12-GE STARGUIDE Equipment Specification - RM 6341.pdf

PDF 2 MB Posted

Attached to
CSP - Nuclear Medicine Renovation & Systems Upgrade at Ben Taub Hospital for Harris Health (Estimated Budget - $4, 000, 000)
Solicitation number
26/0138
Issued by
Harris County, Texas

About this file

This is an equipment specification document for a GE STARGUIDE nuclear medicine imaging system installation at Ben Taub General Hospital in Houston, Texas, part of Harris Health's Nuclear Medicine Renovation & Systems Upgrade project with an estimated budget of $4,000,000. The document provides comprehensive technical specifications and site preparation requirements for the installation of a PET/CT imaging system, including detailed equipment layouts, dimensions, and interconnection diagrams. The specification document includes 18 sheets covering general notes, equipment layouts, radiation protection requirements, structural details, HVAC specifications, and complete electrical requirements. Key equipment components specified include a CT gantry weighing 3,240 kg, an NM gantry weighing 1,700 kg, a patient table, power distribution unit, uninterruptible power supply (UPS), operator console, and associated imaging stations. The document revision history indicates a final study approved on November 7, 2025, with revision B issued on March 3, 2026, reflecting architectural changes and main disconnect panel (MDP) repositioning.

The specification establishes critical site readiness requirements that must be fulfilled before equipment delivery, including floor specifications with maximum slope of 7 mm over 1,000 mm and concrete strength of minimum 30 MPa (4,350 psi). Electrical power requirements specify 380/400/420/440/460/480V three-phase power with maximum demand of 90 kVA (average continuous demand of 22 kVA) at 50/60 Hz frequency. The document mandates customer responsibility for radiation protection design by qualified radiological physicists, vibration mitigation through specialized engineering, structural support installation, and compliance with all local building codes and Nuclear Regulatory Commission regulations. Customer-supplied items include counter tops, lead glass windows, structural supports, wall-mounted equipment backing, electrical infrastructure (conduit, duct, junction boxes, and wiring), HVAC systems, and site preparation work. GE HealthCare provides pre-installation manuals and requires completion of Site Readiness Checklist (DOC2949061) and Worksheet (DOC2949068) before delivery. The document emphasizes that deviations from specifications must be reviewed in writing by GE's project manager prior to implementation.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01 - C1 - Cover Sheet 02 - C2 - Disclaimer - Site Readiness 03 - A1 - General Notes 04 - A2 - Equipment Layout 05 - A3 - Radiation Protection 06 - A4 - Radiation Protection Details 07 - A5 - Equipment Dimensions (1) 08 - A6 - Equipment Dimensions (2) 09 - A6 - Delivery

Houston, TX

Alvin Sumler

STARGUIDE

CPC

GE HealthCare does not take responsibility for any damages resulting from changes on drawings made by others. Errors may occur by not referring to the complete set of final issue drawings. GE HealthCare cannot accept responsibility for any damage due to the partial use of GE HealthCare final issue drawings, however caused. All dimensions are in millimeters unless otherwise specified. Do not scale from printed pdf files. GE HealthCare accepts no responsibility or liability for defective work due to scaling from these drawings. /18NUC-M435485-FIN-00-B.DWG

+1 (262) 2027553

Alvin.sumler@gehealthcare.com

RB 5845893-1EN

USA

1/4"=1'-0"

5566901

03/MAR/2026

Ben Taub General Hospital

REV DATE MODIFICATIONS

A 07/NOV/2025 FINAL (DC-499854)

B 03/MAR/2026 REVISION (DC-514270) Architectural changes and MDP move

A mandatory component of this drawing set is the GE HealthCare Pre Installation manual. Failure to reference the Pre Installation manual will result in incomplete documentation required for site design and preparation.

Pre Installation documents for GE HealthCare products can be accessed on the web at: https://www.gehealthcare.com/support/manuals -

Drawn by Verified by PIM Manual

SheetFormat

Concession

Scale DateFile Name

RevGON/Quote

A3

FINAL STUDY

10 - S1 - Structural Notes 11 - S2 - Structural Layout 12 - S3 - Structural Details (1)

13 - M1 - HVAC

14 - E1 - Electrical Notes 15 - E2 - Electrical Layout 16 - E3 - Electrical Elevations 17 - E4 - Power Requirements 18 - E5 - Details - Interconnections

· A mandatory component of this drawing set is the GE HealthCare Pre-installation manual. Failure to reference the Pre-installation manual will result in incomplete documentation required for site design and preparation.

· The items on the GE HealthCare Site Readiness Checklist DOC2949061 and Worksheet DOC2949068 are REQUIRED to facilitate equipment delivery to the site. Equipment will not be delivered if these requirements are not satisfied.

CUSTOMER SITE READINESS REQUIREMENTS

REQUIRED MANUALS FOR SYSTEM PRE-INSTALLATION

Description Document Number*

Product specific Pre-installation Manual Refer to cover page

*documents can be accessed in multiple languages at https://www.gehealthcare.com/support/manuals

· Any deviation from these drawings must be communicated in writing to and reviewed by your local GE HealthCare installation project manager prior to making changes.

· Make arrangements for any rigging, special handling, or facility modifications that must be made to deliver the equipment to the installation site. If desired, your local GE HealthCare installation project manager can supply a reference list of rigging contractors.

· New construction requires the following;

1. Secure area for equipment,

2. Power for drills and other test equipment,

3. Restrooms.

· Provide for refuse removal and disposal (e.g. crates, cartons, packing)

· It is required to minimize vibrations within the scan room. It is the customer's responsibility to contract a vibration consultant/engineer to implement site design modifications to meet the GE vibration specification. Refer to the system Pre-installation manual for vibration specifications.

