This document is a set of 35% design construction drawings for a repair and replacement project of the main distribution and branch panel boards in Building 6002 at Tinker Air Force Base, Oklahoma.

The project, identified as WWYK050751, involves demolition and reconstruction of electrical, mechanical, architectural, and related systems within a designated space in the facility. Key work includes: removal of existing wood doors, frames, and interior wall finishes; demolition of ACT ceilings, light fixtures, and GWB panels; removal of existing electrical panels, conduits, and branch circuits; disconnection and relocation of HVAC components including supply diffusers; and removal of existing sprinkler heads. New construction encompasses installation of new metal stud framing with Type X gypsum board, new electrical panelboards (6002-PNL-1 at 800A 208Y/120V 3Ø and related panels), new lighting fixtures with integral battery backup, new HVAC supply diffusers connected to existing ductwork, new sprinkler heads, and a new electrical system grounding bus bar. The primary transformer (XMFR-11) is a 300kVA 208Y/120V 3Ø unit with conductors running through 3" PVC Schedule 80 conduit. The project includes coordination with OG&E power utility for feeder disconnection and reconnection, field verification of existing conditions, and compliance with UFC specifications and Tinker AFB electrical standards. The design is dated 10 June 2025, with architectural, mechanical, and electrical disciplines represented across nine drawing sheets including demolition plans, new construction plans, and a one-line electrical diagram.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REVIEWED BY:

REVIEWED BY:

USING AGENCY:

ASBESTOS EVALUATION:

SAFETY:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

INDUSTRIAL HYGIENE:

DATE:

PROJECT DRAWING INDEX SIGNATURES

CORROSION ENGINEER: (CECE)

CE OPERATIONS: (CECO)

COMMUNICATIONS: (COMM)

CHIEF ENGINEER DIR: (CECE)

CHIEF DESIGN BRANCH: (CECE)

DESIGN MANAGER: (CECE)

ZONE MANAGER:

CONSTRUCTION MANAGEMENT: (CECE)

ENVIRONMENTAL:

BASE CIVIL ENGINEER: (CE)

FIRE DEPARTMENT: (CEFT)

GENERAL1. BRAND NAMES: REFERENCE TO SPECIFIC BRAND NAMES

OR COMPANIES IS FOR THE PURPOSE OF ESTABLISHING

MINIMUM QUALITY STANDARDS, IDENTIFICATION AND

GUIDANCE AND IS NOT INTENDED TO LIMIT SELECTION OF

OTHER MANUFACTURERS THAT ARE EQUAL OR EXCEED

THE SPECIFIED ITEMS IN TERMS OF PHYSICAL

PROPERTIES, INCLUDING, COLOR RANGE, FINISH,

DURABILITY, APPEARANCE, PERFORMANCE

CHARACTERISTICS, AND OTHER FACTORS. OTHER

PRODUCTS, MATERIALS, COLORS AND SYSTEMS, MAY BE

SUBMITTED FOR EVALUATION AND

APPROVAL/DISAPPROVAL BY THE CONTRACTING OFFICER.

2. THIS SET OF CONSTRUCTION DOCUMENTS SHALL BE

CONSIDERED AS A WHOLE IN THAT THE GENERAL

CONTRACTOR AND ALL THE SUB-CONTRACTORS ARE

RESPONSIBLE FOR THE INFORMATION PRESENTED ON ALL

SHEETS ON THE SET OF DRAWINGS AND ALL SECTIONS OF

THE SPECIFICATIONS.

3. THE CONTRACTOR IS RESPONSIBLE FOR ERECTING ALL

CONSTRUCTION FENCING AND BARRICADES AS REQUIRED

TO PROTECT CONSTRUCTION MATERIAL AND TO PREVENT

ANY UNAUTHORIZED PERSONNEL FROM ENTERING THE

CONSTRUCTION SITE.

4. ANY DAMAGE TO THE EXISTING GROUNDS OR FACILITIES

CAUSED BY CONSTRUCTION TRAFFIC OR ANY

CONSTRUCTION OPERATION SHALL BE REPAIRED OR

REPLACED BY THE CONTRACTOR TO MATCH OR EXCEED

EXISTING CONDITIONS AT NO ADDITIONAL COST TO THE

GOVERNMENT.

5. ALL WORK NOTED & LOCATED IN THESE DOCS SHALL BE

UNDERSTOOD BY THE CONTRACTOR TO REQUIRE ALL NEW

LABOR & MATERIALS UNLESS SPECIFICALLY NOTED TO BE

"EXISTING" OR "BY OTHERS".

WWYK050751

REPAIR/REPLACE MAIN

DISTRIBUTION & BRANCH

PANEL BOARDS, B6002

KEY PLAN:

GENERAL NOTES:

