08-05-26_2538_AD4_REV.pdf
PDF 7 MB Posted
- Attached to
- Dining Room Addition & Interior Renovations
- Solicitation number
- RFP BAY 260000002591 1
- Issued by
- Bay County, Michigan
About this file
This document is an architectural and electrical specification file for a Dining Room Addition and Interior Renovations project at Bay Arena CSD in Bay City, Michigan. The project encompasses a comprehensive dining facility expansion and renovation including a dining room, cafeteria, kitchen, serving areas, dishwashing station, and associated support spaces. The work also includes renovations to adjacent instructional areas such as classrooms, offices, and specialized labs (machine trades, welding, building trades, auto service, body shop, agricultural, diesel service). The project includes detailed architectural floor plans, building sections, and electrical specifications prepared by TSSF Architects, Inc. in Saginaw, Michigan, with consulting engineering services provided by KTS Engineering Group in Shepherd, Michigan. The electrical specifications indicate the work requires compliance with current Michigan Building Code, National Electrical Code (NEC) 2023, and various state and federal standards including ADA requirements. The project includes specific electrical components such as lighting fixtures, receptacles, disconnect switches, manual motor starters, occupancy sensors, and emergency lighting systems throughout the facility.
The electrical contractor is required to execute the work in compliance with "best trade practices" and coordinate with mechanical, plumbing, and other trades to ensure proper installation. All electrical equipment must be new (unless NEC allows refurbished equipment), UL approved, and specification grade, with specific manufacturers noted as Square D, Siemens, Eaton, G.E., or equivalent. Conductors must be copper only; aluminum is not permitted. All wiring must be installed in EMT (thinwall conduit) unless Romex is explicitly allowed, with all above-ground wiring concealed except where surface raceway is specifically noted and approved. The electrical contractor is responsible for conducting a short-circuit study and ensuring all equipment meets those requirements, performing circuit testing, maintaining updated as-built drawings, and providing one-year warranties on all work and materials. The contractor must submit shop drawings in PDF format via internet a minimum of seven days prior to bidding and obtain all required permits and inspections, with the document containing detailed specifications for panel schedules, grounding, voltage drop calculations, and feeder sizing schedules.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 03-31-26_2538_AD2.pdf | ||
| 06-03-26_2538_AD3.pdf | ||
| 09-08-26_Bid Set.pdf | ||
| 03-25-26_2538_AD1.pdf | ||
| Full Spec (4).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N . W
AS
H
IN
G
TO
N
A
VE
N U
E
TS
SF
A
RC
HI
TE
CT
S, I
NC
SA
G
IN
AW
M
IC
H
IG
AN
MASTER FIRST FLOOR PLAN
BA
Y
AR
EN
AC
IS
D D
IN
IN
G R
O O
M A
D D
IT
IO
N A
N D
R
EN
O
VA
TI
O
N S
FO
R
:MACHINE TRADES
WELDING
BUILDING TRADES
AUDITORIUM
CAFETERIA
AUTO SERVICE LAB BODY SHOP
AG. LAB
MATERIAL
MEDIA
CENTER
RECEIVINGBUILDING
MAINTENANCE
LAB
ADMINISTRATION
HEALTH
WING
AND SCIENCE
GREENHOUSE
GREENHOUSE
DATA PROC.
KITCHEN
DIESEL SERVICE LAB
52'-7"
41'-3"
DINING
SERVING
R1
R1
R1
R1
AREAS OF WORK LEGEND
EXIT
34" EGRESS
MINUMUM CLEARANCE
LIFE SAFETY AREA LEGEND
TRAVEL DISTANCE
EXIT (w/ NUMBER OF OCCUPANTS)
ACT.CAP.
DOOR
EXIT
0 0
ACT.CAP.
DOOR
EXIT
340 38
ACT.CAP.
DOOR
EXIT
340 71 91'-0"
78 ACTUAL OCCUPANT EGRESS COUNT
1-HOUR RATED FIRE BARRIER
2-HOUR RATED FIRE BARRIER
FIRE EXTINGUISHER - MULTI-PURPOSE
DRY CHEMICAL
DINING
OFF.
CLASSRM.
CLASSRM.
R1
R1
R1
OCCUPANT CALCULATIONS
REQUIRED EGRESS WIDTH
TOTAL EGRESS WIDTH REQUIRED:
·180 MAX INTERIOR OCCUPANT x .2" = 36"
TOTAL EGRESS WIDTH PROVIDED:
·THREE 68" CLEAR DOOR EXIT LEAFS = 204"
NUMBER OF EXITS REQUIRED : 2
MICHIGAN BUILDING CODE
FUNCTION OF SPACE FACTOR
EDUCATION 73
TOTAL PROJECT OCCUPANT LOAD 180
ASSEMBLY A-2 1:15 NET 91
1:20 NET
OCCUPANTS
KITCHEN 1:200 GROSS 14
OFFICE 1:150 GROSS 2
ACT.CAP.
DOOR
EXIT
340 205
R
R1
91 55
OFF.
BODY SHOP
OFF.
OFF.
CONF.
OFF.
OFF.
CLASSRM.
RES.
OFF.
CONF.
FUNDAMENTALS LAB
CHILDCARE CLASS
CLASSRM.
R2
R2
R2
R2
R http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com
N . W
AS
H
IN
G
TO
N
A
VE
N U
E
TS
SF
A
RC
HI
TE
CT
S, I
NC
SA
G
IN
AW
M
IC
H
IG
AN
PARTIAL FIRST FLOOR PLAN
DINING ROOM
VEST.
MENS
WOMENS
CLASSROOM
OFFICE112
CLASSROOM
KITCHEN
DINING ROOM
SERVING
CAFETERIA
EX. CORRIDOR
DISH WASHING EX. COOLER EX. FREEZER
STORAGE
PASSAGE
WAIT STATION
STORAGE
EX. SHIP/ REC.
EX. CORRIDOR
EX. STOR.
EX. CONF.
EX. CLASSROOM/ LAB
EX
. P
AS
SA
G E
EX. OFFICE EX. OFFICE
EX. OFFICE EX. OFFICE
EX. CLASSROOM
EX. TLT.
EX. TLT.
EX. CONF.
EX. PASSAGE
EX. STOR. EX. STOR.EX. TLT. EX. TLT. EX. ST.
EX. DAYCARE
EX. OFF.
