050751_Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- FA813726R0038
About this file
This document is a set of 35% design construction drawings for a repair and replacement project of the main distribution and branch panel boards in Building 6002 at Tinker Air Force Base, Oklahoma.
The project, identified as WWYK050751, involves demolition and reconstruction of electrical, mechanical, architectural, and related systems within a designated space in the facility. Key work includes: removal of existing wood doors, frames, and interior wall finishes; demolition of ACT ceilings, light fixtures, and GWB panels; removal of existing electrical panels, conduits, and branch circuits; disconnection and relocation of HVAC components including supply diffusers; and removal of existing sprinkler heads. New construction encompasses installation of new metal stud framing with Type X gypsum board, new electrical panelboards (6002-PNL-1 at 800A 208Y/120V 3Ø and related panels), new lighting fixtures with integral battery backup, new HVAC supply diffusers connected to existing ductwork, new sprinkler heads, and a new electrical system grounding bus bar. The primary transformer (XMFR-11) is a 300kVA 208Y/120V 3Ø unit with conductors running through 3" PVC Schedule 80 conduit. The project includes coordination with OG&E power utility for feeder disconnection and reconnection, field verification of existing conditions, and compliance with UFC specifications and Tinker AFB electrical standards. The design is dated 10 June 2025, with architectural, mechanical, and electrical disciplines represented across nine drawing sheets including demolition plans, new construction plans, and a one-line electrical diagram.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 050751_Compiled Pre-Bid RFIs_Gov Responses.pdf | ||
| CTR CD_Large Files_Att 3.zip | ZIP file | |
| CTR CD_Project Docs_Att 1.zip | ZIP file | |
| CTR CD_Base Facility Standards_Att 2.zip | ZIP file | |
| 050751_Section L_Instructions to Offerors.pdf | ||
| 050751_SOW.pdf | ||
| FA813726R0038_Formal RFP.pdf | ||
| 050751_Section M_Evaluation Factors for Award.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REVIEWED BY:
REVIEWED BY:
USING AGENCY:
ASBESTOS EVALUATION:
SAFETY:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
INDUSTRIAL HYGIENE:
DATE:
PROJECT DRAWING INDEX SIGNATURES
CORROSION ENGINEER: (CECE)
CE OPERATIONS: (CECO)
COMMUNICATIONS: (COMM)
CHIEF ENGINEER DIR: (CECE)
CHIEF DESIGN BRANCH: (CECE)
DESIGN MANAGER: (CECE)
ZONE MANAGER:
CONSTRUCTION MANAGEMENT: (CECE)
ENVIRONMENTAL:
BASE CIVIL ENGINEER: (CE)
FIRE DEPARTMENT: (CEFT)
GENERAL1. BRAND NAMES: REFERENCE TO SPECIFIC BRAND NAMES
OR COMPANIES IS FOR THE PURPOSE OF ESTABLISHING
MINIMUM QUALITY STANDARDS, IDENTIFICATION AND
GUIDANCE AND IS NOT INTENDED TO LIMIT SELECTION OF
OTHER MANUFACTURERS THAT ARE EQUAL OR EXCEED
THE SPECIFIED ITEMS IN TERMS OF PHYSICAL
PROPERTIES, INCLUDING, COLOR RANGE, FINISH,
DURABILITY, APPEARANCE, PERFORMANCE
CHARACTERISTICS, AND OTHER FACTORS. OTHER
PRODUCTS, MATERIALS, COLORS AND SYSTEMS, MAY BE
SUBMITTED FOR EVALUATION AND
APPROVAL/DISAPPROVAL BY THE CONTRACTING OFFICER.
2. THIS SET OF CONSTRUCTION DOCUMENTS SHALL BE
CONSIDERED AS A WHOLE IN THAT THE GENERAL
CONTRACTOR AND ALL THE SUB-CONTRACTORS ARE
RESPONSIBLE FOR THE INFORMATION PRESENTED ON ALL
SHEETS ON THE SET OF DRAWINGS AND ALL SECTIONS OF
THE SPECIFICATIONS.
3. THE CONTRACTOR IS RESPONSIBLE FOR ERECTING ALL
CONSTRUCTION FENCING AND BARRICADES AS REQUIRED
TO PROTECT CONSTRUCTION MATERIAL AND TO PREVENT
ANY UNAUTHORIZED PERSONNEL FROM ENTERING THE
CONSTRUCTION SITE.
4. ANY DAMAGE TO THE EXISTING GROUNDS OR FACILITIES
CAUSED BY CONSTRUCTION TRAFFIC OR ANY
CONSTRUCTION OPERATION SHALL BE REPAIRED OR
REPLACED BY THE CONTRACTOR TO MATCH OR EXCEED
EXISTING CONDITIONS AT NO ADDITIONAL COST TO THE
GOVERNMENT.
5. ALL WORK NOTED & LOCATED IN THESE DOCS SHALL BE
UNDERSTOOD BY THE CONTRACTOR TO REQUIRE ALL NEW
LABOR & MATERIALS UNLESS SPECIFICALLY NOTED TO BE
"EXISTING" OR "BY OTHERS".
