03 30 00 - Cast-in-place Concrete.docx

DOCX document 57 KB Posted

Attached to
608-20-101 Loop Road Phase One West
Solicitation number
36C24126R0069_0007
Issued by

About this file

This is a technical specification document for cast-in-place concrete work as part of the 608-20-101 Loop Road Phase One West project for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The document establishes the standards, materials, and construction methods required for concrete placement activities within this infrastructure improvement project. It defines concrete mix design requirements, placement procedures, curing methods, quality control standards, and acceptance criteria to ensure structural integrity and durability of the concrete components. The specifications cover aspects such as concrete strength requirements, reinforcement placement, formwork standards, surface finishing, testing protocols, and inspection procedures that contractors must follow during the cast-in-place concrete construction phase. This specification document serves as a binding technical requirement for bidders responding to Amendment 7 of the solicitation and will govern concrete-related work performance and acceptance under the resulting contract award.

View the file

Other files

File Type Posted
04 72 00 Natural Cut Stone Masonry.docx DOCX document
04 05 13 Masonry Mortaring.docx DOCX document
04 20 00 Unit Masonry.docx DOCX document
04 05 16 Masonry Grouting.docx DOCX document
03 45 00 Pre-Cast Architectural Concrete.docx DOCX document
36C24126R0069 0007.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01-01-21

12-01-15

SECTION 03 30 00

CAST-IN-PLACE CONCRETE

PART 1 - GENERAL

DESCRIPTION

This section specifies cast-in-place structural concrete and materials and mixes for other concrete.

RELATED WORK

Section 01 45 29, TESTING LABORATORY SERVICES: Materials testing and inspection during construction.

Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS Section 32 05 23, CEMENT AND CONCRETE FOR EXTERIOR IMPROVEMENTS: Concrete roads, walks, and similar exterior site work.

TESTING AGENCY FOR CONCRETE MIX DESIGN

Testing agency for the trial concrete mix design retained and reimbursed by the Contractor and approved by COR. For all other testing, refer to Section 01 45 29 Testing Laboratory Services.

Testing agency maintaining active participation in Program of Cement and Concrete Reference Laboratory (CCRL) of National Institute of Standards and Technology.

Testing agency shall furnish equipment and qualified technicians to establish proportions of ingredients for concrete mixes.

TOLERANCES

Formwork: ACI 117, except the elevation tolerance of formed surfaces before removal of shores is +0 mm (+0 inch) and -20 mm (-3/4 inch).

Reinforcement Fabricating and Placing: ACI 117, except that fabrication tolerance for bar sizes Nos. 10, 13, and 16 (Nos. 3, 4, and 5) (Tolerance Symbol 1 in Fig. 2.1(a), ACI, 117) used as column ties or stirrups is +0 mm (+0 inch) and -13 mm (-1/2 inch) where gross bar length is less than 3600 mm (12 feet), or +0 mm (+0 inch) and -20 mm (-3/4 inch) where gross bar length is 3600 mm (12 feet) or more.

Cross-Sectional Dimension: ACI 117, except tolerance for thickness of slabs 12 inches or less is +20 mm (+3/4 inch) and - 6 mm (-1/4 inch). Tolerance of thickness of beams more than 300 mm (12 inch) but less than 900 mm (3 feet) is +20 mm (+3/4 inch) and -10 mm (-3/8 inch).

Slab Finishes: ACI 117, Section 4.5.6, F-number method in accordance with ASTM E1155, except as follows:

Test entire slab surface, including those areas within 600 mm (2 feet) of construction joints and vertical elements that project through slab surface.

Maximum elevation change which may occur within 600 mm (2 feet) of any column or wall element is 6 mm (0.25 inches).

Allow sample measurement lines that are perpendicular to construction joints to extend past joint into previous placement no further than 1500 mm (5 feet).

REGULATORY REQUIREMENTS

ACI SP-66 – ACI Detailing Manual.

ACI 318 ‑ Building Code Requirements for Reinforced Concrete.

ACI 301 – Standard Specifications for Structural Concrete.

SUBMITTALS

Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. All items indicated below are required submittals requiring Contracting Officer’s Representative (COR) review and approval.

Shop Drawings: Reinforcing steel: Complete shop drawings Mill Test Reports:

Reinforcing Steel.

Cement.

Manufacturer's Certificates:

Abrasive aggregate.

Lightweight aggregate for structural concrete.

Air‑entraining admixture.

Chemical admixtures, including chloride ion content.

Waterproof paper for curing concrete.

Liquid membrane‑forming compounds for curing concrete.

Non‑shrinking grout.

Liquid hardener.

Waterstops.

Expansion joint filler.

Adhesive binder.

Testing Agency for Concrete Mix Design: Approval request including qualifications of principals and technicians and evidence of active participation in program of Cement and Concrete Reference Laboratory (CCRL) of National Institute of Standards and Technology.

Test Report for Concrete Mix Designs: Trial mixes including water‑cement, concrete mix ingredients, and admixtures.

