This is DFCM Addendum #001 issued by the State of Utah Division of Facilities Construction and Management for the Mammoth Creek Hatchery Improvements project (#27087520). The addendum modifies the electrical design specifications for the fish hatchery facility remodel and upgrades being conducted by the Department of Natural Resources Division of Wildlife Resources. Key modifications include changes to the emergency generator system, with the generator downgraded from a 480V three-phase unit to a 240V single-phase generator, relocation of the transformer and new phase converter to the hatchery building, and revisions to the electrical one-line diagram for power distribution. The addendum affects multiple electrical sheets including the Electrical Site Plan (ES101), Hatchery Building Electrical Plan (EL202), and Electrical One-Line Diagram (EP401). Additionally, the addendum references changes to the solicitation schedule, specifically regarding the Substantial Completion Date, with bidders required to acknowledge receipt of the addendum upon bid submission under penalty of disqualification.
The addendum emphasizes that contractors must verify existing power and phasing prior to ordering any equipment associated with the generator system to ensure compatibility with existing power connections. The new electrical system includes a NAPCCO Smart-Boost Phase Converter (SB-60-EE-D3 or equal) to convert 240V single-phase power to 240V three-phase power, which then feeds a 45 KVA step-down transformer for 480/240V delta configuration with high leg output to the hatchery building transfer switch. The phase converter location, transformer specifications, and associated electrical modifications are detailed on the revised drawing sheets dated September 9, 2026. All general contractors bidding on this prequalified Stage II project must be currently on the DFCM Prequalified Contractors list, with the construction cost estimate established at $346,789.00.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DFCM Addendum Cover Page, 9.2.2026
DFCM Addendum #001
Reference: Mammoth Creek Hatchery Improvements DFCM Project #27087520 U3P Event #CR27013
Date: September 14, 2026
To: General Contrators
From: The Division of Facilities Construction and Management
Note:
This
Addendum shall be included as part of the Contract Documents. Items in this Addendum apply to all drawings and specification sections whether referenced or not involving the portion of the work added, deleted, modified, or otherwise addressed in the Addendum. Bidders are required to acknowledge receipt of this Addendum when their bid is submitted. Failure to do so may subject the Bidder to disqualification.
Addendum Items
Solicitation Schedule Changes: See the ‘Revised Solicitation’ document attached under the ‘Supporting Documents’ in U3P. Changes have been made to the following events:
Substantial Completion Date
DFCM Addendum Items: N/A
Click to enter text Click to enter text Click to enter text
A/E Addendum Items: A/E Addendum # 001- Dated 09/09/2026 Click to enter text
Total Attached Pages: 5
( 8 0 1 ) 5 3 0 - 3 1 4 8 r e s o l u t g r o u p . c o m i n f o @ r e s o l u t g r o u p . c o m
ELECTRICAL ADDENDUM 1
DATE: September 9, 2026
PROJECT NO: 26-0526
PROJECT: Mammoth Creek Fish Hatchery Improvements
DIVISION 26:
DRAWINGS
SHEET ES101 – ELECTRICAL SITE PLAN
1. The transformer and a new phase converter (associated with generator) have been added/relocated to the hatchery building where one of the generators is being removed.
SHEET EL202 – HATCHERY BUILDING ELECTRICAL PLAN
1. The transformer and a new phase converter (associated with generator) have been shown on the floor plans for the hatchery building.
SHEET EP401 – ELECTRICAL ONE-LINE DIAGRAM
1. The emergency one-line has been revised as follows:
a. The generator was changed to a 240V single phase generator instead of 480V.
The size of the breakers in the generator have also been modified.
b. One of the breakers feeds directly to the transfer switch in the filtration building.
c. The “second” breaker feeds a new phase converter (refer to Keynote (X1) on this sheet. The phase converter will convert the 240V single phase to 240V three phase. Then, the intent is to feed that three phase power to a buck boost transformer for 480/240V delta with a high leg which then feeds transfer switch in hatchery building.
( 8 0 1 ) 5 3 0 - 3 1 4 8 r e s o l u t g r o u p . c o m i n f o @ r e s o l u t g r o u p . c o m
d. Prior to ordering any equipment associated with generator (generator, transformer, phase converter, etc.) the contractor will need to verify the existing power and phasing to insure that new generator components are compatible with existing power connections.