EX. CORRIDOR
BA
Y
AR
EN
AC
IS
D D
IN
IN
G R
O O
M A
D D
IT
IO
N A
N D
R
EN
O
VA
TI
O
N S
FO
R
ALTERNATE NO. 1
A6.0
A6.0
A6.0
0A
100B
LOCKERS
4B
104A
PREP AREA
A8.0
A8.0
A6.0
A6.0
ENLARGED FLOOR PLAN1
A2.0
MENS
WOMENS
A8.0 2
A8.0
7 A8.0
A2.0
A2.0
ENLARGED FLOOR PLAN2
A2.0
A8.0
A8.0
A PARTITION WALL
NON-RATED
NON-BEARING WALL
WALL TYPES
B
A
B PARTITION WALL
2 HR-RATED (UL U419)
NON-BEARING WALL
A
AC
A
B
A
C
C
A8.05A8.0
4.5
4.8
6.6
6.9
7.3
8.2
B
VVUUTTSSRRQQPPOONNMMLLKKJJIIHHGGFFEEDDCCBBAAZY
A8.0
A8.0
A
B
104C
C
C PARTITION WALL
1 HR-RATED (UL U419)
NON-BEARING WALL
R
R1
R1
R1
R1
R1
R1
R1
R
R2
D SHAFT WALL
2 HR-RATED (UL U438)
NON-BEARING WALL
R2
D http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com
N . W
AS
H
IN
G
TO
N
A
VE
N U
E
TS
SF
A
RC
HI
TE
CT
S, I
NC
SA
G
IN
AW
M
IC
H
IG
AN
BA
Y
AR
EN
AC
IS
D D
IN
IN
G R
O O
M A
D D
IT
IO
N A
N D
R
EN
O
VA
TI
O
N S
FO
R
BUILDING SECTION1
A6.0
BUILDING SECTION2
A6.0
BUILDING SECTION3
A6.0
A7.0
A7.02
A7.0
567566.6 4.8 4.5 6.66.97.3 4.8 4.5
PP QQ RR SS TT UU VV
DINING ROOM
DINING ROOM
VEST.
WOMENS
WOMENS
MENS
A6.0
WALL SECTION4
A6.0
R2
R
QQPP
R2
GENERAL ELECTRICAL NOTES & SPECIFICATIONS:
1. EXECUTE THE WORK REQUIRED IN A MANNER EVIDENCED AS THE "BEST TRADE PRACTICES"
CONTRIBUTING TO EFFICIENCY OF OPERATION, MINIMUM MAINTENANCE, ACCESSIBILITY AND
AESTHETICS OF THE INSTALLATION.
2. MECHANICAL AND ELECTRICAL PLANS ARE DIAGRAMMATIC IN NATURE, INTENDED TO
INDICATE DESIGN INTENT ONLY. CONTRACTOR IS RESPONSIBLE TO COORDINATE SPECIFIC
LOCATIONS OF ITEMS AND ADJUST AS REQUIRED TO ACCOMMODATE CODE REQUIREMENTS,
MANUFACTURER'S INSTALLATION REQUIREMENTS, AND THE WORK OF OTHER TRADES.
3. MECHANICAL AND ELECTRICAL INFORMATION IS PRESENTED ON AN X-REFERENCED
BACKGROUND PLAN. IN CASE OF CONFLICT BETWEEN BACKGROUND PLAN AND
ARCHITECTURAL FLOOR PLAN, ARCHITECTURAL FLOOR PLAN SHALL GOVERN.
4. RUN ALL PIPING, CONDUIT, ETC. CONCEALED IN WALLS WHENEVER POSSIBLE AND AVOID
EXPOSED INSTALLATION UNLESS SPECIFICALLY REQUIRED (TYPICAL UNLESS NOTED
OTHERWISE ON DRAWINGS). IN ANY LOCATIONS WHERE CONCEALMENT IS NOT POSSIBLE,
CONTACT ENGINEER PRIOR TO INSTALLATION FOR PERMISSION FROM ENGINEER.
5. THE ENGINEER WILL NOT HAVE CONTROL OR CHARGE OF CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES, OR PROCEDURES. ENGINEER IS NOT RESPONSIBLE FOR SAFETY
PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK; AND WILL NOT BE
RESPONSIBLE FOR CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH
THOSE DOCUMENTS PREPARED BY THE ENGINEER.
6. ALL CONSTRUCTION SHALL BE DONE IN COMPLIANCE WITH CURRENT CODES, INCLUDING:
MICHIGAN BUILDING CODE, MICHIGAN PLUMBING CODE, MICHIGAN MECHANICAL CODE,
NATIONAL ELECTRICAL CODE (NEC), MICHIGAN BUILDING REHABILITATION CODE (WHEN
APPLICABLE), NFPA CODES, LIFE SAFETY CODE (WHEN APPLICABLE), AMERICANS WITH
DISABILITIES ACT (ADA), MICHIGAN BARRIER FREE CODES, MICHIGAN ENERGY CODE,
MICHIGAN DEPARTMENT OF PUBLIC HEALTH CODES (WHEN APPLICABLE), AND ALL OTHER
LOCAL, STATE, AND FEDERAL APPLICABLE CODES. THE CONTRACTOR SHALL UTILIZE THE
LATEST ADOPTED EDITIONS OF ALL CODES.
7. IF BIDDING CONTRACTOR WOULD LIKE TO SUBSTITUTE ANY SPECIFIED ELECTRICAL DEVICES, LIGHT FIXTURES, CONTROLLERS, PANELS, DISCONNECTS, VFD'S, ELEC. GEAR, ETC., THEY MUST
PROVIDE SUBMITTAL TYPE DRAWINGS TO THE ENGINEER A MINIMUM OF 7 DAYS PRIOR TO
BIDDING THE PROJECT. IF THESE APPROVAL DRAWINGS ARE NOT SUBMITTED AND APPROVED,
THE SPECIFIED EQUIPMENT MUST BE USED - NO EXCEPTIONS.
8. EQUIPMENT AND MATERIALS SHALL BE UL APPROVED AND SPECIFICATION GRADE.
9. ELECTRICAL CONTRACTORS SHALL SECURE PERMITS AND INSPECTIONS REQUIRED BY STATE
AND LOCAL LAWS AND ORDINANCES AND PAY ALL FEES AND EXPENSES IN CONNECTION
THEREWITH AS A PART OF THEIR WORK UNDER THIS CONTRACT.
10. UPON COMPLETION OF WORK, FURNISH OWNER CERTIFICATES OF FINAL INSPECTION AND
APPROVAL FROM AUTHORITIES HAVING JURISDICTION.
11. ALL CONDUCTORS SHALL BEAR IDENTIFICATION AS TO SIZE AND TYPE OF INSULATION AND
SHALL BE EQUIPPED WITH WIRE MARKERS INDICATING THE CIRCUIT NUMBER, WIRE NUMBER
AND/OR PHASE LETTER.
