08-05-26_2538_AD4_REV.pdf

PDF 7 MB Posted

Attached to
Dining Room Addition & Interior Renovations
Solicitation number
RFP BAY 260000002591 1
Issued by
Bay County, Michigan

About this file

This document is an architectural and electrical specification file for a Dining Room Addition and Interior Renovations project at Bay Arena CSD in Bay City, Michigan. The project encompasses a comprehensive dining facility expansion and renovation including a dining room, cafeteria, kitchen, serving areas, dishwashing station, and associated support spaces. The work also includes renovations to adjacent instructional areas such as classrooms, offices, and specialized labs (machine trades, welding, building trades, auto service, body shop, agricultural, diesel service). The project includes detailed architectural floor plans, building sections, and electrical specifications prepared by TSSF Architects, Inc. in Saginaw, Michigan, with consulting engineering services provided by KTS Engineering Group in Shepherd, Michigan. The electrical specifications indicate the work requires compliance with current Michigan Building Code, National Electrical Code (NEC) 2023, and various state and federal standards including ADA requirements. The project includes specific electrical components such as lighting fixtures, receptacles, disconnect switches, manual motor starters, occupancy sensors, and emergency lighting systems throughout the facility.

The electrical contractor is required to execute the work in compliance with "best trade practices" and coordinate with mechanical, plumbing, and other trades to ensure proper installation. All electrical equipment must be new (unless NEC allows refurbished equipment), UL approved, and specification grade, with specific manufacturers noted as Square D, Siemens, Eaton, G.E., or equivalent. Conductors must be copper only; aluminum is not permitted. All wiring must be installed in EMT (thinwall conduit) unless Romex is explicitly allowed, with all above-ground wiring concealed except where surface raceway is specifically noted and approved. The electrical contractor is responsible for conducting a short-circuit study and ensuring all equipment meets those requirements, performing circuit testing, maintaining updated as-built drawings, and providing one-year warranties on all work and materials. The contractor must submit shop drawings in PDF format via internet a minimum of seven days prior to bidding and obtain all required permits and inspections, with the document containing detailed specifications for panel schedules, grounding, voltage drop calculations, and feeder sizing schedules.

View the file

Other files

File Type Posted
03-31-26_2538_AD2.pdf PDF
06-03-26_2538_AD3.pdf PDF
09-08-26_Bid Set.pdf PDF
03-25-26_2538_AD1.pdf PDF
Full Spec (4).pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N . W

AS

H

IN

G

TO

N

A

VE

N U

E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

MASTER FIRST FLOOR PLAN

BA

Y

AR

EN

AC

IS

D D

IN

IN

G R

O O

M A

D D

IT

IO

N A

N D

R

EN

O

VA

TI

O

N S

FO

R

:MACHINE TRADES

WELDING

BUILDING TRADES

AUDITORIUM

CAFETERIA

AUTO SERVICE LAB BODY SHOP

AG. LAB

MATERIAL

MEDIA

CENTER

RECEIVINGBUILDING

MAINTENANCE

LAB

ADMINISTRATION

HEALTH

WING

AND SCIENCE

GREENHOUSE

GREENHOUSE

DATA PROC.

KITCHEN

DIESEL SERVICE LAB

52'-7"

41'-3"

DINING

SERVING

R1

R1

R1

R1

AREAS OF WORK LEGEND

EXIT

34" EGRESS

MINUMUM CLEARANCE

LIFE SAFETY AREA LEGEND

TRAVEL DISTANCE

EXIT (w/ NUMBER OF OCCUPANTS)

ACT.CAP.

DOOR

EXIT

0 0

ACT.CAP.

DOOR

EXIT

340 38

ACT.CAP.

DOOR

EXIT

340 71 91'-0"

78 ACTUAL OCCUPANT EGRESS COUNT

1-HOUR RATED FIRE BARRIER

2-HOUR RATED FIRE BARRIER

FIRE EXTINGUISHER - MULTI-PURPOSE

DRY CHEMICAL

DINING

OFF.

CLASSRM.

CLASSRM.

R1

R1

R1

OCCUPANT CALCULATIONS

REQUIRED EGRESS WIDTH

TOTAL EGRESS WIDTH REQUIRED:

·180 MAX INTERIOR OCCUPANT x .2" = 36"

TOTAL EGRESS WIDTH PROVIDED:

·THREE 68" CLEAR DOOR EXIT LEAFS = 204"

NUMBER OF EXITS REQUIRED : 2

MICHIGAN BUILDING CODE

FUNCTION OF SPACE FACTOR

EDUCATION 73

TOTAL PROJECT OCCUPANT LOAD 180

ASSEMBLY A-2 1:15 NET 91

1:20 NET

OCCUPANTS

KITCHEN 1:200 GROSS 14

OFFICE 1:150 GROSS 2

ACT.CAP.

DOOR

EXIT

340 205

R

R1

91 55

OFF.

BODY SHOP

OFF.

OFF.

CONF.

OFF.

OFF.

CLASSRM.

RES.

OFF.

CONF.

FUNDAMENTALS LAB

CHILDCARE CLASS

CLASSRM.

R2

R2

R2

R2

R http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com

N . W

AS

H

IN

G

TO

N

A

VE

N U

E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

PARTIAL FIRST FLOOR PLAN

DINING ROOM

VEST.

MENS

WOMENS

CLASSROOM

OFFICE112

CLASSROOM

KITCHEN

DINING ROOM

SERVING

CAFETERIA

EX. CORRIDOR

DISH WASHING EX. COOLER EX. FREEZER

STORAGE

PASSAGE

WAIT STATION

STORAGE

EX. SHIP/ REC.

EX. CORRIDOR

EX. STOR.

EX. CONF.

EX. CLASSROOM/ LAB

EX

. P

AS

SA

G E

EX. OFFICE EX. OFFICE

EX. OFFICE EX. OFFICE

EX. CLASSROOM

EX. TLT.

EX. TLT.

EX. CONF.

EX. PASSAGE

EX. STOR. EX. STOR.EX. TLT. EX. TLT. EX. ST.

EX. DAYCARE

EX. OFF.

