photo 4 Description Smokes
Photo 5
Photo 5 Description Batteries die for replacement
Photo 6
Photo 6 Description Power in proper state / circuit not labeled in red and or breaker lock
Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Photo 7 Description Location of duct detector
Photo 8 Description Test switch
Photo 9 Description Tested on battery backup
Photo 10 Photo 11 Photo 12
Photo 10 Description Battery trouble
Photo 11 Description Device count
Photo 12 Description Version of system
Photo 13 Photo 14 Photo 15 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Photo 13 Description Audibles tested
Photo 14 Description Elevator shunt trip tested
Photo 15 Description Heats on site
Notes and Recommendations
Notes and Recommendations
BATTERIES ARE GETTING REPLACED BY RANDY
Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/17/2018 Time 18:52
Inspector Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04461 www.gocanvas.com 452BF92E-B2E3-4F70-A754-7FF0399753DB
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
RANDY ON SITE MAINT
Date 09/17/2018
Time 18:52
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link