GENERAL SPECIFICATIONS

· GE is not responsible for the installation of developers and associated equipment, lighting, cassette trays and protective screens or derivatives not mentioned in the order.

· The final study contains recommendations for the location of GE equipment and associated devices, electrical wiring and room arrangements. When preparing the study, every effort has been made to consider every aspect of the actual equipment expected to be installed.

· The layout of the equipment offered by GE, the dimensions given for the premises, the details provided for the pre-installation work and electrical power supply are given according to the information noted during on-site study and the wishes expressed by the customer.

· The room dimensions used to create the equipment layout may originate from a previous layout and may not be accurate as they may not have been verified on site. GE cannot take any responsibility for errors due to lack of information.

· Dimensions apply to finished surfaces of the room.

· Actual configuration may differ from options presented in some typical views or tables.

· If this set of final drawings has been approved by the customer, any subsequent modification of the site must be subject to further investigation by GE about the feasibility of installing the equipment. Any reservations must be noted.

· The equipment layout indicates the placement and interconnection of the indicated equipment components.

There may be local requirements that could impact the placement of these components. It remains the customer's responsibility to ensure that the site and final equipment placement complies with all applicable local requirements.

· All work required to install GE equipment must be carried out in compliance with the building regulations and the safety standards of legal force in the country concerned.

· These drawings are not to be used for actual construction purposes. The company cannot take responsibility for any damage resulting therefrom.

CUSTOMER RESPONSIBILITIES

· It is the responsibility of the customer to prepare the site in accordance with the specifications stated in the final study. A detailed site readiness checklist is provided by GE. It is the responsibility of the customer to ensure all requirements are fulfilled and that the site conforms to all specifications defined in the checklist and final study. The GE Project Manager of Installation (PMI) will work in cooperation with the customer to follow up and ensure that actions in the checklist are complete, and if necessary, will aid in the rescheduling of the delivery and installation date.

· Prior to installation, a structural engineer of record must ensure that the floor and ceiling is designed in such a way that the loads of the installed system can be securely borne and transferred. The layout of additional structural elements, dimensioning and the selection of appropriate installation methods are the sole responsibility of the structural engineer. Execution of load bearing structures supporting equipment on the ceiling, floor or walls are the customer's responsibility.

RADIO-PROTECTION

· Suitable radiological protection must be determined by a qualified radiological physicist in conformation with local regulations. GE does not take responsibility for the specification or provision of radio-protection.

DISCLAIMER

THE UNDERSIGNED, HEREBY CERTIFIES THAT I HAVE READ AND APPROVED THE PLANS IN THIS DOCUMENT.

DATE NAME SIGNATURE

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital C2 - Disclaimer - Site Readiness 02

RADIOACTIVE ISOTOPES

Since the system involves the use of radioactive isotopes, compliance with Nuclear Regulatory Commission regulations, or similar regulatory requirements (depending on the country), must be adhered to and all permissions obtained well in advance. It is recommended that regulatory compliance is arranged early in the site planning process.

It is essential that all preparations are completed so that required source materials can be obtained prior to installation, including calibration sources. Take into consideration that these sources may have fairly long delivery lead times, yet may also have a short half life, so that it may not be advisable to store them over long periods of time.

USING RADIOACTIVE ISOTOPES

RADIOACTIVE ISOTOPES FOR SYSTEM CALIBRATION

DESCRIPTION

Basic calibration Site has license for Tc99m

Tc99m will be available during installation

Isotopes to be used at site are available for installation.

Note: Specify age and strength Co57 (Line Source)

ENVIRONMENT

ALTITUDE

· Operating altitude: from -150 m [-492 ft] to 3000 m [9,843 ft].

MAGNETIC FIELD SPECIFICATIONS

· In order to avoid interference on the system, the static field limits from the surrounding environment must be less than 1 Gauss in both the scan and the operator rooms.

· The ambient static magnetic field in the system location must be less than 1 Gauss.

· The ambient AC magnetic fields must be below 0.01 Gauss peak.

· The system must be installed in an x-ray protected room providing an attenuation of at least 12 db for radio disturbances from 30 MHz to 1 GHz.

MAXIMUM GANTRY AUDIBLE NOISE LEVEL

· The system creates acoustic noise. In compliance with IEC 601-1-1 standard the measured noise (at 1 m [3.3 ft] distance away from the system) is less than 70 db. It is recommended that the wall and ceiling surface is of a sound dampening material to avoid noise reverberation and amplification.

· Take into account that the system includes an intercom communication system connecting the Operator room and the Scan room, to enable the operator to give the patient instructions during the examination.

VIBRATION SPECIFICATIONS

· The system components are sensitive to vibration in the frequency range of 0.5 to 20 Hz, depending on the amplitude of the vibration. It is the customer’s responsibility to contract a vibration consultant or qualified engineer to verify that these specifications are met and implement an appropriate solution.

· To minimize vibrations, the system must be installed on a solid floor, as far as possible from vibration sources (parking lots, roadways, subways, heliports, trains, hallways, elevators, hospital power plants... etc).