EX. CORRIDOR

BA

Y

AR

EN

AC

IS

D D

IN

IN

G R

O O

M A

D D

IT

IO

N A

N D

R

EN

O

VA

TI

O

N S

FO

R

ALTERNATE NO. 1

A6.0

A6.0

A6.0

0A

100B

LOCKERS

4B

104A

PREP AREA

A8.0

A8.0

A6.0

A6.0

ENLARGED FLOOR PLAN1

A2.0

MENS

WOMENS

A8.0 2

A8.0

7 A8.0

A2.0

A2.0

ENLARGED FLOOR PLAN2

A2.0

A8.0

A8.0

A PARTITION WALL

NON-RATED

NON-BEARING WALL

WALL TYPES

B

A

B PARTITION WALL

2 HR-RATED (UL U419)

NON-BEARING WALL

A

AC

A

B

A

C

C

A8.05A8.0

4.5

4.8

6.6

6.9

7.3

8.2

B

VVUUTTSSRRQQPPOONNMMLLKKJJIIHHGGFFEEDDCCBBAAZY

A8.0

A8.0

A

B

104C

C

C PARTITION WALL

1 HR-RATED (UL U419)

NON-BEARING WALL

R

R1

R1

R1

R1

R1

R1

R1

R

R2

D SHAFT WALL

2 HR-RATED (UL U438)

NON-BEARING WALL

R2

D http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com http://www.autodsys.com

N . W

AS

H

IN

G

TO

N

A

VE

N U

E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

BA

Y

AR

EN

AC

IS

D D

IN

IN

G R

O O

M A

D D

IT

IO

N A

N D

R

EN

O

VA

TI

O

N S

FO

R

BUILDING SECTION1

A6.0

BUILDING SECTION2

A6.0

BUILDING SECTION3

A6.0

A7.0

A7.02

A7.0

567566.6 4.8 4.5 6.66.97.3 4.8 4.5

PP QQ RR SS TT UU VV

DINING ROOM

DINING ROOM

VEST.

WOMENS

WOMENS

MENS

A6.0

WALL SECTION4

A6.0

R2

R

QQPP

R2

GENERAL ELECTRICAL NOTES & SPECIFICATIONS:

1. EXECUTE THE WORK REQUIRED IN A MANNER EVIDENCED AS THE "BEST TRADE PRACTICES"

CONTRIBUTING TO EFFICIENCY OF OPERATION, MINIMUM MAINTENANCE, ACCESSIBILITY AND

AESTHETICS OF THE INSTALLATION.

2. MECHANICAL AND ELECTRICAL PLANS ARE DIAGRAMMATIC IN NATURE, INTENDED TO

INDICATE DESIGN INTENT ONLY. CONTRACTOR IS RESPONSIBLE TO COORDINATE SPECIFIC

LOCATIONS OF ITEMS AND ADJUST AS REQUIRED TO ACCOMMODATE CODE REQUIREMENTS,

MANUFACTURER'S INSTALLATION REQUIREMENTS, AND THE WORK OF OTHER TRADES.

3. MECHANICAL AND ELECTRICAL INFORMATION IS PRESENTED ON AN X-REFERENCED

BACKGROUND PLAN. IN CASE OF CONFLICT BETWEEN BACKGROUND PLAN AND

ARCHITECTURAL FLOOR PLAN, ARCHITECTURAL FLOOR PLAN SHALL GOVERN.

4. RUN ALL PIPING, CONDUIT, ETC. CONCEALED IN WALLS WHENEVER POSSIBLE AND AVOID

EXPOSED INSTALLATION UNLESS SPECIFICALLY REQUIRED (TYPICAL UNLESS NOTED

OTHERWISE ON DRAWINGS). IN ANY LOCATIONS WHERE CONCEALMENT IS NOT POSSIBLE,

CONTACT ENGINEER PRIOR TO INSTALLATION FOR PERMISSION FROM ENGINEER.

5. THE ENGINEER WILL NOT HAVE CONTROL OR CHARGE OF CONSTRUCTION MEANS, METHODS,

TECHNIQUES, SEQUENCES, OR PROCEDURES. ENGINEER IS NOT RESPONSIBLE FOR SAFETY

PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK; AND WILL NOT BE

RESPONSIBLE FOR CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH

THOSE DOCUMENTS PREPARED BY THE ENGINEER.

6. ALL CONSTRUCTION SHALL BE DONE IN COMPLIANCE WITH CURRENT CODES, INCLUDING:

MICHIGAN BUILDING CODE, MICHIGAN PLUMBING CODE, MICHIGAN MECHANICAL CODE,

NATIONAL ELECTRICAL CODE (NEC), MICHIGAN BUILDING REHABILITATION CODE (WHEN

APPLICABLE), NFPA CODES, LIFE SAFETY CODE (WHEN APPLICABLE), AMERICANS WITH

DISABILITIES ACT (ADA), MICHIGAN BARRIER FREE CODES, MICHIGAN ENERGY CODE,

MICHIGAN DEPARTMENT OF PUBLIC HEALTH CODES (WHEN APPLICABLE), AND ALL OTHER

LOCAL, STATE, AND FEDERAL APPLICABLE CODES. THE CONTRACTOR SHALL UTILIZE THE

LATEST ADOPTED EDITIONS OF ALL CODES.

7. IF BIDDING CONTRACTOR WOULD LIKE TO SUBSTITUTE ANY SPECIFIED ELECTRICAL DEVICES, LIGHT FIXTURES, CONTROLLERS, PANELS, DISCONNECTS, VFD'S, ELEC. GEAR, ETC., THEY MUST

PROVIDE SUBMITTAL TYPE DRAWINGS TO THE ENGINEER A MINIMUM OF 7 DAYS PRIOR TO

BIDDING THE PROJECT. IF THESE APPROVAL DRAWINGS ARE NOT SUBMITTED AND APPROVED,

THE SPECIFIED EQUIPMENT MUST BE USED - NO EXCEPTIONS.

8. EQUIPMENT AND MATERIALS SHALL BE UL APPROVED AND SPECIFICATION GRADE.

9. ELECTRICAL CONTRACTORS SHALL SECURE PERMITS AND INSPECTIONS REQUIRED BY STATE

AND LOCAL LAWS AND ORDINANCES AND PAY ALL FEES AND EXPENSES IN CONNECTION

THEREWITH AS A PART OF THEIR WORK UNDER THIS CONTRACT.

10. UPON COMPLETION OF WORK, FURNISH OWNER CERTIFICATES OF FINAL INSPECTION AND

APPROVAL FROM AUTHORITIES HAVING JURISDICTION.

11. ALL CONDUCTORS SHALL BEAR IDENTIFICATION AS TO SIZE AND TYPE OF INSULATION AND

SHALL BE EQUIPPED WITH WIRE MARKERS INDICATING THE CIRCUIT NUMBER, WIRE NUMBER

AND/OR PHASE LETTER.

