This is DFCM Addendum #001 issued by the State of Utah Division of Facilities Construction and Management for the Mammoth Creek Hatchery Improvements project (#27087520). The addendum modifies the electrical design specifications for the fish hatchery facility remodel and upgrades being conducted by the Department of Natural Resources Division of Wildlife Resources. Key modifications include changes to the emergency generator system, with the generator downgraded from a 480V three-phase unit to a 240V single-phase generator, relocation of the transformer and new phase converter to the hatchery building, and revisions to the electrical one-line diagram for power distribution. The addendum affects multiple electrical sheets including the Electrical Site Plan (ES101), Hatchery Building Electrical Plan (EL202), and Electrical One-Line Diagram (EP401). Additionally, the addendum references changes to the solicitation schedule, specifically regarding the Substantial Completion Date, with bidders required to acknowledge receipt of the addendum upon bid submission under penalty of disqualification.

The addendum emphasizes that contractors must verify existing power and phasing prior to ordering any equipment associated with the generator system to ensure compatibility with existing power connections. The new electrical system includes a NAPCCO Smart-Boost Phase Converter (SB-60-EE-D3 or equal) to convert 240V single-phase power to 240V three-phase power, which then feeds a 45 KVA step-down transformer for 480/240V delta configuration with high leg output to the hatchery building transfer switch. The phase converter location, transformer specifications, and associated electrical modifications are detailed on the revised drawing sheets dated September 9, 2026. All general contractors bidding on this prequalified Stage II project must be currently on the DFCM Prequalified Contractors list, with the construction cost estimate established at $346,789.00.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DFCM Addendum Cover Page, 9.2.2026

DFCM Addendum #001

Reference: Mammoth Creek Hatchery Improvements DFCM Project #27087520 U3P Event #CR27013

Date: September 14, 2026

To: General Contrators

From: The Division of Facilities Construction and Management

Note:

This

Addendum shall be included as part of the Contract Documents. Items in this Addendum apply to all drawings and specification sections whether referenced or not involving the portion of the work added, deleted, modified, or otherwise addressed in the Addendum. Bidders are required to acknowledge receipt of this Addendum when their bid is submitted. Failure to do so may subject the Bidder to disqualification.

Addendum Items

Solicitation Schedule Changes: See the ‘Revised Solicitation’ document attached under the ‘Supporting Documents’ in U3P. Changes have been made to the following events:

Substantial Completion Date

DFCM Addendum Items: N/A

Click to enter text Click to enter text Click to enter text

A/E Addendum Items: A/E Addendum # 001- Dated 09/09/2026 Click to enter text

Total Attached Pages: 5

( 8 0 1 ) 5 3 0 - 3 1 4 8 r e s o l u t g r o u p . c o m i n f o @ r e s o l u t g r o u p . c o m

ELECTRICAL ADDENDUM 1

DATE: September 9, 2026

PROJECT NO: 26-0526

PROJECT: Mammoth Creek Fish Hatchery Improvements

DIVISION 26:

DRAWINGS

SHEET ES101 – ELECTRICAL SITE PLAN

1. The transformer and a new phase converter (associated with generator) have been added/relocated to the hatchery building where one of the generators is being removed.

SHEET EL202 – HATCHERY BUILDING ELECTRICAL PLAN

1. The transformer and a new phase converter (associated with generator) have been shown on the floor plans for the hatchery building.

SHEET EP401 – ELECTRICAL ONE-LINE DIAGRAM

1. The emergency one-line has been revised as follows:

a. The generator was changed to a 240V single phase generator instead of 480V.

The size of the breakers in the generator have also been modified.

b. One of the breakers feeds directly to the transfer switch in the filtration building.

c. The “second” breaker feeds a new phase converter (refer to Keynote (X1) on this sheet. The phase converter will convert the 240V single phase to 240V three phase. Then, the intent is to feed that three phase power to a buck boost transformer for 480/240V delta with a high leg which then feeds transfer switch in hatchery building.

