FA_18-0919_4480_JNU_office.pdf

PDF 3 MB Posted

Attached to
TNF Fire Alarm Annual Inspection Federal contract opportunity
Solicitation number
12010919Q0068
Issued by
Department of Agriculture Forest Service R10-Alaska Region

About this file

Juneau Office

View the file

Other files for this federal contract opportunity

Other files attached to TNF Fire Alarm Annual Inspection, newest first.
File Type Posted
FA_18-0926_4530_TNB_office.pdf PDF
FA_18-0927_4534_CRG_office.pdf PDF
FA_18-0924_4506_KTN_whse.pdf PDF
FA_18-0925_4523_WRG_office.pdf PDF
FA_18-0919_4475_JNU_bunkhouse.pdf PDF
FA_18-0924_4507_KTN_bunkhouse.pdf PDF
FA_18-0924_4505_KTN_office.pdf PDF
FA_18-0925_4524_WRG_whse.pdf PDF
FA_18-0926_4531_TNB_whse.pdf PDF
FA_18-0924_4515_SEADC.PDF PDF
FA_18-0919_4470_MGVC.PDF PDF
FA_18-0917_4461_JNU_FSL.PDF PDF
FA_18-0815_4396_Sitka_office.pdf PDF
SKM_C45819062319260.pdf PDF
FA_18-0918_4463_HNH_office.pdf PDF
wage_determination.pdf PDF
12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service - Tongass Juneau Office

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com

Fire Alarm Inspection Report Status

Status

Date 09/19/2018

Time 11:50

Owner /Client / Contracting Agency

Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2

City Sitka State

AK

Zip 99835

Representative

Telephone

Fax None Email None

Property Name (User)

Name Juneau Office Address 1 8510 Mendenhall Loop Road Address 2

City Juneau State

AK

Contact

Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Zip 99801

Monitoring Entity

Contact / Agency

LJ ALARM

Telephone 789-7940

Monitoring Account Ref. No.

Approving Agency

Contact

USDA

Telephone

Service

Service Annually

Other (Specify)

Prior To Any Testing Notifications Are

Made To Other (Specify) Yes/No Who Time

Monitoring Entity Yes LJ ALARM 11:51

Type Transmission

Type Transmission Digital

Other (Specify)

Control Panel

Control Panel Manufacturer

SIMPLEX

Control Panel Model

Control Panel Location

FRONT ENTRY NEAR RECEPTION

Is Panel in "normal" conditions upon arrival?

Yes Circuit Styles

SLC

Number of Circuits

Software Rev.

N/A Last Date System Had Any Service Performed

PREVIOUS ANNUAL INSPECTION

Last Date that Any Software or Configuration Was Revised Unknown

Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Printer Model None Location

Did Printer Function Properly

Is Printer Supervised?

Alarm-Initiating Devices and Circuit Information Description If Other

(Specify) Quantity of

Devices Installed

Quantity of Devices Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Manual Fire Alarm Boxes

8 8 8 0 CLASS B

Smoke Detectors 48 48 47 1 CLASS B Heat Detectors 4 4 4 0 CLASS B

Alarm Verification

Alarm Verification feature is Disabled

Alarm Notification Appliances & Circuit Info Description If Other

(Specify) Quantity of Appliances

Installed

Quantity of Appliances

Tested

Quantity of Devices Passed

Quantity of Devices

Failed

Circuit Style

Horn/Strobes 26 26 26 0 CLASS B Strobes 9 9 9 0 CLASS B Decibel Levels

Location Description Ambient Level Alarm Level Entire Complex 56 104

Alarm Notification Circuits

No. of alarm notification appliance circuits

Are circuits monitored for integrity?

Yes

Control Equipment Description of

Equipment If Other (Specify)

Quantity Installed

Quantity Tested Quantity Passed Quantity Failed

Elevator Recall 3 3 3 0 Other SHUNT TRIP HEAT

FOR ELEVATOR

MACHINE RM

1 1 1 0

Initiating Device Circuit

Quantity

Style(s)

CLASS B

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Signaling Line Circuits

Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity

Style(s)

CLASS B

System Primary Power Supply

(a) Primary (Main) Location (of Primary Supply Panelboard)

WITHIN ELECTRICAL RM ON FIRST

FLOOR ACROSS FROM ELEVATOR

Nominal Voltage 120/208

Amps Overcurrent Protection Type

BREAKER

Overcurrent Protection Amps

Disconnecting Means Location

PPE #9

Secondary (standby) Power Supply Type Location Battery

Dated:

Storage Battery:

Amp Hour Rating

Battery Type

Other Battery

Type

Calculated capacity in Amp-Hours to operate system for 24 hours.