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A1 - General Notes 03

BY ITEM DESCRIPTION

MAX

HEAT

OUTPUT

(BTU/h)

WEIGHT

(lbs)

MAX

HEAT

OUTPUT

(W)

WEIGHT

(kg)

B 1 MAIN DISCONNECT PANEL (MDP) - 115 - 52.2

A 2 POWER DISTRIBUTION UNIT (PDU) 3398 816 996 370

A 3 PARTIAL UPS 14.4 KVA 5122 609 1501.1 276

A 4 CCTV CAMERA - - - -

A 5 GANTRY 17138 7144 5023 3240

A 6 PATIENT TABLE 682 1228 200 557

A 7 CCTV MONITOR - 8 - 3.5

A 8 OPERATOR CONSOLE 3200 144 938 65.1

A 9 IMAGE GENERATOR CONSOLE 512 49 150 22.4

A 10 NM ACQUISITION STATION 256 25 75 11.3

LEGEND

A GE SUPPLIED D AVAILABLE FROM GE

B GE SUPPLIED/CONTRACTOR INSTALLED E EQUIPMENT EXISTING IN ROOM

C CUSTOMER/CONTRACTOR SUPPLIED AND

INSTALLED * ITEM TO BE REINSTALLED FROM

ANOTHER SITE

EXAM ROOM HEIGHT

FINISHED FLOOR TO SLAB HEIGHT

FALSE CEILING HEIGHT

15'-0"

9'-0"

C 11 COUNTER TOP FOR EQUIPMENT

C 12 LEAD GLASS WINDOW

C 13 MINIMUM OPENING FOR EQUIPMENT DELIVERY IS 1219 mm x 2032 mm [40 in x 80 in] CONTINGENT ON A 2438 mm [96 in] CORRIDOR WIDTH

For Accessory Sales: (866) 281-7545 Options 1, 2, 1, 2 or mail to: gehcaccessorysales@ge.com

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A2 - Equipment Layout 041/4"=1'-0"

EXAM ROOM

CONTROL ROOM

8'-1 0"

9'-11"

24'-5"

5'-11"

11'-1 1"

17'-7

3'-5"

2'-7"

2'-4

"1'-8"

0.7

2.05 3.384.71

7.38

7.38 4.71

2.05

2.0

0.7

0.7

0.

0.

0.12

0.12

0.

0.12

RADIATION PROTECTION LAYOUT

SHIELDING REQUIREMENTS SCALING

CHANGED PARAMETER (mAs) MULTIPLICATION FACTOR (new mAs/100)

80 kV 0.21

120 kV 0.71

140 kV 1.00 16x0.625 LD/8x1.25 LD/4x2.5 LD/Fluoro 5 mm 0.59 4x1.25 LD/5 mm (1i)/Fluoro 2.5 mm 0.40 1x1.25 mm images/2x0.625 LD/1x1.25 0.20/0.10 4x3.75 mm images 0.82

SHIELDING REQUIREMENTS:

Radiation shielding regulations differ from one country or state to another. It is the customer’s responsibility to ensure that radiation protection and shielding comply with such regulations and requirements during site preparation and system installation and operation.

The system produces x-ray radiation and involves the use and storage of radionuclides.

Appropriate barriers such as walls, lead-shielded glass, lead shields, etc. can be installed to protect staff from unnecessary exposure to radiation.

Patients become significant sources of radioactivity; therefore consideration should be given to maximize the distance between the patient and operator during the uptake and acquisition phases of scan procedures.

Scatter-room shielding requirements must be reviewed by a qualified radiological health physicist taking into consideration:

· Scatter radiation levels within the scan room

· Equipment placement

· Weekly projected workloads (#patient/day technique (kvp*ma))

· Materials used for construction of walls, floors, ceiling, doors, and windows

· Access to areas surrounding the Scan Room

· Equipment in areas surrounding the Scan Room (for example: film developer, film storage)

BACKGROUND RADIATION

When the system is calibrated, background radiation from surrounding areas may adversely affect calibration. Therefore all radiation sources must be suitably shielded, including:

· Waiting/Injection areas

· Radionuclide storage and preparation area (sometimes known as “hot lab”) As a general guideline, if the anticipated background radiation in the Scan Room will be higher than 0.1mR/h (1microGy/h), then appropriate additional shielding should be installed.

Shielding of the Scan Room includes walls, lead-shielded glass, lead shields, etc. and must be sufficient to protect staff from unnecessary exposure to radiation. The shielding requirements must be determined by a qualified radiological health physicist, taking into consideration:

· Local regulatory requirements

· Facility policy

· CT scatter radiation levels within the scanning room

· Patient location and level of radiation from patients after intake of radionuclides

· Equipment placement

· Materials used for construction of walls, floors, ceiling, doors, and windows

· Weekly projected work-loads (# patient/day technique (kvp*ma))

· Access to areas surrounding the Scan Room

· Equipment in areas surrounding the Scan Room (for example: film developer, film storage)

· Protection of operator room, included leaded window, walls and door

The mAs, kV and aperture scaling factors shown in the table can be used to adjust exposure levels to the scan technique used at the site.

NOTE: Actual measurements can vary. All measurements have an accuracy of ±20% because of measurement equipment, technique, and system-to-system variation.