( 8 0 1 ) 5 3 0 - 3 1 4 8 r e s o l u t g r o u p . c o m i n f o @ r e s o l u t g r o u p . c o m

d. Prior to ordering any equipment associated with generator (generator, transformer, phase converter, etc.) the contractor will need to verify the existing power and phasing to insure that new generator components are compatible with existing power connections.

J

EC

7090 .63

EMERGENCY

GENERATOR

'ATS1'

'ATS2'

'SH'

S5 S5 S4

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

HB

HB

HB

HB

S6

'TE'

S3 REFER TO ENLARGED

SHOP BUILDING PLANS

ON SHEET EL201

REFER TO E

NLARGED

HATCHERY B

UILDIN

G P

LANS

ON S

HEET E

L202

HB

HB

HB

HB

HB

HB

HB

HB

S2

S8

HB

HB

LP1-25,27

S9

'PC'

S7

S

TA TE OF U

T A H

P R O F

ES

SIO

NAL ENGIN

E E R

No. 7892177-2202

IAN

MADISON

1575 S. River Rd., Suite 101

St. George, Utah 84790

435.352.1050

GallowayUS.com

Checked By:

Project No:

Drawn By:

COPYRIGHT

THESE PLANS ARE AN INSTRUMENT OF SERVICE

STAMP

# Date Issue/Description

AND ARE THE PROPERTY OF GALLOWAY, AND MAY

NOT BE DUPLICATED, DISCLOSED, OR

REPRODUCED WITHOUT THE WRITTEN CONSENT

OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS

WILL BE ENFORCED AND PROSECUTED.

D F

C M

S ta m p

07/31/2026

9/4/2026 3:14:46 PM

A ut od es k D oc s:

//U D

F

-U D

F -U

T -H at ch

-M am m ot h- C re ek

B

R

/2

6_ M am m ot h

C re ek F is h

H at ch er y Im pr ov em en ts _v

.r vt

ELECTRICAL SITE

PLAN

ES101

260526

RESOLUT

I.M.

H A

T C

H , U

T A

H

M am m ot h C re ek

F is h H at ch er y

Im pr ov em en ts

SHEET KEYNOTES

S1 PROVIDE NEW LIGHT FIXTURE TYPE SHOWN. MAINTAIN EXISTING CIRCUIT/CONTROL.

S2 EXTEND EXISTING 1-1/2" CONDUIT DOWN SURFACE OF BUILDING TO UNDERGROUND. PROVIDE AN IN-GRADE

JUNCTION BOX IN LANDSCAPE AREA AND EXTEND 1-1/2" CONDUIT TO RV PEDESTALS.

S3 IN PANEL 'SH' REPLACE EXISTING 80A/2P BREAKER WITH 90A/2P BREAKER FOR RV PEDESTAL CIRCUIT.

PROVIDE (3) #2 CU CONDUCTORS AND (1) #6 GROUND IN RACEWAY SPECIFIED FROM PANEL 'SH' TO RV

PEDESTALS.

S4 PROVIDE (1) 1-1/2" CONDUIT WITH (3) #2 CU CONDUCTORS AND (1) #6 GROUND.

S5 CONTRACTOR TO PROVIDE DIRECT BURIED RV PEDESTAL HERITAGE H75P-3 (OR EQUAL). MOUNT THE TWO PEDESTALS BACK-TO-BACK. PROVIDE BOLLARD PROTECTION FOR RV PEDESTALS AS REQUIRED BY NATIONAL AND/OR LOCAL CODES. REFER TO DIAGRAM C007. PRIOR TO ROUGH-IN VERIFY EXACT PEDESTAL

LOCATIONS WITH OWNER.

S6 LOCATION OF NEW EMERGENCY GENERATOR. REFER TO ONE-LINE DIAGRAM.

S7 LOCATION OF NEW PHASE CONVERTER AND NEW STEP DOWN TRANSFORMER. REFER TO ONE-LINE DIAGRAM

AND SHEET EL202.