DISCIPLINE

PROJECT

LOCATION

1 G-101 GENERAL NOTES & VICINITY MAP

SHT.SEQ. SHEET TITLE

OF

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

0J

U N

TE

PA

-S R

M

C B

AR

BO

ZA

G-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

GE

NE

RA

L N

OT

ES

AN

D

VI

CI

NI

TY

M

AP

01 09

E-001 ELECTRICAL SYMBOLS AND ABBREVIATIONS

MD-101 MECHANICAL DEMOLITION PLAN

M-101 MECHANICAL PLAN5

ED-101 ELECTRICAL DEMOLITION PLAN

E-101 ELECTRICAL PLAN

AD-101 ARCHITECTURAL DEMOLITION PLAN

A-101 ARCHITECTURAL PLAN

E-601 ELECTRICAL DEMO AND NEW WORK ONE LINE DIAGRAM9

R U

N W

AY

8/

RUNWAY 13/31

TA

XI

W

AY

G

TAXIW

AY H

TAXIWAY B

TAXIWAY C

TAXIWAY M

TA

XI

W

AY

K

TAXIWAY E

TAXIWAY A

TA

XIW

AY E

E

TAXIWAY F

TAXIWAY D

TAXIWAY E

TAXIWAY J

TA

XI

W

AY

G

TAXIWAY A

TAXIW

AY H

TAXIWAY C

TAXIWAY D

TAXIWAY EE

TAXIWAY F

Elm C reek

Cr ut ch o

Cr ee k

Kuhlman Creek

Soldier Creek

Kuhlman Creek

Elm C reek

East Crutcho Creek

Elm Creek

El m

C re ek

Elm Creek

Elm C reek

Elm CreekElm C reek

Ku hlm an C re ek

Ea st

C ru tc ho

C re ek

Elm C ree k

West Crutcho Creek

W es t C ru tc ho

C re ek

Elm Creek

Soldier Creek

Elm C reek

Soldier CreekSoldier Creek

Ea st

C ru tc ho

C re ek

Elm Creek

Ea st

C ru tc ho

C re ek

East C rutcho C reek

Soldier Creek

So ld ie r C re ek

East C rutch o Creek

Soldier C reek

Soldier C reek

So ld ie r C re ek

East Crutcho Creek

416506

21222121

59475946

11401128

62540

61089

838837

62509

62528

62523

62501X

43774

62512

62516

62525

3592135916

99999

62543

32101

71086

53902

50414

55300

56601

930G

948-E

911-E

948-W

61019

911-W

33001

35913

62501

65672

930S

45134

43609

42116

62517

62515

62526

62527

62503

62513

61289

62542

62501OK

11289

62501

15930

15908

15904

15904

15908

15908

15904

15904

15908

62502

41046

62501

62514

62501

61018

71089

45134

96022

43120

41157

44045

45815

40592

43610

62522

41163

15930

15930

11824

Arnold St.

Ea st

D r.

SE 74th St

SE 59th St.

Ai r D ep ot

Patrol Rd.

St af f D r.

Reserve Rd.

5th Ave

"A " A ve

M un iti on s R d.

W ar eh ou se R d.

"B " A ve

7th St.

"H " A ve

M cN ar ne y Av e.

Mitchell Ave

Al er t R d.

Co ok

A ve

W es t D r.

"E "A ve

Extender Dr.

Sentry Rd.

34th St.

Twining Dr.

5th Ave.

Jo ne s

Globemaster Dr.

To w er R d.

Vanaman Rd.

In du st ria l B lv d.

So ut h St

1st St.

Do ol itt le

A ve

Pi cn ic R d.

Ja m es D r.

W ol fe D r.

Ai r D ep ot

Ai r D ep ot

"D " A ve

Perimeter Rd.

Rapcon Rd.

Reserve Rd

"L " A ve

Mercury Rd.

1st St.

Br ow n Dr

Po nd

R d.

O ld

A ir

De po t

Airey Dr.

General Motors Dr

Bradley Dr.

Entrance Road "C"

Entrance Road "A"

"C " A ve

"C " A ve

Vandenberg Dr.

Hi llt op R d.

Do rm ito ry

R d.

Dormitory Rd.

"M " A ve

Chennault Dr.

M itc he ll A ve

Spaatz Dr.

Co m m od ity D r.

Doolittle Ave

W hi te D r.

3rd Ave.

"D " D riv e

Ba ll

Pa rk

R d.

Joint STARS Dr.

Ai r D ep ot

B lv d

Turbine Dr. Turbine Dr.

Central Plant Dr.

6th St.6th St.

Falco n Dr.

Blackb ird

Dr.

W ey la nd

L oo p

Pegasus Dr.

Thunderbolt D r.

Munitions Rd. Ext.

Codding Rd.

Starlifter Dr.

Chidlaw Ct.

Co rs ai r D r.

Ra pt or Ct

N ig ht H aw k

Ct

Ph an to m

D r.

Fr an kl in

Po w er ho us e

Dr

Sk ym as te r D r.

Spaatz Ct.

La w re nc e

M un de ll

Nabors Dr.

In tr ud er

D r.

M cN ic kl e

M ill er D r.

Ta il

Fe at he r D r.

Holden Dr.

Ai re y C ir.

Smith Ct.

Ra ve n Ct

Air Dep ot Ai r D ep ot

Vanaman Rd.

1st St.

1st St.

TAXIWAY F

Ra w li ng s A ve

Mitc he ll A ve

Mercury Rd.

Ra ily ar d

Rd

He rc ul es

R d.

"F " A ve

Pr op ul sio n Dr

Stratofortress Dr.

96021

Arnold St.

Sentry Rd.

Arnold St.

TINKER AFB, OK

VICINITY MAP

GOTT

GATE

TINKER GATE

PASS & ID B6611

EAKER GATE

VANCE

GATE

HOPE

GATE

LEGEND

CONTRACTOR

HAUL ROUTE

TRUCK GATE

PIAZZA GATE

BASE CIVIL

ENGINEER

B400

BASE

OPERATIONS

B240

CONTRACTING

B3

HRUSKOCY

GATE

FIRE DEPARTMENT

B117

LIBERATOR GATE

LANCER

GATE

PROJECT

LOCATION

PROJECT

LOCATION

15904

15904

15904

15904

M cN ar ne y Av e.

Dormitory Rd.

Arnold St.

OF

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

0J

U N

TE

PA

-S R

M

M N

O

EL

AD-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

AR

CH

IT

EC

TU

RA

L

DE

MO

LIT

IO

N

PL

AN

02 09

AD-101

ARCHITECTURAL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

DEMOLITION KEYED NOTES

DEMOLISH EXISTING WOOD DOOR, FRAME, AND WALL FOR INSTALLATION OF NEW DOOR.

DEMOLISH INNER LAYER OF GWB PANELS FROM CMU WALLS.

DEMOLISH FINISH FLOOR TO SUBSTRATE BELOW.

DEMOLISH ACT CEILING AND GRID INCLUDING LIGHT FIXTURES AND SUPPLY GRILL IN IT'S

ENTIRETY - REFER ELECTRICAL AND MECHANICAL.