12. IDENTIFY ELECTRICAL EQUIPMENT WITH THE NAME OF THE EQUIPMENT, THE EQUIPMENT
CONTROLLED, OR THE SYSTEM INVOLVED. DISCONNECT SWITCHES AND MOTOR STARTERS
SHALL HAVE NAMEPLATES TO INDICATE THE EQUIPMENT THEY CONTROL. ALL ELECTRICAL
EQUIPMENT POWER PANELS SHALL HAVE NAMEPLATES DESIGNATING THEIR NAMES AND
VOLTAGE RATING, SUCH AS LP-A, 120/208 VOLT, 3 PHASE, 4 WIRE. NAMEPLATES SHALL BE
ENGRAVED THREE-LAYER PLASTIC, BLACK LETTERS ON WHITE BACKGROUND FOR NORMAL
POWER AND WHITE LETTERS ON RED BACKGROUND FOR EMERGENCY/STANDBY POWER
PANELS AND ASSOCIATED EQUIPMENT. NO HANDWRITTEN OR PRINTED LABELING WILL BE
ACCEPTED AS FINAL RECORD UPON PROJECT COMPLETION. NAMEPLATES SHALL BE A MINIMUM
OF 1” X 3”, OR AS NOTED ON NAMEPLATE SCHEDULE IF THERE IS ONE ON DRAWINGS. AS A
TEXT SIZE MINIMUM:
A. SWITCHBOARD OR PANELBOARD MAINS: 1” HIGH
B. SWITCHBOARD OR PANELBOARD BRANCHES: ½” HIGH
C. STARTERS/DISCONNECTS: ½” HIGH
D. MANUAL MOTOR STARTERS: ¼” HIGH
13. PANEL SCHEDULES SHALL BE TYPEWRITTEN AND INSTALLED FOR EVERY PANEL, BE IT NEW OR EXISTING. FOR EXISTING PANELS, CIRCUITRY SHALL BE VERIFIED PRIOR TO UPDATING PANEL
SCHEDULE. HANDWRITTEN SCHEDULES, AND/OR CROSSED OFF EXISTING SCHEDULES ARE NOT
ACCEPTABLE.
14. ALL WORK AND MATERIALS SHALL BE GUARANTEED IN WRITING FOR (1) YEAR FROM PROJECT
COMPLETION UNLESS A FURTHER GUARANTEE IS NOTED ELSEWHERE.
15. ALL SWITCHES, RECEPTACLES, SMALL MANUAL MOTOR STARTERS, OR TOGGLE SWITCHES
SHALL HAVE THE CIRCUIT NUMBER IDENTIFIED ON THE DEVICE COVER PLATE USING CLEAR
ADHESIVE TAPE LABELS WITH ¼” HIGH PRINTED BLOCK CHARACTERS IN BLACK. NO
HANDWRITTEN LABELS WILL BE ACCEPTED AS FINAL RECORD.
16. THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH CONDITIONS OF WHICH WILL AFFECT THE WORK HE IS TO PERFORM. THE SUBMISSION OF A PROPOSAL BY THIS
CONTRACTOR SHALL BE CONCLUSIVE EVIDENCE THAT THIS CONTRACTOR HAS VISITED THE
SITE AND HAS GIVEN PROPER CONSIDERATION AND EVALUATION OF THESE CONDITIONS IN
THE PREPARATION OF HIS PROPOSAL. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE ON HIS
BEHALF FOR EXTRA EXPENSE INCURRED DUE TO FAILURE OR NEGLECT ON HIS PART TO MAKE
THIS VISIT AND EXAMINATION.
17. WHERE ACTIVE SEWERS, GAS, ELECTRIC, OR OTHER SERVICES ARE ENCOUNTERED DURING
THE PERFORMANCE OF THIS CONTRACT, THE CONTRACTOR SHALL PROTECT, BRACE AND
SUPPORT THEM AS REQUIRED. DO NOT PREVENT, INTERRUPT OR DISTURB OPERATION OF
EXISTING SERVICES THAT ARE TO REMAIN. RELOCATE EXISTING SERVICES IF/AS REQUIRED.
18. THE CONTRACTOR SHALL CHECK THE UTILITY COMPANIES AND MUNICIPAL AGENCIES FOR
EXACT LOCATIONS OF SERVICES WHICH THEY MAY EXPECT TO ENCOUNTER.
19. IN GENERAL, MOUNTING HEIGHTS ABOVE FINISHED FLOOR TO THE CENTERLINE OF BOXES
AND EQUIPMENT SHALL BE AS PER AMERICANS WITH DISABILITIES ACT, AND MICHIGAN
BARRIER FREE CODES.
20. WORK SHALL BE PERFORMED BY SKILLED MECHANICS WELL VERSED IN THEIR PARTICULAR
TRADES.
21. RESPONSIBILITY FOR CARE AND PROTECTION OF ELECTRICAL WORK RESTS WITH THE
CONTRACTOR UNTIL IS HAS BEEN TESTED AND ACCEPTED.
22. CONTRACTOR IS TO CHECK DOOR SWINGS WITH ARCHITECTURAL PLANS AND MOUNT LIGHT
SWITCHES, CONTROLS, ETC., ACCORDINGLY. VERIFY WITH LATEST ARCHITECTURAL
DRAWINGS.
23. ELECTRICAL EQUIPMENT SHALL BE SQUARE D, SIEMENS, EATON, G.E. OR MATCH EXISTING.
24. DISCONNECT SWITCHES SHALL BE NEMA HEAVY DUTY, FUSIBLE OR NON-FUSIBLE AS NOTED ON
PLANS, WITH A NEMA 3R ENCLOSURE WHEN MOUNTED OUTDOORS.
25. THE NEUTRAL CONDUCTOR OF THE WIRING SYSTEM TOGETHER WITH THE CONDUIT SYSTEM
AND SERVICE EQUIPMENT SHALL BE GROUNDED AND SIZED PER NEC ARTICLE 250 – SEE
DETAIL ON DRAWINGS ALSO.
26. HOLES THROUGH WALLS OR PARTITIONS REQUIRED FOR ELECTRICAL WORK SHALL BE
NEATLY CUT TO SIZE. CONDUITS PENETRATING OUTSIDE WALLS SHALL BE SEALED
ACCORDINGLY, UNDERGROUND CONDUITS SHALL HAVE LINK SEALS. PENETRATIONS OF FIRE
RATED ASSEMBLIES SHALL BE FIRE-STOPPED BY APPROVED METHODS AND MATERIALS. NO
BEAMS OR OTHER STRUCTURAL MEMBERS SHALL BE DRILLED, BURNED, OR CUT.
27. LOCATIONS OF WIRING DEVICES SUCH AS LIGHT SWITCHES, DUPLEX RECEPTACLES,
THERMOSTATS, ETC., SHALL BE COORDINATED WITH OTHER TRADES.