The units of measure used for radiation levels have been changed in this document, from mR (millirads) to μGy (micrograys). The conversion factor is : 1 mR = 10 μGy

The illustrations on this page were created using the following technique:

- Body Phantom, 140kV, 100mA, 1 sec, 4x5 mm

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A3 - Radiation Protection 05

EXAM ROOM

CONTROL ROOM

8'-1 0"

9'-11"

Z [m]

X [m]

1.5

0.5

-0.5

-1

-1.5 -5 -4 -3 -2 -1 0 1

1.5

0.5

-0.5

-1 -5 -4 -3 -2 -1 0 1

Z [m]

Y [m]

RADIATION SCATTER - BODY PHANTOM

Plan View

Elevation

NOTE: 140 kV 100 mAs/scan 1 sec 4 x 5mm

DETAIL NOT TO SCALE

0.7

2.05

3.38

4.71

7.38

7.38

4.71

2.05

2.05

0.7

0.7

0.7

0.7 0.12

0.12 0.12

0.12

0.68

0.2 0.1

0.1 0.2

1.35 2.69 4.69

0.68

1.35 2.69

4.696.699.3613.36

RADIATION SCATTER - HEAD PHANTOM

Z [m]

X [m]

1.5

0.5

-0.5

-1

-1.5 -5 -4 -3 -2 -1 0 1

1.5

0.5

-0.5

-1 -5 -4 -3 -2 -1 0 1

Z [m]

Y [m]

Plan View

Elevation

0.17

0.91

1.36

2.25

3.15 4.49

0.046

0.046

0.17

0.17

0.17

0.17

4.49 3.15

2.25

2.25

0.24

0.5

1.

79 2.

0.24 0.1

0.1 0.24

0.5 1.79

2.513.586.27

NOTE: 140 kV 100 mAs/scan 1 sec 4 x 5mm

DETAIL NOT TO SCALE

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A4 - Radiation Protection Details 06

MAIN DISCONNECT PANEL

FRONT VIEW SIDE VIEWTOP VIEW

4xTYP. Ø11

[Ø0.4 in]

[20 in]

[2 in

[1 in

[4 in]260

[10 in]

[21 in]

[3 in

[8 in]

[11 in]

SCALE 1:10

Center of gravity

POWER DISTRIBUTION UNIT (PDU)

Indicates air flow (Convection)

[35.4 in]

[14.2 in]

[5 .9 in

[2 1.

in

[3

5.

in ] 700

[27.6 in]

[9.3 in]

Service Area

TOP VIEW

Minimum air flow clearance

FRONT VIEW SIDE VIEW

Seismic mounting brackets

[4 1.

in

[1 9.

in

[13.8 in] 12

[5

.1 in

[5.9 in]

[5 .5 in

[8 .7 in

[15.3 in]

[15.3 in]

SCALE 1:20

Center of gravity

FRONT VIEW

SIDE VIEW

GANTRY WITH PATIENT TABLE

Optional table extender

[88.2 in]

[8 1.

in

[106.1 in]

[69.4 in]

[72.8 in]

[13.8 in]

[4 5.

in

[24 in]

SCALE 1:50

CUSTOMER SUPPLIED TABLE AND CONSOLES

SCALE 1:20

SIDE VIEW FRONT VIEW FRONT VIEW

[18 in]

[7 in]

CT Open Console (1)

NM Acquisition Station (2) (2)

(3)

(2) (3)

Center of gravity

[3 in]

[9 in]

[8 in

] 38

[1 in

(1)

[8.7 in]314

[12 in]

[22 in]

[8 in]

Image Generator Console (3)

[4 in]

[12 in]

[9 in

] 44

[1 in

[15.7 in]

[2 2.

in

[3.8 in]

[24.3 in]

[1 2.

in

]293 [11.5 in]

[6.8 in]

TOP VIEW

Indicates air flow (Convection)

(1)

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A5 - Equipment Dimensions (1) 07

UNINTERRUPTIBLE POWER SUPPLY

[12 in]

[4 7.

in

[33.5 in]

[4 7.

in

[12 in]

[3 3.

in

[2 in

[1 7.

in

[3.2 in]

TOP VIEW FRONT VIEW SIDE VIEW

Center of GravitySCALE 1:20

[5 .9 in

[3 in

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A6 - Equipment Dimensions (2) 08

DELIVERY DETAILS

CT GANTRY:

NOT TO SCALE

CORRIDOR/ELEVATOR

MINIMAL DIMENSIONS

(without 90 degree turns):

L=2810 mm [110.63 in] W=1150 mm [45.28 in] H=2000 mm [78.75 in]

2041 kg [4500 lbs]

THE CUSTOMER/CONTRACTOR SHOULD:

· Provide an area adjacent to the installation site for delivery and unloading of the GE equipment.

· Ensure that the dimensions of all doors, corridors, ceiling heights are sufficient to accommodate the movement of GE equipment from the delivery area into the definitive installation room.

· Ensure that access routes for equipment will accommodate the weights of the equipment and any transportation, lifting and rigging equipment.

· Ensure that all necessary arrangements for stopping and unloading on public or private property not belonging to the customer have been made.

NM GANTRY:

PATIENT TABLE: CORRIDOR/ELEVATOR MINIMAL DIMENSIONS (without 90 degree turns):

L=2809 mm [110.6 in] W=1000 mm [39.4 in] H=1400 mm [55.1 in] Weight: 557 kg [1228 lb]

CORRIDOR/ELEVATOR

MINIMAL DIMENSIONS

(without 90 degree turns):

L=2200 mm [86.61 in] (with small casters) W=960 mm [37.80 in] H=1950 mm [76.77 in]

L=2675 [105.32 in]

H=

[7

6.

in

1700 kg [3748 lbs]

W=907 [35.71 in]

H=

[7

8.

in

W=1290 [50.79 in]

L=2810 [110.63 in]

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital A6 - Delivery 09

STRUCTURAL NOTES

· All units that are wall mounted or wall supported are to be provided with supports where necessary. Wall supports are to be supplied and installed by the customer or his contractors. See plan and detail sheets for suggested locations and mounting hole locations.

· Floor slabs on which equipment is to be installed must be flat and level to specifications.

· Dimensions are to finished surfaces of room.

· For seismic regions ensure supports span three members.