DEMOLISH GWB PANEL FROM INTERIOR METAL LINER.

DEMOLISH GWB PANELS, ENCLOSURE FRAMING, AND SHELVING AT EXISTING CONDUIT

AND SAFETY SWITCH.

REMOVE EXISTING SPRINKLER HEAD FOR INSTALLATION OF NEW HEADS - REFER FIRE

PROTECTION SOW.

EXISTING CMU WALL EXTENDS ABOVE EXISTING CEILING HEIGHT AND IS NOT FULL HEIGHT.

(APPROXIMATELY 9'-0” +/- AFF)

EXISTING CMU WALL EXTENDS TO STRUCTURE (APPROXIMATELY 12'-6” +/- AFF)

EXISTING METAL PANEL ON METAL BUILDING STRUCTURE WITH INTERIOR METAL LINER -

EXTENDS TO STRUCTURE (APPROXIMATELY 12'-6” +/- AFF)

B6002 KEYPLAN

PROJECT

LOCATION

GENERAL NOTES

A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD

OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.

B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING

OUTAGES PRIOR TO CONSTRUCTION.

C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT

PRIOR TO INSTALLATION.

10 5

ABOVE

ABOVEOFFICE

MECH

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

JU

N

TE

PA

-S R

M

M N

O

EL

A-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

AR

CH

IT

EC

TU

AL

P

LA

N

03 09

A-101

ARCHITECTURAL PLAN

SCALE: 1/4" = 1'-0"

A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD

OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.

B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING

OUTAGES PRIOR TO CONSTRUCTION.

C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT

PRIOR TO INSTALLATION.

KEYED NOTES

B6002 KEYPLAN

PROJECT

LOCATION

1 4

93 7

PRIME NEW GWB WALLS. PAINT ELECTRICAL ROOM GWB WALLS WITH EPOXY PAINT.

PATCH AND REPAIR CMU WALLS TO RECEIVE PAINT. PAINT WITH EPOXY PAINT.

PATCH AND REPAIR METAL LINER TO RECEIVE PAINT. PAINT WITH EPOXY PAINT.

PREP CONCRETE FLOOR AND CLEAN TO BARE CONCRETE. APPLY DENSIFIER TO CONCRETE FLOOR

AS PER MANUFACTURER'S RECOMMENDATIONS.

NEW 3070 METAL DOOR AND FRAME. PAINT TO MATCH EXISTING ADJACENT DOOR FRAMES WITHIN

BUILDING.

PROVIDE METAL FRAMING TO STRUCTURE ABOVE: 5/8” TYPE X GWB (ON ONE SIDE) ON 6” METAL

FRAMING, 25 GA @ 16” O.C. WITH MINERAL WOOL BATT INSULATION.

PROVIDE NEW LIGHTING - REFER ELECTRICAL.

PROVIDE WALL MOUNTED SUPPLY GRILL - REFER MECHANICAL.

PROVIDE UP TURNED SPRINKLER HEADS - REFER FIRE PROTECTION SOW.

PROVIDE METAL FRAMING AT NEW DOOR LOCATION. 5/8" TYPE X GWB BOTH SIDES, ON 6" METAL

FRAMING. 25GA AT 16" O.C. WITH MINERAL WOOL BATT INSULATION. EXTEND FRAMING

AND GWB TO STRUCTURE ABOVE. PROVIDE DOUBLE STUDS AT EACH SIDE DOOR FRAME.

MEN WOMEN

TOOL CRIB

OFFICE

MECHELEC

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

0J

U N

TE

PA

-S R

M

Q G

AU

N

A

MD-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

ME

CH

AN

IC

AL

DE

MO

LIT

IO

N

PL

AN

04 09

MD-101

MECHANICAL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

DEMOLITION KEYED NOTES

CONTRACTOR SHALL PERFORM A PRE-TAB OF THE EXISTING SYSTEM AND REPORT

EXISTING CONDITIONS TO GOVERNMENT.

DEMOLISH EXISTING SUPPLY DIFFUSER AND DISCONNECT FROM EXISTING DUCTWORK.

EXISTING SPRINKLER HEADS. REMOVE HEADS - REF FIRE PROTECTION SOW.

B6002 KEYPLAN

PROJECT

LOCATION

GENERAL NOTES

A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD

OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.

B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING

OUTAGES PRIOR TO CONSTRUCTION.

C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT

PRIOR TO INSTALLATION.

OFFICE

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

0J

U N

TE

PA

-S R

M

Q G

U

AN

A

M-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

ME

CH

AN

IC

AL

P

LA

N

05 09

M-101

MECHANICAL PLAN

SCALE: 1/4" = 1'-0"

GENERAL NOTES

A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD

OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.

B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING

OUTAGES PRIOR TO CONSTRUCTION.

C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT

PRIOR TO INSTALLATION.

KEYED NOTES

PROVIDE & INSTALL NEW WALL MOUNTED SUPPLY AIR DIFFUSER AND CONNECT TO

EXISTING DUCTWORK.

CONTRACTOR SHALL PERFORM A FINAL TAB OF THE SYSTEM AND REPORT CONDITIONS TO

THE GOVERNMENT.

PROVIDE NEW UPRIGHT HEADS AT EXISTING SPRINKLER SYSTEM. REF FIRE PROTECTION

SOW.

B6002 KEYPLAN

PROJECT

LOCATION

1 2

MEN WOMEN

TOOL CRIB

ELEC

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

0J

U N

TE

PA

-S R

M

C B

AR

BO

ZA

E-001

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

EL

EC

TR

IC

AL

S

YM

BO

LS

AN

D

AB

BR

EV

IA

TI

ON

S

06 09

ELECTRICAL SYMBOLS LEGENDS AND ABBREVIATIONS

SYMBOL NOTES

1. THESE SYMBOLS APPLY TO THE ENTIRE SET OF CONTRACT DRAWINGS.

2. ALL SYMBOLS ARE NOT NECESSARILY USED IN THE DRAWINGS FOR THIS PROJECT. LISTING OF

SYMBOLS DOES NOT IMPLY THAT ALL SYMBOLS ARE USED IN THE CONTRACT DRAWINGS.