28. IN GENERAL, ALL MOTORS ARE FURNISHED AND INSTALLED UNDER THE MECHANICAL
SECTION OF THE SPECIFICATIONS. ALL STARTERS, FUSED SWITCHES, SAFETY SWITCHES,
INCLUDING ALL POWER WIRING SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR.
29. OUTLET BOXES IN THE SAME WALL BUT SERVING DIFFERENT ROOMS SHALL BE AT LEAST 4"
APART TO MINIMIZE NOISE TRANSMISSION. WHEN LOCATED ON FIRE WALLS, THEY SHALL BE
24" APART.
30. LIGHTING AND CONTROL WIRING SHALL BE TESTED FOR SHORTS AND OPENS AND SHALL BE
GIVEN A COMPLETE OPERATIONAL TEST.
31. THE CONTRACTOR SHALL TEST ALL CIRCUITS AS SOON AS CONDUCTORS ARE INSTALLED AND
MAKE FINAL TESTS WHEN ALL WORK IS COMPLETE. IF CIRCUITS ARE NOT PROPERLY
CONTROLLED AND INSULATED AT TIME OF EACH FINAL TEST, THE NECESSARY REPAIRS AND
TESTS SHALL BE MADE AT THE CONTRACTORS EXPENSE.
32. ELECTRICAL EQUIPMENT SHALL MEET INSTALLATION STANDARDS PROVIDED IN NEC ARTICLE
110. COORDINATE LOCATIONS OF M.E.P. ITEMS WITH CONTRACTORS PRIOR TO
CONSTRUCTION TO ASSURE THAT CLEARANCES ARE MET. LACK OF COORDINATION BETWEEN
CONTRACTORS WILL NOT RESULT IN EXTRA MONIES AWARDED FOR RELOCATION OF M.E.P.
ITEMS.
33. CHECK FINAL LOCATIONS OF LIGHT FIXTURES AND CEILING ELECTRICAL ITEMS WITH
GRILLES AND REGISTERS, CAMERAS, FANS, SPRINKLER HEADS, ETC. COORDINATE WITH
RESPECTIVE CONTRACTORS PRIOR TO INSTALLATION. NO MONIES WILL BE AWARDED TO
CONTRACTORS HAVING TO RELOCATE ITEMS DUE TO LACK OF COORDINATION BETWEEN
CONTRACTORS. MECHANICAL AND ELECTRICAL PLANS SHOW SCHEMATIC LOCATIONS ONLY –
REFERENCE ARCHITECTURAL REFLECTIVE CEILING PLANS.
34. ANY DISCREPANCIES BETWEEN ARCHITECTURAL DRAWINGS AND ELECTRICAL DRAWINGS
SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO
INSTALLATION.
35. CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF DRAWINGS REFLECTING
"AS BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT
DIMENSIONS AND ELEVATIONS FOR ALL UNDERGROUND AND/OR CONCEALED WORK. UPON
COMPLETION OF THIS PROJECT, THE CONTRACTOR SHALL DELIVER TO THE CONSTRUCTION
MANAGER OR GENERAL CONTRACTOR THE AS-BUILT DRAWINGS. AS BUILT DRAWINGS MUST
BE IN THE POSSESSION OF THE C.M. OR G.C. PRIOR TO FINAL PAYMENT TO THE E.C.
36. THE WIRING METHOD(S) USED SHALL BE SUITABLE FOR THE INSTALLATION AND USE IN
CONFORMITY WITH THE PROVISIONS PROVIDED BY THE NEC, LISTED OR LABELED
EQUIPMENT SHALL BE USED OR INSTALLED IN ACCORDANCE WITH ANY INSTRUCTIONS
INCLUDED IN THE LISTING OR LABELING. REFER TO NEC, SECTION 110.3(A) AND (B).
37. THE MAIN SERVICE DISCONNECTS SHALL BE IDENTIFIED AS THE MAIN SERVICE
DISCONNECTION MEANS PER NEC 2023, ARTICLE 230.70(B).
38. CONTRACTOR SHALL CHECK ELECTRICAL FLOOR PLANS FOR "ISLAND" TYPE ELECTRICAL
OUTLETS AND INSTALL UNDER-FLOOR CONDUITS AND WIRING ACCORDINGLY. SEE PLANS.
39. ARC-FLASH HAZARD WARNING SHALL BE PROVIDED AT ALL ELECTRICAL PANELS PER NEC
2023, SECTION 110.16
40. FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN THE
OPINION OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS ARE
REQUIRED TO PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR SHALL REQUEST
AN INTERPRETATION FROM THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE
WORK. IT THE CONTRACTOR FAILS TO MAKE SUCH A REQUEST, NO EXCUSE WILL
THEREAFTER BE ENTERTAINED FOR FAILURE TO PROVIDE FIRST-CLASS WORKABLE SYSTEMS.
ENGINEER HAS THE FINAL SAY AS TO WHAT IS CONSIDERED “FIRST CLASS WORKABLE
SYSTEMS”.
41. SHOP DRAWINGS ARE TO BE THOROUGHLY CHECKED (AND NOTED SO ON FRONT COVER) BY
THE CONTRACTOR PRIOR TO SUBMITTING THEM TO THE ARCHITECT/ENGINEER. REVIEW BY
THE ENGINEER, SHALL NOT BE CONSTRUED AS A COMPLETE CHECK, BUT ONLY THAT THE
GENERAL METHOD OF CONSTRUCTION AND DETAILING IS SATISFACTORY. REVIEW SHALL
NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS WHICH MAY EXIST.
SHOP DRAWINGS ARE TO BE SUBMITTED VIA INTERNET IN PDF FORM. NO HARD COPIES WILL
BE ACCEPTED. IF E.C. DOES NOT REVIEW DRAWINGS AND NOTES SAME ON FRONT COVER
PRIOR TO SUBMITTAL TO ARCHITECT/ENGINEER, THEY WILL BE REJECTED.
42. ELECTRICAL CONTRACTOR IS TO REFER TO THE TEMPERATURE CONTROL SECTION OF THE
SPECIFICATIONS AND THE MECHANICAL EQUIPMENT SCHEDULE FOR DEFINITION OF WHICH
TRADES ARE RESPONSIBLE FOR HVAC INTERLOCKS AND OPERATIONAL SWITCHES.