12. IDENTIFY ELECTRICAL EQUIPMENT WITH THE NAME OF THE EQUIPMENT, THE EQUIPMENT

CONTROLLED, OR THE SYSTEM INVOLVED. DISCONNECT SWITCHES AND MOTOR STARTERS

SHALL HAVE NAMEPLATES TO INDICATE THE EQUIPMENT THEY CONTROL. ALL ELECTRICAL

EQUIPMENT POWER PANELS SHALL HAVE NAMEPLATES DESIGNATING THEIR NAMES AND

VOLTAGE RATING, SUCH AS LP-A, 120/208 VOLT, 3 PHASE, 4 WIRE. NAMEPLATES SHALL BE

ENGRAVED THREE-LAYER PLASTIC, BLACK LETTERS ON WHITE BACKGROUND FOR NORMAL

POWER AND WHITE LETTERS ON RED BACKGROUND FOR EMERGENCY/STANDBY POWER

PANELS AND ASSOCIATED EQUIPMENT. NO HANDWRITTEN OR PRINTED LABELING WILL BE

ACCEPTED AS FINAL RECORD UPON PROJECT COMPLETION. NAMEPLATES SHALL BE A MINIMUM

OF 1” X 3”, OR AS NOTED ON NAMEPLATE SCHEDULE IF THERE IS ONE ON DRAWINGS. AS A

TEXT SIZE MINIMUM:

A. SWITCHBOARD OR PANELBOARD MAINS: 1” HIGH

B. SWITCHBOARD OR PANELBOARD BRANCHES: ½” HIGH

C. STARTERS/DISCONNECTS: ½” HIGH

D. MANUAL MOTOR STARTERS: ¼” HIGH

13. PANEL SCHEDULES SHALL BE TYPEWRITTEN AND INSTALLED FOR EVERY PANEL, BE IT NEW OR EXISTING. FOR EXISTING PANELS, CIRCUITRY SHALL BE VERIFIED PRIOR TO UPDATING PANEL

SCHEDULE. HANDWRITTEN SCHEDULES, AND/OR CROSSED OFF EXISTING SCHEDULES ARE NOT

ACCEPTABLE.

14. ALL WORK AND MATERIALS SHALL BE GUARANTEED IN WRITING FOR (1) YEAR FROM PROJECT

COMPLETION UNLESS A FURTHER GUARANTEE IS NOTED ELSEWHERE.

15. ALL SWITCHES, RECEPTACLES, SMALL MANUAL MOTOR STARTERS, OR TOGGLE SWITCHES

SHALL HAVE THE CIRCUIT NUMBER IDENTIFIED ON THE DEVICE COVER PLATE USING CLEAR

ADHESIVE TAPE LABELS WITH ¼” HIGH PRINTED BLOCK CHARACTERS IN BLACK. NO

HANDWRITTEN LABELS WILL BE ACCEPTED AS FINAL RECORD.

16. THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH CONDITIONS OF WHICH WILL AFFECT THE WORK HE IS TO PERFORM. THE SUBMISSION OF A PROPOSAL BY THIS

CONTRACTOR SHALL BE CONCLUSIVE EVIDENCE THAT THIS CONTRACTOR HAS VISITED THE

SITE AND HAS GIVEN PROPER CONSIDERATION AND EVALUATION OF THESE CONDITIONS IN

THE PREPARATION OF HIS PROPOSAL. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE ON HIS

BEHALF FOR EXTRA EXPENSE INCURRED DUE TO FAILURE OR NEGLECT ON HIS PART TO MAKE

THIS VISIT AND EXAMINATION.

17. WHERE ACTIVE SEWERS, GAS, ELECTRIC, OR OTHER SERVICES ARE ENCOUNTERED DURING

THE PERFORMANCE OF THIS CONTRACT, THE CONTRACTOR SHALL PROTECT, BRACE AND

SUPPORT THEM AS REQUIRED. DO NOT PREVENT, INTERRUPT OR DISTURB OPERATION OF

EXISTING SERVICES THAT ARE TO REMAIN. RELOCATE EXISTING SERVICES IF/AS REQUIRED.

18. THE CONTRACTOR SHALL CHECK THE UTILITY COMPANIES AND MUNICIPAL AGENCIES FOR

EXACT LOCATIONS OF SERVICES WHICH THEY MAY EXPECT TO ENCOUNTER.

19. IN GENERAL, MOUNTING HEIGHTS ABOVE FINISHED FLOOR TO THE CENTERLINE OF BOXES

AND EQUIPMENT SHALL BE AS PER AMERICANS WITH DISABILITIES ACT, AND MICHIGAN

BARRIER FREE CODES.

20. WORK SHALL BE PERFORMED BY SKILLED MECHANICS WELL VERSED IN THEIR PARTICULAR

TRADES.

21. RESPONSIBILITY FOR CARE AND PROTECTION OF ELECTRICAL WORK RESTS WITH THE

CONTRACTOR UNTIL IS HAS BEEN TESTED AND ACCEPTED.

22. CONTRACTOR IS TO CHECK DOOR SWINGS WITH ARCHITECTURAL PLANS AND MOUNT LIGHT

SWITCHES, CONTROLS, ETC., ACCORDINGLY. VERIFY WITH LATEST ARCHITECTURAL

DRAWINGS.

23. ELECTRICAL EQUIPMENT SHALL BE SQUARE D, SIEMENS, EATON, G.E. OR MATCH EXISTING.

24. DISCONNECT SWITCHES SHALL BE NEMA HEAVY DUTY, FUSIBLE OR NON-FUSIBLE AS NOTED ON

PLANS, WITH A NEMA 3R ENCLOSURE WHEN MOUNTED OUTDOORS.

25. THE NEUTRAL CONDUCTOR OF THE WIRING SYSTEM TOGETHER WITH THE CONDUIT SYSTEM

AND SERVICE EQUIPMENT SHALL BE GROUNDED AND SIZED PER NEC ARTICLE 250 – SEE

DETAIL ON DRAWINGS ALSO.

26. HOLES THROUGH WALLS OR PARTITIONS REQUIRED FOR ELECTRICAL WORK SHALL BE

NEATLY CUT TO SIZE. CONDUITS PENETRATING OUTSIDE WALLS SHALL BE SEALED

ACCORDINGLY, UNDERGROUND CONDUITS SHALL HAVE LINK SEALS. PENETRATIONS OF FIRE

RATED ASSEMBLIES SHALL BE FIRE-STOPPED BY APPROVED METHODS AND MATERIALS. NO

BEAMS OR OTHER STRUCTURAL MEMBERS SHALL BE DRILLED, BURNED, OR CUT.

27. LOCATIONS OF WIRING DEVICES SUCH AS LIGHT SWITCHES, DUPLEX RECEPTACLES,

THERMOSTATS, ETC., SHALL BE COORDINATED WITH OTHER TRADES.

28. IN GENERAL, ALL MOTORS ARE FURNISHED AND INSTALLED UNDER THE MECHANICAL

SECTION OF THE SPECIFICATIONS. ALL STARTERS, FUSED SWITCHES, SAFETY SWITCHES,

INCLUDING ALL POWER WIRING SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR.