· Customers contractor must provide all penetrations in post tension floors.

· Customers contractor must provide and install any non-standard anchoring. Documents for standard anchoring methods are included with GE equipment drawings for geographic areas that require such documentation.

· Customers contractor must provide and install hardware for "through the floor" anchoring and/or any bracing under access floors. This contractor must also provide floor drilling that cannot be completed because of an obstruction encountered while drilling by the GE installer such as rebar etc.

· It is the customer's responsibility to perform any floor or wall penetrations that may be required. The customer is also responsible for ensuring that no subsurface utilities (e.g., electrical or any other form of wiring, conduits, piping, duct work or structural supports (i.e. post tension cables or rebar)) will interfere or come in contact with subsurface penetration operations (e.g. drilling and installation of anchors/screws) performed during the installation process. To ensure worker safety, GE installers will perform surface penetration operations only after the customer's validation and completion of the "GE surface penetration permit"

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital S1 - Structural Notes 10

ITEM DESCRIPTION

1 Floor contact area for discovery gantry and patient table. See detail on sheet S3 for more information.

(CONTRACTOR SUPPLIED & INSTALLED)

2 Support Backing, locate as shown

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital S2 - Structural Layout 111/4"=1'-0"

EXAM ROOM

CONTROL ROOM

8'-1 0"

9'-11"

1'-3

NOT TO SCALE

FLOOR SPECIFICATIONS

· Floor leveling area: 537 cm x 217 cm [17.6 ft x7.2 ft] (covering the entire planned area of table and gantry surface)

· Slope less than 7 mm [0.28 in] over 1000 mm [39.37 in]

· Flatness: the surface must be smooth, with deviations of no more than 5 mm [0.2 in] over 1500 mm [59 in] in any direction

· Floor surface: a single poured surface

· Floor strength: in order to enable mounting of the system floor anchors, concrete floors must have a minimum cube strength of fc=4350 psi. (30 MPa) at 28 days (curing time) for 25/30 concrete

· Floor thickness: the system's floor anchors are designed for use only on concrete floors that meet the minimal 140 mm [6.5 in] concrete floor requirements

· It is the customer/contractor responsibility to have appropriate tests performed to determine and measure concrete strength

NM GANTRY MAIN

ANCHORING

[3

.8 in

CT TRANSPORTER

ANCHORING Alternative anchoring location (x10)

8.

..1

[0

.4

0.

in

[3

.5

3.

in

[4 in

Main anchor (x16)

M in

. 1

[6 .5 in

M in

. 1

[5 .5 in

[6 in

ANCHORING/LOADING DISTRIBUTION TO THE FLOOR

SCALE 1:25

(1) CT Scan Line

(2) NM FOV

(3) Longitudinal Axis

(4) Cable inlet coring Ø200 [Ø7.9 in] or

200x80 [7.9x3.1 in] deep flush floor duct in this area

(5) Alternative locations for gantry cables inlet

(6) CT Gantry transporter anchor points 8×HILTI-HSL-3-M10/20 anchors - Long and short plates

(7) CT Service Lead Screw brackets 4xHILTI-HSL-3 M10/20

(8) CT Service Plates 4xHILTI-HSL-3-M10/20

(9) Table mounting anchor points

9×HILTI-HSL-3-M10/40 anchors

(10) NM Gantry anchor points

4×HST3-M16x260 160/140 anchors Main anchoring points Alternative anchoring points Center of gravity

[2 2.

in

[1.4 in]

[49.7 in]

[2 4.

in

[1 0.

in

[6 4.

in

] 20

[7 9.

in

[3 2.

in

[5.4 in]

[9.1 in]

[1 7.

in

[7 4.

in

A. NM Gantry rear pads 375 Kg [827 lb] on each Ø90 mm [Ø3.5 in] pad

B. NM Gantry front pads 300 Kg [661 lb] on each Ø90 mm [Ø3.5 in] pad

C. CT Gantry load 1890 Kg [4167 lb] distributed on 2 floor plates

D. Patient table load 557 Kg [1223 lb] distributed on 2 floor plates

[2 9.

in

[1 in

[9

.7 in

CT gantry 1890 kg

[4167 lbs]

NM gantry 1350 kg

[2976 lbs]

Table 557 kg [1223 lbs]

D

B

A

C

[9 .7 in

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital S3 - Structural Details (1) 12

HEAT DISSIPATION

OPTIONS

Partial UPS Exam room or Technical room 1.501 5122

DESCRIPTION ROOM

HEAT DISSIPATION

(kW)

HEAT DISSIPATION

(BTU/hr)

MAX MAX

NM Gantry

Exam room

2.273 7750 CT Gantry 2.750 9383

Patient Table 0.200 682

Power Distribution Unit (PDU) Exam room or Technical room 0.996 3400

CT console

Control Room

0.938 3200 NM Acquisition Station (computer only) 0.075 256 Image Generator Console (computer only) 0.075 256

WARNING This chart contains only the principal components of the PET/CT system and does not include information about non-GEHC supplied equipment.

TEMPERATURE AND HUMIDITY SPECIFICATIONS

AIR RENEWAL

According to local standards.

NOTE

In case of using air conditioning systems that have a risk of water leakage it is recommended not to install it above electric equipment or to take measures to protect the equipment from dropping water.

CT STORAGE CONDITIONS

IN-USE CONDITIONS

(1) non condensing

(2) NM subsystem: The NM gantry is shipped, with the detectors assembled, via Pharma shipment, in a controlled environment.