43. ALL ROOF EQUIPMENT THAT HAS POWER TO IT MUST BE PROVIDED WITH A DUPLEX
RECEPTACLE (WP AND GFI) WITHIN 25 FEET OF THE UNIT. MOUNT RECEPTACLES ON
HOUSING, CIRCUIT WITH NEARBY RECEPTACLES BELOW, AND NOT WITH ROOF UNIT PER NEC
NOTE: ROOF RECEPTACLES MAY OR MAY NOT BE SHOWN ON PLANS
44. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO CHECK THE RELATED MECHANICAL/KITCHEN/
REFRIGERATION/ELEVATOR/ETC. DRAWINGS TO SEE WHAT DISCONNECT
SWITCHES/STARTERS/RELAYS/ETC. ARE PACKAGED IN BY THE SPECIFIC EQUIPMENT
SUPPLIERS. IF NONE ARE SPECIFICALLY NOTED THE E.C. IS RESPONSIBLE TO PROVIDE AND
INSTALL AS REQUIRED FOR SEQUENCES OF OPERATION. E.C. IS TO REVIEW
MECHANICAL/KITCHEN/REFRIGERATION/ELEVATOR/ETC. SEQUENCES OF OPERATION, FOUND
IN SECTIONS OF THE DRAWINGS AND SPECIFICATIONS OTHER THAN THE ELECTRICAL
SECTIONS FOR SAID SEQUENCES. DISCONNECT SWITCHES/STARTERS/RELAYS/ETC. MAY OR
MAY NOT BE SHOWN ON THE ELECTRICAL DRAWINGS.
45. MANUALS: PER MICHIGAN ENERGY CODES (SPECIFICALLY ASHRAE 90.1 STANDARDS),
CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL AND
MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL
INCLUDE, AT A MINIMUM, THE FOLLOWING:
A. SUBMITTAL DATA FOR ALL ELECTRICAL EQUIPMENT CLEARLY STATING EQUIPMENT
RATING, EXACTLY WHAT MODELS, ACCESSORIES, OPTIONS ARE INSTALLED.
B. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE
CLEARLY IDENTIFIED.
C. NAMES AND ADDRESSES AND PHONE NUMBERS/EMAIL ADDRESSES FOR AT LEAST ONE
QUALIFIED SERVICE AGENCY FOR EACH PIECE OF EQUIPMENT. A COMPLETE NARRATIVE
OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
46. WIRING TO BE MINIMUM #12 (FOR RUNS OVER 100 FEET, MINIMUM #10).
47. ALL EQUIPMENT INSTALLED AS PART OF THIS PROJECT SHALL BE NEW, REFURBISHED
EQUIPMENT MAY BE USED WHERE NEC ALLOWS.
48. CONTRACTOR IS RESPONSIBLE TO PERFORM THE SHORT CIRCUIT STUDY FOR THE PROJECT
AND THAT ALL ELECTRICAL EQUIPMENT SHALL BE ADJUSTED TO MEET THOSE
REQUIREMENTS.
49. ALL ABOVE GROUND WIRING TO BE INSTALLED IN EMT (THINWALL CONDUIT) UNLESS ROMEX
IS EXPLICITLY ALLOWED.
50. OCCUPANCY AND TOGGLE SWITCHES AS WELL AS RECEPTACLES SHALL BE SPECIFICATION
GRADE, COLOR TO BE CHOSEN BY ARCHITECT DURING SHOP DRAWING STAGE.
51. DEVICE PLATES FOR SWITCHES, RECEPTACLES, TELEPHONE, COMPUTER, ETC., SHALL BE AS
MANUFACTURED PASS AND SEYMOUR, HUBBELL, OR BRYANT. THEY SHALL BE 0.040” THICK
BRUSHED STAINLESS STEEL UNLESS NOTED OTHERWISE. FOR EXISTING PROJECTS, COVER
PLATES SHALL MATCH OTHERS IN THE AREA UNLESS NOTED OTHERWISE.
52. ALL BUSSING AND WIRING TO BE COPPER. NO ALUMINUM IS ALLOWED ON THIS PROJECT.
53. ALL NEW ELECTRICAL DEVICES AND ASSOCIATED OUTLET BOXES SHALL BE FLUSH MOUNTED
UNLESS NOTED OTHERWISE. ALL CONDUIT AND WIRING SHALL BE CONCEALED. SURFACE
RACEWAY AND ASSOCIATED BOXES SHALL ONLY BE PERMITTED WHERE NOTED AND SHALL BE
DISCUSSED WITH C.M. OR G.C. PRIOR TO INSTALLATION.
54. CONNECT ALL EMERGENCY AND EXIT BATTERY PACKS TO NEARBY LIGHTING CIRCUITS AHEAD
OF SWITCHES PER NEC SO EMERGENCY/EXIT LIGHTS OPERATE ON LOSS OF POWER.
55. ELECTRICAL CONTRACTOR SHALL “RING OUT” ALL CIRCUITS IN EXISTING PANELBOARDS
AFFECTED BY THE WORK OF THIS PROJECT AND PROVIDE UPDATED TYPED PANELBOARD
DIRECTORIES. PROVIDE BLANK COVERS WHERE BREAKERS HAVE BEEN REMOVED.
END OF ELECTRICAL NOTES/SPECIFICATIONS
ELECTRICAL FIXTURE LEGEND
DUPLEX RECEPTACLE AT 46" AFF
DUPLEX RECEPTACLE AT 18" AFF
SPLIT-CIRCUIT DUPLEX RECEPTACLE AT 18" AFF
QUAD RECEPTACLE AT 18" AFF
JUNCTION BOX
DISCONNECT SWITCH, NON-FUSED, HEAVY DUTY, HP-RATED - ASSUME 30 AMP SWITCH UNO
ON ONE LINE DIAGRAM OR FLOOR PLANS.
MANUAL MOTOR STARTER
DATA LEGEND
DATA ROUGH-IN
DISTRIBUTION LEGEND
RECEPTACLE PANELBOARD (208Y/120V, 3Ø, 4W), REFER TO PANEL
SCHEDULES FOR MORE INFORMATION.
LOW VOLTAGE:
DATA CABLING TO BE HANDLED BY OWNERS VENDER,
E.C. SHALL PROVIDE ALL CONDUITS, BACK BOXES AND
PULL WIRE PER DRAWINGS.
" INCHES
# NUMBER
' FEET
1P 1 POLE (2P, 3P, 4P, ETC.)