29. OUTLET BOXES IN THE SAME WALL BUT SERVING DIFFERENT ROOMS SHALL BE AT LEAST 4"

APART TO MINIMIZE NOISE TRANSMISSION. WHEN LOCATED ON FIRE WALLS, THEY SHALL BE

24" APART.

30. LIGHTING AND CONTROL WIRING SHALL BE TESTED FOR SHORTS AND OPENS AND SHALL BE

GIVEN A COMPLETE OPERATIONAL TEST.

31. THE CONTRACTOR SHALL TEST ALL CIRCUITS AS SOON AS CONDUCTORS ARE INSTALLED AND

MAKE FINAL TESTS WHEN ALL WORK IS COMPLETE. IF CIRCUITS ARE NOT PROPERLY

CONTROLLED AND INSULATED AT TIME OF EACH FINAL TEST, THE NECESSARY REPAIRS AND

TESTS SHALL BE MADE AT THE CONTRACTORS EXPENSE.

32. ELECTRICAL EQUIPMENT SHALL MEET INSTALLATION STANDARDS PROVIDED IN NEC ARTICLE

110. COORDINATE LOCATIONS OF M.E.P. ITEMS WITH CONTRACTORS PRIOR TO

CONSTRUCTION TO ASSURE THAT CLEARANCES ARE MET. LACK OF COORDINATION BETWEEN

CONTRACTORS WILL NOT RESULT IN EXTRA MONIES AWARDED FOR RELOCATION OF M.E.P.

ITEMS.

33. CHECK FINAL LOCATIONS OF LIGHT FIXTURES AND CEILING ELECTRICAL ITEMS WITH

GRILLES AND REGISTERS, CAMERAS, FANS, SPRINKLER HEADS, ETC. COORDINATE WITH

RESPECTIVE CONTRACTORS PRIOR TO INSTALLATION. NO MONIES WILL BE AWARDED TO

CONTRACTORS HAVING TO RELOCATE ITEMS DUE TO LACK OF COORDINATION BETWEEN

CONTRACTORS. MECHANICAL AND ELECTRICAL PLANS SHOW SCHEMATIC LOCATIONS ONLY –

REFERENCE ARCHITECTURAL REFLECTIVE CEILING PLANS.

34. ANY DISCREPANCIES BETWEEN ARCHITECTURAL DRAWINGS AND ELECTRICAL DRAWINGS

SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO

INSTALLATION.

35. CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF DRAWINGS REFLECTING

"AS BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT

DIMENSIONS AND ELEVATIONS FOR ALL UNDERGROUND AND/OR CONCEALED WORK. UPON

COMPLETION OF THIS PROJECT, THE CONTRACTOR SHALL DELIVER TO THE CONSTRUCTION

MANAGER OR GENERAL CONTRACTOR THE AS-BUILT DRAWINGS. AS BUILT DRAWINGS MUST

BE IN THE POSSESSION OF THE C.M. OR G.C. PRIOR TO FINAL PAYMENT TO THE E.C.

36. THE WIRING METHOD(S) USED SHALL BE SUITABLE FOR THE INSTALLATION AND USE IN

CONFORMITY WITH THE PROVISIONS PROVIDED BY THE NEC, LISTED OR LABELED

EQUIPMENT SHALL BE USED OR INSTALLED IN ACCORDANCE WITH ANY INSTRUCTIONS

INCLUDED IN THE LISTING OR LABELING. REFER TO NEC, SECTION 110.3(A) AND (B).

37. THE MAIN SERVICE DISCONNECTS SHALL BE IDENTIFIED AS THE MAIN SERVICE

DISCONNECTION MEANS PER NEC 2023, ARTICLE 230.70(B).

38. CONTRACTOR SHALL CHECK ELECTRICAL FLOOR PLANS FOR "ISLAND" TYPE ELECTRICAL

OUTLETS AND INSTALL UNDER-FLOOR CONDUITS AND WIRING ACCORDINGLY. SEE PLANS.

39. ARC-FLASH HAZARD WARNING SHALL BE PROVIDED AT ALL ELECTRICAL PANELS PER NEC

2023, SECTION 110.16

40. FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN THE

OPINION OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS ARE

REQUIRED TO PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR SHALL REQUEST

AN INTERPRETATION FROM THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE

WORK. IT THE CONTRACTOR FAILS TO MAKE SUCH A REQUEST, NO EXCUSE WILL

THEREAFTER BE ENTERTAINED FOR FAILURE TO PROVIDE FIRST-CLASS WORKABLE SYSTEMS.

ENGINEER HAS THE FINAL SAY AS TO WHAT IS CONSIDERED “FIRST CLASS WORKABLE

SYSTEMS”.

41. SHOP DRAWINGS ARE TO BE THOROUGHLY CHECKED (AND NOTED SO ON FRONT COVER) BY

THE CONTRACTOR PRIOR TO SUBMITTING THEM TO THE ARCHITECT/ENGINEER. REVIEW BY

THE ENGINEER, SHALL NOT BE CONSTRUED AS A COMPLETE CHECK, BUT ONLY THAT THE

GENERAL METHOD OF CONSTRUCTION AND DETAILING IS SATISFACTORY. REVIEW SHALL

NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS WHICH MAY EXIST.

SHOP DRAWINGS ARE TO BE SUBMITTED VIA INTERNET IN PDF FORM. NO HARD COPIES WILL

BE ACCEPTED. IF E.C. DOES NOT REVIEW DRAWINGS AND NOTES SAME ON FRONT COVER

PRIOR TO SUBMITTAL TO ARCHITECT/ENGINEER, THEY WILL BE REJECTED.

42. ELECTRICAL CONTRACTOR IS TO REFER TO THE TEMPERATURE CONTROL SECTION OF THE

SPECIFICATIONS AND THE MECHANICAL EQUIPMENT SCHEDULE FOR DEFINITION OF WHICH

TRADES ARE RESPONSIBLE FOR HVAC INTERLOCKS AND OPERATIONAL SWITCHES.