EXAM ROOM CONTROL ROOM

Temperature Min Recommended Max Min Recommended Max

18°C [64°F]

22°C [72°F]

26°C [79°F]

18°C [64°F]

22°C [72°F]

26°C [79°F]

Temperature gradient ≤ 3°C/h [≤ 5°F/h] ≤ 3°C/h [≤ 5°F/h] Relative humidity (1) 30% to 60% 30% to 60% Humidity gradient ≤ 5%/h ≤ 5%/h

Temperature -20°C to +70°C

-4°F to +158°F Temperature gradient ≤ 3°C/h (≤ 5°F/h) Relative humidity (1) 20% to 95% Atmospheric pressure 50kPa to 106kPa Humidity gradient ≤ 5%/h

NM STORAGE CONDITIONS (2)

Temperature

+5°C to +50°C

+41°F to +122°F Temperature gradient ≤ 3°C/h (≤ 5°F/h) Relative humidity (1) 30% to 70% Atmospheric pressure 70kPa to 106kPa Humidity gradient ≤ 5%/h

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital M1 - HVAC 13

CONNECTIVITY REQUIREMENTS

Your new GE Healthcare imaging modality will require local and remote connectivity to enable our full range of digital support:

· Local connectivity - This allows your system to connect to local devices such as PACS and modality worklist.

We will require network information to configure the system(s), and a live ethernet port(s) prior to the delivery of the system(s).

· Remote connectivity - Your GE Healthcare service warranty includes InSite™ (applicable to InSite capable products), a powerful broadband-based service which enables digital tools that can help guard your hospital against equipment downtime and revenue loss by quickly connecting you to a GE Healthcare expert.

Depending on product family and software version, imaging systems can be connected in one of the following methods:

1. TLS over TCP Port 443 (Preferred method for new products) via:

a. DNS resolution

b. Customer-provided Proxy or

c. GE Proxy (Available in some regions)

2. Site-to-Site IPsec VPN tunnel

Please provide the GE project manager with the contact information for the resource that can provide information required to set up these connections. GEHC will send out communication to these contacts, which will include the project's Connectivity requirements, and a Connectivity form. This form will need to be completed and returned to GEHC prior to delivery of the system to ensure the system is tested and connectivity is enabled prior to the completion of the installation.

ELECTRICAL NOTES

· All junction boxes, conduit, duct, duct dividers, switches, circuit breakers, cable tray, etc., are to be supplied and installed by customers electrical contractor.

· Conduit and duct runs shall have sweep radius bends

· Conduits and duct above ceiling or below finished floor must be installed as near to ceiling or floor as possible to reduce run length.

· Ceiling mounted junction boxes illustrated on this plan must be installed flush with finished ceiling.

· All ductwork must meet the following requirements:

1.Ductwork shall be metal with dividers and have removable, accessible covers.

2.Ductwork shall be certified/rated for electrical power purposes.

3.Ductwork shall be electrically and mechanically bonded together in an approved manner.

4.PVC as a substitute must be used in accordance with all local and national codes.

· All openings in raceway and access flooring are to be cut out and finished off with grommet material by the customers contractor.

· General contractor to insert pull cords for all cable run conduits between the equipment room and the operators control room.

· 10 foot pigtails at all junction points.

· Grounding is critical to equipment function and patient safety. Site must conform to wiring specifications shown on this plan.

1. All wires specified shall be copper stranded, flexible, thermo-plastic, color coded, cut 10 foot long at outlet boxes, duct termination points or stubbed conduit ends. All conductors, power, signal and ground, must be run in a conduit or duct system. Electrical contractor shall ring out and tag all wires at both ends. Wire runs must be continuous copper stranded and free from splices.

1.1. Aluminum or solid wires are not allowed.

2. Wire sizes given are for use of equipment. Larger sizes may be required by local codes.

3. It is recommended that all wires be color coded, as required in accordance with national and local electrical codes.

4. Conduit sizes shall be verified by the architect, electrical engineer or contractor, in accordance with local or national codes.

5. Convenience outlets are not illustrated. Their number and location are to be specified by others. Locate at least one convenience outlet close to the system control, the power distritbution unit and one on each wall of the procedure room. Use hospital approved outlet or equivalent.

6. General room illumination is not illustrated. Caution should be taken to avoid excessive heat from overhead spotlights. Damage can occur to ceiling mounting components and wiring if high wattage bulbs are used.

Recommend low wattage bulbs no higher than 75 watts and use dimmer controls (except MR). Do not mount lights directly above areas where ceiling mounted accessories will be parked.

7. Routing of cable ductwork, conduits, etc., must run direct as possible otherwise may result in the need for greater than standard cable lengths (refer to the interconnection diagram for maximum usable lengths point to point).

8. Conduit turns to have large, sweeping bends with minimum radius in accordance with national and local electrical codes.

9. A special grounding system is required in all procedure rooms by some national and local codes. It is recommended in areas where patients might be examined or treated under present, future, or emergency conditions. Consult the governing electrical code and confer with appropriate customer administrative personnel to determine the areas requiring this type of grounding system.

10. The maximum point to point distances illustrated on this drawing must not be exceeded.

11. Physical connection of primary power to GE equipment is to be made by customers electrical contractor with the supervision of a GE representative. The GE representative would be required to identify the physical connection location, and insure proper handling of GE equipment.

12. GEHC conducts power audits to verify quality of power being delivered to the system. The customer's electrical contractor is required to be available to support this activity.

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital E1 - Electrical Notes 14

C

B

A

D

ITEM QTY

Electrical Outlet Legend

Customer/contractor supplied and installed items unless otherwise specified.

Height above floor determined by local codes unless otherwise specified.