S8 FOR FEEDERS FROM GENERATOR TO ATS1 FOLLOW EDGE OF EXISTING SIDEWALK TO BUILDING AND THEN

PENETRATE BUILDING TO PHASE CONVERTER 'PC'.

S9 PROVIDE CIRCUITS SHOWN FOR GENERATOR BATTERY CHARGER AND HEATER.

SCALE = 1" = 20'-0"

ELECTRICAL SITE PLAN

1 2026/09/09 ADDENDUM #1

R

WAP

J

J J

WAP

PP

OS

T

T

T

T

TELECOMM

CABINET

D5 D6 D5

D5

D4

D5

D7

D5

EMERGENCY

GENERATOR

'ATS1'

'E'

'1A'

D9D9

D9

D9

E-3

W5

E-3

W5

A

A A

1" EMT

1" EMT

E2

E1

E2

TELECOMM

CABINET

E-1

E-1

E-1E-6

E-8

E-6 E-6

'ATS1'

U

D

1-1/2" EMT

E-1

E-1

'A'

RTU-1

A-17

(ON ROOF)

WP

WP

E4

WH-1

E5

'E'

E4

UH-3

E4

UH-2

E4

UH-1

WP

WP

WP

A-17

A- 19,21,23

IEC-1

A- 25,27,29

DF-1

ON ROOF)

(ON ROOF)

E5

E5

'PC' 'TE'

S

TA TE OF U

T A H

P R O F

ES

SIO

NAL ENGIN

E E R

No. 7892177-2202

IAN

MADISON

1575 S. River Rd., Suite 101

St. George, Utah 84790

435.352.1050

GallowayUS.com

Checked By:

Project No:

Drawn By:

COPYRIGHT

THESE PLANS ARE AN INSTRUMENT OF SERVICE

STAMP

# Date Issue/Description

AND ARE THE PROPERTY OF GALLOWAY, AND MAY

NOT BE DUPLICATED, DISCLOSED, OR

REPRODUCED WITHOUT THE WRITTEN CONSENT

OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS

WILL BE ENFORCED AND PROSECUTED.

D F

C M

S ta m p

07/31/2026

9/4/2026 3:14:48 PM

A ut od es k D oc s:

//U D

F

-U D

F -U

T -H at ch

-M am m ot h- C re ek

B

R

/2

6_ M am m ot h

C re ek F is h

H at ch er y Im pr ov em en ts _v

.r vt

HATCHERY

BUILDING

ELECTRICAL PLAN

EL202

260526

RESOLUT

I.M.

H A

T C

H , U

T A

H

M am m ot h C re ek

F is h H at ch er y

Im pr ov em en ts

0 4' 8'2' 1/4" = 1'-0"

HATCHERY BUILDING DEMOLITION PLAN

0 4' 8'2' 1/4" = 1'-0"

HATCHERY BUILDING ELECTRICAL PLAN

SHEET KEYNOTES

D4 EXISTING LIGHT FIXTURES TO BE REMOVED AND REPLACED WITH NEW LIGHT FIXTURES. REFER TO

ELECTRICAL PALN FOR NEW FIXTURE TYPE. PROVIDE EXTENSION RING FOR ADDITIONAL GYP BOARD BEING

INSTALLED ON CEILING. MAINTAIN EXISTING CIRCUIT AND CONTROL.

D5 EXISTING RECEPTACLES TO BE REMOVED. MAINTAIN HOMERUN CONDUIT TO PANLE 'E'. REFER TO

ELECTRICAL PLAN FOR MORE INFORMATION.

D6 EXISTING BATTERY OPERATED RADON DETECTOR TO BE REMOVED AND REINSTALLED.

D7 EXISTING ROUTER AND WIFI TO BE REMOVED AND SALVAGED OT OWNER.