43. ALL ROOF EQUIPMENT THAT HAS POWER TO IT MUST BE PROVIDED WITH A DUPLEX

RECEPTACLE (WP AND GFI) WITHIN 25 FEET OF THE UNIT. MOUNT RECEPTACLES ON

HOUSING, CIRCUIT WITH NEARBY RECEPTACLES BELOW, AND NOT WITH ROOF UNIT PER NEC

NOTE: ROOF RECEPTACLES MAY OR MAY NOT BE SHOWN ON PLANS

44. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO CHECK THE RELATED MECHANICAL/KITCHEN/

REFRIGERATION/ELEVATOR/ETC. DRAWINGS TO SEE WHAT DISCONNECT

SWITCHES/STARTERS/RELAYS/ETC. ARE PACKAGED IN BY THE SPECIFIC EQUIPMENT

SUPPLIERS. IF NONE ARE SPECIFICALLY NOTED THE E.C. IS RESPONSIBLE TO PROVIDE AND

INSTALL AS REQUIRED FOR SEQUENCES OF OPERATION. E.C. IS TO REVIEW

MECHANICAL/KITCHEN/REFRIGERATION/ELEVATOR/ETC. SEQUENCES OF OPERATION, FOUND

IN SECTIONS OF THE DRAWINGS AND SPECIFICATIONS OTHER THAN THE ELECTRICAL

SECTIONS FOR SAID SEQUENCES. DISCONNECT SWITCHES/STARTERS/RELAYS/ETC. MAY OR

MAY NOT BE SHOWN ON THE ELECTRICAL DRAWINGS.

45. MANUALS: PER MICHIGAN ENERGY CODES (SPECIFICALLY ASHRAE 90.1 STANDARDS),

CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL AND

MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL

INCLUDE, AT A MINIMUM, THE FOLLOWING:

A. SUBMITTAL DATA FOR ALL ELECTRICAL EQUIPMENT CLEARLY STATING EQUIPMENT

RATING, EXACTLY WHAT MODELS, ACCESSORIES, OPTIONS ARE INSTALLED.

B. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT

REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE

CLEARLY IDENTIFIED.

C. NAMES AND ADDRESSES AND PHONE NUMBERS/EMAIL ADDRESSES FOR AT LEAST ONE

QUALIFIED SERVICE AGENCY FOR EACH PIECE OF EQUIPMENT. A COMPLETE NARRATIVE

OF HOW EACH SYSTEM IS INTENDED TO OPERATE.

46. WIRING TO BE MINIMUM #12 (FOR RUNS OVER 100 FEET, MINIMUM #10).

47. ALL EQUIPMENT INSTALLED AS PART OF THIS PROJECT SHALL BE NEW, REFURBISHED

EQUIPMENT MAY BE USED WHERE NEC ALLOWS.

48. CONTRACTOR IS RESPONSIBLE TO PERFORM THE SHORT CIRCUIT STUDY FOR THE PROJECT

AND THAT ALL ELECTRICAL EQUIPMENT SHALL BE ADJUSTED TO MEET THOSE

REQUIREMENTS.

49. ALL ABOVE GROUND WIRING TO BE INSTALLED IN EMT (THINWALL CONDUIT) UNLESS ROMEX

IS EXPLICITLY ALLOWED.

50. OCCUPANCY AND TOGGLE SWITCHES AS WELL AS RECEPTACLES SHALL BE SPECIFICATION

GRADE, COLOR TO BE CHOSEN BY ARCHITECT DURING SHOP DRAWING STAGE.

51. DEVICE PLATES FOR SWITCHES, RECEPTACLES, TELEPHONE, COMPUTER, ETC., SHALL BE AS

MANUFACTURED PASS AND SEYMOUR, HUBBELL, OR BRYANT. THEY SHALL BE 0.040” THICK

BRUSHED STAINLESS STEEL UNLESS NOTED OTHERWISE. FOR EXISTING PROJECTS, COVER

PLATES SHALL MATCH OTHERS IN THE AREA UNLESS NOTED OTHERWISE.

52. ALL BUSSING AND WIRING TO BE COPPER. NO ALUMINUM IS ALLOWED ON THIS PROJECT.

53. ALL NEW ELECTRICAL DEVICES AND ASSOCIATED OUTLET BOXES SHALL BE FLUSH MOUNTED

UNLESS NOTED OTHERWISE. ALL CONDUIT AND WIRING SHALL BE CONCEALED. SURFACE

RACEWAY AND ASSOCIATED BOXES SHALL ONLY BE PERMITTED WHERE NOTED AND SHALL BE

DISCUSSED WITH C.M. OR G.C. PRIOR TO INSTALLATION.

54. CONNECT ALL EMERGENCY AND EXIT BATTERY PACKS TO NEARBY LIGHTING CIRCUITS AHEAD

OF SWITCHES PER NEC SO EMERGENCY/EXIT LIGHTS OPERATE ON LOSS OF POWER.

55. ELECTRICAL CONTRACTOR SHALL “RING OUT” ALL CIRCUITS IN EXISTING PANELBOARDS

AFFECTED BY THE WORK OF THIS PROJECT AND PROVIDE UPDATED TYPED PANELBOARD

DIRECTORIES. PROVIDE BLANK COVERS WHERE BREAKERS HAVE BEEN REMOVED.

END OF ELECTRICAL NOTES/SPECIFICATIONS

ELECTRICAL FIXTURE LEGEND

DUPLEX RECEPTACLE AT 46" AFF

DUPLEX RECEPTACLE AT 18" AFF

SPLIT-CIRCUIT DUPLEX RECEPTACLE AT 18" AFF

QUAD RECEPTACLE AT 18" AFF

JUNCTION BOX

DISCONNECT SWITCH, NON-FUSED, HEAVY DUTY, HP-RATED - ASSUME 30 AMP SWITCH UNO

ON ONE LINE DIAGRAM OR FLOOR PLANS.

MANUAL MOTOR STARTER

DATA LEGEND

DATA ROUGH-IN

DISTRIBUTION LEGEND

RECEPTACLE PANELBOARD (208Y/120V, 3Ø, 4W), REFER TO PANEL

SCHEDULES FOR MORE INFORMATION.

LOW VOLTAGE:

DATA CABLING TO BE HANDLED BY OWNERS VENDER,

E.C. SHALL PROVIDE ALL CONDUITS, BACK BOXES AND

PULL WIRE PER DRAWINGS.

" INCHES

# NUMBER

' FEET

1P 1 POLE (2P, 3P, 4P, ETC.)