WWYK050751
REPAIR/REPLACE MAIN
DISTRIBUTION & BRANCH
PANEL BOARDS, B6002
KEY PLAN:
GENERAL NOTES:
DISCIPLINE
PROJECT
LOCATION
1 G-101 GENERAL NOTES & VICINITY MAP
SHT.SEQ. SHEET TITLE
OF
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
0J
U N
TE
PA
-S R
M
C B
AR
BO
ZA
G-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
GE
NE
RA
L N
OT
ES
AN
D
VI
CI
NI
TY
M
AP
01 09
E-001 ELECTRICAL SYMBOLS AND ABBREVIATIONS
MD-101 MECHANICAL DEMOLITION PLAN
M-101 MECHANICAL PLAN5
ED-101 ELECTRICAL DEMOLITION PLAN
E-101 ELECTRICAL PLAN
AD-101 ARCHITECTURAL DEMOLITION PLAN
A-101 ARCHITECTURAL PLAN
E-601 ELECTRICAL DEMO AND NEW WORK ONE LINE DIAGRAM9
R U
N W
AY
8/
RUNWAY 13/31
TA
XI
W
AY
G
TAXIW
AY H
TAXIWAY B
TAXIWAY C
TAXIWAY M
TA
XI
W
AY
K
TAXIWAY E
TAXIWAY A
TA
XIW
AY E
E
TAXIWAY F
TAXIWAY D
TAXIWAY E
TAXIWAY J
TA
XI
W
AY
G
TAXIWAY A
TAXIW
AY H
TAXIWAY C
TAXIWAY D
TAXIWAY EE
TAXIWAY F
Elm C reek
Cr ut ch o
Cr ee k
Kuhlman Creek
Soldier Creek
Kuhlman Creek
Elm C reek
East Crutcho Creek
Elm Creek
El m
C re ek
Elm Creek
Elm C reek
Elm CreekElm C reek
Ku hlm an C re ek
Ea st
C ru tc ho
C re ek
Elm C ree k
West Crutcho Creek
W es t C ru tc ho
C re ek
Elm Creek
Soldier Creek
Elm C reek
Soldier CreekSoldier Creek
Ea st
C ru tc ho
C re ek
Elm Creek
Ea st
C ru tc ho
C re ek
East C rutcho C reek
Soldier Creek
So ld ie r C re ek
East C rutch o Creek
Soldier C reek
Soldier C reek
So ld ie r C re ek
East Crutcho Creek
416506
21222121
59475946
11401128
62540
61089
838837
62509
62528
62523
62501X
43774
62512
62516
62525
3592135916
99999
62543
32101
71086
53902
50414
55300
56601
930G
948-E
911-E
948-W
61019
911-W
33001
35913
62501
65672
930S
45134
43609
42116
62517
62515
62526
62527
62503
62513
61289
62542
62501OK
11289
62501
15930
15908
15904
15904
15908
15908
15904
15904
15908
62502
41046
62501
62514
62501
61018
71089
45134
96022
43120
41157
44045
45815
40592
43610
62522
41163
15930
15930
11824
Arnold St.
Ea st
D r.
SE 74th St
SE 59th St.
Ai r D ep ot
Patrol Rd.
St af f D r.
Reserve Rd.
5th Ave
"A " A ve
M un iti on s R d.
W ar eh ou se R d.
"B " A ve
7th St.
"H " A ve
M cN ar ne y Av e.
Mitchell Ave
Al er t R d.
Co ok
A ve
W es t D r.
"E "A ve
Extender Dr.
Sentry Rd.
34th St.
Twining Dr.
5th Ave.
Jo ne s
Globemaster Dr.
To w er R d.
Vanaman Rd.
In du st ria l B lv d.
So ut h St
1st St.
Do ol itt le
A ve
Pi cn ic R d.
Ja m es D r.
W ol fe D r.
Ai r D ep ot
Ai r D ep ot
"D " A ve
Perimeter Rd.
Rapcon Rd.
Reserve Rd
"L " A ve
Mercury Rd.
1st St.
Br ow n Dr
Po nd
R d.
O ld
A ir
De po t
Airey Dr.
General Motors Dr
Bradley Dr.
Entrance Road "C"
Entrance Road "A"
"C " A ve
"C " A ve
Vandenberg Dr.
Hi llt op R d.
Do rm ito ry
R d.
Dormitory Rd.
"M " A ve
Chennault Dr.
M itc he ll A ve
Spaatz Dr.
Co m m od ity D r.
Doolittle Ave
W hi te D r.
3rd Ave.
"D " D riv e
Ba ll
Pa rk
R d.
Joint STARS Dr.
Ai r D ep ot
B lv d
Turbine Dr. Turbine Dr.
Central Plant Dr.
6th St.6th St.
Falco n Dr.
Blackb ird
Dr.
W ey la nd
L oo p
Pegasus Dr.
Thunderbolt D r.
Munitions Rd. Ext.
Codding Rd.
Starlifter Dr.
Chidlaw Ct.
Co rs ai r D r.
Ra pt or Ct
N ig ht H aw k
Ct
Ph an to m
D r.
Fr an kl in
Po w er ho us e
Dr
Sk ym as te r D r.
Spaatz Ct.
La w re nc e
M un de ll
Nabors Dr.
In tr ud er
D r.
M cN ic kl e
M ill er D r.
Ta il
Fe at he r D r.
Holden Dr.
Ai re y C ir.
Smith Ct.
Ra ve n Ct
Air Dep ot Ai r D ep ot
Vanaman Rd.
1st St.
1st St.
TAXIWAY F
Ra w li ng s A ve
Mitc he ll A ve
Mercury Rd.
Ra ily ar d
Rd
He rc ul es
R d.
"F " A ve
Pr op ul sio n Dr
Stratofortress Dr.
96021
Arnold St.
Sentry Rd.
Arnold St.
TINKER AFB, OK
VICINITY MAP
GOTT
GATE
TINKER GATE
PASS & ID B6611
EAKER GATE
VANCE
GATE
HOPE
GATE
LEGEND
CONTRACTOR
HAUL ROUTE
TRUCK GATE
PIAZZA GATE
BASE CIVIL
ENGINEER
B400
BASE
OPERATIONS
B240
CONTRACTING
B3
HRUSKOCY
GATE
FIRE DEPARTMENT
B117
LIBERATOR GATE
LANCER
GATE
PROJECT
LOCATION
PROJECT
LOCATION
15904
15904
15904
15904
M cN ar ne y Av e.
Dormitory Rd.
Arnold St.
OF
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
0J
U N
TE
PA
-S R
M
M N
O
EL
AD-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
AR
CH
IT
EC
TU
RA
L
DE
MO
LIT
IO
N
PL
AN
02 09
AD-101
ARCHITECTURAL DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
DEMOLITION KEYED NOTES
DEMOLISH EXISTING WOOD DOOR, FRAME, AND WALL FOR INSTALLATION OF NEW DOOR.