Calculated capacity in Amp-Hours to operate system for 60 hours.

Control Panel In facp 9/16 12/7 Sealed Lead- Acid

N/A N/A N/A

Secondary (standby) Power Primary Power Supply Location of

Primary Power Supply

(Distribution Panel)

Nominal Voltage of Primary Power

Supply

Amps of Primary Power Supply

Overcurrent Protection Type

Overcurrent Protection Amps

Disconnecting Means Location

Same as main power above

120 20 BREAKER 20 PPE 9

Generator System

Engine-driven generator dedicated to fire alarm system.

None

Location of fuel storage:

Other Backup

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

None

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

System Tests And Inspections Type Visual Functional Comments

Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring

Secondary Power Type Visual Functional Comments

Battery Condition Load Voltage Discharge Test Charger Test

Transient Suppressors

Transient Suppressors Visual

Comments

Notification Appliances Notification Appliances Visual Functional Comments

Audible/Visual Combination Visible

Initiating & Supervisory Device Tests & Inspection Device

Type Loc. & S/N Visual

Check Functional

Test Factory Setting

Measured Setting

Pass/Fail Comments

PULLS Entry and Exit points

Pass

HEATS MECHANICAL

SPACES

Pass

SMOKES CEILINGS

LOCATED

THROUGH

OUT

Pass

Emergency Communications Equipment Type Visual Functional Comments

Call-in Signal

Central Station Monitoring Type of Signal Yes/No Time Comments

Alarm Signal Yes 11:10 Trouble Signal Yes 10:11 Alarm Restoration Yes 06:12 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Type of Signal Yes/No Time Comments Trouble Signal Restoration Yes 06:12 Notifications That Testing is Complete Notification Given

To Other (Specify) Yes/No Who Time

Monitoring Agency Yes LJ alarm 13:11

Deficiencies and Issues

The following did not operate correctly

** THERE WAS ONE SMOKE DETECTOR THAT APPEARED

TO NOT RESPOND TO TEST SMOKE COULD ONLY GET IT

TO GO INTO ALARM VIA TEST MAGNET IT SEEMS THE

DEVICE

MAY NEED TO BE REPLACED : MIDDLE SMOKE IN A106

STORAGE

System restored to normal operation

Date 09/19/2018 Time 13:11 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Pictures

Photo 1

Photo 1 Description Panel tagged

Photo 2

Photo 2 Description Room locations and smoke detector location descriptions need updating

Photo 3

Photo 3 Description System in the green upon completion

Photo 4

Photo 4 Description Power supply info

Photo 5

Photo 5 Description Power supply info

Photo 6 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Photo 6 Description

DBS

Photo 7 Photo 8 Photo 9

Photo 7 Description In alarm Db

Photo 8 Description Ambient DB

Photo 9 Description Breaker info

Photo 10 Photo 11 Photo 12 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Photo 10 Description System tested on battery

Photo 11 Description Shunt trip works

Photo 12 Description Elevator in normal state

Photo 13 Photo 14 Photo 15

Photo 13 Description Info

Photo 14 Description Heats on site

Photo 15 Description Panel info

Photo 16 Photo 17 Photo 18 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Photo 16 Description Conductor integrity

Photo 17 Description Strobes on site

Photo 18 Description Pull stations

Photo 19 Photo 20

Photo 19 Description Smokes

Photo 20 Description Horn strobes

Notes and Recommendations

Notes and Recommendations

** ROOM LIST AND SMOKE LOCATIONS NEED UPDATING

http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

No.

04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42

Plan of Corrective Action:

**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A

Corrective Action and Date Taken:

**NONE TAKEN AT THIS TIME

Inspector Information

This testing was performed in accordance with (Standard/Edition)

CURRENT NFPA 72 STANDARDS

Name of Inspector

ALEXANDER MARTINEZ

License Number 10-009

Date 09/19/2018 Time 13:19

Inspector Signature

Inspector Signature

Owner or Representative Information

Name of Owner or Representative Logan Wild Date 09/19/2018

Time 13:19

Owner or Representative Signature

Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link