J
EC
7090 .63
EMERGENCY
GENERATOR
'ATS1'
'ATS2'
'SH'
S5 S5 S4
S1
S1
S1
S1
S1
S1
S1
S1
S1
S1
HB
HB
HB
HB
S6
'TE'
S3 REFER TO ENLARGED
SHOP BUILDING PLANS
ON SHEET EL201
REFER TO E
NLARGED
HATCHERY B
UILDIN
G P
LANS
ON S
HEET E
L202
HB
HB
HB
HB
HB
HB
HB
HB
S2
S8
HB
HB
LP1-25,27
S9
'PC'
S7
S
TA TE OF U
T A H
P R O F
ES
SIO
NAL ENGIN
E E R
No. 7892177-2202
IAN
MADISON
1575 S. River Rd., Suite 101
St. George, Utah 84790
435.352.1050
GallowayUS.com
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
D F
C M
S ta m p
07/31/2026
9/4/2026 3:14:46 PM
A ut od es k D oc s:
//U D
F
-U D
F -U
T -H at ch
-M am m ot h- C re ek
B
R
/2
6_ M am m ot h
C re ek F is h
H at ch er y Im pr ov em en ts _v
.r vt
ELECTRICAL SITE
PLAN
ES101
260526
RESOLUT
I.M.
H A
T C
H , U
T A
H
M am m ot h C re ek
F is h H at ch er y
Im pr ov em en ts
SHEET KEYNOTES
S1 PROVIDE NEW LIGHT FIXTURE TYPE SHOWN. MAINTAIN EXISTING CIRCUIT/CONTROL.
S2 EXTEND EXISTING 1-1/2" CONDUIT DOWN SURFACE OF BUILDING TO UNDERGROUND. PROVIDE AN IN-GRADE
JUNCTION BOX IN LANDSCAPE AREA AND EXTEND 1-1/2" CONDUIT TO RV PEDESTALS.
S3 IN PANEL 'SH' REPLACE EXISTING 80A/2P BREAKER WITH 90A/2P BREAKER FOR RV PEDESTAL CIRCUIT.
PROVIDE (3) #2 CU CONDUCTORS AND (1) #6 GROUND IN RACEWAY SPECIFIED FROM PANEL 'SH' TO RV
PEDESTALS.
S4 PROVIDE (1) 1-1/2" CONDUIT WITH (3) #2 CU CONDUCTORS AND (1) #6 GROUND.
S5 CONTRACTOR TO PROVIDE DIRECT BURIED RV PEDESTAL HERITAGE H75P-3 (OR EQUAL). MOUNT THE TWO PEDESTALS BACK-TO-BACK. PROVIDE BOLLARD PROTECTION FOR RV PEDESTALS AS REQUIRED BY NATIONAL AND/OR LOCAL CODES. REFER TO DIAGRAM C007. PRIOR TO ROUGH-IN VERIFY EXACT PEDESTAL
LOCATIONS WITH OWNER.
S6 LOCATION OF NEW EMERGENCY GENERATOR. REFER TO ONE-LINE DIAGRAM.
S7 LOCATION OF NEW PHASE CONVERTER AND NEW STEP DOWN TRANSFORMER. REFER TO ONE-LINE DIAGRAM
AND SHEET EL202.
S8 FOR FEEDERS FROM GENERATOR TO ATS1 FOLLOW EDGE OF EXISTING SIDEWALK TO BUILDING AND THEN
PENETRATE BUILDING TO PHASE CONVERTER 'PC'.
S9 PROVIDE CIRCUITS SHOWN FOR GENERATOR BATTERY CHARGER AND HEATER.
SCALE = 1" = 20'-0"
ELECTRICAL SITE PLAN
1 2026/09/09 ADDENDUM #1
R
WAP
J
J J
WAP
PP
OS
T
T
T
T
TELECOMM
CABINET
D5 D6 D5
D5
D4
D5
D7
D5
EMERGENCY
GENERATOR
'ATS1'
'E'
'1A'
D9D9
D9
D9
E-3
W5
E-3
W5
A
A A
1" EMT
1" EMT
E2
E1
E2
TELECOMM
CABINET
E-1
E-1
E-1E-6
E-8
E-6 E-6
'ATS1'
U
D
1-1/2" EMT
E-1
E-1
'A'
RTU-1
A-17
(ON ROOF)
WP
WP
E4
WH-1
E5
'E'
E4
UH-3
E4
UH-2
E4
UH-1
WP
WP
WP
A-17
A- 19,21,23
IEC-1
A- 25,27,29
DF-1
ON ROOF)
(ON ROOF)
E5
E5
'PC' 'TE'
S
TA TE OF U
T A H
P R O F
ES
SIO
NAL ENGIN
E E R
No. 7892177-2202
IAN
MADISON
1575 S. River Rd., Suite 101
St. George, Utah 84790
435.352.1050
GallowayUS.com
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
D F
C M
S ta m p
07/31/2026
9/4/2026 3:14:48 PM
A ut od es k D oc s:
//U D
F
-U D
F -U
T -H at ch
-M am m ot h- C re ek
B
R
/2
6_ M am m ot h
C re ek F is h
H at ch er y Im pr ov em en ts _v
.r vt
HATCHERY
BUILDING
ELECTRICAL PLAN
EL202
260526
RESOLUT
I.M.