System emergency off (SEO), (recommended height 1.2m [48"] above floor) X-Ray room warning light control panel

X-Ray ON lamp (L1) - 24V

Door interlock switch (needed only if required by state/local codes) Dedicated telephone line(s)

Network outlet Duplex hospital grade, dedicated wall outlet 120-v, single phase power

Cable Length Note:

Routing of cable ductwork, conduits, etc., must run direct as possible otherwise may result in the need for greater than standard cable lengths (refer to the interconnection diagram for maximum usable lengths point to point).

13 CCTV Monitor 12 CCTV Camera 1 1 25

Additional Conduit Runs (Contractor Supplied and Installed)

From (Bubble # / Item)

To (Bubble # / Item) Qty

Size In. mm

3 Phase Power 1 Main Disconnect Panel 1 As req'd As req'd

1 Main Disconnect Panel Emergency Off 1 1 13

7 Power Distribution Unit 1 As req'd As req'd

7 Power Distribution Unit Door Switch 1 1 13

Warning Light Control 1 1 13

Warning Light 1 1 13

1 Phase Power 1 1 13

1 Main Disconnect Panel 9 Partial UPS

1 1 1/4 30

3 Power Distribution Unit 1 2 50

Item Electrical Layout Item List

BASIC SYSTEM

1 Main disconnect panel (MDP)

2 Suitable chase nipples, refer to Anchoring/Loading Distribution to the Floor detail on sheet S3 (Gantry)

3 Grommeted opening (PDU)

4 Grommeted opening (Console)

5 2 1/2" [64] conduit above ceiling

6 3 1/2" [89] conduit above ceiling

7 Box above ceiling - size per local code (exam room)

8 Box above ceiling - size per local code (control room)

9 4" x 4" x 4" [100 x 100 x 100] box (Partial UPS)

10 10" x 3 1/2" [250 x 100] flush wall duct with minimum 2 dividers

11 12" x 3" [300 x 100] trench duct with minimum 2 dividers

12 4" x 4" x 4" [100 x 100 x 100] box (CCTV Camera)

13 4" x 4" x 4" [100 x 100 x 100] box (CCTV Monitor)

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital E2 - Electrical Layout 151/4"=1'-0"

EXAM ROOM

CONTROL ROOM

8'-1 0"

9'-11"

5'-1"0'-9

7'-4

0'-7

3'-6"

0'-9"

0'-3"

8'-1

1'-3

1'-9

BA

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital E3 - Electrical Elevations 161/4"=1'-0"

C

15'-0"

0'-0"

9'-0"

15'-0"

0'-0"

9'-0"

15'-0"

0'-0"

9'-0"

0' -9

1' -6

TB

D

TB

D 0'

-6

13 4 10

1' -6

0' -9

5' -0

0' -9

D

15'-0"

0'-0"

9'-0"

POWER DISTRIBUTION

SEO3

24 V

PDU

For Scan Room

Warning Light and Door Interlock

Connections Detail refer to the next page

Emergency OFF (Control room)

Emergency OFF (Exam room) If applicable

Emergency OFF (Technical room)

If applicable Refer to Table1

Table1:

MDP MDP Main Disconnect Panel PDU Power Distribution Unit SEO Emergency OFF Button latching twist-to release style with two normally closed (NC) contacts

Y Remote Operator Control Station with "ON" and "OFF" buttons

Table2:

24 V

24 V (1)

Cable SUPPLIED BY CUSTOMER Cable SUPPLIED BY GEHC Equipment SUPPLIED BY

CUSTOMER

Equipment SUPPLIED BY GEHC

(1)

(1)

YRemote ON/OFF (Control room)

If applicable 24 V

(2)

SEO2

SEO1

For Main Supply (3 phases) Feeder and Ground wire size Refer to Table2

Feeder Table The information below assumes the use of copper wire, rated 75 C and run in steel conduit. All ampacity is determined in accordance with the National Electrical Code (NFPA 70), Table 310-16 (2002). The ampacity of the circuit protection device listed above determines the minimum feeder size, except where total source regulation limits require a larger size. If the wire size does not match the below list, please select the nearest wire size as per to local standards.

Feeder length from Power Substation to MDP - ft (m)

Minimum Wire Size, AWG or MCM (mm²)/VAC

380 VAC 400 VAC 420 VAC 440 VAC 460 VAC 480 VAC

50 (15) 2 (35) 2 (35) 3 (30) 3 (30) 3 (30) 3 (30)

100 (30) 2 (35) 2 (35) 3 (30) 3 (30) 3 (30) 3 (30)

150 (46) 2 (35) 2 (35) 3 (30) 3 (30) 3 (30) 3 (30)

200 (61) 2 (35) 2 (35) 3 (30) 3 (30) 3 (30) 3 (30)

250 (76) 1 (45) 1 (45) 2 (35) 2 (35) 2 (35) 3 (30)

300 (91) 1/0 (50) 1/0 (50) 1 (45) 1 (45) 2 (35) 2 (35)

350 (107) 2/0 (70) 1/0 (50) 1/0 (50) 1 (45) 1 (45) 1 (45)

400 (122) 2/0 (70) 2/0 (70) 1/0 (50) 1/0 (50) 1/0 (50) 1 (45)

Sub-Feeder length from MDP to PDU - ft (m)

32 (9.7536) 2 (35) 2 (35) 3 (30) 3 (30) 3 (30) 3 (30) Grounding

Run a dedicated 1/0 [50 mm²] or larger insulated copper ground wire from the power source to the MDP and from MDP to the PDU. Run the ground wire in the same raceway with the three-phase wires.