3. COLORS FOR ALL OUTLETS AND SWITCHES SHALL BE AS SHOWN ON ARCHITECTURAL PLANS.

4. ALL MOUNTING HEIGHTS SHOWN IN SYMBOL LEGEND SHALL BE AS PER TAS/ADA

REQUIREMENTS UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS.

5. BRANCH CIRCUIT NUMBERS MAY BE SHOWN NEXT TO SYMBOLS IN MULTIWIRE CIRCUITS.

6. EQUIPMENT IDENTIFIERS, MATCHING EQUIPMENT SCHEDULES, ARE DISPLAYED ATTACHED TO

SYMBOLS BY LEADER ARROWS, UON.

7. SYMBOL ORIENTATION DOES NOT IMPLY DEVICE OR EQUIPMENT ORIENTATION, UNLESS NOTED AS SUCH. SEE REFLECTED CEILING PLANS FOR LIGHT FIXTURE POSITIONS AND ORIENTATIONS.

8. SYMBOL SIZE DOES NOT IMPLY EQUIPMENT SIZE, UON.

9. LOWER CASE LETTER IN POSITION "X" INDICATES FIXTURES CONTROLLED BY SAME LETTER.

10. PLAN SYMBOLS USE THE FOLLOWING LINE TYPE CONVENTION AND ARE REPRESENTED AS

FOLLOWS:

LINETYPE, DENOTES EXISTING TO REMAIN

LINETYPE, DENOTES EXISTING TO BE DEMOLISHED

LINETYPE, DENOTES NEW U.G. OR CONCEALED CONSTRUCTION

LINETYPE, DENOTES NEW CONSTRUCTION

LINETYPE, DENOTES LIGHTING SWITCHLEG

A AMPERES OR TRIP

AMPERES

AC ALTERNATING CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC SYMMETRICAL AMPS

INTERRUPTING CAPACITY

AWG AMERICAN WIRE GAUGE

A/R AS REQUIRED

ARR. ARRESTOR

BLDG BUILDING

BRKT BRACKET

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CL CURRENT LIMITING

CO CONDUIT ONLY

CTL CONTROL

DC DIRECT CURRENT

D.T.C. DATA TERMINAL CABINET

EMCS ENERGY MONITORING AND

CONTROL SYSTEM

FACP FIRE ALARM CONTROL

PANEL

FT FOOT, FEET

GFCI GROUND FAULT CIRCUIT

INTERRUPTER, 5MA

PERSONNEL PROTECTION

UNLESS OTHERWISE NOTED.

GRD GROUND

HZ HERTZ

IAW IN ACCORDANCE WITH

IG ISOLATED GROUND

IN INCH, INCHES

IR INFRARED

KV KILOVOLTS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPS REACTIVE

KWH KILOWATT HOURS

L-L LINE TO LINE

L-N LINE TO NEUTRAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MTD MOUNTED

MTG MOUNTING

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NEUT NEUTRAL

N.O. NORMALLY OPEN

NLT NOT LESS THAN

NMT NOT MORE THAN

OH OVERHEAD

PAS PUBLIC ADDRESS SYSTEM

PE PHOTOELECTRIC

PH PHASE

PLCS PLACES

PNL PANELBOARD

PVC POLYVINYL CHLORIDE

ELECTRICAL RACEWAY

USED ONLY U.G., CARLON

OR EQUIVALENT

RC RIGID STEEL CONDUIT

REF REFERENCE

REQ'D REQUIRED

RGC RIGID GALVANIZED STEEL

CONDUIT

RM ROOM

RMC RIGID METALIC CONDUIT

SHT SHEET

SOB STANDOFF BRACKET

SPACE SPACE(S) ONLY (NO

BREAKER DEVICE)

SPARE SPARE BREAKER OR

DEVICE

SPDT SINGLE-POLE,

DOUBLE-THROW

SPECS CONTRACT SPECIFICATIONS

SPST SINGLE-POLE,

SINGLE-THROW

S/N SOLID NEUTRAL

TB TELEPHONE BACKBOARD

TYP TYPICAL

UG UNDERGROUND

UL LISTED BY UNDERWRITER'S

LABORATORIES

UON UNLESS OTHERWISE NOTED

V VOLTS

VA VOLT AMPERES

W WATT

WH WEATHERHEAD

W/ WITH

Ø PHASE

2W+G CIRCUIT TYPE

3W+G CIRCUIT TYPE

4W+G CIRCUIT TYPE

ABBREVIATIONS

POWER SYMBOLS LEGEND

DESCRIPTIONSYMBOL

RECEPTACLE, DUPLEX, 20A, 250V, GROUNDING 2W+G, NEMA

5-20R

RECEPTACLE, DUPLEX, FLOOR MOUNTED, FLUSH, 20A, 250V,

GROUNDING 2W+G NEMA 5-20R.

RECEPTACLE, DUPLEX, CEILING MOUNTED, 20A, 250V,

GROUNDING 2W+G, NEMA 5-20R

RECEPTACLE, QUADRAPLEX

RECEPTACLE, SPECIAL PURPOSE

RECEPTACLE, CLOCK

JUNCTION BOX, ABOVE CEILING

JUNCTION BOX, WALL MOUNTED, SERVING COMPUTER LOAD.