D9 EXISTING MECHANICAL UNIT TO BE REMOVED AND REPLACED. DISCONNECT AND REMOVE POWER AND ANY ASSOCIATED EQUIPMENT DISCONNECTS. MAINTAIN EXISTING CIRCUIT FOR NW MECHANICAL EQUIPMENT.

E1 PROVIDE DOUBLE GANG DEEP JUNCTION BOX WITH (1) 1" ENT CONDUIT TO TELECOMM CABINET FOR OWNER

PROVIDED WIRING.

E2 PROVIDE SINGLE GANG DEEP JUNCTION BOX.

E4 NEW MECHANICAL EQUIPMENT. PROVIDE NEW DISCONNECT SHOWN AND CONNECT EXISTING CIRCUIT TO

NEW EQUIPMENT.

E5 PROVIDE (2) 20A/1P BREAKERS FOR EXISTING 'E' PANEL. NEW BREAKERS TO MATCH EXISTING SIEMENS

EQUIPMENT.

1 2026/09/09 ADDENDUM #1

MMMM

#4

'LP1'

PANEL

NE N E

#4

NE

MMMM

#4

'LP1'

PANEL

NE

200A 2P

TO UTILITY CONNECTION

NOTES:

1. FOR GROUND CONDUCTOR IN PARALLEL RUNS, SIZE IN ACCORDANCE WITH NEC

PARAGRAPH 250-122.

2. GND. CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE CONDUCTORS

3. ALL COPPER CABLE TO BE THHN/THWN.

* 200% NEUTRAL, DERATED TO 80% BASED ON NEC 310.15.B(5)(C)

COPPER CONDUCTOR

& CONDUIT SCHEDULE

SIZEQUAN.

CONDUCTOR

TYPE SETS

MAX. O.C.

PROT.

COND.

AMPS

CONDUIT

SIZE

EQ. GND.

COND.

3"

3"350

500 4"

250-5 5*

4"

3"

4400-4

3400-3

4350-4

3350-3

44/0

2/0

3/0

1/0

1"

1"

1"

1"

1"

3/4"

3/4"

1-1/2"

1-1/2"

1-1/2"

1-1/4"

2"

2"

2"

2-1/2"

250300

4/0200-5 5*

2"

2"

4/0

3/0

2/0

1/0

3"

3"

2-1/2"

2"

2"

1-1/2"

1-1/4"

1-1/4"

1-1/4"

1"

1"

4300-4

3300-3

4250-4

3250-3

4200-4

3200-3

4175-4

3175-3

4150-4

3150-3

4110-4

3110-3

4100-4

3100-3

490-4

390-3

290-2

470-4

370-3

270-2

460-4

360-3

260-2

440-4

340-3

240-2

430-4

330-3

230-2 30 3/4"10 10

2-1/2"

4"5005*4 3/0121612001200-5

1000-5 1000 1072 2/04 5* 400 4"

4"3505*3 1/0744800800-5

2 3"500 1600-5 600 608 5*

4"500411 500418040004000-4

4"50048 400304030003000-4

2500-4 2500 2660 3507 4 500 4"

1200-4 1200 1240 3/04 4 350 4"

1000-4 1000 1140 2/03 4 500 4"

800-4 800 760 1/02 4 500 4"

2 3"350 1600-4 600 620 4

800-3 800 760 1/02 3 500 4"

3620600600-3 1350 3"2

1000-3 1000 1140 2/03 3 500 4"

1200-3 1200 1240 3/04 3 350 4"

4"40035 4/0167516001600-3

4"4005*6 4/0160816001600-5

4"40045 4/0167516001600-4

2000-4 2000 2010 2506 4 400 4"

5*368400400-5 34/0 3"2

6190 2"90-5 5*88 1

61/0125 2"5*125-5 120 1

62/0150 2"5*150-5 140 1

63/0175175-5 5* 2-1/2"160 1

3350300 3"4300-5 268 1

3500 4"350350-5 5*304 1

EXISTING 'ATS2'