H A
T C
H , U
T A
H
M am m ot h C re ek
F is h H at ch er y
Im pr ov em en ts
0 4' 8'2' 1/4" = 1'-0"
HATCHERY BUILDING DEMOLITION PLAN
0 4' 8'2' 1/4" = 1'-0"
HATCHERY BUILDING ELECTRICAL PLAN
SHEET KEYNOTES
D4 EXISTING LIGHT FIXTURES TO BE REMOVED AND REPLACED WITH NEW LIGHT FIXTURES. REFER TO
ELECTRICAL PALN FOR NEW FIXTURE TYPE. PROVIDE EXTENSION RING FOR ADDITIONAL GYP BOARD BEING
INSTALLED ON CEILING. MAINTAIN EXISTING CIRCUIT AND CONTROL.
D5 EXISTING RECEPTACLES TO BE REMOVED. MAINTAIN HOMERUN CONDUIT TO PANLE 'E'. REFER TO
ELECTRICAL PLAN FOR MORE INFORMATION.
D6 EXISTING BATTERY OPERATED RADON DETECTOR TO BE REMOVED AND REINSTALLED.
D7 EXISTING ROUTER AND WIFI TO BE REMOVED AND SALVAGED OT OWNER.
D9 EXISTING MECHANICAL UNIT TO BE REMOVED AND REPLACED. DISCONNECT AND REMOVE POWER AND ANY ASSOCIATED EQUIPMENT DISCONNECTS. MAINTAIN EXISTING CIRCUIT FOR NW MECHANICAL EQUIPMENT.
E1 PROVIDE DOUBLE GANG DEEP JUNCTION BOX WITH (1) 1" ENT CONDUIT TO TELECOMM CABINET FOR OWNER
PROVIDED WIRING.
E2 PROVIDE SINGLE GANG DEEP JUNCTION BOX.
E4 NEW MECHANICAL EQUIPMENT. PROVIDE NEW DISCONNECT SHOWN AND CONNECT EXISTING CIRCUIT TO
NEW EQUIPMENT.
E5 PROVIDE (2) 20A/1P BREAKERS FOR EXISTING 'E' PANEL. NEW BREAKERS TO MATCH EXISTING SIEMENS
EQUIPMENT.
1 2026/09/09 ADDENDUM #1
MMMM
#4
'LP1'
PANEL
NE N E
#4
NE
MMMM
#4
'LP1'
PANEL
NE
200A 2P
TO UTILITY CONNECTION
NOTES:
1. FOR GROUND CONDUCTOR IN PARALLEL RUNS, SIZE IN ACCORDANCE WITH NEC
PARAGRAPH 250-122.
2. GND. CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE CONDUCTORS
3. ALL COPPER CABLE TO BE THHN/THWN.
* 200% NEUTRAL, DERATED TO 80% BASED ON NEC 310.15.B(5)(C)
COPPER CONDUCTOR
& CONDUIT SCHEDULE
SIZEQUAN.
CONDUCTOR
TYPE SETS
MAX. O.C.
PROT.
COND.
AMPS
CONDUIT
SIZE
EQ. GND.
COND.