RECEPTACLE, DUPLEX, SERVING COMPUTER LOAD. 20A, 250V,

GROUNDING 2W+G RECEPTACLE, NEMA 5-20R

SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC

ONLY), SINGLE-POLE, MOUNT 48" AFF

SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC

ONLY), THREE-WAY, SPDT. MOUNT 48" AFF

SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC

ONLY), FOUR-WAY, SPDT. MOUNT 48" AFF

SWITCH, DIMMER, 120V, 1500 WATT. MOUNT 48" AFF

BRANCH CIRCUIT HOME RUN WITH NEUTRAL, PHASE AND

EQUIPMENT GROUND RESPECTIVELY

BRANCH CIRCUIT HOME RUN IDENTIFIER

RACEWAY, ABOVE FLOOR

COMBINATION STARTER/DISCONNECT WITH HOA

SWITCH-COORDINATE WITH MECH. CONTRACTOR.

SWITCH, DISCONNECT

PANELBOARD, SURFACE MOUNTED

PANELBOARD, RECESSED

MOTOR W/HORSEPOWER

GENERAL NOTES:

(APPLICABLE TO ALL ELECTRICAL SHEETS)

1. EQUIPMENT INTERRUPTING CAPACITIES SPECIFIED IN THE

CONTRACT DOCUMENTS ARE BASED UPON EQUIPMENT

CHARACTERISTICS AND IMPEDANCES SHOWN ON THE DRAWINGS.

IF ACTUAL INSTALLED EQUIPMENT DEVIATES FROM THESE

CHARACTERISTICS OR HAS LOWER IMPEDANCES. THE

CONTRACTOR SHALL INCREASE THE INTERRUPTING CAPACITIES

OF ALL ITEMS ON THE LOAD SIDE OF THE DEVIANT EQUIPMENT IN

DIRECT PROPORTION TO THE CHANGED CHARACTERISTICS.

INTERRUPTING CAPACITIES SHALL NOT BE REDUCED TO VALUES

LESS THAN THOSE REQUIRED BY THE CONTRACT DOCUMENTS.

2. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE

ELECTRICAL EQUIPMENT OR SYSTEMS PENETRATE FIRE RATED

WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL

LOCATIONS.

3. CONTROL WIRING P&ID'S FOR MECHANICAL EQUIPMENT ARE NOT

SHOWN ON THESE SHEETS.

4. RISER AND ONE-LINE DIAGRAMS ARE MEANT TO SHOW

ELECTRICAL RELATIONSHIPS FOR EQUIPMENT, AND THEREFORE

MAY NOT INCLUDE ALL REQUIRED EQUIPMENT DEVICES, AND

ACCESSORIES.

DESCRIPTIONSYMBOL

TRANSFORMER, POWER, KVA RATING, WINDING VOLTAGES AND

CONNECTIONS ARE SHOWN NEXT TO SYMBOL

ONE-LINE & CONTROL SCHEMATIC LEGEND

TRANSFORMER, CURRENT, TURNS RATIO, SHOWN NEXT TO

SYMBOL

GROUNDING CONNECTION. WHEN USED WITH TRANSFORMER

WINDING SYMBOL IT INDICATES A NEUTRAL GROUNDING

CONNECTION (ON SECONDARY SIDE ONLY)

GROUNDED WYE WINDING CONNECTION

DELTA CONNECTED

RELAY OR CONTACTOR CONTACTS

SEPARABLE (PLUG-IN) CONNECTOR OR CONNECTION FOR

DRAWOUT ASSEMBLIES

SCHEMATIC, CIRCUIT CONNECTIONS

CIRCUIT BREAKER, MOLDED CASE, TRIP CURRENT [A] AND

QUANTITY OF POLES [P] SHOWN NEXT TO SYMBOL

SWITCH, DISCONNECT, NON-FUSED, LOAD BREAK. CONTINUOUS

CURRENT RATING [A] AND QUANTITY OF POLES [P] SHOWN NEXT

TO SYMBOL

SWITCH, DISCONNECT, FUSED, LOAD BREAK. FUSE AMPERE

RATING [A] AND FUSE TYPE SHOWN NEXT TO SYMBOL

FUSE, AMPERE RATING [A] AND FUSE TYPE SHOWN NEXT TO

SYMBOL

MOTOR THERMAL OVERLOAD PROTECTOR

INTEGRAL PHOTOELECTRIC CELL AND RELAY (PHOTOCONTROL)

WATTHOUR METER

CONTACTOR OR RELAY COIL. LETTER(S) INSIDE OF SYMBOL

MATCH CONTACTS CONTROLLED

SURGE ARRESTER, VALVE TYPE ARRESTER KV RATING SHOWN

NEXT TO SYMBOL

EQUIPMENT ENCLOSURE

SYMBOL MODIFIERS

DESCRIPTIONSYMBOL

AUDIBLE AND VISUALAV

EXISTINGE

FIXED TEMPERATUREF

GROUND FAULT CIRCUIT INTERRUPTERGFI

NEWN

ITEM OR DEVICE RECESSED INTO MOUNTING SURFACER

RADIO FREQUENCYRF

WEATHERPROOFWP

DEVICE MOUNTED ABOVE COUNTER TOPAC

RECEPTACLE SERVING COMPUTER LOAD.C

GROUNDING LEGEND

DESCRIPTIONSYMBOL

CONDUCTOR, BARE, UON

GROUNDING CONNECTION, COUNTERPOISE TO GROUND ROD.

B

FIRE DETECTION SYMBOLS LEGEND

DESCRIPTIONSYMBOL

FIRE ALARM CONTROL PANEL

FIRE ALARM MANUAL PULL STATION

REMOTE ANNUNCIATOR PANEL

FIRE ALARM SIGNALING DEVICE, VISUAL ONLY

FIRE ALARM SIGNALING DEVICE, AUDIO/VISUAL, HORN AND

LIGHT (1 ASSEMBLY)

FIRE ALARM TRANSMITTER

FIRE HEAT DETECTOR, W/ TEMPERATURE OR RATE OF RISE.