@ AT
A AMPERE
A.F.F. ABOVE FINISHED FLOOR
ACLG ABOVE CEILING
ACT ABOVE COUNTER
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFCI ARC FAULT COMBINATION CIRCUIT INTERRUPTER
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUA-STAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
B.F. BOTTLE FILLER
B.M.S. BUILDING MANAGEMENT SYSTEM
BATT BATTERY
BLDG BUILDING
C. CONDUIT
CAB CABINET
CAT CATALOG
CAT6 CATEGORY 6 CABLING
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CL CONNECTED LOAD
COF COFFEE MAKER
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION, CONTINUOUS
CONTR CONTRACTOR
CP CIRCULATING PUMP
CT CURRENT TRANSOFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DL DEMAND LOAD
DN DOWN
DPR DAMPER
DS DISCONNECT SWITCH
DWG DRAWING
E.C. ELECTRICAL CONTRACTOR
E.T.R. EXISTING TO REMAIN
ELEC ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABP FIRE ALARM BOOSTER SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FASP FIRE ALARM SLAVE PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED DISCONNECT SWITCH
G.C. GENERAL CONTRACTOR
GA GAUGE
GAL GALLON
GALV GALVANIZED
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP GYPSUM BOARD
H.V.A.C. HEATING, VENTILATING & AIR CONDITIONING
HOA HAND-OFF-AUTO SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
I/W INTERLOCK WITH
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT- AMPERE RECTIVE
KW KILOWATT
KWC KILOWATT CONNECTED
KWD KILOWATT DEMAND
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LP LIGHTNING PEOTECTION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
M.C. MECHANICAL CONTRACTOR
M.E.P. MECHANICAL ELECTRICAL PLUMBING
M/C MOMENTARY CONTACT
MAGS MAGNETIC STARTER
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MCP MAIN CIRCUIT BREAKER
MDC MAIN DISRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELEC MFGR'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
P PLATE
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
REX REMOVE EXISTING
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
SP SPARE
SPEC SPECIFICATION
SPKR SPEAKER
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SWL SWITCH WITH LIGHTS
SYM SYMMETRICAL
SYS SYSTEM
T-STAT THERMOSTAT
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UCR UNDER COUNTER REFRIGERATOR
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VOL VOLUME
W WATT
W.G. WIRE GUARD
W/ WITH
W/O WITHOUT
WH WATER HEATER
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
℄ CENTER LINE
∠ ANGLE
▲ DELTA
ABBREVIATIONS
LIGHTING FIXTURE LEGEND
EXIT SIGN
PENDANT FIXTURE
RECESSED DOWN ROUND FIXTURE
2' X 2' FIXTURE
2' X 2' FIXTURE WITH BATTERY-BACKUP
2' X 4' FIXTURE
WALL SCONCE
EMERGENCY LIGHT
NEW
EXISTING
DEMOLISHED
PHASE LINE TYPES
LIGHTING DEVICE SCHEDULE
DIMMER SWITCH
LOW VOLTAGE SWITCH
WALL OCCUPANCY SENSOR SWITCH
SWITCH
CEILING MOUNTED OCCUPANCY SENSOR
ROOM CONTROLLER
ELECTRICAL SHEET INDEX
SHEET NO. TITLE
E0.0 ELECTRICAL LEGENDS & NOTES
E1.0 ELECTRICAL POWER FLOOR PLAN
E1.1 ELECTRICAL POWER ROOF PLAN
E2.0 ELECTRICAL LIGHTING FLOOR PLAN
E2.1 PHOTOMETRIC SITE PLAN
E3.0 ONE LINE DIAGRAM
E4.0 ELECTRICAL PANEL SCHEDULES
E5.0 ELECTRICAL DETAILS
ED1 ELECTRICAL POWER DEMO
ED2 ELECTRICAL LIGHTING DEMO
PROJECT NO.
SHEET NO.
APPROVED
DRAWN BY
DATE
N
W
A S
H
IN
G T
O N
A V
E N
U E
S A
G
IN
A W
M
IC
H
IG
A
N D A T E
N O
T S
S F
A
R C
H
IT
E C
T S
I
N C
A R C H
IT
E C T S
P L A N N E R S
IN
T E R
IO
R S
CONSULTING ENGINEER
491 E. WRIGHT AVE. SHEPHERD, MI 48883
989-567-1100 | info@KTSEngineeringGroup.com
KTS PROJECT NO.: C
O
PY
R
IG
H T
A
LL
R
IG
H T S
R
ES
ER
V
ED
E0.0
JWA
03/17/2026
KTS
26-0299
B A Y
C
IT
Y M
IC
H
IG
A N
D
IN
IN
G
R O
O M
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
S F
O R
B A
Y A
R E
N A
C I S
D
R
C O D E
R E V
IE
W
R E S P O N S E
J
J J
J
J
J
KA1 KA2KB1 KB2 C.B.
FACP
ALTERNATE NO. 1
CAFETERIA
SERVING
DINING ROOM
DISHWASHING
108 STORAGE
STORAGE
WAIT
STATION
PASSAGE
KITCHEN
113 CLASSROOM
DINING
VESTIBULE
MENS
WOMENS
LOCKERS
OFFICE
CLASSROOM
PREP AREA
FCU-1
ETR ETR
ETR
ETRETR
ETR
ETR
KC
ETR
KC- 10
GFI
KC- 10
GFI
KC- 8KC- 12
KC- 8
KC- 15
GFI
KC- 5
GFI
KC- 8
KC- 8 KC- 8
KC- 7
KC- 7
KC- 7
KC- 9
KC- 9
KC- 9
KC- 9
KC- 8
KC- 14
GFI
KC- 14
GFI
KC- 14
GFI
KC- 7
KC- 13 KC- 13
KC- 13
KC- 13KC- 13
KC- 13
KC- 13 KC- 11
M
3 EWH-1
KC- 20KC- 18
KC- 1
KC- 15
KC- 15
KC- 7
KC- 7
KC- 16
GFI
KC- 17,19
FACP
ETR
ACU-1
KC- 3
A
A
A
R2
R2
R2
POWER KEYNOTES:
1 . POWERED THROUGH OUTSIDE UNIT "CU-1".
2 . E.C. TO USE EXISTING CIRCUIT FOR NEW RECEPTACLES.
3 . RECEPTACLE FOR ELECTRIC WATER HEATER "EWH-1" LOCATED ABOVE CEILING. E.C. TO
COORDINATE RECEPTACLE LOCATION WITH "EWH.1" INSTALLER.
4 . ELECTRIC HAND DRYER SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL
CONTRACTOR, EQUAL TO "WORLD DRYER" SANITIZE+DRY. FINISH TO BE DECIDED BY
OWNER. 120/1/60. 950 WATTS. DEDICATED 15 AMP CIRCUIT. HEIGHT PER ARCHITECURAL
DRAWINGS.
5 . POWER FOR COFFEE STATION, VERIFY LOCATION WITH OWNER.
6 . PORTABLE SALAD BAR, VERIFY LOCATION WITH OWNER.
7 . E.C. VERIFY POWER FOR DROP DOWN SCREEN. E.C. TO VERIFY LOCATION WITH OWNER.
8 . HOT SERVING LINE, E.C. TO VERIFY LOCATION WITH OWNER.
1/8" = 1'-0"
MAIN FLOOR PLAN - POWER
PROJECT NO.
SHEET NO.