3"
3"350
500 4"
250-5 5*
4"
3"
4400-4
3400-3
4350-4
3350-3
44/0
2/0
3/0
1/0
1"
1"
1"
1"
1"
3/4"
3/4"
1-1/2"
1-1/2"
1-1/2"
1-1/4"
2"
2"
2"
2-1/2"
250300
4/0200-5 5*
2"
2"
4/0
3/0
2/0
1/0
3"
3"
2-1/2"
2"
2"
1-1/2"
1-1/4"
1-1/4"
1-1/4"
1"
1"
4300-4
3300-3
4250-4
3250-3
4200-4
3200-3
4175-4
3175-3
4150-4
3150-3
4110-4
3110-3
4100-4
3100-3
490-4
390-3
290-2
470-4
370-3
270-2
460-4
360-3
260-2
440-4
340-3
240-2
430-4
330-3
230-2 30 3/4"10 10
2-1/2"
4"5005*4 3/0121612001200-5
1000-5 1000 1072 2/04 5* 400 4"
4"3505*3 1/0744800800-5
2 3"500 1600-5 600 608 5*
4"500411 500418040004000-4
4"50048 400304030003000-4
2500-4 2500 2660 3507 4 500 4"
1200-4 1200 1240 3/04 4 350 4"
1000-4 1000 1140 2/03 4 500 4"
800-4 800 760 1/02 4 500 4"
2 3"350 1600-4 600 620 4
800-3 800 760 1/02 3 500 4"
3620600600-3 1350 3"2
1000-3 1000 1140 2/03 3 500 4"
1200-3 1200 1240 3/04 3 350 4"
4"40035 4/0167516001600-3
4"4005*6 4/0160816001600-5
4"40045 4/0167516001600-4
2000-4 2000 2010 2506 4 400 4"
5*368400400-5 34/0 3"2
6190 2"90-5 5*88 1
61/0125 2"5*125-5 120 1
62/0150 2"5*150-5 140 1
63/0175175-5 5* 2-1/2"160 1
3350300 3"4300-5 268 1
3500 4"350350-5 5*304 1
EXISTING 'ATS2'
200A, 1PH, 3 POLE
EXISTING 35KW PROPANE GENERATOR
240V, 1 PHASE, 3 WIRE
NEMA 3R ENCLOSURE
EXISTING METER/MAIN
SERVICE DISCONNECT
EXISTING FILTRATION BUILDING ONE-LINE DIAGRAM
EXISTING 'ATS1'
100A, 3PH, 4 POLE
EXISTING 30KW PROPANE GENERATOR
480V, 3 PHASE, 4 WIRE
NEMA 3R ENCLOSURE
EXISTING HATCHERY BUILDING ONE-LINE DIAGRAM
45A 3P
TO MEC.
HOUSE
EXISTING 100A DISCONNECT
MOUNTED ON SIDE OF BUILDING
100A 3P
SPACE
ONLY
50A 3P
50A 3P
30A 3P
100A 3P
MAIN DISTRIBUTION PANEL 'MDP'
277/480V, 3 P HASE, 4 WIRE
NEMA 3R, 18,000 AIC
LOCATED ON ROOF
TO MEC.
HOUSE
EXISTING 100A DISCONNECT
MOUNTED ON SIDE OF BUILDING
100A 3P
SPACE
ONLY
50A 3P
50A 3P
30A 3P
100A 3P
MAIN DISTRIBUTION PANEL 'MDP'
277/480V, 3 PHASE, 4 WIRE
NEMA 3R, 18,000 AIC
LOCATED ON ROOF
EXISTING 'ATS1'
100A, 3PH, 4 POLE
150A 3P
TO UTILITY CONNECTION
EXISTING 'ATS2'
200A, 1PH, 3 POLE
60KW PROPANE GENERATOR
240V, 1 PHASE, 3 WIRE
NEMA 3R ENCLOSURE
EXISTING METER/MAIN
SERVICE DISCONNECT
150A 2P
#2 CU
NEW 70A DISCONNECT
MOUNTED INSIDE BUILDING
ADJACENT TO TRANSFORMER
TRANSFORMER 'TE'
240V-DELTA 480/240V (LT) DELTA
3 PHASE, 4 WIRE
45 KVA
150-3
NEW EMERGENCY ONE-LINE DIAGRAM
D10D10
'PC'
X1 150-4
150-3 70-4 70-4
S
TA TE OF U
T A H
P R O F
ES
SIO
NAL ENGIN
E E R
No. 7892177-2202
IAN
MADISON
1575 S. River Rd., Suite 101
St. George, Utah 84790
435.352.1050
GallowayUS.com
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
# Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
D F
C M
S ta m p
07/31/2026
9/4/2026 3:14:49 PM
A ut od es k D oc s:
//U D
F
-U D
F -U
T -H at ch
-M am m ot h- C re ek
B
R
/2
6_ M am m ot h
C re ek F is h
H at ch er y Im pr ov em en ts _v
.r vt
ELECTRICAL
ONE-LINE
DIAGRAM
EP401
260526
RESOLUT
I.M.
H A
T C
H , U
T A
H
M am m ot h C re ek
F is h H at ch er y
Im pr ov em en ts
NOT TO SCALEEP401
1 Electrical One-Line Diagram
1 2026/09/09 ADDENDUM #1
SHEET KEYNOTES
D10 REMOVE EXISTING FEEDERS, WIRING, CONDUIT, BOXES, ETC.
X1 PROVIDE NAPCCO SMART-BOOST PHASE CONVERTER SB-60-EE-D3 (OR EQUAL).