SMOKE DETECTOR

SPRINKLER SYSTEM VALVE TAMPER SWITCH

SPRINKLER SYSTEM FLOW SWITCH

FIREMANS TELEPHONE

ELEVATOR RECALL

SCHEMATIC CIRCUIT

ELECTRICAL BUSS

CABLE OR WIRE

D

WYE CONNECTEDY

LIGHTING SYMBOLS LEGEND

SURFACE RECEPTACLE STRIP

RACEWAY, RISER UP

RACEWAY, RISER DOWN

THERMOSTAT BY MECHANICAL CONTRACTORT

POWER SYMBOLS LEGEND (CONTINUED)

DESCRIPTIONSYMBOL

RECEPTACLE, DUPLEX, SPECIAL PURPOSE

TELEPHONE RECEPTACLE, WALL MOUNTED

BELL

SPEAKER, CEILING MOUNTED

MICROPHONE, CEILING MOUNTED

SPEAKER CONTROL

SOUND CABINET

AUDIO/VISUAL PROJECTOR

CEILING FAN

CABLE TV OUTLET

EXHAUST FAN

SWITCH, OCCUPANCY SENSOR

WIREMOLD

240 VOLT 20 AMP RECEPTACLE

WATER PROOFWP

SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC

ONLY), DOUBLE-POLE, MOUNT 48" AFF

SWITCH, PULL SWITCH, CEILING MOUNTED

DESCRIPTIONSYMBOL

FLUORESCENT/LED, SURFACE OR PENDANT, RECESSED CEILING

MOUNTED

FLUORESCENT/LED, WALL MOUNTED

NIGHT LIGHT, FLUORESCENT/LED FIXTURE WITH INTERGAL

EMERGENCY BALLAST

CFL/HID/LED FIXTURE, RECESSED CEILING MOUNTED

CFL/HID/LED FIXTURE, WALL MOUNTED

EXIT SIGN, LIGHTED, SURFACE OR PENDANT, CEILING MOUNTED

W/LIGHTED FACE AND DIRECTIONAL ARROW.

EXIT SIGN, LIGHTED, WALL MOUNTED.

EMERGENCY LIGHT, 2 LAMPS, BATTERY POWERED

BRANCH CIRCUIT HOME RUN

CFL/HID/LED FIXTURE, SURFACE OR PENDANT

FIRE ALARM SIGNALING DEVICE, BELL

TRANSFORMER, DRY TYPE

NIGHT LIGHTNL

DATA RECEPTACLE, WALL MOUNTED

TELEPHONE/DATA RECEPTACLE, WALL MOUNTED

SURGE PROTECTION DEVICE

GROUND FAULT PROTECTION

VARIABLE FREQUENCY DRIVER

C

F

C

J

C J

W

S

S2

S3

S4

SDM

S

EL-5

T

M 1/20HP

S

M

TV

M

VFD

3P 1200A

M

C

SPD

GFP

FCP

F

FSA

FTR

135°

ESR

SYSTEM FURNITURE POINT IN WALL

FLOOR BOX WITH RECEPTACLE AND DATA OUTLET

SOS

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

0J

U N

TE

PA

-S R

M

C B

AR

BO

ZA

ED-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

EL

EC

TR

IC

AL

DE

MO

LIT

IO

N

PL

AN

07 09

ED-101

ELECTRICAL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

DEMOLITION GENERAL NOTES

A. ALL INFORMATION AND GENERAL ARRANGEMENTS SHOWN ON DRAWINGS ARE DIAGRAMMATIC

AND SHOW DESIGN INTENT INFORMATION ONLY. CONTRACTOR SHALL VERIFY ALL DIMENSIONS

AND EXISTING CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION.

B. CONTRACT DOCUMENTS WERE PREPARED FROM FIELD SURVEYS, THEY ARE NOT INTENDED TO

DEPICT UNFORESEEN CONDITIONS THAT MAY ADVERSELY AFFECT THE ELECTRICAL SYSTEM

DEMOLITION OR INSTALLATION. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS PRIOR TO STARTING ANY WORK.

C. THE CONTRACTOR SHALL VERIFY THE EXACT LOCATION AND QUANTITIES OF EXISTING

ELECTRICAL FIXTURES, EQUIPMENT, DEVICES, AND COMPONENTS AFFECTED BY THE PROJECT

WORKS INCLUDED BUT NOT LIMITED TO ELECTRICAL PANELBOARDS, DISCONNECTS,

RECEPTACLES, LIGHT FIXTURES, SWITCHES, CABLES, CONDUITS, AND RACEWAYS, ETC THAT

ARE AFFECTED BY THIS RENOVATION WORKS.

D. CONTRACTOR SHALL PROVIDE AN ADEQUATE CONSTRUCTION BARRIER TO PROTECT ALL

ADJACENT AREAS FROM DAMAGE DURING DEMOLITION AND CONSTRUCTION.

E. ANY ELECTRICAL FIXTURE, DEVICE, EQUIPMENT AND COMPONENTS ENCOUNTERED DURING

THE DEMOLITION IN AREAS AFFECTED BY THE RENOVATION WORK ( INCLUDING THOSE NOT

SHOWN ON THE DRAWINGS) SHALL BE PROTECTED FROM DAMAGE DURING THE DEMOLITION

AND CONSTRUCTION PHASES OF WORK.

F. ALL DEMOLISHED EQUIPMENT SHALL REMAIN PROPERTY OF THE US GOVERNMENT.

CONTRACTOR SHALL CONSULT WITH CONTRACTING OFFICER FOR DIRECTION ON PROPER

DISPOSAL OR STORAGE OF ALL DEMOLISHED EQUIPMENT.

G. COORDINATE ALL SHUTDOWNS AND REQUIRED WORK IN EACH SPACE WITH THE

USER/GOVERNMENT A MINIMUM OF FOUR WEEKS PRIOR TO STARTING ANY WORK.

H. COORDINATE WITH OTHER TRADES FOR ADDITIONAL DEMOLITION WORK REQUIRED WITHIN

RENOVATED AREA.

