Juneau Bunkhouse

View the file

Other files for this federal contract opportunity

Other files attached to TNF Fire Alarm Annual Inspection, newest first.
File Type Posted
FA_18-0924_4506_KTN_whse.pdf PDF
FA_18-0925_4523_WRG_office.pdf PDF
FA_18-0926_4530_TNB_office.pdf PDF
FA_18-0927_4534_CRG_office.pdf PDF
FA_18-0919_4480_JNU_office.pdf PDF
FA_18-0925_4524_WRG_whse.pdf PDF
FA_18-0926_4531_TNB_whse.pdf PDF
FA_18-0924_4515_SEADC.PDF PDF
FA_18-0924_4507_KTN_bunkhouse.pdf PDF
FA_18-0924_4505_KTN_office.pdf PDF
FA_18-0815_4396_Sitka_office.pdf PDF
SKM_C45819062319260.pdf PDF
FA_18-0919_4470_MGVC.PDF PDF
FA_18-0917_4461_JNU_FSL.PDF PDF
FA_18-0918_4463_HNH_office.pdf PDF
wage_determination.pdf PDF
12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service - Tongass Juneau Bunkhouse

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com

Fire Alarm Inspection Report Status

Status

Date 09/19/2018

Time 14:55

Owner /Client / Contracting Agency

Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2

City Sitka State

AK

Zip 99835

Representative

Telephone

Fax

Email

Property Name (User)

Name Juneau Bunkhouse Address 1 8490 Mendenhall Loop Road Address 2

City Juneau State

AK

Contact

Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

Zip 99801

Monitoring Entity

Contact / Agency LJ Alarms

Monitoring Account Ref. No.

Approving Agency

Contact

Service

Service Annually

Other (Specify)

Prior To Any Testing Notifications Are

Made To Other (Specify) Yes/No Who Time

Monitoring Entity Yes 14:56 Building Management Yes 14:56

Type Transmission

Type Transmission Digital

Other (Specify)

Control Panel

Control Panel Manufacturer

SIMPLEX

Control Panel Model

Control Panel Location

LAUNDRY ROOM

Is Panel in "normal" conditions upon arrival?

YES

Circuit Styles

SLC

Number of Circuits

Software Rev.

N/A Last Date System Had Any Service Performed Last Date that Any Software or Configuration Was Revised N/A

Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

Printer Model N/A Location N/A

Did Printer Function Properly N/A Is Printer Supervised?

N/A

Alarm-Initiating Devices and Circuit Information Description If Other

(Specify) Quantity of

Devices Installed

Quantity of Devices Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Smoke Detectors 120v SMOKE

DETECTORS

MONITORED

THROUGH

MODULE

10 10 10 0

Alarm Verification

Alarm Verification feature is

Alarm Notification Appliances & Circuit Info Description If Other

(Specify) Quantity of Appliances

Installed

Quantity of Appliances

Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Bells 2 2 2 0 Horn/Strobes 6 6 6 0

Alarm Notification Circuits

No. of alarm notification appliance circuits

Are circuits monitored for integrity?

Initiating Device Circuit

Quantity

Style(s)

Signaling Line Circuits

Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity

Style(s)

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

System Primary Power Supply

(a) Primary (Main) Location (of Primary Supply Panelboard)

LAUNDRY ROOM

Nominal Voltage 120v

Amps

Overcurrent Protection Type

BREAKER

Overcurrent Protection Amps

Disconnecting Means Location

Secondary (standby) Power Supply Type Location Battery

Dated:

Storage Battery:

Amp Hour Rating

Battery Type

Other Battery

Type

Calculated capacity in Amp-Hours to operate system for 24 hours.

Calculated capacity in Amp-Hours to operate system for 60 hours.

Control Panel IN PANEL 2017 7 Sealed Lead- Acid

Secondary (standby) Power Primary Power Supply Location of

Primary Power Supply

(Distribution Panel)

Nominal Voltage of Primary Power

Supply

Amps of Primary Power Supply

Overcurrent Protection Type

Overcurrent Protection Amps

Disconnecting Means Location

Generator System

Engine-driven generator dedicated to fire alarm system.

N/A

Location of fuel storage:

N/A

Other Backup

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

N/A

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

System Tests And Inspections Type Visual Functional Comments

Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

Type Visual Functional Comments Ground-Fault Monitoring

Transient Suppressors

Transient Suppressors Visual

Comments

Notification Appliances Notification Appliances Visual Functional Comments

Audible/Visual Combination

Central Station Monitoring Type of Signal Yes/No Time Comments

Alarm Signal Yes 15:03 Alarm Restoration Yes 15:03 Notifications That Testing is Complete Notification Given

To Other (Specify) Yes/No Who Time

Building Management Yes 15:03 Monitoring Agency Yes 15:03 Fire Department Yes 15:03

Deficiencies and Issues

The following did not operate correctly

System restored to normal operation

Date 09/19/2018 Time 15:03 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

Pictures

Photo 1

Photo 1 Description

FACP IN NORMAL CONDITION

PRYOR TO LEAVING

Photo 2 Photo 3

Photo 3 Description

HORNSTROBES IN COMMON AREAS

Photo 4

Photo 4 Description

BREAKER PANEL FOR FACP

Photo 5 Photo 6

Photo 6 Description

HANGING DETECTOR

Photo 7 Photo 8 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

Photo 8 Description

SMOKE DETECTORS IN COMMON

AREAS

Notes and Recommendations

Notes and Recommendations IT WAS NOTED AND DETECTED THAT THERE ARE STAND ALONE SMOKE DETECTORS IN UNITS. DETECTORS DATE BACK TO 2005, RECOMMEND REPLACING ALL SMOKE DETECTORS PER NFPA 72. DETECTORS DO NOT REPORT BACK TO PANEL. DETECTOR IN STORAGE NEXT TO LAUNDRY IN 8-PLEX IS HANGING. NOT ABLE TO ACCESS ALL

UNITS, UNDETERMINED AMOUNT OF DETECTORS.

Plan of Corrective Action:

CONTACT TAYLOR FIRE 907-373-1760

Corrective Action and Date Taken:

Inspector Information

This testing was performed in accordance with (Standard/Edition)

NFPA 72

Name of Inspector

Date 09/19/2018 Time http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04475 www.gocanvas.com DC021B2F-957C-4678-BE32-57F63B419460

ALEXANDER MARTINEZ

License Number 10-009

15:10

Inspector Signature

Inspector Signature

Owner or Representative Information

Name of Owner or Representative

Date 09/19/2018

Time 15:10

Owner or Representative Signature

Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link