FA_18-0926_4530_TNB_office.pdf
PDF 2 MB Posted
- Attached to
- TNF Fire Alarm Annual Inspection Federal contract opportunity
- Solicitation number
- 12010919Q0068
About this file
Thorne Bay Office
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA_18-0924_4506_KTN_whse.pdf | ||
| FA_18-0925_4523_WRG_office.pdf | ||
| FA_18-0919_4480_JNU_office.pdf | ||
| FA_18-0925_4524_WRG_whse.pdf | ||
| FA_18-0926_4531_TNB_whse.pdf | ||
| FA_18-0924_4515_SEADC.PDF | ||
| FA_18-0927_4534_CRG_office.pdf | ||
| FA_18-0919_4475_JNU_bunkhouse.pdf | ||
| FA_18-0924_4507_KTN_bunkhouse.pdf | ||
| FA_18-0924_4505_KTN_office.pdf | ||
| FA_18-0815_4396_Sitka_office.pdf | ||
| SKM_C45819062319260.pdf | ||
| FA_18-0919_4470_MGVC.PDF | ||
| FA_18-0917_4461_JNU_FSL.PDF | ||
| FA_18-0918_4463_HNH_office.pdf | ||
| 12010919Q0068_Solicitation_for_Fire_Alarm_Inspection.pdf | ||
| wage_determination.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service - Tongass Thorne Bay Office
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
725 W. Wasair Dr. Wasilla, AK 99654 907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date 09/26/2018
Time 11:55
Owner /Client / Contracting Agency
Name USDA Forest Service - Tongass Address 1 2108 Halibut Point Rd Address 2
City Sitka State
AK
Zip 99835
Representative
LOGAN WILD
Telephone
Fax None Email None
Property Name (User)
Name Thorne Bay Office Address 1 1312 Federal Way Address 2
City Thorne Bay State
AK
Contact Same Telephone http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Zip 99919
Monitoring Entity
Contact / Agency
LJ ALARM
Monitoring Account Ref. No.
Approving Agency
Contact
USDA
Service
Service Annually
Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes LJ ALARM 11:06
Type Transmission
Type Transmission Digital
Other (Specify)
Control Panel
Control Panel Manufacturer
EST
Control Panel Model
EST1
Control Panel Location Front entry
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles Idc Number of Circuits
Software Rev.
N/A Last Date System Had Any Service Performed
PREVIOUS ANNUAL INSPECTION
Last Date that Any Software or Configuration Was Revised None
Printer http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Printer Model None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
5 5 5 0 CLASS B
Smoke Detectors 7 7 7 0 CLASS B Heat Detectors 1 1 1 0 CLASS B
Alarm Verification
Alarm Verification feature is Disabled
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horns 1 1 1 0 CLASS B Strobes 4 4 4 0 CLASS B Horn/Strobes 7 7 7 0 CLASS B Decibel Levels
Location Description Ambient Level Alarm Level Entire office 47 89
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
Elevator Recall 3 3 3 0
Initiating Device Circuit
Quantity
Style(s)
CLASS B
Signaling Line Circuits http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
CLASS B
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard) Boiler rm Nominal Voltage 120/208
Amps Overcurrent Protection Type
BREAKER
Overcurrent Protection Amps
Disconnecting Means Location Panel A 29
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel In panel 2013 DUE
FOR
REPLACEMENT
12/7 Sealed Lead- Acid
N/A N/A N/A
Dialer In panel 5/13 12/7 Sealed Lead- Acid
N/A N/A N/A
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Same 120 20 BREAKER 20 Same Same 120 20 BREAKER 20 Same
Generator System
Engine-driven generator dedicated to fire alarm system.
None
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
None Emergency system described in NFPA 70, Article 700 meets the performance requirements of Article 700 or 701
System Tests And Inspections Type Visual Functional Comments
Control Unit Interface Equipment Lamps/LEDS Fuses Primary Power Supply Trouble Signals Disconnect Switches Ground-Fault Monitoring
Secondary Power Type Visual Functional Comments
Battery Condition DUE FOR REPLACEMENT Load Voltage Discharge Test Charger Test
Transient Suppressors
Transient Suppressors Visual
Comments
Notification Appliances Notification Appliances Visual Functional Comments
Audible Audible/Visual Combination Visible
Initiating & Supervisory Device Tests & Inspection Device
Type Loc. & S/N Visual
Check Functional
Test Factory Setting
Measured Setting
Pass/Fail Comments
Smokes Ceilings located through out first floor front of elevator and elevator machine room
Pass
Heat Boiler rm Pass Due for test or replacement and only tested via shorted circuit for integrity http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Device Type
Loc. & S/N Visual Check
Functional Test
Factory Setting
Measured Setting
Pass/Fail Comments
Pulls Entry and exit Pass Emergency Communications Equipment
Type Visual Functional Comments Call-in Signal
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 12:17 Alarm Restoration Yes 12:18 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Monitoring Agency Yes LJ ALARM 12:30
Deficiencies and Issues
The following did not operate correctly
** HEAT DETECTOR DUE FOR TEST OR REPLACEMENT
** BATTERIES DUE FOR TEST OR REPLACEMENT
** UNCLEAR LAST TIME SMOKES HAVE BEEN
SENSITIVITY TESTED RECOMMEND PERFORMING THIS
ON NEXT ANNUAL INSPEXTION
System restored to normal operation
Date 09/26/2018 Time 13:17 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Pictures
Photo 1
Photo 1 Description Conductor integrity
Photo 2
Photo 2 Description Dialer conductor integrity and info
Photo 3
Photo 3 Description Panel info
Photo 4
Photo 4 Description Panel info
Photo 5
Photo 5 Description Pull stations on site
Photo 6
Photo 6 Description Horn tested on site
Photo 7 Photo 8 Photo 9 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Photo 7 Description Smokes tested on site
Photo 8 Description Horn strobes on site
Photo 9 Description Elevator recall tested
Photo 10 Photo 11 Photo 12
Photo 10 Description Heat due for test or replacement
Photo 11 Description Power supply
Photo 12 Description Heat circuit integrity
Photo 13 Photo 14 Photo 15 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Photo 13 Description Ambient Db
Photo 14 Description Alarm Db
Photo 15 Description Panel tagged and in the proper state
Notes and Recommendations
Notes and Recommendations None Plan of Corrective Action:
**CONTACT TAYLOR FIRE @907-373-1760 FOR P.O.C.A
Corrective Action and Date Taken:
**NONE TAKEN AT THIS TIME
Inspector Information
This testing was performed in accordance with (Standard/Edition)
CURRENT NFPA 72 STANDARDS
Name of Inspector
ALEXANDER MARTINEZ
License Number 10-009
Date 09/26/2018 Time 12:23
Inspector Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
04530 www.gocanvas.com B4DCAFC9-6AD4-4468-89A8-06FCD44E7426
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
LOGAN WILD
Date 09/26/2018
Time 13:23
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link