1-ODOT_106_Group5_SHA1210_EDCO_332.pdf
PDF 80 KB Posted
- Attached to
- Competitive Selection OH|DOT10626-1
- Contract number
- DOT10626-1
- Issued by
- Ohio
About this file
This document is a technical specification sheet for the Edco SHA-1210 filtering surge protector, a 120 VAC single-phase power protection device. While the document does not explicitly detail a state or local contract, the file metadata suggests an association with ODOT (Oregon Department of Transportation) and a potential government procurement context.
The Edco SHA-1210 is a surge protection device designed to absorb power line noise and switching transients, with key technical specifications including a 395 VAC clamping voltage, 10A operating current, and peak surge current capabilities of 32.5 kA/Mode. The device features a multi-stage hybrid design, 60 dB maximum noise filtering, nanosecond response time, and incorporates a series choke. It offers protection across line-to-neutral, line-to-ground, and neutral-to-ground modes, operates in temperatures from -40°C to +85°C, and comes with a 5-year warranty. The compact unit weighs 2 lbs and measures 2.375H x 3.125W x 7.125L inches, with mounting provisions for easy installation in electrical systems.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Operating Temperature
Dimensions (Inches)
Weight
Mounting
Edco SHA-1210 120 VAC — 1 Phase The Edco SHA-1210 fi ltering surge protector absorbs power line noise and switching transients that other suppressors and RFI fi lters pass through.
The Edco SHA-1210 can replace the RFI fi lter when high attenuation of noise above 25 MHz is not required.
If random time-base, memory loss, or other problems are affecting some of your intersections, this state-of-the-art protector can be of great benefi t when properly installed.
General Technical Specifi cations
AC Hot Buss Cabinet Power
120 VAC
Input
Earth
Protected Power Source
(to controller and other sensitive electronics)
CB
Main Neutral
Neutral Buss
Site Variable (Option)
Edco
SHA-1210
AC In
AC Out
Neutral Out
Eq u ip m en t
Sid e
M ain
Earth
Installation
Caution:
1. This product could become excessively hot and rupture in the rare event of power line conditions or surge that exceed its rated operating specifi cation. Appropriate precautions should be exercised.
2. High voltages are present on electrical termination. Unit should be serviced by qualifi ed personnel only.
AC Power — Series Connected
Part Number Edco SHA-1210
Operating Voltage 120 VAC
Clamping Voltage 395 VAC
Operating Current 10A
Peak Surge Current 32.5 kA/Mode, 52 kA/Phase, 84.5 kA/Total
Operating Frequency 47-63 Hz
EMI Attenuation 60 dB typ
SPD Technology MOVs w/L-C Filter
Modes of Protection L-N, L-G, N-G
Status Indication NA
Connection Type 1/4-20 Stainless Steel Stud
-40°C to +85°C
2.375H x 3.125W x 7.125L
2 lbs
HOLE (6 places) 3/16" dia.
PLATE
1.28"
1.28"
3.125"
7.125" 6.65"
Features
■ Multi-stage hybrid design
■ 60 dB maximum noise filtering
■ Nanosecond response time
■ Incorporates series choke
■ 5 year warranty