Juneau Office
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0926_4530_TNB_office.pdf | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0924_4506_KTN_whse.pdf | ||
| FA_18-0925_4523_WRG_office.pdf | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4507_KTN_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0919_4470_MGVC.PDF | ||
| FA_18-0917_4461_JNU_FSL.PDF | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| wage_determination.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass Juneau Office
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/19/2018
Time 11:50
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
Telephone
Fax None Email None
Property Name (User)
Name Juneau Office Address 1 8510 Mendenhall Loop Road Address 2
City Juneau State
AK
Contact
Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Zip 99801
Monitoring Entity
Contact / Agency
LJ ALARM
Telephone 789-7940
Monitoring Account Ref. No.
Approving Agency
Contact
USDA
Telephone
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 11:51
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
SIMPLEX
Control Panel Model
Control Panel Location
FRONT ENTRY NEAR RECEPTION
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
SLC
Number of Circuits
Software Rev.
N/A Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised Unknown
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
8 8 8 0 CLASS B
Smoke Detectors 48 48 47 1 CLASS B Heat Detectors 4 4 4 0 CLASS B
Alarm Verification
Alarm Verification feature is Disabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horn/Strobes 26 26 26 0 CLASS B Strobes 9 9 9 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level Entire Complex 56 104
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
Elevator Recall 3 3 3 0 Other SHUNT TRIP HEAT
FOR ELEVATOR
MACHINE RM
1 1 1 0
Initiating Device Circuit
Quantity
Style(s)
CLASS B
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Signaling Line Circuits
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
CLASS B
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard)
WITHIN ELECTRICAL RM ON FIRST
FLOOR ACROSS FROM ELEVATOR
Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location
PPE #9
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel In facp 9/16 12/7 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Same as main power above
120 20 BREAKER 20 PPE 9
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
None
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
System Tests And Inspections Type Visual Functional Comments
Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring
Secondary Power Type Visual Functional Comments
Battery Condition Load Voltage Discharge Test Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Notification Appliances Notification Appliances Visual Functional Comments
Audible/Visual Combination Visible
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
PULLS Entry and Exit points
Pass
HEATS MECHANICAL
SPACES
Pass
SMOKES CEILINGS
LOCATED
THROUGH
OUT
Pass
Emergency Communications Equipment Type Visual Functional Comments
Call-in Signal
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 11:10 Trouble Signal Yes 10:11 Alarm Restoration Yes 06:12 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Type of Signal Yes/No Time Comments Trouble Signal Restoration Yes 06:12 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ alarm 13:11
Deficiencies and Issues
The following did not operate correctly
** THERE WAS ONE SMOKE DETECTOR THAT APPEARED
TO NOT RESPOND TO TEST SMOKE COULD ONLY GET IT
TO GO INTO ALARM VIA TEST MAGNET IT SEEMS THE
DEVICE
MAY NEED TO BE REPLACED : MIDDLE SMOKE IN A106
STORAGE
System restored to normal operation
Date 09/19/2018 Time 13:11 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Pictures
Photo 1
Photo 1 Description Panel tagged
Photo 2
Photo 2 Description Room locations and smoke detector location descriptions need updating
Photo 3
Photo 3 Description System in the green upon completion
Photo 4
Photo 4 Description Power supply info
Photo 5
Photo 5 Description Power supply info
Photo 6 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Photo 6 Description
DBS
Photo 7 Photo 8 Photo 9
Photo 7 Description In alarm Db
Photo 8 Description Ambient DB
Photo 9 Description Breaker info
Photo 10 Photo 11 Photo 12 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Photo 10 Description System tested on battery
Photo 11 Description Shunt trip works
Photo 12 Description Elevator in normal state
Photo 13 Photo 14 Photo 15
Photo 13 Description Info
Photo 14 Description Heats on site
Photo 15 Description Panel info
Photo 16 Photo 17 Photo 18 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Photo 16 Description Conductor integrity
Photo 17 Description Strobes on site
Photo 18 Description Pull stations
Photo 19 Photo 20
Photo 19 Description Smokes
Photo 20 Description Horn strobes
Notes and Recommendations
Notes and Recommendations
** ROOM LIST AND SMOKE LOCATIONS NEED UPDATING
http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04480 www.gocanvas.com F840EF82-C240-4AA5-AF09-E7FF4B239C42
Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/19/2018 Time 13:19
Inspector Signature
Inspector Signature
Owner or Representative Information
Name of Owner or Representative Logan Wild Date 09/19/2018
Time 13:19
Owner or Representative Signature