Notes :

(1) Wire size: 4x2mm² [14AWG] and 1x2mm² [14AWG] GND

(2) Power control cable: 3 m [10 ft], multi-conductor, 24V DC

For Sub-Feeder and Ground wire size refer to Table2

Partial UPS (option)

GEHC Supplied Main Disconnect Panel (MDP) Region CAT number Amps Europe

Asia E4502AH 110

EMEA (380-415V) E45021BH 110

USCAN E4502AG 90

· Power supply should come into a Main Disconnect Panel (MDP) containing the protective units and controls.

· Governing electrical codes may require a neutral wire. If present, neutral must be terminated in MDP.

· The section of the supply cable should be calculated in accordance with its length and the maximum permissible voltage drops.

· There must be difference between supply cable protective device at the beginning of the installation (main low-voltage transformer side) and the protective devices in the MDP.

SUPPLY CHARACTERISTICS

· Power input must be separate from any others which may generate transients (elevators, air conditioning, radiology rooms equipped with high speed film changers...).

· All equipment (lighting, power outlets, etc...) installed with GE system components must be powered separately.

· Phase imbalance 2% maximum.

· Maximum voltage variation at full load = 6% (Including line impedance).

· Transients must be less than 1500 V peak. (on a 400 V line)

GROUND SYSTEM

· System of equipotential grounding.

· Equipotential: The equipotential link will be by means of an equipotential bar. This equipotential bar should be connected to the protective earth conductors in the ducts of the non GE cableways and to additional equipotential connections linking up all the conducting units in the rooms where GE system units are located.

· The impedance of the earth bar should be less than or equal to 0.5 Ohm.

CABLES

· Power and cable installation must comply with the distribution diagram.

· All cables must be isolated and flexible, cable color codes must comply with standards for electrical installation.

· The cables from signaling and remote control (Y, SEO, L...) will go to MDP with a pigtail length of 1.5 m, and will be connected during installation. Each conductor will be identified and isolated (screw connector).

CABLEWAYS

The general rules for laying cableways should meet the conditions laid down in current standards and regulations, with regard to:

· Protecting cables against water (cableways should be waterproof).

· Protecting cables against abnormal temperatures (proximity to heating pipes or ducts).

· Protecting cables against temperature shocks.

· Replacing cables (cableways should be large enough for cables to be replaced).

· Metal cableways should be grounded.

POWER REQUIREMENTS

POWER SUPPLY

POWER SUPPLY 380/400/420/440/460/480V ± 10%, 3 PHASE + GND

FREQUENCIES 50/60 Hz ± 3 Hz MAXIMUM POWER DEMAND 90 kVA AVERAGE (CONTINUOUS) POWER DEMAND 22 kVA POWER FACTOR 0.85 (140 kV, 380 mA)

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital E4 - Power Requirements 17

TYPICAL CABLE MANAGEMENT

FLUSH FLOOR DUCT

Waterproof joint removable cover Dividers as required per local code

NOT TO SCALE

Removable coverplate

WALL DUCT

Dividers as required per local code

Partial UPS (Option)

Can be ordered from GE

INTERCONNECTIONS

CONTROL ROOM

CT Gantry

NM Gantry

NM Acquisition Station

PDU

MDP

16.76 m [55 ft]3.60 m

[12 ft]

11.30 m [37 ft]

16.50 m [54.1]

22.86 m [75 ft]

EXAM ROOM / TECHNICAL ROOM

Table 1 m [3.3 ft]

2 m [6.6 ft]

22.86 m [75 ft]

Console11.5 m [37.7 ft]

CUSTOMER

SUPPLIED

EXAM ROOM

SCAN ROOM WARNING LIGHT AND DOOR INTERLOCK

PDU

DOOR SWITCH (2)

EXP_INTLK

PGND

CONTROL

BOARD

KD6

KD5

KD7

TS6

FUSE

24V max

READY LIGHT

SYS-ON LIGHT

L N

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

X-RAY LIGHTR1 R1

R2

R3

Facility Input Power (3)

PDU Power Distribution Unit TS6 Terminal Block 6

Cable SUPPLIED BY CUSTOMER Cable SUPPLIED BY GE Equipment SUPPLIED BY CUSTOMER Equipment SUPPLIED BY GE

Fuse Relay coil and contact -normally open (de-energized state)

Control power transformer

R2

R3

Notes :

(1) Wire size: 2mm² [14 AWG] at 24V

(2) Door Interlock circuit is jumpered out if a door switch is not provided.

(3) Grounding not shown on the detail, but must comply with local codes.

DateRev /18NUC-M435485-FIN-00-B.DWG B 03/MAR/2026STARGUIDEBen Taub General Hospital E5 - Details - Interconnections 18

Sheets and Views
NUC-M435485-FIN-00-B-C1 - Cover Sheet
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-C2 - Disclaimer - Site Readiness
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A1 - General Notes
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A2 - Equipment Layout
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A3 - Radiation Protection
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A4 - Radiation Protection Details
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A5 - Equipment Dimensions (1)
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A6 - Equipment Dimensions (2)
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-A6 - Delivery
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-S1 - Structural Notes
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-S2 - Structural Layout
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-S3 - Structural Details (1)
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-M1 - HVAC
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-E1 - Electrical Notes
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-E2 - Electrical Layout
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-E3 - Electrical Elevations
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-E4 - Power Requirements
OLE1
OLE2
OLE3
NUC-M435485-FIN-00-B-E5 - Details - Interconnections
OLE1
OLE2
OLE3

File details come from the government source that posted it. Updated .