APPROVED
DRAWN BY
DATE
N
W
A S
H
IN
G T
O N
A V
E N
U E
S A
G
IN
A W
M
IC
H
IG
A
N D A T E
N O
T S
C
H
IT
E C
T S
I
N C
A R C H
IT
E C T S
P L A N N E R S
IN
T E R
IO
R S
CONSULTING ENGINEER
491 E. WRIGHT AVE. SHEPHERD, MI 48883
989-567-1100 | info@KTSEngineeringGroup.com
KTS PROJECT NO.: C
O
PY
R
IG
H T
A
LL
R
IG
H T S
R
ES
ER
V
ED
E1.0
JWA
03/17/2026
KTS
26-0299
B A Y
C
IT
Y M
IC
H
IG
A N
D
IN
IN
G
R O
O M
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
S F
O R
B A
Y A
R E
N A
C I S
D
A
A D D E N D U M
R
C O D E
R E V
IE
W
R E S P O N S E
R
C O D E
R E V
IE
W
R E S P O N S E
RECEPTACLE CONTROL MATRIX
KEYNOTE TYPE SENSOR FULL OFF TIME NOTES
A
OCCUPANCY
SENSOR
AUTO ON/OFF 20 MINS
RECEPTACLE CONTROL SHALL ONLY
CONTROL SPLIT-CIRCUIT RECEPTACLES.
ALUMINUM CONDUCTORS
15-20 12 12 3/4'' 3/4'' 3/4'' 3/4''
NOT ACCEPTABLE
25-30 10 10 3/4'' 3/4'' 3/4'' 3/4''
35-40 8 10 3/4'' 3/4'' 3/4'' 3/4''
45-50 8 (6) 10 3/4'' 3/4'' 3/4'' 3/4''
60 6 (4) 10 3/4''(1) 3/4''(1) 3/4''(1) 3/4''(1)
70 4 8 1'' 1 1/4'' 1 1/4'' 1 1/4''
80 4 (3) 8 1'' 1 1/4'' 1 1/4'' 1 1/4''
90-100 3 (2) 8 1 1/4'' 1 1/4'' 1 1/4'' 1 1/4'' 1 6 1 1/2'' 1 1/4'' 1 1/2''
110 2 (1) 6 - 1 1/4'' 1 1/4'' 1 1/4'' (1 1/2'') 1/O 4 - 1 1/2'' 2''
125 1 (1/0) 6 - 1 1/4'' (1 1/2'') 1 1/4'' (1 1/2'') 1 1/2'' 2/O 4 - 1 1/2'' 2''
150 1/O 6 - 1 1/2'' 1 1/2'' 1 1/2'' 3/O 4 - 2'' 2 1/2''
175 2/O 6 - 2'' 2'' 2'' 4/O 4 - 2'' 2 1/2''
200 3/O 6 - 2'' 2'' 2 1/2'' 250 4 - 2'' 3''
225 4/O 4 - 2'' 2'' 2 1/2'' 300 2 - 2 1/2'' 3''
250 250 4 - 2 1/2'' 2 1/2'' 2 1/2'' 350 2 - 2 1/2'' 3''
300 350 4 - 2 1/2'' 2 1/2'' 3'' 500 2 - 3'' 3 1/2''
350 500 3 - 3'' 3'' 3'' 2-4/O 2-1/O - 2-2'' 2-2''
400 500 3 - 3'' 3'' 3'' 2-250 2-1/O - 2-2'' 2- 2 1/2''
450 2-4/O 2-2 - 2-2'' 2-2'' 2- 2 1/2'' 2-300 2-1/O - 2- 2 1/2'' 2-3''
500 2-250 2-2 - 2- 2 1/2'' 2- 2 1/2'' 2- 2 1/2'' 2-350 2-1/O - 2- 2 1/2'' 2-3''
600 2-350 2-1 - 2- 2 1/2'' 2- 2 1/2'' 2-3'' 2-500 2-2/O - 2-3'' 2-3 1/2''
700 2-500 2-1/O - 2-3'' 2-3'' 2-3'' 2-600 2-3/O - 2-3'' 2-3 1/2''
800 3-500 2-1/O - 2-3'' 2-3'' 2-3 1/2'' 3-400 3-3/O - 3-3'' 3-3 1/2''
1000 3-400 3-2/O - 3-3'' 3-3'' 3-3'' 3-600 3-4/O - 3-3 1/2'' 3-3 1/2''
1200 3-600 3-3/O - 3-3 1/2'' 3-3 1/2'' 3-3 1/2'' 4-500 4-250 - 4-3'' 4-3 1/2''
1600 4-600 4-4/O - 4-3 1/2'' 4-3 1/2'' 4-3 1/2'' 5-600 5-350 - 5-3 1/2'' 5-4''
2000 5-600 5-250 - 5-3 1/2'' 5-3 1/2'' 5-3 1/2'' 6-600 6-400 - 6-3 1/2'' 6-4''
FEEDER AND BRANCH CIRCUIT SIZING SCHEDULE - GENERAL PURPOSE
COPPER CONDUCTORS
OVERCURRENT
DEVICE RATING
(AMPERES)
WIRE SIZE
(AWG OR KCMIL)
CONDUIT SIZE
WIRE SIZE
(AWG OR KCMIL)
CONDUIT SIZE
PHASE & NEUTRAL GROUND
SINGLE PHASE
2 WIRE+G
(1PH,1IN,1G)
SINGLE PHASE
3 WIRE+G
(2PH,1IN,1G)
THREE PHASE
3 WIRE+G
(3PH,1G)
THREE PHASE
& NEUTRAL
4 WIRE+G
(3PH,1IN,1G)
PHASE & NEUTRAL GROUND
SINGLE
PHASE
3 WIRE+G
(2PH,1IN,1G)
THREE PHASE
3 WIRE+G
(3PH,1G)
THREE PHASE
& NEUTRAL
4 WIRE+G
(3PH,1IN,1G)
NOTES:
1. CONTRACTOR TO SIZE FEEDERS AND BRANCH CIRCUITS BASED ON THIS SCHEDULE AND OVER CURRENT DEVICE SIZE, UNLESS NOTED OTHERWISE.
2. CONDUCTORS ARE BASED ON THHN/THWN UP TO AND INCLUDING #4/O. LARGER THAN #4/O ARE BASED ON TYPE XHHW.
3. CONDUCTORS ARE BASED ON 90°C, 600V. INSULATED COPPER WIRE APPLIED AT 75° FOR TERMINATION RATED 60/75°C OR 75°C. FOR TERMINATION RATED 60°C, USE CONDUCTORS AND
CONDUIT SIZED INDICATED IN PARENTHESES.
