FA_18-0919_4470_MGVC.PDF
PDF 2 MB Posted
- Attached to
- TNF Fire Alarm Annual Inspection Federal contract opportunity
- Solicitation number
- 12010919Q0068
About this file
Mendenhall Glacier Visitor Center
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0924_4506_KTN_whse.pdf | ||
| FA_18-0925_4523_WRG_office.pdf | ||
| FA_18-0919_4480_JNU_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0926_4530_TNB_office.pdf | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4507_KTN_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0917_4461_JNU_FSL.PDF | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf | ||
| wage_determination.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass MG Visitors Center
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/19/2018
Time 09:23
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
Telephone
Fax None Email None
Property Name (User)
Name MG Visitors Center Address 1 600 Glacier Spur Road Address 2
City Juneau State
AK
Contact
Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Zip 99801
Monitoring Entity
Contact / Agency
LJ ALARM
Monitoring Account Ref. No.
UNKNOWN
Approving Agency
Contact
USDA
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 09:26
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
SIMPLEX
Control Panel Model 4100U
Control Panel Location
1ST FLOOR NEXT TO MANAGERS
OFFICE
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
SLC
Number of Circuits
Software Rev.
N/A Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised
APRIL 2018
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
6 6 6 0 CLASS B
Smoke Detectors 9 9 9 0 CLASS B Duct Detectors 6 6 6 0 CLASS B
Alarm Verification
Alarm Verification feature is Enabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horn/Strobes 10 10 10 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level
ENTIRE BUILDING 52 102
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
Elevator Recall 3 3 3 0 Door Holders 1 1 1 0 AHU Shutdown 4 4 4 0
Initiating Device Circuit
Quantity
Style(s)
CLASS B
Signaling Line Circuits http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
CLASS B
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard)
IN BOILER RM
Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location
EM 15
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel IN FACP 8/14 12/33 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Same as above 120 20 BREAKER 20 Em 15
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
None
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
System Tests And Inspections http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Type Visual Functional Comments Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring
Secondary Power Type Visual Functional Comments
Battery Condition Load Voltage Discharge Test Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Notification Appliances Notification Appliances Visual Functional Comments
Audible Audible/Visual Combination
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
PULLS ENTRY AND
EXIT
Pass
SMOKES CEILINGS
LOCATED-
THROUGH
OUT
Pass
DUCT
DETECTORS
AHUS Pass
Emergency Communications Equipment Type Visual Functional Comments
Call-in Signal
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 09:49 Alarm Restoration Yes 09:50 Trouble Signal Yes 09:51 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Type of Signal Yes/No Time Comments Trouble Signal Restoration Yes 09:52 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ ALARM 09:50
Deficiencies and Issues
The following did not operate correctly
** HEAT BASE IN BOILER NEEDS REPLACEMENT AS IT IS
CURRENTLY HANGING FROM CONDUCTORS
** HORN STROBE FAILED NEXT TO MANAGERS OFFICE
OUTSIDE BOILER RM ENTRY DOORS RECOMMEND
REPLACEMENT
System restored to normal operation
Date 09/19/2018 Time 09:50 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Pictures
Photo 1
Photo 1 Description Power supply
Photo 2
Photo 2 Description Dialer sent signals and went into trouble
Photo 3
Photo 3 Description Heats tested
Photo 4
Photo 4 Description Duct Detectors tested
Photo 5
Photo 5 Description Base needs replacement on heat detector
Photo 6
Photo 6 Description Pull stations tested on site
Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Photo 7 Description Smokes on site
Photo 8 Description
DBS AMBIENT
Photo 9 Description
DBS IN ALARM
Photo 10 Photo 11 Photo 12
Photo 10 Description
DBS
Photo 11 Description
FAILED HORN STROBE
Photo 12 Description
FAILED HORN STROBE
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Photo 13 Photo 14 Photo 15
Photo 13 Description
CONDUCTOR INTEGRITY
Photo 14 Description
BATTERY INFO
Photo 15 Description
SYSTEM GREEN
Photo 16
Photo 16 Description
SYSTEM TAGGED
Notes and Recommendations http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04470 www.gocanvas.com 387177D2-40DF-4570-8912-9CE70817F4C2
Notes and Recommendations
APPEARS PANEL MAY HAVE BEEN UPGRADED ALSO ELEVATORS HAVE BEEN UPGRADED
Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/19/2018 Time 09:56
Inspector Signature
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
LOGAN WILD
Date 09/19/2018
Time 09:57
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link