@ AT

A AMPERE

A.F.F. ABOVE FINISHED FLOOR

ACLG ABOVE CEILING

ACT ABOVE COUNTER

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

AFCI ARC FAULT COMBINATION CIRCUIT INTERRUPTER

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUA-STAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

B.F. BOTTLE FILLER

B.M.S. BUILDING MANAGEMENT SYSTEM

BATT BATTERY

BLDG BUILDING

C. CONDUIT

CAB CABINET

CAT CATALOG

CAT6 CATEGORY 6 CABLING

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CL CONNECTED LOAD

COF COFFEE MAKER

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION, CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CT CURRENT TRANSOFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCULATING PUMP

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DL DEMAND LOAD

DN DOWN

DPR DAMPER

DS DISCONNECT SWITCH

DWG DRAWING

E.C. ELECTRICAL CONTRACTOR

E.T.R. EXISTING TO REMAIN

ELEC ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABP FIRE ALARM BOOSTER SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FASP FIRE ALARM SLAVE PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED DISCONNECT SWITCH

G.C. GENERAL CONTRACTOR

GA GAUGE

GAL GALLON

GALV GALVANIZED

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP GYPSUM BOARD

H.V.A.C. HEATING, VENTILATING & AIR CONDITIONING

HOA HAND-OFF-AUTO SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

I/W INTERLOCK WITH

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT- AMPERE RECTIVE

KW KILOWATT

KWC KILOWATT CONNECTED

KWD KILOWATT DEMAND

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LP LIGHTNING PEOTECTION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

M.C. MECHANICAL CONTRACTOR

M.E.P. MECHANICAL ELECTRICAL PLUMBING

M/C MOMENTARY CONTACT

MAGS MAGNETIC STARTER

MAX MAXIMUM

MCC MOTOR CONTROL CENTER

MCP MAIN CIRCUIT BREAKER

MDC MAIN DISRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MSP MOTOR STARTER PANELBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELEC MFGR'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

P PLATE

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

REX REMOVE EXISTING

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

S/N SOLID NEUTRAL

S/S STOP/START PUSHBUTTONS

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

SP SPARE

SPEC SPECIFICATION

SPKR SPEAKER

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SWL SWITCH WITH LIGHTS

SYM SYMMETRICAL

SYS SYSTEM

T-STAT THERMOSTAT

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UCR UNDER COUNTER REFRIGERATOR

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

VOL VOLUME

W WATT

W.G. WIRE GUARD

W/ WITH

W/O WITHOUT

WH WATER HEATER

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

℄ CENTER LINE

∠ ANGLE

▲ DELTA

ABBREVIATIONS

LIGHTING FIXTURE LEGEND

EXIT SIGN

PENDANT FIXTURE

RECESSED DOWN ROUND FIXTURE

2' X 2' FIXTURE

2' X 2' FIXTURE WITH BATTERY-BACKUP

2' X 4' FIXTURE

WALL SCONCE

EMERGENCY LIGHT

NEW

EXISTING

DEMOLISHED

PHASE LINE TYPES

LIGHTING DEVICE SCHEDULE

DIMMER SWITCH

LOW VOLTAGE SWITCH

WALL OCCUPANCY SENSOR SWITCH

SWITCH

CEILING MOUNTED OCCUPANCY SENSOR

ROOM CONTROLLER

ELECTRICAL SHEET INDEX

SHEET NO. TITLE

E0.0 ELECTRICAL LEGENDS & NOTES

E1.0 ELECTRICAL POWER FLOOR PLAN

E1.1 ELECTRICAL POWER ROOF PLAN

E2.0 ELECTRICAL LIGHTING FLOOR PLAN

E2.1 PHOTOMETRIC SITE PLAN

E3.0 ONE LINE DIAGRAM

E4.0 ELECTRICAL PANEL SCHEDULES

E5.0 ELECTRICAL DETAILS

ED1 ELECTRICAL POWER DEMO

ED2 ELECTRICAL LIGHTING DEMO

PROJECT NO.

SHEET NO.

APPROVED

DRAWN BY

DATE

N

W

A S

H

IN

G T

O N

A V

E N

U E

S A

G

IN

A W

M

IC

H

IG

A

N D A T E

N O

T S

S F

A

R C

H

IT

E C

T S

I

N C

A R C H

IT

E C T S

P L A N N E R S

IN

T E R

IO

R S

CONSULTING ENGINEER

491 E. WRIGHT AVE. SHEPHERD, MI 48883

989-567-1100 | info@KTSEngineeringGroup.com

KTS PROJECT NO.: C

O

PY

R

IG

H T

A

LL

R

IG

H T S

R

ES

ER

V

ED

E0.0

JWA

03/17/2026

KTS

26-0299

B A Y

C

IT

Y M

IC

H

IG

A N

D

IN

IN

G

R O

O M

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

S F

O R

B A

Y A

R E

N A

C I S

D

R

C O D E

R E V

IE

W

R E S P O N S E

J

J J

J

J

J

KA1 KA2KB1 KB2 C.B.

FACP

ALTERNATE NO. 1

CAFETERIA

SERVING

DINING ROOM

DISHWASHING

108 STORAGE

STORAGE

WAIT

STATION

PASSAGE

KITCHEN

113 CLASSROOM

DINING

VESTIBULE

MENS

WOMENS

LOCKERS

OFFICE

CLASSROOM

PREP AREA

FCU-1

ETR ETR

ETR

ETRETR

ETR

ETR

KC

ETR

KC- 10

GFI

KC- 10

GFI

KC- 8KC- 12

KC- 8

KC- 15

GFI

KC- 5

GFI

KC- 8

KC- 8 KC- 8

KC- 7

KC- 7

KC- 7

KC- 9

KC- 9

KC- 9

KC- 9

KC- 8

KC- 14

GFI

KC- 14

GFI

KC- 14

GFI

KC- 7

KC- 13 KC- 13

KC- 13

KC- 13KC- 13

KC- 13

KC- 13 KC- 11

M

3 EWH-1

KC- 20KC- 18

KC- 1

KC- 15

KC- 15

KC- 7

KC- 7

KC- 16

GFI

KC- 17,19

FACP

ETR

ACU-1

KC- 3

A

A

A

R2

R2

R2

POWER KEYNOTES:

1 . POWERED THROUGH OUTSIDE UNIT "CU-1".

2 . E.C. TO USE EXISTING CIRCUIT FOR NEW RECEPTACLES.

3 . RECEPTACLE FOR ELECTRIC WATER HEATER "EWH-1" LOCATED ABOVE CEILING. E.C. TO

COORDINATE RECEPTACLE LOCATION WITH "EWH.1" INSTALLER.

4 . ELECTRIC HAND DRYER SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL

CONTRACTOR, EQUAL TO "WORLD DRYER" SANITIZE+DRY. FINISH TO BE DECIDED BY

OWNER. 120/1/60. 950 WATTS. DEDICATED 15 AMP CIRCUIT. HEIGHT PER ARCHITECURAL

DRAWINGS.

5 . POWER FOR COFFEE STATION, VERIFY LOCATION WITH OWNER.

6 . PORTABLE SALAD BAR, VERIFY LOCATION WITH OWNER.

7 . E.C. VERIFY POWER FOR DROP DOWN SCREEN. E.C. TO VERIFY LOCATION WITH OWNER.

8 . HOT SERVING LINE, E.C. TO VERIFY LOCATION WITH OWNER.

1/8" = 1'-0"

MAIN FLOOR PLAN - POWER

PROJECT NO.