4. CONDUIT SIZES ARE VALID FOR EMT OR RGS. CONDUIT SIZES SHALL BE ADJUSTED AS REQUIRED FOR OTHERS TYPES OF CONDUIT.
5. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE REQUIRED WIRE SIZES TO ACCOMMODATE MECHANICAL EQUIPMENT LUG SIZES.
6. SIZE OF DISCONNECT SWITCH LOCATED AT EQUIPMENT SHALL BE SIZED BASED UPON OVERCURRENT PROTECTION OF THAT DEVICE.
7. OBTAIN APPROVAL FROM ENGINEER PRIOR TO INSTALLING DIFFERENT SIZE/QUANTITY OF CONDUCTORS TO OBTAIN AN EQUIVALENT AMPACITY.
8. SPLICE FROM ALUMINUM TO COPPER PRIOR TO ENTERING EQUIPMENT LISTED FOR USE WITH COPPER CONDUCTORS ONLY OR USE COPPER CONDUCTORS FOR THE ENTIRE LENGTH OF FEEDER.
REFER TO N.E.C. ARTICLE 250
GROUNDING DETAIL
NOT TO SCALE
**WHERE JOB REQUIRES OR
WHERE AVALIABLE.
1. MAIN DISTRIBUTION PANEL.
2. NEUTRAL BUS.
3. EQUIPMENT GROUND BAR KIT.
4. 10' -0" X 3/4" COPPERWELD GROUND ROD.
5. CADWELD OR APPROVED CLAMP.
6. APPROVED PIPE CLAMP.
7. UNDERGOUND METAL PIPE.**
8. CADWELD OR APPROVED CONNECTION
9. BUILDING STEEL**
10. SUBPANEL
11. WIRE SIZED PER N.E.C., ARTICLE 250
12. CONCRETE-ENCASED ELECTRODE PER N.E.C.,
ARTICLE 250.52(A)(3)**
11 10
11 8
BREAK TAB TO SEPARATE UPPER AND LOWER
RECEPTACLES POWER.
UPPER RECEPTACLE SHALL BE CONNECT TO
CIRCUIT CONTROLLED BY ROOM OCCUPANCY
SENSORS THAT RECEPTACLE IS SERVING,
AUTOMATIC SHUTOFF AFTER ROOM IS
UNOCCUPIED FOR 20 MINUTES.
LOWER RECEPTACLE WILL BE CONNECTED TO
SAME CIRCUIT AS UPPER RECEPTACLE, BUT
WILL BE CONNECTED BEFORE CONTROL DEVICE
SO THAT THE LOWER RECEPTACLE WILL HAVE
CONSTANT POWER AS LONG AS CONTROLLING
CIRCUIT BREAKER IS ON.
SYMBOL AS PER NEC FIGURE 406.3(F)
DISPLAYED ON RECEPTACLE FACE
"CONTROLLED" PER NEC 406.3(F) DISPLAYED
ON RECEPTACLE FACE
SPLIT-CIRCUIT RECEPTACLE
NOT TO SCALE
BRANCH CIRCUIT VOLTAGE DROP WIRING SCHEDULE FOR SINGLE PHASE CIRCUITS
BRANCH CIRCUIT RATING(A) WIRE SIZE
MAXIMUM BRANCH CIRCUIT LENGTH (IN FEET)
120V 208V 240V 277V 480V
20A 12 83 143 165 191 331
10 128 222 256 295 511
8 201 348 402 464 804
6 313 542 625 721 1250
30A 10 85 148 170 197 341
8 134 232 268 309 536
6 208 361 417 481 833
4 313 542 625 721 1250
NOTES:
1. THE ABOVE TABLE VALUES ARE BASED ON COPPER CONDUCTORS, IN STEEL CONDUIT, WITH A LOAD FACTOR OF .85 PER NEC CHAPTER 9, TABLE 9.
2. PROVIDE BRANCH CIRCUIT CONDUCTORS AS INDICATED IN THE TABLE ABOVE FOR ALL LIGHTING AND RECEPTACLE BRANCH CIRCUITS. WHERE BRANCH CIRCUITS SERVE DEDICATED EQUIPMENT, THE CONTRACTOR MAY
PERFORM VOLTAGE DROP CALCULATIONS BASED ON ACTUAL EQUIPMENT CONNECTED LOAD AND PROVIDE CONDUCTORS APPROPRIATELY SIZED TO LIMIT VOLTAGE DROP TO A MAXIMUM OF 3%.
3. CONDUCTOR SIZES ARE BASED ON MAXIMUM OF 9 CURRENT CARRYING CONDUCTORS IN A SINGLE CONDUIT.
4. LIMITS FOR CONDUCTOR LENGTHS SHOWN ARE BASED ON A MAXIMUM BRANCH CIRCUIT LOADING OF 64% OF THE BRANCH BREAKER RATING AND A MAXIMUM OF 3% VOLTAGE DROP TO COMPLY WITH ASHRAE 90.1 AND
THE NEC. FOR CIRCUITS LOADED GREATER THAN 64% OF BRANCH BREAKER RATING, THE CONTRACTOR SHALL PROVIDE CONDUCTORS APPROPRIATELY SIZED TO LIMIT VOLTAGE DROP TO 3%.
PROJECT NO.
SHEET NO.
APPROVED
DRAWN BY
DATE
N
W
A S
H
IN
G T
O N
A V
E N
U E
S A
G
IN
A W
M
IC
H
IG
A
N D A T E
N O
T S
C
H
IT
E C
T S
I
N C
A R C H
IT
E C T S
P L A N N E R S
IN
T E R
IO
R S
CONSULTING ENGINEER
491 E. WRIGHT AVE. SHEPHERD, MI 48883
989-567-1100 | info@KTSEngineeringGroup.com
KTS PROJECT NO.: C
O
PY
R
IG
H T
A
LL
R
IG
H T S
R
ES
ER
V
ED
E5.0
JWA
03/17/2026
KTS
26-0299
B A Y
C
IT
Y M
IC
H
IG
A N
D
IN
IN
G
R O
O M
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
S F
O R
B A
Y A
R E
N A
C I S
D
R
C O D E
R E V
IE
W
R E S P O N S E
| 2410_001 |
| scan0405 |
| 2538_A0.1-Arch D (24 x 36) |
| Sheets and Views |
| Arch D (24 x 36) |
| 2538_A2.0-Arch D (24 x 36) |
| Sheets and Views |
| Arch D (24 x 36) |
| 2538_A6.0-Arch D (24 x 36) |
| Sheets and Views |
| Arch D (24 x 36) |
| 2026-06-02 BAISD Dining - E - Code Review R2 |
| Sheets |
| E0.0 - ELECTRICAL LEGENDS & NOTES |
| E1.0 - ELECTRICAL POWER FLOOR PLAN |
| E5.0 - ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .