FA_18-0925_4524_WRG_whse.pdf

PDF 2 MB Posted

Attached to
TNF Fire Alarm Annual Inspection Federal contract opportunity
Solicitation number
12010919Q0068
Issued by
Department of Agriculture Forest Service R10-Alaska Region

About this file

Wrangell Warehouse

View the file

Other files for this federal contract opportunity

Other files attached to TNF Fire Alarm Annual Inspection, newest first.
File Type Posted
FA_18-0924_4506_KTN_whse.pdf PDF
FA_18-0925_4523_WRG_office.pdf PDF
FA_18-0919_4480_JNU_office.pdf PDF
FA_18-0926_4531_TNB_whse.pdf PDF
FA_18-0924_4515_SEADC.PDF PDF
FA_18-0926_4530_TNB_office.pdf PDF
FA_18-0927_4534_CRG_office.pdf PDF
FA_18-0919_4475_JNU_bunkhouse.pdf PDF
FA_18-0924_4507_KTN_bunkhouse.pdf PDF
FA_18-0924_4505_KTN_office.pdf PDF
FA_18-0815_4396_Sitka_office.pdf PDF
SKM_C45819062319260.pdf PDF
FA_18-0919_4470_MGVC.PDF PDF
FA_18-0917_4461_JNU_FSL.PDF PDF
FA_18-0918_4463_HNH_office.pdf PDF
12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf PDF
wage_determination.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service - Tongass Wrangell Warehouse

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com

Fire Alarm Inspection Report Status

Status

Date 09/25/2018

Time 12:09

Owner /Client / Contracting Agency

Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2

City Sitka State

AK

Zip 99835

Representative

LOGAN WILD

Telephone

Fax None Email None

Property Name (User)

Name Wrangell Warehouse Address 1 525 Bennett Street Address 2

City Wrangell State

AK

Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Zip 99929

Monitoring Entity

Contact / Agency None

Monitoring Account Ref. No.

Approving Agency

Contact

USDA

Service

Service Annually

Other (Specify)

Prior To Any Testing Notifications Are

Made To Other (Specify) Yes/No Who Time

Building Occupants Yes ON SITE STAFF 12:10

Type Transmission

Type Transmission Other

Other (Specify) None

Control Panel

Control Panel Manufacturer

SILENT KNIGHT

Control Panel Model

Control Panel Location

NEAR BOILER ROOM WALL SIDE OF

BUILDING IN CORNER

Is Panel in "normal" conditions upon arrival?

Yes Circuit Styles

IDC

Number of Circuits

Software Rev.

N/A Last Date System Had Any Service Performed

PREVIOUS ANNUAL INSPECTION

Last Date that Any Software or Configuration Was Revised None

Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Printer Model

Location

Did Printer Function Properly

Is Printer Supervised?

Alarm-Initiating Devices and Circuit Information Description If Other

(Specify) Quantity of

Devices Installed

Quantity of Devices Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Manual Fire Alarm Boxes

4 4 4 0 CLASS B

Smoke Detectors 5 5 5 0 CLASS B Heat Detectors 3 3 3 0 CLASS B

Alarm Verification

Alarm Verification feature is Disabled

Alarm Notification Appliances & Circuit Info Description If Other

(Specify) Quantity of Appliances

Installed

Quantity of Appliances

Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Horns 3 3 3 0 CLASS B Decibel Levels

Location Description Ambient Level Alarm Level Entire building 51 94

Alarm Notification Circuits

No. of alarm notification appliance circuits

Are circuits monitored for integrity?

Yes

Initiating Device Circuit

Quantity

Style(s)

CLASS B

Signaling Line Circuits

Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity

Style(s)

CLASS B

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

System Primary Power Supply

(a) Primary (Main) Location (of Primary Supply Panelboard)

NEXT TO FACP

Nominal Voltage 120/208

Amps Overcurrent Protection Type

BREAKER

Overcurrent Protection Amps

Disconnecting Means Location Panel m 14

Secondary (standby) Power Supply Type Location Battery

Dated:

Storage Battery:

Amp Hour Rating

Battery Type

Other Battery

Type

Calculated capacity in Amp-Hours to operate system for 24 hours.

Calculated capacity in Amp-Hours to operate system for 60 hours.

Control Panel In panel 10/11 DUE

FOR

REPLACEMENT

STATUS 2

12/7 Sealed Lead- Acid

N/A N/A N/A

Secondary (standby) Power Primary Power Supply Location of

Primary Power Supply

(Distribution Panel)

Nominal Voltage of Primary Power

Supply

Amps of Primary Power Supply

Overcurrent Protection Type

Overcurrent Protection Amps

Disconnecting Means Location

Same 120 20 BREAKER 20 Same

Generator System

Engine-driven generator dedicated to fire alarm system.

Location of fuel storage:

Other Backup

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

None

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

System Tests And Inspections Type Visual Functional Comments

Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Type Visual Functional Comments Disconnect Switches Ground-Fault Monitoring

Secondary Power Type Visual Functional Comments

Battery Condition DUE FOR REPLACEMENT

STATUS 2

Load Voltage LOW Discharge Test LOW Charger Test

Transient Suppressors

Transient Suppressors Visual

Comments

Notification Appliances Notification Appliances Visual Functional Comments

Audible

Initiating & Supervisory Device Tests & Inspection Device

Type Loc. & S/N Visual

Check Functional

Test Factory Setting

Measured Setting

Pass/Fail Comments

SMOKES THROUGH

OUT

WAREHOUSE

Pass ONE IN

WOOD SHOP

AREA WAS IN

ALARM ON

ARRIVAL

APPEARS IT

IS DUE FOR

SENSITIVITY

TESTING OR

REPLACEMENT

IF

CONTINUES

TO FALSE

ALARM

PULLS Entry and exit Pass

HEATS SPOT TYPE

NEAR

MECHANICAL

AND

STORAGE

AREAS

Fail APPEARS

THESE ARE

DUE FOR

TEST OR

REPLACEMENT

Notifications That Testing is Complete Notification Given

To Other (Specify) Yes/No Who Time

Building Occupants Yes On site personnel 13:05 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Deficiencies and Issues

The following did not operate correctly

** APPEARS SMOKES MAY BE DUE FOR SENSITIVITY

TESTING AND OR ONE DUE FOR REPLACEMENT IN THE

WOOD SHOP AREA ON ARRIVAL PANEL WAS IN ALARM

AND SILENCED POSSIBLE NUISANCE ALARM SMOKE

DETECTOR

** HEAT DETECTORS ARE DUE FOR TEST OR

REPLACEMENT OVER FIFTEEN YEARS OLD

** BATTERIES ARE DUE FOR REPLACEMENT STATUS 2

System restored to normal operation

Date 09/25/2018 Time 14:05 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Pictures

Photo 1

Photo 1 Description Heats due for test or replacement spot type 135

Photo 2

Photo 2 Description Smokes tested on site

Photo 3

Photo 3 Description Horns tested on site

Photo 4

Photo 4 Description Smokes tested on site

Photo 5

Photo 5 Description

SMOKE IN ALARM ON ARRIVAL AND

SILENCED DUE FOR REPLACEMENT

OR SENSITIVITY TESTING

Photo 6

Photo 6 Description Heat on site due for test or replacement http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Photo 7 Photo 8 Photo 9

Photo 7 Description Pull stations tested on site

Photo 8 Description Outside horn tested

Photo 9 Description Panel info

Photo 10 Photo 11 Photo 12

Photo 10 Description Panel conductor integrity

Photo 11 Description Power supply

Photo 12 Description Horn tested

Photo 13 Photo 14 Photo 15 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

Photo 13 Description Smokes tested on site

Photo 14 Description Batteries due for replacement

Photo 15 Description Ambient Db

Photo 16

Photo 16 Description Alarm Db

Notes and Recommendations

Notes and Recommendations ** RECOMMEND TYING ALARM RELAY INTO PANEL TO COMMUNICATE WITH OTHER MAIN OFFICE PANEL AS BOT BUILDINGS ARE CONNECTED VIA A ROOF BREEZEWAY AND TO EXPEDITE EMERGENCY RESPONSE IN THE EVENT

OF A FIRE IN THE WAREHOUSE

Plan of Corrective Action:

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04524 www.gocanvas.com F56A7B5D-DE90-4B67-BFB9-A2A77E72AD7A

**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A

Corrective Action and Date Taken:

**NONE TAKEN AT THIS TIME

Inspector Information

This testing was performed in accordance with (Standard/Edition)

CURRENT NFPA 72 STANDARDS

Name of Inspector

ALEXANDER MARTINEZ

License Number 10-009

Date 09/25/2018 Time 15:14

Inspector Signature

Inspector Signature

Owner or Representative Information

Name of Owner or Representative

LOGAN WILD

Date 09/25/2018

Time 15:14

Owner or Representative Signature

Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

File details come from the government source that posted it.