DEMOLITION KEYED NOTES

FEEDERS WILL BE DISCONNECTED, REMOVED AND REINSTALLED AT NEW LOCATION. NEW

TRENCH WILL BE REQUIRED. COORDINATE WITH POWER UTILITY COMPANY (OG&E) FOR

DE-ENERGIZE / DISCONNECTION OF THE CONDUCTORS.

THE DISCONNECT SWITCH DISC-7, CT ENCLOSURE AND ALL INTERIOR AND EXTERIOR

CONDUITS WILL BE REMOVED TO THE NEAREST JUNCTION BOX OR COUPLING INSIDE THE

BUILDING. CONDUCTORS MUST BE PROTECTED FROM PHYSICAL DAMAGE DURING

CONSTRUCTION PROJECT.

BRANCH CIRCUITS MUST BE LABELED AND REMOVED FOR FURTHER RECONNECTION TO

THE NEW PANELBOARDS.

EXISTING TIMERS AND/OR STARTERS REMAIN IN PLACE.

REMOVE EXISTING LIGHT FIXTURES IN THE OFFICE AND MECHANICAL ROOM.

CONDUIT AND CABLE FOR PANEL 6002-PNL-8, CONDUIT TO REMAIN ABANDONED IN PLACE,

CABLE TO BE CUT BACK FLUSH WITH FLOOR AND REMAIN ABANDONED IN PLACE.

B6002 KEYPLAN

PROJECT

LOCATION

3 4

OFFICE

MECH

DISC-7

FA

CU

FA

-6

PN

L-

PN

L-

PN

L-

9 3

TI

M

ER

-4

M O

N

AC

O

FA

-5

-P N

L-

CT

ENCLOSURE

XMFR-11 300kVA 208Y/120V, 3Ø

(3) SETS - (4) #350 MCM

3" PVC CONDUITEXISTING DISCONNECT

400A, 3Ø, 250V

FUSED 300A

(4) #350 MCM,

(1) #2 AWG, GND

3" EMT CONDUIT

OVERHEAD

(4) #4/0 AWG,

(1) #4 AWG, GND

2-1/2" CONDUIT

UNDERGROUND

TO 6006-PNL-1

0A

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

35% DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

TE

PA

-S R

M

C B

AR

BO

ZA

E-101

T

KI

SE

R

D S

H

AN

N O

N

En gr

\D es ig n\ s\

\2

1\

0_ Su pp or t\0 _3

_D ra w in gs \M od el

EL

EC

TR

IC

AL

P

LA

N

08 09

E-101

ELECTRICAL PLAN

SCALE: 1/4" = 1'-0"

GENERAL NOTES

A. CONTRACTOR MUST VERIFY THE ELECTRICAL FIELD REQUIREMENTS AND INSTALL THE NEW

EQUIPMENT IN A NEAT AND WORKMANSHIP MANNER PER CODE, UFC SPECIFICATIONS AND

TAFB ELECTRICAL STANDARDS.

B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY POWER OUTAGES, UTILITY

DISCONNECT OR UNDERGROUND EXCAVATION PRIOR TO CONSTRUCTION.

C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL MOUNTED DEVICES AND

CONTROL EQUIPMENT PRIOR INSTALLATION.

D. CONTRACTOR SHALL REPLACE EXISTING CONDUCTORS, CONDUITS, SUPPORTS, AND ANY

OTHER ASSOCIATED COMPONENT WITH WEATHERPROOF MATERIALS.

E. REFER TO MECHANICAL FOR ADDITIONAL INFORMATION. VERIFY ALL POWER CONNECTIONS

AND INSTALLATIONS REQUIREMENTS WITH MANUFACTURER'S PRIOR TO ROUGH-IN.

F. NEW CIRCUIT BREAKERS SHALL MATCH EXISTING MANUFACTURER BRAND AND SHORT

CIRCUIT RATINGS OF EXISTING PANELBOARDS.

G. CONTRACTOR SHALL TRACE ALL EXISTING TO REMAIN CIRCUITS. ANY UN-USED CIRCUITS

SHALL BE SWITCHED TO 'OFF' POSITION AND LABELED AS 'SPARE'. THE CIRCUIT

DIRECTORIES MUST BE UPDATED FOR ALL PANELS INVOLVED IN THE PROJECT.

KEYED NOTES

NEW FEEDER CONDUCTORS WILL BE INSTALLED BETWEEN UTILITY TRANSFORMER AND

NEW PANELBOARD. COORDINATE WITH POWER UTILITY COMPANY (OG&E) FOR

RECONNECTION.

CONTRACTOR WILL EXTEND THE BRANCH CIRCUITS AND RECONNECT THE 3" CONDUIT

THAT WAS REMOVED BACK TO NEAREST JUNCTION BOX OR COUPLING, SEE KEYED NOTE 2,

SHEET ED-101, TO NEW "MDP" PANELBOARD.

PANELBOARD MOUNTED ON CONCRETE PAD THAT FEEDS THE CARWASH IN THE NEW

ELECTRICAL ROOM.

THE NEW WIREWAY ELECTRICAL GUTTER WILL BE INSTALLED IN THE SAME LOCATION.

EXISTING CIRCUITS AND EQUIPMENT (TIMERS, STARTERS, DISCONNECTS) WILL BE

RECONNECTED.

CONTRACTOR MUST VERIFY FUNCTIONALITY OF THE EQUIPMENT WHEN PROJECT IS

COMPLETED (ROTATION AND CONTINUITY).

NEW LIGHTING FIXTURES WILL BE INSTALLED IN THE SAME LOCATION AS FIXTURES WITH

INTEGRAL BATTERY BACKUP WILL BE INSTALLED NEXT TO THE EXIT DOORS.

OVERHEAD SERVICE FOR PANELBOARD "B", CONTRACTOR TO PROVIDE AND INSTALL NEW

EMT CONDUIT AND CONDUCTORS AS NEEDED.