200A, 1PH, 3 POLE

EXISTING 35KW PROPANE GENERATOR

240V, 1 PHASE, 3 WIRE

NEMA 3R ENCLOSURE

EXISTING METER/MAIN

SERVICE DISCONNECT

EXISTING FILTRATION BUILDING ONE-LINE DIAGRAM

EXISTING 'ATS1'

100A, 3PH, 4 POLE

EXISTING 30KW PROPANE GENERATOR

480V, 3 PHASE, 4 WIRE

NEMA 3R ENCLOSURE

EXISTING HATCHERY BUILDING ONE-LINE DIAGRAM

45A 3P

TO MEC.

HOUSE

EXISTING 100A DISCONNECT

MOUNTED ON SIDE OF BUILDING

100A 3P

SPACE

ONLY

50A 3P

50A 3P

30A 3P

100A 3P

MAIN DISTRIBUTION PANEL 'MDP'

277/480V, 3 P HASE, 4 WIRE

NEMA 3R, 18,000 AIC

LOCATED ON ROOF

TO MEC.

HOUSE

EXISTING 100A DISCONNECT

MOUNTED ON SIDE OF BUILDING

100A 3P

SPACE

ONLY

50A 3P

50A 3P

30A 3P

100A 3P

MAIN DISTRIBUTION PANEL 'MDP'

277/480V, 3 PHASE, 4 WIRE

NEMA 3R, 18,000 AIC

LOCATED ON ROOF

EXISTING 'ATS1'

100A, 3PH, 4 POLE

150A 3P

TO UTILITY CONNECTION

EXISTING 'ATS2'

200A, 1PH, 3 POLE

60KW PROPANE GENERATOR

240V, 1 PHASE, 3 WIRE

NEMA 3R ENCLOSURE

EXISTING METER/MAIN

SERVICE DISCONNECT

150A 2P

#2 CU

NEW 70A DISCONNECT

MOUNTED INSIDE BUILDING

ADJACENT TO TRANSFORMER

TRANSFORMER 'TE'

240V-DELTA 480/240V (LT) DELTA

3 PHASE, 4 WIRE

45 KVA

150-3

NEW EMERGENCY ONE-LINE DIAGRAM

D10D10

'PC'

X1 150-4

150-3 70-4 70-4

S

TA TE OF U

T A H

P R O F

ES

SIO

NAL ENGIN

E E R

No. 7892177-2202

IAN

MADISON

1575 S. River Rd., Suite 101

St. George, Utah 84790

435.352.1050

GallowayUS.com

Checked By:

Project No:

Drawn By:

COPYRIGHT

THESE PLANS ARE AN INSTRUMENT OF SERVICE

STAMP

# Date Issue/Description

AND ARE THE PROPERTY OF GALLOWAY, AND MAY

NOT BE DUPLICATED, DISCLOSED, OR

REPRODUCED WITHOUT THE WRITTEN CONSENT

OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS

WILL BE ENFORCED AND PROSECUTED.

D F

C M

S ta m p

07/31/2026

9/4/2026 3:14:49 PM

A ut od es k D oc s:

//U D

F

-U D

F -U

T -H at ch

-M am m ot h- C re ek

B

R

/2

6_ M am m ot h

C re ek F is h

H at ch er y Im pr ov em en ts _v

.r vt

ELECTRICAL

ONE-LINE

DIAGRAM

EP401

260526

RESOLUT

I.M.

H A

T C

H , U

T A

H

M am m ot h C re ek

F is h H at ch er y

Im pr ov em en ts

NOT TO SCALEEP401

1 Electrical One-Line Diagram

1 2026/09/09 ADDENDUM #1

SHEET KEYNOTES

D10 REMOVE EXISTING FEEDERS, WIRING, CONDUIT, BOXES, ETC.

X1 PROVIDE NAPCCO SMART-BOOST PHASE CONVERTER SB-60-EE-D3 (OR EQUAL).