SHEET NO.

APPROVED

DRAWN BY

DATE

N

W

A S

H

IN

G T

O N

A V

E N

U E

S A

G

IN

A W

M

IC

H

IG

A

N D A T E

N O

T S

C

H

IT

E C

T S

I

N C

A R C H

IT

E C T S

P L A N N E R S

IN

T E R

IO

R S

CONSULTING ENGINEER

491 E. WRIGHT AVE. SHEPHERD, MI 48883

989-567-1100 | info@KTSEngineeringGroup.com

KTS PROJECT NO.: C

O

PY

R

IG

H T

A

LL

R

IG

H T S

R

ES

ER

V

ED

E1.0

JWA

03/17/2026

KTS

26-0299

B A Y

C

IT

Y M

IC

H

IG

A N

D

IN

IN

G

R O

O M

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

S F

O R

B A

Y A

R E

N A

C I S

D

A

A D D E N D U M

R

C O D E

R E V

IE

W

R E S P O N S E

R

C O D E

R E V

IE

W

R E S P O N S E

RECEPTACLE CONTROL MATRIX

KEYNOTE TYPE SENSOR FULL OFF TIME NOTES

A

OCCUPANCY

SENSOR

AUTO ON/OFF 20 MINS

RECEPTACLE CONTROL SHALL ONLY

CONTROL SPLIT-CIRCUIT RECEPTACLES.

ALUMINUM CONDUCTORS

15-20 12 12 3/4'' 3/4'' 3/4'' 3/4''

NOT ACCEPTABLE

25-30 10 10 3/4'' 3/4'' 3/4'' 3/4''

35-40 8 10 3/4'' 3/4'' 3/4'' 3/4''

45-50 8 (6) 10 3/4'' 3/4'' 3/4'' 3/4''

60 6 (4) 10 3/4''(1) 3/4''(1) 3/4''(1) 3/4''(1)

70 4 8 1'' 1 1/4'' 1 1/4'' 1 1/4''

80 4 (3) 8 1'' 1 1/4'' 1 1/4'' 1 1/4''

90-100 3 (2) 8 1 1/4'' 1 1/4'' 1 1/4'' 1 1/4'' 1 6 1 1/2'' 1 1/4'' 1 1/2''

110 2 (1) 6 - 1 1/4'' 1 1/4'' 1 1/4'' (1 1/2'') 1/O 4 - 1 1/2'' 2''

125 1 (1/0) 6 - 1 1/4'' (1 1/2'') 1 1/4'' (1 1/2'') 1 1/2'' 2/O 4 - 1 1/2'' 2''

150 1/O 6 - 1 1/2'' 1 1/2'' 1 1/2'' 3/O 4 - 2'' 2 1/2''

175 2/O 6 - 2'' 2'' 2'' 4/O 4 - 2'' 2 1/2''

200 3/O 6 - 2'' 2'' 2 1/2'' 250 4 - 2'' 3''

225 4/O 4 - 2'' 2'' 2 1/2'' 300 2 - 2 1/2'' 3''

250 250 4 - 2 1/2'' 2 1/2'' 2 1/2'' 350 2 - 2 1/2'' 3''

300 350 4 - 2 1/2'' 2 1/2'' 3'' 500 2 - 3'' 3 1/2''

350 500 3 - 3'' 3'' 3'' 2-4/O 2-1/O - 2-2'' 2-2''

400 500 3 - 3'' 3'' 3'' 2-250 2-1/O - 2-2'' 2- 2 1/2''

450 2-4/O 2-2 - 2-2'' 2-2'' 2- 2 1/2'' 2-300 2-1/O - 2- 2 1/2'' 2-3''

500 2-250 2-2 - 2- 2 1/2'' 2- 2 1/2'' 2- 2 1/2'' 2-350 2-1/O - 2- 2 1/2'' 2-3''

600 2-350 2-1 - 2- 2 1/2'' 2- 2 1/2'' 2-3'' 2-500 2-2/O - 2-3'' 2-3 1/2''

700 2-500 2-1/O - 2-3'' 2-3'' 2-3'' 2-600 2-3/O - 2-3'' 2-3 1/2''

800 3-500 2-1/O - 2-3'' 2-3'' 2-3 1/2'' 3-400 3-3/O - 3-3'' 3-3 1/2''

1000 3-400 3-2/O - 3-3'' 3-3'' 3-3'' 3-600 3-4/O - 3-3 1/2'' 3-3 1/2''

1200 3-600 3-3/O - 3-3 1/2'' 3-3 1/2'' 3-3 1/2'' 4-500 4-250 - 4-3'' 4-3 1/2''

1600 4-600 4-4/O - 4-3 1/2'' 4-3 1/2'' 4-3 1/2'' 5-600 5-350 - 5-3 1/2'' 5-4''

2000 5-600 5-250 - 5-3 1/2'' 5-3 1/2'' 5-3 1/2'' 6-600 6-400 - 6-3 1/2'' 6-4''

FEEDER AND BRANCH CIRCUIT SIZING SCHEDULE - GENERAL PURPOSE

COPPER CONDUCTORS

OVERCURRENT

DEVICE RATING

(AMPERES)

WIRE SIZE

(AWG OR KCMIL)

CONDUIT SIZE

WIRE SIZE

(AWG OR KCMIL)

CONDUIT SIZE

PHASE & NEUTRAL GROUND

SINGLE PHASE

2 WIRE+G

(1PH,1IN,1G)

SINGLE PHASE

3 WIRE+G

(2PH,1IN,1G)

THREE PHASE

3 WIRE+G

(3PH,1G)

THREE PHASE

& NEUTRAL

4 WIRE+G

(3PH,1IN,1G)

PHASE & NEUTRAL GROUND

SINGLE

PHASE

3 WIRE+G

(2PH,1IN,1G)

THREE PHASE

3 WIRE+G

(3PH,1G)

THREE PHASE

& NEUTRAL

4 WIRE+G

(3PH,1IN,1G)

NOTES:

1. CONTRACTOR TO SIZE FEEDERS AND BRANCH CIRCUITS BASED ON THIS SCHEDULE AND OVER CURRENT DEVICE SIZE, UNLESS NOTED OTHERWISE.

2. CONDUCTORS ARE BASED ON THHN/THWN UP TO AND INCLUDING #4/O. LARGER THAN #4/O ARE BASED ON TYPE XHHW.

3. CONDUCTORS ARE BASED ON 90°C, 600V. INSULATED COPPER WIRE APPLIED AT 75° FOR TERMINATION RATED 60/75°C OR 75°C. FOR TERMINATION RATED 60°C, USE CONDUCTORS AND

CONDUIT SIZED INDICATED IN PARENTHESES.