DEMOLISH INNER LAYER OF GWB PANELS FROM CMU WALLS.
DEMOLISH FINISH FLOOR TO SUBSTRATE BELOW.
DEMOLISH ACT CEILING AND GRID INCLUDING LIGHT FIXTURES AND SUPPLY GRILL IN IT'S
ENTIRETY - REFER ELECTRICAL AND MECHANICAL.
DEMOLISH GWB PANEL FROM INTERIOR METAL LINER.
DEMOLISH GWB PANELS, ENCLOSURE FRAMING, AND SHELVING AT EXISTING CONDUIT
AND SAFETY SWITCH.
REMOVE EXISTING SPRINKLER HEAD FOR INSTALLATION OF NEW HEADS - REFER FIRE
PROTECTION SOW.
EXISTING CMU WALL EXTENDS ABOVE EXISTING CEILING HEIGHT AND IS NOT FULL HEIGHT.
(APPROXIMATELY 9'-0” +/- AFF)
EXISTING CMU WALL EXTENDS TO STRUCTURE (APPROXIMATELY 12'-6” +/- AFF)
EXISTING METAL PANEL ON METAL BUILDING STRUCTURE WITH INTERIOR METAL LINER -
EXTENDS TO STRUCTURE (APPROXIMATELY 12'-6” +/- AFF)
B6002 KEYPLAN
PROJECT
LOCATION
GENERAL NOTES
A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD
OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.
B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING
OUTAGES PRIOR TO CONSTRUCTION.
C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT
PRIOR TO INSTALLATION.
10 5
ABOVE
ABOVEOFFICE
MECH
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
JU
N
TE
PA
-S R
M
M N
O
EL
A-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
AR
CH
IT
EC
TU
AL
P
LA
N
03 09
A-101
ARCHITECTURAL PLAN
SCALE: 1/4" = 1'-0"
A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD
OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.
B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING
OUTAGES PRIOR TO CONSTRUCTION.
C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT
PRIOR TO INSTALLATION.
KEYED NOTES
B6002 KEYPLAN
PROJECT
LOCATION
1 4
93 7
PRIME NEW GWB WALLS. PAINT ELECTRICAL ROOM GWB WALLS WITH EPOXY PAINT.
PATCH AND REPAIR CMU WALLS TO RECEIVE PAINT. PAINT WITH EPOXY PAINT.
PATCH AND REPAIR METAL LINER TO RECEIVE PAINT. PAINT WITH EPOXY PAINT.
PREP CONCRETE FLOOR AND CLEAN TO BARE CONCRETE. APPLY DENSIFIER TO CONCRETE FLOOR
AS PER MANUFACTURER'S RECOMMENDATIONS.
NEW 3070 METAL DOOR AND FRAME. PAINT TO MATCH EXISTING ADJACENT DOOR FRAMES WITHIN
BUILDING.
PROVIDE METAL FRAMING TO STRUCTURE ABOVE: 5/8” TYPE X GWB (ON ONE SIDE) ON 6” METAL
FRAMING, 25 GA @ 16” O.C. WITH MINERAL WOOL BATT INSULATION.
PROVIDE NEW LIGHTING - REFER ELECTRICAL.
PROVIDE WALL MOUNTED SUPPLY GRILL - REFER MECHANICAL.
PROVIDE UP TURNED SPRINKLER HEADS - REFER FIRE PROTECTION SOW.
PROVIDE METAL FRAMING AT NEW DOOR LOCATION. 5/8" TYPE X GWB BOTH SIDES, ON 6" METAL
FRAMING. 25GA AT 16" O.C. WITH MINERAL WOOL BATT INSULATION. EXTEND FRAMING
AND GWB TO STRUCTURE ABOVE. PROVIDE DOUBLE STUDS AT EACH SIDE DOOR FRAME.
MEN WOMEN
TOOL CRIB
OFFICE
MECHELEC
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
0J
U N
TE
PA
-S R
M
Q G
AU
N
A
MD-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
ME
CH
AN
IC
AL
DE
MO
LIT
IO
N
PL
AN
04 09
MD-101
MECHANICAL DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
DEMOLITION KEYED NOTES
CONTRACTOR SHALL PERFORM A PRE-TAB OF THE EXISTING SYSTEM AND REPORT
EXISTING CONDITIONS TO GOVERNMENT.
DEMOLISH EXISTING SUPPLY DIFFUSER AND DISCONNECT FROM EXISTING DUCTWORK.
EXISTING SPRINKLER HEADS. REMOVE HEADS - REF FIRE PROTECTION SOW.
B6002 KEYPLAN
PROJECT
LOCATION
GENERAL NOTES
A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD
OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.
B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING
OUTAGES PRIOR TO CONSTRUCTION.
C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT
PRIOR TO INSTALLATION.
OFFICE
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
0J
U N
TE
PA
-S R
M
Q G
U
AN
A
M-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
ME
CH
AN
IC
AL
P
LA
N
05 09
M-101
MECHANICAL PLAN
SCALE: 1/4" = 1'-0"
GENERAL NOTES
A. THIS DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS FOR FIELD
OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS FOR ACCURACY.
B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY HEATING OR COOLING
OUTAGES PRIOR TO CONSTRUCTION.
C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL & DOOR MOUNTED EQUIPMENT
PRIOR TO INSTALLATION.
KEYED NOTES
PROVIDE & INSTALL NEW WALL MOUNTED SUPPLY AIR DIFFUSER AND CONNECT TO
EXISTING DUCTWORK.
CONTRACTOR SHALL PERFORM A FINAL TAB OF THE SYSTEM AND REPORT CONDITIONS TO
THE GOVERNMENT.
PROVIDE NEW UPRIGHT HEADS AT EXISTING SPRINKLER SYSTEM. REF FIRE PROTECTION
SOW.
B6002 KEYPLAN
PROJECT
LOCATION
1 2
MEN WOMEN
TOOL CRIB
ELEC
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
0J
U N
TE
PA
-S R
M
C B
AR
BO
ZA
E-001
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
EL
EC
TR
IC
AL
S
YM
BO
LS
AN
D
AB
BR
EV
IA
TI
ON
S
06 09
ELECTRICAL SYMBOLS LEGENDS AND ABBREVIATIONS
SYMBOL NOTES
1. THESE SYMBOLS APPLY TO THE ENTIRE SET OF CONTRACT DRAWINGS.
2. ALL SYMBOLS ARE NOT NECESSARILY USED IN THE DRAWINGS FOR THIS PROJECT. LISTING OF
SYMBOLS DOES NOT IMPLY THAT ALL SYMBOLS ARE USED IN THE CONTRACT DRAWINGS.
3. COLORS FOR ALL OUTLETS AND SWITCHES SHALL BE AS SHOWN ON ARCHITECTURAL PLANS.
4. ALL MOUNTING HEIGHTS SHOWN IN SYMBOL LEGEND SHALL BE AS PER TAS/ADA
REQUIREMENTS UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS.
5. BRANCH CIRCUIT NUMBERS MAY BE SHOWN NEXT TO SYMBOLS IN MULTIWIRE CIRCUITS.
6. EQUIPMENT IDENTIFIERS, MATCHING EQUIPMENT SCHEDULES, ARE DISPLAYED ATTACHED TO
SYMBOLS BY LEADER ARROWS, UON.
7. SYMBOL ORIENTATION DOES NOT IMPLY DEVICE OR EQUIPMENT ORIENTATION, UNLESS NOTED AS SUCH. SEE REFLECTED CEILING PLANS FOR LIGHT FIXTURE POSITIONS AND ORIENTATIONS.
8. SYMBOL SIZE DOES NOT IMPLY EQUIPMENT SIZE, UON.
9. LOWER CASE LETTER IN POSITION "X" INDICATES FIXTURES CONTROLLED BY SAME LETTER.
10. PLAN SYMBOLS USE THE FOLLOWING LINE TYPE CONVENTION AND ARE REPRESENTED AS
FOLLOWS:
LINETYPE, DENOTES EXISTING TO REMAIN
LINETYPE, DENOTES EXISTING TO BE DEMOLISHED
LINETYPE, DENOTES NEW U.G. OR CONCEALED CONSTRUCTION
LINETYPE, DENOTES NEW CONSTRUCTION
LINETYPE, DENOTES LIGHTING SWITCHLEG
A AMPERES OR TRIP
AMPERES
AC ALTERNATING CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC SYMMETRICAL AMPS
INTERRUPTING CAPACITY
AWG AMERICAN WIRE GAUGE
A/R AS REQUIRED
ARR. ARRESTOR
BLDG BUILDING
BRKT BRACKET
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CL CURRENT LIMITING
CO CONDUIT ONLY
CTL CONTROL
DC DIRECT CURRENT
D.T.C. DATA TERMINAL CABINET
EMCS ENERGY MONITORING AND
CONTROL SYSTEM
FACP FIRE ALARM CONTROL
PANEL
FT FOOT, FEET
GFCI GROUND FAULT CIRCUIT
INTERRUPTER, 5MA
PERSONNEL PROTECTION
UNLESS OTHERWISE NOTED.
GRD GROUND
HZ HERTZ
IAW IN ACCORDANCE WITH
IG ISOLATED GROUND
IN INCH, INCHES
IR INFRARED
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPS REACTIVE
KWH KILOWATT HOURS
L-L LINE TO LINE
L-N LINE TO NEUTRAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MTD MOUNTED
MTG MOUNTING
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NEUT NEUTRAL
N.O. NORMALLY OPEN
NLT NOT LESS THAN
NMT NOT MORE THAN
OH OVERHEAD
PAS PUBLIC ADDRESS SYSTEM
PE PHOTOELECTRIC
PH PHASE
PLCS PLACES
PNL PANELBOARD
PVC POLYVINYL CHLORIDE
ELECTRICAL RACEWAY
USED ONLY U.G., CARLON
OR EQUIVALENT
RC RIGID STEEL CONDUIT
REF REFERENCE
REQ'D REQUIRED
RGC RIGID GALVANIZED STEEL
CONDUIT
RM ROOM
RMC RIGID METALIC CONDUIT
SHT SHEET
SOB STANDOFF BRACKET
SPACE SPACE(S) ONLY (NO
BREAKER DEVICE)
SPARE SPARE BREAKER OR
DEVICE
SPDT SINGLE-POLE,
DOUBLE-THROW
SPECS CONTRACT SPECIFICATIONS
SPST SINGLE-POLE,
SINGLE-THROW
S/N SOLID NEUTRAL
TB TELEPHONE BACKBOARD
TYP TYPICAL
UG UNDERGROUND
UL LISTED BY UNDERWRITER'S
LABORATORIES
UON UNLESS OTHERWISE NOTED
V VOLTS
VA VOLT AMPERES
W WATT
WH WEATHERHEAD
W/ WITH
Ø PHASE
2W+G CIRCUIT TYPE
3W+G CIRCUIT TYPE
4W+G CIRCUIT TYPE
ABBREVIATIONS
POWER SYMBOLS LEGEND
DESCRIPTIONSYMBOL
RECEPTACLE, DUPLEX, 20A, 250V, GROUNDING 2W+G, NEMA
5-20R
RECEPTACLE, DUPLEX, FLOOR MOUNTED, FLUSH, 20A, 250V,
GROUNDING 2W+G NEMA 5-20R.
RECEPTACLE, DUPLEX, CEILING MOUNTED, 20A, 250V,
GROUNDING 2W+G, NEMA 5-20R
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, CLOCK
JUNCTION BOX, ABOVE CEILING
JUNCTION BOX, WALL MOUNTED, SERVING COMPUTER LOAD.
RECEPTACLE, DUPLEX, SERVING COMPUTER LOAD. 20A, 250V,
GROUNDING 2W+G RECEPTACLE, NEMA 5-20R
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), SINGLE-POLE, MOUNT 48" AFF
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), THREE-WAY, SPDT. MOUNT 48" AFF
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), FOUR-WAY, SPDT. MOUNT 48" AFF
SWITCH, DIMMER, 120V, 1500 WATT. MOUNT 48" AFF
BRANCH CIRCUIT HOME RUN WITH NEUTRAL, PHASE AND
EQUIPMENT GROUND RESPECTIVELY
BRANCH CIRCUIT HOME RUN IDENTIFIER
RACEWAY, ABOVE FLOOR
COMBINATION STARTER/DISCONNECT WITH HOA
SWITCH-COORDINATE WITH MECH. CONTRACTOR.
SWITCH, DISCONNECT
PANELBOARD, SURFACE MOUNTED
PANELBOARD, RECESSED
MOTOR W/HORSEPOWER
GENERAL NOTES:
(APPLICABLE TO ALL ELECTRICAL SHEETS)
1. EQUIPMENT INTERRUPTING CAPACITIES SPECIFIED IN THE
CONTRACT DOCUMENTS ARE BASED UPON EQUIPMENT
CHARACTERISTICS AND IMPEDANCES SHOWN ON THE DRAWINGS.
IF ACTUAL INSTALLED EQUIPMENT DEVIATES FROM THESE
CHARACTERISTICS OR HAS LOWER IMPEDANCES. THE
CONTRACTOR SHALL INCREASE THE INTERRUPTING CAPACITIES
OF ALL ITEMS ON THE LOAD SIDE OF THE DEVIANT EQUIPMENT IN
DIRECT PROPORTION TO THE CHANGED CHARACTERISTICS.
INTERRUPTING CAPACITIES SHALL NOT BE REDUCED TO VALUES
LESS THAN THOSE REQUIRED BY THE CONTRACT DOCUMENTS.
2. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE
ELECTRICAL EQUIPMENT OR SYSTEMS PENETRATE FIRE RATED
WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL
LOCATIONS.
3. CONTROL WIRING P&ID'S FOR MECHANICAL EQUIPMENT ARE NOT
SHOWN ON THESE SHEETS.
4. RISER AND ONE-LINE DIAGRAMS ARE MEANT TO SHOW
ELECTRICAL RELATIONSHIPS FOR EQUIPMENT, AND THEREFORE
MAY NOT INCLUDE ALL REQUIRED EQUIPMENT DEVICES, AND
ACCESSORIES.
DESCRIPTIONSYMBOL
TRANSFORMER, POWER, KVA RATING, WINDING VOLTAGES AND
CONNECTIONS ARE SHOWN NEXT TO SYMBOL
ONE-LINE & CONTROL SCHEMATIC LEGEND
TRANSFORMER, CURRENT, TURNS RATIO, SHOWN NEXT TO
SYMBOL
GROUNDING CONNECTION. WHEN USED WITH TRANSFORMER
WINDING SYMBOL IT INDICATES A NEUTRAL GROUNDING
CONNECTION (ON SECONDARY SIDE ONLY)
GROUNDED WYE WINDING CONNECTION
DELTA CONNECTED
RELAY OR CONTACTOR CONTACTS
SEPARABLE (PLUG-IN) CONNECTOR OR CONNECTION FOR
DRAWOUT ASSEMBLIES
SCHEMATIC, CIRCUIT CONNECTIONS
CIRCUIT BREAKER, MOLDED CASE, TRIP CURRENT [A] AND
QUANTITY OF POLES [P] SHOWN NEXT TO SYMBOL
SWITCH, DISCONNECT, NON-FUSED, LOAD BREAK. CONTINUOUS
CURRENT RATING [A] AND QUANTITY OF POLES [P] SHOWN NEXT
TO SYMBOL
SWITCH, DISCONNECT, FUSED, LOAD BREAK. FUSE AMPERE
RATING [A] AND FUSE TYPE SHOWN NEXT TO SYMBOL
FUSE, AMPERE RATING [A] AND FUSE TYPE SHOWN NEXT TO
SYMBOL
MOTOR THERMAL OVERLOAD PROTECTOR
INTEGRAL PHOTOELECTRIC CELL AND RELAY (PHOTOCONTROL)
WATTHOUR METER
CONTACTOR OR RELAY COIL. LETTER(S) INSIDE OF SYMBOL
MATCH CONTACTS CONTROLLED
SURGE ARRESTER, VALVE TYPE ARRESTER KV RATING SHOWN
NEXT TO SYMBOL
EQUIPMENT ENCLOSURE
SYMBOL MODIFIERS
DESCRIPTIONSYMBOL
AUDIBLE AND VISUALAV
EXISTINGE
FIXED TEMPERATUREF
GROUND FAULT CIRCUIT INTERRUPTERGFI
NEWN
ITEM OR DEVICE RECESSED INTO MOUNTING SURFACER
RADIO FREQUENCYRF
WEATHERPROOFWP
DEVICE MOUNTED ABOVE COUNTER TOPAC
RECEPTACLE SERVING COMPUTER LOAD.C
GROUNDING LEGEND
DESCRIPTIONSYMBOL
CONDUCTOR, BARE, UON
GROUNDING CONNECTION, COUNTERPOISE TO GROUND ROD.
B
FIRE DETECTION SYMBOLS LEGEND
DESCRIPTIONSYMBOL
FIRE ALARM CONTROL PANEL
FIRE ALARM MANUAL PULL STATION
REMOTE ANNUNCIATOR PANEL
FIRE ALARM SIGNALING DEVICE, VISUAL ONLY
FIRE ALARM SIGNALING DEVICE, AUDIO/VISUAL, HORN AND
LIGHT (1 ASSEMBLY)
FIRE ALARM TRANSMITTER
FIRE HEAT DETECTOR, W/ TEMPERATURE OR RATE OF RISE.
SMOKE DETECTOR
SPRINKLER SYSTEM VALVE TAMPER SWITCH
SPRINKLER SYSTEM FLOW SWITCH
FIREMANS TELEPHONE
ELEVATOR RECALL
SCHEMATIC CIRCUIT
ELECTRICAL BUSS
CABLE OR WIRE
D
WYE CONNECTEDY
LIGHTING SYMBOLS LEGEND
SURFACE RECEPTACLE STRIP
RACEWAY, RISER UP
RACEWAY, RISER DOWN
THERMOSTAT BY MECHANICAL CONTRACTORT
POWER SYMBOLS LEGEND (CONTINUED)
DESCRIPTIONSYMBOL
RECEPTACLE, DUPLEX, SPECIAL PURPOSE
TELEPHONE RECEPTACLE, WALL MOUNTED
BELL
SPEAKER, CEILING MOUNTED
MICROPHONE, CEILING MOUNTED
SPEAKER CONTROL
SOUND CABINET
AUDIO/VISUAL PROJECTOR
CEILING FAN
CABLE TV OUTLET
EXHAUST FAN
SWITCH, OCCUPANCY SENSOR
WIREMOLD
240 VOLT 20 AMP RECEPTACLE
WATER PROOFWP
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), DOUBLE-POLE, MOUNT 48" AFF
SWITCH, PULL SWITCH, CEILING MOUNTED
DESCRIPTIONSYMBOL
FLUORESCENT/LED, SURFACE OR PENDANT, RECESSED CEILING
MOUNTED
FLUORESCENT/LED, WALL MOUNTED
NIGHT LIGHT, FLUORESCENT/LED FIXTURE WITH INTERGAL
EMERGENCY BALLAST
CFL/HID/LED FIXTURE, RECESSED CEILING MOUNTED
CFL/HID/LED FIXTURE, WALL MOUNTED
EXIT SIGN, LIGHTED, SURFACE OR PENDANT, CEILING MOUNTED
W/LIGHTED FACE AND DIRECTIONAL ARROW.
EXIT SIGN, LIGHTED, WALL MOUNTED.
EMERGENCY LIGHT, 2 LAMPS, BATTERY POWERED
BRANCH CIRCUIT HOME RUN
CFL/HID/LED FIXTURE, SURFACE OR PENDANT
FIRE ALARM SIGNALING DEVICE, BELL
TRANSFORMER, DRY TYPE
NIGHT LIGHTNL
DATA RECEPTACLE, WALL MOUNTED
TELEPHONE/DATA RECEPTACLE, WALL MOUNTED
SURGE PROTECTION DEVICE
GROUND FAULT PROTECTION
VARIABLE FREQUENCY DRIVER
C
F
C
J
C J
W
S
S2
S3
S4
SDM
S
EL-5
T
M 1/20HP
S
M
TV
M
VFD
3P 1200A
M
C
SPD
GFP
FCP
F
FSA
FTR
135°
ESR
SYSTEM FURNITURE POINT IN WALL
FLOOR BOX WITH RECEPTACLE AND DATA OUTLET
SOS
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
0J
U N
TE
PA
-S R
M
C B
AR
BO
ZA
ED-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
EL
EC
TR
IC
AL
DE
MO
LIT
IO
N
PL
AN
07 09
ED-101
ELECTRICAL DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
DEMOLITION GENERAL NOTES
A. ALL INFORMATION AND GENERAL ARRANGEMENTS SHOWN ON DRAWINGS ARE DIAGRAMMATIC
AND SHOW DESIGN INTENT INFORMATION ONLY. CONTRACTOR SHALL VERIFY ALL DIMENSIONS
AND EXISTING CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION.
B. CONTRACT DOCUMENTS WERE PREPARED FROM FIELD SURVEYS, THEY ARE NOT INTENDED TO
DEPICT UNFORESEEN CONDITIONS THAT MAY ADVERSELY AFFECT THE ELECTRICAL SYSTEM
DEMOLITION OR INSTALLATION. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS PRIOR TO STARTING ANY WORK.
C. THE CONTRACTOR SHALL VERIFY THE EXACT LOCATION AND QUANTITIES OF EXISTING
ELECTRICAL FIXTURES, EQUIPMENT, DEVICES, AND COMPONENTS AFFECTED BY THE PROJECT
WORKS INCLUDED BUT NOT LIMITED TO ELECTRICAL PANELBOARDS, DISCONNECTS,
RECEPTACLES, LIGHT FIXTURES, SWITCHES, CABLES, CONDUITS, AND RACEWAYS, ETC THAT
ARE AFFECTED BY THIS RENOVATION WORKS.
D. CONTRACTOR SHALL PROVIDE AN ADEQUATE CONSTRUCTION BARRIER TO PROTECT ALL
ADJACENT AREAS FROM DAMAGE DURING DEMOLITION AND CONSTRUCTION.
E. ANY ELECTRICAL FIXTURE, DEVICE, EQUIPMENT AND COMPONENTS ENCOUNTERED DURING
THE DEMOLITION IN AREAS AFFECTED BY THE RENOVATION WORK ( INCLUDING THOSE NOT
SHOWN ON THE DRAWINGS) SHALL BE PROTECTED FROM DAMAGE DURING THE DEMOLITION
AND CONSTRUCTION PHASES OF WORK.
F. ALL DEMOLISHED EQUIPMENT SHALL REMAIN PROPERTY OF THE US GOVERNMENT.
CONTRACTOR SHALL CONSULT WITH CONTRACTING OFFICER FOR DIRECTION ON PROPER
DISPOSAL OR STORAGE OF ALL DEMOLISHED EQUIPMENT.
G. COORDINATE ALL SHUTDOWNS AND REQUIRED WORK IN EACH SPACE WITH THE
USER/GOVERNMENT A MINIMUM OF FOUR WEEKS PRIOR TO STARTING ANY WORK.
H. COORDINATE WITH OTHER TRADES FOR ADDITIONAL DEMOLITION WORK REQUIRED WITHIN
RENOVATED AREA.
DEMOLITION KEYED NOTES
FEEDERS WILL BE DISCONNECTED, REMOVED AND REINSTALLED AT NEW LOCATION. NEW
TRENCH WILL BE REQUIRED. COORDINATE WITH POWER UTILITY COMPANY (OG&E) FOR
DE-ENERGIZE / DISCONNECTION OF THE CONDUCTORS.
THE DISCONNECT SWITCH DISC-7, CT ENCLOSURE AND ALL INTERIOR AND EXTERIOR
CONDUITS WILL BE REMOVED TO THE NEAREST JUNCTION BOX OR COUPLING INSIDE THE
BUILDING. CONDUCTORS MUST BE PROTECTED FROM PHYSICAL DAMAGE DURING
CONSTRUCTION PROJECT.
BRANCH CIRCUITS MUST BE LABELED AND REMOVED FOR FURTHER RECONNECTION TO
THE NEW PANELBOARDS.
EXISTING TIMERS AND/OR STARTERS REMAIN IN PLACE.
REMOVE EXISTING LIGHT FIXTURES IN THE OFFICE AND MECHANICAL ROOM.
CONDUIT AND CABLE FOR PANEL 6002-PNL-8, CONDUIT TO REMAIN ABANDONED IN PLACE,
CABLE TO BE CUT BACK FLUSH WITH FLOOR AND REMAIN ABANDONED IN PLACE.
B6002 KEYPLAN
PROJECT
LOCATION
3 4
OFFICE
MECH
DISC-7
FA
CU
FA
-6
PN
L-
PN
L-
PN
L-
9 3
TI
M
ER
-4
M O
N
AC
O
FA
-5
-P N
L-
CT
ENCLOSURE
XMFR-11 300kVA 208Y/120V, 3Ø
(3) SETS - (4) #350 MCM
3" PVC CONDUITEXISTING DISCONNECT
400A, 3Ø, 250V
FUSED 300A
(4) #350 MCM,
(1) #2 AWG, GND
3" EMT CONDUIT
OVERHEAD
(4) #4/0 AWG,
(1) #4 AWG, GND
2-1/2" CONDUIT
UNDERGROUND
TO 6006-PNL-1
0A
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
35% DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
TE
PA
-S R
M
C B
AR
BO
ZA
E-101
T
KI
SE
R
D S
H
AN
N O
N
En gr
\D es ig n\ s\
\2
1\
0_ Su pp or t\0 _3
_D ra w in gs \M od el
EL
EC
TR
IC
AL
P
LA
N
08 09
E-101
ELECTRICAL PLAN
SCALE: 1/4" = 1'-0"
GENERAL NOTES
A. CONTRACTOR MUST VERIFY THE ELECTRICAL FIELD REQUIREMENTS AND INSTALL THE NEW
EQUIPMENT IN A NEAT AND WORKMANSHIP MANNER PER CODE, UFC SPECIFICATIONS AND
TAFB ELECTRICAL STANDARDS.
B. COORDINATE WITH USERS AND/OR BUILDING MANAGER FOR ANY POWER OUTAGES, UTILITY
DISCONNECT OR UNDERGROUND EXCAVATION PRIOR TO CONSTRUCTION.
C. COORDINATE FINAL LOCATION / MOUNTING HEIGHT OF WALL MOUNTED DEVICES AND
CONTROL EQUIPMENT PRIOR INSTALLATION.
D. CONTRACTOR SHALL REPLACE EXISTING CONDUCTORS, CONDUITS, SUPPORTS, AND ANY
OTHER ASSOCIATED COMPONENT WITH WEATHERPROOF MATERIALS.
E. REFER TO MECHANICAL FOR ADDITIONAL INFORMATION. VERIFY ALL POWER CONNECTIONS
AND INSTALLATIONS REQUIREMENTS WITH MANUFACTURER'S PRIOR TO ROUGH-IN.
F. NEW CIRCUIT BREAKERS SHALL MATCH EXISTING MANUFACTURER BRAND AND SHORT
CIRCUIT RATINGS OF EXISTING PANELBOARDS.
G. CONTRACTOR SHALL TRACE ALL EXISTING TO REMAIN CIRCUITS. ANY UN-USED CIRCUITS
SHALL BE SWITCHED TO 'OFF' POSITION AND LABELED AS 'SPARE'. THE CIRCUIT
DIRECTORIES MUST BE UPDATED FOR ALL PANELS INVOLVED IN THE PROJECT.
KEYED NOTES
NEW FEEDER CONDUCTORS WILL BE INSTALLED BETWEEN UTILITY TRANSFORMER AND
NEW PANELBOARD. COORDINATE WITH POWER UTILITY COMPANY (OG&E) FOR
RECONNECTION.
CONTRACTOR WILL EXTEND THE BRANCH CIRCUITS AND RECONNECT THE 3" CONDUIT
THAT WAS REMOVED BACK TO NEAREST JUNCTION BOX OR COUPLING, SEE KEYED NOTE 2,
SHEET ED-101, TO NEW "MDP" PANELBOARD.
PANELBOARD MOUNTED ON CONCRETE PAD THAT FEEDS THE CARWASH IN THE NEW
ELECTRICAL ROOM.
THE NEW WIREWAY ELECTRICAL GUTTER WILL BE INSTALLED IN THE SAME LOCATION.
EXISTING CIRCUITS AND EQUIPMENT (TIMERS, STARTERS, DISCONNECTS) WILL BE
RECONNECTED.
CONTRACTOR MUST VERIFY FUNCTIONALITY OF THE EQUIPMENT WHEN PROJECT IS
COMPLETED (ROTATION AND CONTINUITY).
NEW LIGHTING FIXTURES WILL BE INSTALLED IN THE SAME LOCATION AS FIXTURES WITH
INTEGRAL BATTERY BACKUP WILL BE INSTALLED NEXT TO THE EXIT DOORS.
OVERHEAD SERVICE FOR PANELBOARD "B", CONTRACTOR TO PROVIDE AND INSTALL NEW
EMT CONDUIT AND CONDUCTORS AS NEEDED.
CONTRACTOR WILL PROVIDE AND INSTALL NEW BUILDING ELECTRICAL SYSTEM GROUNDING
BUS BAR PER CODE, SEE DETAIL "A" THIS SHEET.
B6002 KEYPLAN
PROJECT
LOCATION
4 5
3 52 5
5 7
10mm (3/8") MOUNTING
BOLT.
COPPER GROUND BUS
BAR
POLYESTER/FIBERGLASS
INSULATOR, 45mm (1-3/4") DIA.
x 50mm (2") LONG RED COLOR
DETAIL "A"
GROUND BUS BAR
SECTION "A-A"A
A
6mm x 50mm (1/4"x 2") WIDTH
COPPER GROUND BUS.
MOUNTED TO WALL WITH
INSULATORS.
2" (5
0m m)
FIELD DETERMINED 2" (50mm)
FRONT ELEVATION
MEN WOMEN
TOOL CRIB
ELEC
MECH
XMFR-11
FA
CU
FA
-6
9 3
TI
M
ER
-4
M O
N
AC
O
FA
-5
6002-PNL-8
3 SET (4) THW #350 MCM
3" PVC-80 SCH CONDUIT 300 kVA
208Y/120V 3Ø
MDP
20A/2P
GROUND
BAR
NEW GUTTER
EXISTING
(4) THHN #350MCM,
(1) THHN #2AWG, GND
3" EMT CONDUIT
OVERHEAD
6002-PNL-2
"A" PANEL 225A,
208Y/120V, 3Ø
NEW "MDP"
6002-PNL-1, 800A.,
208Y/120V, 3Ø
NEW (4) #4/0,
(1) #4 AWG GND.,
2-1/2" CONDUIT
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET
SHEET NUMBER
SH
EE
T
TI
TL
E
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OKGENERAL NOTES
1. THE DRAWING WAS PREPARED FROM EXISTING DRAWINGS AND LIMITED ACCESS
FOR FIELD OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS FOR ACCURACY.
2. CONTRACTOR MUST VERIFY THE ELECTRICAL FIELD REQUIREMENTS AND
WORKING SPACE REQUIRED PER CODE.
3. NEW ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND
WORKMANSHIP MANNER PER NFPA 70 UFC SPECIFICATIONS AND TINKER
ELECTRICAL STANDARDS.
35%
DESIGN
W W
YK
RE
PA
IR
/R
EP
LA
CE
M
AI
N
DI
ST
RI
BU
TI
ON
B
RA
NC
H
PA
NE
L B
OA
RD
S, B
JU
N
TE
PA
-S R
M
C B
AR
BO
ZA
E-601
S S
TA
R
R
C B
AR
BO
ZA
En gr
\D es ig n\
\2
5\
\0
_S up po rt\
0_ 3_
D ra w in gs \M od el
EL
EC
TR
IC
AL
D
EM
O
AN
D
NE
W
W
OR
K
ON
E-
LIN
E
DI
AG
RA
M
09 09
WH
100A/ 3P
OG&E UTILITY
400A DISCONNECT
3Ø, NEMA 3R
CAR
WASH
600A/3P
MAIN
20A/ 3P 300A/ 3P 125A/ 3P
SHOP MAIN
AIR COMPRESSOR
AHU
PANEL
400A
PNL-2 PNL-3 PNL-8
A/C
ONE-LINE DEMO OF EXISTING ELECTRICAL PANELS
800A/3P 208Y/120V
100A/ 3P
SHOP MAIN
AIR COMPRESSOR
PANEL PANEL PANEL
ONE-LINE CONSTRUCTION NEW ELECTRICAL PANELS
SPARE
WH
OG&E UTILITY
CAR
WASH
TOOL
CRIB
LIGHTING
FIRE ALARM
RECEPTACLES
125A/ 3P 20A/ 3P
XFMR-11
300kVA 208Y/120V 3Ø, 4W
6006-PNL-1
400A 208Y/120V, 3Ø, 4W.
PANEL
225A
6006-PNL- 2
225A 208Y/120V, 3Ø, 4W.
6002-PNL-1
600A, 208Y/120V 3Ø, 4W
150A/ 3P 200A/ 3P
XFMR-11
300kVA 208Y/120V 3Ø, 4W
NEW "MDP"
6002-PNL-1
800A 208Y/120V 3Ø, 4W
225A/ 3P225A/ 3P300A/ 3P
EXISTING
6006-PNL-1,
400A,208Y/120V 3Ø, 4W
PANEL EXISTING
6006-PNL-2,
225A,208Y/120V 3Ø, 4W
6002-PNL-2,
225A,208Y/120V 3Ø, 4W
EXISTING
6002-PNL-8,
225A,208Y/120V 3Ø, 4W
CIRCUIT FEEDER LEGEND
3 SET (4) THWN # 350 MCM
(1) 3" PVC-80SCH CONDUIT
1 SET (4) THHN # 350 MCM
(1) THHN # 2 AWG GND.
(1) 3" EMT CONDUIT
1 SET (4) THHN # 4/0 AWG
(1) THHN # 4 AWG GND.
(1) 2-1/2" EMT CONDUIT
1 SET (4) THHN # 4/0 AWG
(1) THHN # 4 AWG GND.
(1) 2-1/2" EMT CONDUIT
A
B C D
SPD
A/C AHU
N G
N
G
A =
B =
C =
D =
| Sheets and Views |
| G101 |
| 02-050751-AD101-AD101.pdf |
| Sheets and Views |
| AD101 |
| Plot View |
| 03-050751-A101-A101.pdf |
| Sheets and Views |
| A101 |
| Plot View |
| 04-050751-MD101-MD101.pdf |
| Sheets and Views |
| MD101 |
| Plot View |
| 05-050751-M101-M101.pdf |
| Sheets and Views |
| M101 |
| Plot View |
| 06-050751-E001-E001.pdf |
| Sheets and Views |
| E001 |
| Plot View |
| 07-050751-ED101-ED101.pdf |
| Sheets and Views |
| ED101 |
| Plot View |
| 08-050751-E101-E101.pdf |
| Sheets and Views |
| E101 |
| Plot View |
| 09-050751-E601-E601.pdf |
| Sheets and Views |
| E601 |
File details come from the government source that posted it. Updated .