CONTRACTOR WILL PROVIDE AND INSTALL NEW BUILDING ELECTRICAL SYSTEM GROUNDING

BUS BAR PER CODE, SEE DETAIL "A" THIS SHEET.

B6002 KEYPLAN

PROJECT

LOCATION

4 5

3 52 5

5 7

10mm (3/8") MOUNTING

BOLT.

COPPER GROUND BUS

BAR

POLYESTER/FIBERGLASS

INSULATOR, 45mm (1-3/4") DIA.

x 50mm (2") LONG RED COLOR

DETAIL "A"

GROUND BUS BAR

SECTION "A-A"A

A

6mm x 50mm (1/4"x 2") WIDTH

COPPER GROUND BUS.

MOUNTED TO WALL WITH

INSULATORS.

2" (5

0m m)

FIELD DETERMINED 2" (50mm)

FRONT ELEVATION

MEN WOMEN

TOOL CRIB

ELEC

MECH

XMFR-11

FA

CU

FA

-6

9 3

TI

M

ER

-4

M O

N

AC

O

FA

-5

6002-PNL-8

3 SET (4) THW #350 MCM

3" PVC-80 SCH CONDUIT 300 kVA

208Y/120V 3Ø

MDP

20A/2P

GROUND

BAR

NEW GUTTER

EXISTING

(4) THHN #350MCM,

(1) THHN #2AWG, GND

3" EMT CONDUIT

OVERHEAD

6002-PNL-2

"A" PANEL 225A,

208Y/120V, 3Ø

NEW "MDP"

6002-PNL-1, 800A.,

208Y/120V, 3Ø

NEW (4) #4/0,

(1) #4 AWG GND.,

2-1/2" CONDUIT

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OKGENERAL NOTES

1. THE DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS

FOR FIELD OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS FOR ACCURACY.

2. CONTRACTOR MUST VERIFY THE ELECTRICAL FIELD REQUIREMENTS AND

WORKING SPACE REQUIRED PER CODE.

3. NEW ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND

WORKMANSHIP MANNER PER NFPA 70 UFC SPECIFICATIONS AND TINKER

ELECTRICAL STANDARDS.

35%

DESIGN

W W

YK

RE

PA

IR

/R

EP

LA

CE

M

AI

N

DI

ST

RI

BU

TI

ON

B

RA

NC

H

PA

NE

L B

OA

RD

S, B

JU

N

TE

PA

-S R

M

C B

AR

BO

ZA

E-601

S S

TA

R

R

C B

AR

BO

ZA

En gr

\D es ig n\

\2

5\

\0

_S up po rt\

0_ 3_

D ra w in gs \M od el

EL

EC

TR

IC

AL

D

EM

O

AN

D

NE

W

W

OR

K

ON

E-

LIN

E

DI

AG

RA

M

09 09

WH

100A/ 3P

OG&E UTILITY

400A DISCONNECT

3Ø, NEMA 3R

CAR

WASH

600A/3P

MAIN

20A/ 3P 300A/ 3P 125A/ 3P

SHOP MAIN

AIR COMPRESSOR

AHU

PANEL

400A

PNL-2 PNL-3 PNL-8

A/C

ONE-LINE DEMO OF EXISTING ELECTRICAL PANELS

800A/3P 208Y/120V

100A/ 3P

SHOP MAIN

AIR COMPRESSOR

PANEL PANEL PANEL

ONE-LINE CONSTRUCTION NEW ELECTRICAL PANELS

SPARE

WH

OG&E UTILITY

CAR

WASH

TOOL

CRIB

LIGHTING

FIRE ALARM

RECEPTACLES

125A/ 3P 20A/ 3P

XFMR-11

300kVA 208Y/120V 3Ø, 4W

6006-PNL-1

400A 208Y/120V, 3Ø, 4W.

PANEL

225A

6006-PNL- 2

225A 208Y/120V, 3Ø, 4W.

6002-PNL-1

600A, 208Y/120V 3Ø, 4W

150A/ 3P 200A/ 3P

XFMR-11

300kVA 208Y/120V 3Ø, 4W

NEW "MDP"

6002-PNL-1

800A 208Y/120V 3Ø, 4W

225A/ 3P225A/ 3P300A/ 3P

EXISTING

6006-PNL-1,

400A,208Y/120V 3Ø, 4W

PANEL EXISTING

6006-PNL-2,

225A,208Y/120V 3Ø, 4W

6002-PNL-2,

225A,208Y/120V 3Ø, 4W

EXISTING

6002-PNL-8,

225A,208Y/120V 3Ø, 4W

CIRCUIT FEEDER LEGEND

3 SET (4) THWN # 350 MCM

(1) 3" PVC-80SCH CONDUIT

1 SET (4) THHN # 350 MCM

(1) THHN # 2 AWG GND.

(1) 3" EMT CONDUIT

1 SET (4) THHN # 4/0 AWG

(1) THHN # 4 AWG GND.

(1) 2-1/2" EMT CONDUIT

1 SET (4) THHN # 4/0 AWG

(1) THHN # 4 AWG GND.

(1) 2-1/2" EMT CONDUIT

A

B C D

SPD

A/C AHU

N G

N

G

A =

B =

C =

D =

Sheets and Views
G101
02-050751-AD101-AD101.pdf
Sheets and Views
AD101
Plot View
03-050751-A101-A101.pdf
Sheets and Views
A101
Plot View
04-050751-MD101-MD101.pdf
Sheets and Views
MD101
Plot View
05-050751-M101-M101.pdf
Sheets and Views
M101
Plot View
06-050751-E001-E001.pdf
Sheets and Views
E001
Plot View
07-050751-ED101-ED101.pdf
Sheets and Views
ED101
Plot View
08-050751-E101-E101.pdf
Sheets and Views
E101
Plot View
09-050751-E601-E601.pdf
Sheets and Views
E601

File details come from the government source that posted it. Updated .