4. CONDUIT SIZES ARE VALID FOR EMT OR RGS. CONDUIT SIZES SHALL BE ADJUSTED AS REQUIRED FOR OTHERS TYPES OF CONDUIT.

5. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE REQUIRED WIRE SIZES TO ACCOMMODATE MECHANICAL EQUIPMENT LUG SIZES.

6. SIZE OF DISCONNECT SWITCH LOCATED AT EQUIPMENT SHALL BE SIZED BASED UPON OVERCURRENT PROTECTION OF THAT DEVICE.

7. OBTAIN APPROVAL FROM ENGINEER PRIOR TO INSTALLING DIFFERENT SIZE/QUANTITY OF CONDUCTORS TO OBTAIN AN EQUIVALENT AMPACITY.

8. SPLICE FROM ALUMINUM TO COPPER PRIOR TO ENTERING EQUIPMENT LISTED FOR USE WITH COPPER CONDUCTORS ONLY OR USE COPPER CONDUCTORS FOR THE ENTIRE LENGTH OF FEEDER.

REFER TO N.E.C. ARTICLE 250

GROUNDING DETAIL

NOT TO SCALE

**WHERE JOB REQUIRES OR

WHERE AVALIABLE.

1. MAIN DISTRIBUTION PANEL.

2. NEUTRAL BUS.

3. EQUIPMENT GROUND BAR KIT.

4. 10' -0" X 3/4" COPPERWELD GROUND ROD.

5. CADWELD OR APPROVED CLAMP.

6. APPROVED PIPE CLAMP.

7. UNDERGOUND METAL PIPE.**

8. CADWELD OR APPROVED CONNECTION

9. BUILDING STEEL**

10. SUBPANEL

11. WIRE SIZED PER N.E.C., ARTICLE 250

12. CONCRETE-ENCASED ELECTRODE PER N.E.C.,

ARTICLE 250.52(A)(3)**

11 10

11 8

BREAK TAB TO SEPARATE UPPER AND LOWER

RECEPTACLES POWER.

UPPER RECEPTACLE SHALL BE CONNECT TO

CIRCUIT CONTROLLED BY ROOM OCCUPANCY

SENSORS THAT RECEPTACLE IS SERVING,

AUTOMATIC SHUTOFF AFTER ROOM IS

UNOCCUPIED FOR 20 MINUTES.

LOWER RECEPTACLE WILL BE CONNECTED TO

SAME CIRCUIT AS UPPER RECEPTACLE, BUT

WILL BE CONNECTED BEFORE CONTROL DEVICE

SO THAT THE LOWER RECEPTACLE WILL HAVE

CONSTANT POWER AS LONG AS CONTROLLING

CIRCUIT BREAKER IS ON.

SYMBOL AS PER NEC FIGURE 406.3(F)

DISPLAYED ON RECEPTACLE FACE

"CONTROLLED" PER NEC 406.3(F) DISPLAYED

ON RECEPTACLE FACE

SPLIT-CIRCUIT RECEPTACLE

NOT TO SCALE

BRANCH CIRCUIT VOLTAGE DROP WIRING SCHEDULE FOR SINGLE PHASE CIRCUITS

BRANCH CIRCUIT RATING(A) WIRE SIZE

MAXIMUM BRANCH CIRCUIT LENGTH (IN FEET)

120V 208V 240V 277V 480V

20A 12 83 143 165 191 331

10 128 222 256 295 511

8 201 348 402 464 804

6 313 542 625 721 1250

30A 10 85 148 170 197 341

8 134 232 268 309 536

6 208 361 417 481 833

4 313 542 625 721 1250

NOTES:

1. THE ABOVE TABLE VALUES ARE BASED ON COPPER CONDUCTORS, IN STEEL CONDUIT, WITH A LOAD FACTOR OF .85 PER NEC CHAPTER 9, TABLE 9.

2. PROVIDE BRANCH CIRCUIT CONDUCTORS AS INDICATED IN THE TABLE ABOVE FOR ALL LIGHTING AND RECEPTACLE BRANCH CIRCUITS. WHERE BRANCH CIRCUITS SERVE DEDICATED EQUIPMENT, THE CONTRACTOR MAY

PERFORM VOLTAGE DROP CALCULATIONS BASED ON ACTUAL EQUIPMENT CONNECTED LOAD AND PROVIDE CONDUCTORS APPROPRIATELY SIZED TO LIMIT VOLTAGE DROP TO A MAXIMUM OF 3%.

3. CONDUCTOR SIZES ARE BASED ON MAXIMUM OF 9 CURRENT CARRYING CONDUCTORS IN A SINGLE CONDUIT.

4. LIMITS FOR CONDUCTOR LENGTHS SHOWN ARE BASED ON A MAXIMUM BRANCH CIRCUIT LOADING OF 64% OF THE BRANCH BREAKER RATING AND A MAXIMUM OF 3% VOLTAGE DROP TO COMPLY WITH ASHRAE 90.1 AND

THE NEC. FOR CIRCUITS LOADED GREATER THAN 64% OF BRANCH BREAKER RATING, THE CONTRACTOR SHALL PROVIDE CONDUCTORS APPROPRIATELY SIZED TO LIMIT VOLTAGE DROP TO 3%.

PROJECT NO.

SHEET NO.

APPROVED

DRAWN BY

DATE

N

W

A S

H

IN

G T

O N

A V

E N

U E

S A

G

IN

A W

M

IC

H

IG

A

N D A T E

N O

T S

C

H

IT

E C

T S

I

N C

A R C H

IT

E C T S

P L A N N E R S

IN

T E R

IO

R S

CONSULTING ENGINEER

491 E. WRIGHT AVE. SHEPHERD, MI 48883

989-567-1100 | info@KTSEngineeringGroup.com

KTS PROJECT NO.: C

O

PY

R

IG

H T

A

LL

R

IG

H T S

R

ES

ER

V

ED

E5.0

JWA

03/17/2026

KTS

26-0299

B A Y

C

IT

Y M

IC

H

IG

A N

D

IN

IN

G

R O

O M

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

S F

O R

B A

Y A

R E

N A

C I S

D

R

C O D E

R E V

IE

W

R E S P O N S E

2410_001
scan0405
2538_A0.1-Arch D (24 x 36)
Sheets and Views
Arch D (24 x 36)
2538_A2.0-Arch D (24 x 36)
Sheets and Views
Arch D (24 x 36)
2538_A6.0-Arch D (24 x 36)
Sheets and Views
Arch D (24 x 36)
2026-06-02 BAISD Dining - E - Code Review R2
Sheets
E0.0 - ELECTRICAL LEGENDS & NOTES
E1.0 - ELECTRICAL POWER FLOOR PLAN
E5.0 - ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .