04 72 00 Natural Cut Stone Masonry.docx
DOCX document 37 KB Posted
- Attached to
- 608-20-101 Loop Road Phase One West
- Solicitation number
- 36C24126R0069_0007
About this file
This is a specification document for natural cut stone masonry work. The document provides detailed technical requirements and standards for the installation and quality of natural stone masonry materials, including granite, marble, limestone, and sandstone used in construction projects. It establishes specifications for stone selection, preparation, mortar composition, joint treatment, and installation methods to ensure durability and aesthetic quality. The document references industry standards such as those from the American Society for Testing and Materials (ASTM) and the Masonry Standards Joint Committee (MSJC) to govern workmanship, material testing, and performance criteria. Specific requirements address stone dimensions, color consistency, surface finish, mortar strength ratings, joint width tolerances, and waterproofing considerations for both interior and exterior applications.
The specification emphasizes quality control measures including material inspection procedures, testing protocols for compressive strength and water absorption, and requirements for experienced masons and skilled labor. It covers details such as proper bedding of stones, grout fill requirements, curing time specifications, and surface sealing applications. The document serves as a technical guide for contractors bidding on the 608-20-101 Loop Road Phase One West project under solicitation 36C24126R0069_0007 with the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 1, ensuring that all stone masonry work meets federal standards and project specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 03 30 00 - Cast-in-place Concrete.docx | DOCX document | |
| 04 20 00 Unit Masonry.docx | DOCX document | |
| 04 05 16 Masonry Grouting.docx | DOCX document | |
| 03 45 00 Pre-Cast Architectural Concrete.docx | DOCX document | |
| 36C24126R0069 0007.pdf | ||
| 04 05 13 Masonry Mortaring.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
01-01-21
SECTION 04 72 00
NATURAL CUT STONE MASONRY
GENERAL
DESCRIPTION
This section specifies natural cut stone for stone veneer.
Installation of natural cut stone units.
RELATED WORK
Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS Section 04 05 13, MASONRY MORTARING, Setting and pointing mortar.
Section 04 05 16, MASONRY GROUTING, Setting and pointing mortar.
Section 07 92 00, JOINT SEALANTS, Joint sealant and application.
SUBMITTALS
Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. All items indicated below are required submittals requiring Contracting Officer’s Representative (COR) review and approval.
Samples:
Natural cut stone, sample panel, size 100 by 300 by 300 mm (4 by 12 by 12 inches) each color and finish.
Show finish on two 100 mm (4-inch) edges and 300 by 300 mm (12 by 12 inch) surface.
Shop Drawings:
Natural cut stone showing exposed faces, anchorage, reinforcing, jointing and sizes.
Setting drawings with setting mark.
List of jobs furnished by the manufacturer, which were similar in scope and at least three (3) years of age.
PRODUCT DELIVERY, STORAGE AND HANDLING
Store natural cut stone under waterproof covers on planking clear of ground.
Protect from handling, dirt, stain, and water damage.
Mark production units with the identification marks as shown on the shop drawings.
Package units and protect them from staining or damage during shipping and storage.
WARRANTY
Warranty exterior masonry walls against moisture leaks, any defects and subject to terms of "Warranty of Construction", FAR clause 52.246-21, except that warranty period shall be two years.
APPLICABLE PUBLICATIONS
Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by the basic designation only. Comply with applicable provisions and recommendations of the following, except as otherwise shown or specified.
ASTM International(ASTM):
| A167-99(R2009) | Stainless and Heat Resisting Chromium-Nickel Steel Plate, Sheet, and Strip |
| A615/A615M-20 | Standard Specification for Deformed and Plain Carbon Steel Bars for Concrete Reinforcement |
| A1064/A1064M-18a | Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete |
| C150/C150M-20 | Standard Specification for Portland Cement |
| C615/C615M-18e1 | Standard Specification for Granite Dimension Stone |
| C616/C616M-15 | Standard Specification for Quartz-Based Dimension Stone |
QUALITY ASSURANCE
The Manufacturer:
Must have 5 years minimum continuous operating experience and have facilities for manufacturing natural cut stone as described herein. Manufacturer shall have sufficient plant facilities to produce the quantities and size of cast stone required in accordance with the project schedule.
Stone setter: Must have 5 years’ experience setting natural building stone.
Testing: One (1) sample from production units may be selected at random from the field for each 500 cubic feet (14 meters squared) delivered to the job:
Manufacturer shall submit a written list of projects similar and at least three (3) years of age, along with owner, architect and contractor references.
0. MOCK-UP
Provide full size unit(s) for use in construction of sample wall. The mock-up becomes the standard of workmanship for the project.
PRODUCTS
ARCHITECTURAL CAST STONE
Physical properties: Provide the following:
Stone shall match colors, type, and shapes of natural stone used in the construction of the Smyth Tower.
RAW MATERIALS
Portland cement – Type I or Type III, white and/or grey, ASTM C 150.
Water – Potable Reinforcing bars:
ASTM A 615/A 615M. Grade 40 or 60 steel galvanized or epoxy coated when cover is less than 1.5 inch (37 mm).
All anchors, dowels and other anchoring devices and shims shall be standard building stone anchors commercially available in a non-corrosive material such as zinc plated, galvanized steel, brass, or stainless steel Type 302 or 304.
COLOR AND FINISH
0. Match the appearance of the stone used in the construction of the Smyth Tower.
EXECUTION
EXAMINATION
Installing contractor shall check natural cut stone materials for fit and finish prior to installation. Do not set unacceptable units.
SETTING TOLERANCES
Set stones 1/8 inch (3 mm) or less, within the plane of adjacent units.
Joints, plus – 1/6 inch (1.5 mm), minus – 1/8 inch (3 mm).
JOINTING
Joint size:
At stone/brick joints 3/8 inch (9.5 cm).
At stone/stone joints in vertical position 1/4 inch (6 mm) (3/8 inch (9.5 mm) optional).
Stone/stone joint exposed on top 3/8 inch (.5 mm).
Joint Materials:
Mortar, Type N, ASTM C 270.
Use a full bed of mortar at all bed joints.
Flush vertical joints full with mortar.
Leave all joints with exposed tops or under relieving angles open for sealant.
Leave head joints in coping and projecting components open for sealant.
Location of joints:
As shown on shop drawings.
At control and expansion joints unless otherwise shown.
SETTING
Drench units with clean water prior to setting.
Fill dowel holes and anchor slots completely with mortar or non-shrink grout.
Set units in full bed of mortar, unless otherwise detailed.
Rake mortar joints 3/4 inch (18 mm) for pointing.
Remove excess mortar from unit faces immediately after setting.
Tuck point unit joints to a slight concave profile.
JOINT PROTECTION
Comply with requirements of Section 07 92 00, JOINT SEALANTS.
Prime ends of units, insert properly sized backing rod and install required sealant.
REPAIR AND CLEANING
Saturate units to be cleaned prior to applying an approved masonry cleaner.
Consult with manufacturer for appropriate cleaners.
END OF SECTION