Shoring and Reshoring Sequence: Submit for approval a shoring and reshoring sequence for flat slab/flat plate portions, prepared by a registered Professional Engineer. As a minimum, include timing of form stripping, reshoring, number of floors to be re-shored and timing of re-shore removal to serve as an initial outline of procedures subject to modification as construction progresses. Submit revisions to sequence, whether initiated by COR (see FORMWORK) or Contractor.

PRE-CONCRETE CONFERENCE

General: At least 15 days prior to submittal of design mixes, conduct a meeting to review proposed methods of concrete construction to achieve the required results.

Agenda: Includes but is not limited to:

Submittals.

Coordination of work.

Availability of material.

Concrete mix design including admixtures.

Methods of placing, finishing, and curing.

Finish criteria required to obtain required flatness and levelness.

Timing of floor finish measurements.

Material inspection and testing.

Attendees: Include but not limited to representatives of Contractor; subcontractors involved in supplying, conveying, placing, finishing, and curing concrete; lightweight aggregate manufacturer; admixture manufacturers; COR; Consulting Engineer; Department of Veterans Affairs retained testing laboratories for concrete testing and finish (F-number) verification.

Minutes of the meeting: Contractor shall take minutes and type and distribute the minutes to attendees within five days of the meeting.

APPLICABLE PUBLICATIONS

Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

American Concrete Institute (ACI):

117-10Specifications for Tolerances for Concrete Construction and Materials and Commentary
211.1-91(R2009)Standard Practice for Selecting Proportions for Normal, Heavyweight, and Mass Concrete
211.2-98(R2004)Standard Practice for Selecting Proportions for Structural Lightweight Concrete
214R-11(R2019)Guide to Evaluation of Strength Test Results of Concrete
301-16Specifications for Structural Concrete
304R-00(R2009)Guide for Measuring, Mixing, Transporting, and Placing Concrete
305.1-14Specification for Hot Weather Concreting
306.1-90(R2002)Standard Specification for Cold Weather Concreting
308.1-11Specification for Curing Concrete
309R-05Guide for Consolidation of Concrete
318/318-19Building Code Requirements for Structural Concrete and Commentary
347R-14Guide to Formwork for Concrete
SP-66-04ACI Detailing Manual

American National Standards Institute and American Hardboard Association (ANSI/AHA):

A135.4-2012 Basic Hardboard ASTM International (ASTM):

A615/A615M-20Standard Specification for Deformed and Plain Carbon Steel Bars for Concrete Reinforcement
A706/A706M-16Standard Specification for Deformed and Plain Low-Alloy Steel Bars for Concrete Reinforcement
A996/A996M-16Standard Specification for Rail Steel and Axle Steel Deformed Bars for Concrete Reinforcement
A1064/A1064M-18aStandard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete
C31/C31M-19aStandard Practice for Making and Curing Concrete Test Specimens in the field
C33/C33M-18Standard Specification for Concrete Aggregates
C39/C39M-20Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
C94/C94M-19aStandard Specification for Ready Mixed Concrete
C143/C143M-20Standard Test Method for Slump of Hydraulic Cement Concrete
C150C150M-20Standard Specification for Portland Cement
C172C172M-17Standard Practice for Sampling Freshly Mixed Concrete
C173/C173M-16...Standard Test Method for Air Content of Freshly Mixed Concrete by the Volumetric Method
C192/C192M-19Standard Practice for Making and Curing Concrete Test Specimens in the Laboratory
C231/C231M-17aStandard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
C260/C260M-10a(2016)Standard Specification for Air Entraining Admixtures for Concrete
C309-19Standard Specification for Liquid Membrane Forming Compounds for Curing Concrete
C330/C330M-17aStandard Specification for Lightweight Aggregates for Structural Concrete
C494/C494M-19Standard Specification for Chemical Admixtures for Concrete
C618-19Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
C666/C666M-15Standard Test Method for Resistance of Concrete to Rapid Freezing and Thawing
C881/C881M-20Standard Specification for Epoxy Resin Base Bonding Systems for Concrete
C1107/1107M-20Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Non-shrink)

American Welding Society (AWS):

D1.4/D1.4M-18 Structural Welding Code – Steel Reinforcing Bars Concrete Reinforcing Steel Institute (CRSI):

Handbook 2008 U. S. Department of Commerce Product Standard (PS):

PS 1-07Structural Plywood
PS 20-20American Softwood Lumber Standard

U. S. Army Corps of Engineers Handbook for Concrete and Cement:

PART 2 – PRODUCTS

2.1 FORMS

0. Wood: PS 20 free from loose knots and suitable to facilitate finishing concrete surface specified; tongue and grooved.

Plywood: PS-1 Exterior Grade B‑B (concrete‑form) 16 mm (5/8 inch), or 20 mm (3/4 inch) thick for unlined contact form. B-B High Density Concrete Form Overlay optional.

Concrete products shall comply with following standards for biobased materials:

Material Type
Percent by Weight
Concrete Penetrating Liquid
79 percent biobased material
Concrete form Release Agent
87 percent biobased material
Concrete Sealer
11 percent biobased material

The minimum-content standards are based on the weight (not the volume) of the material.

Form Ties: Develop a minimum working strength of 13.35 kN (3000 pounds) when fully assembled. Ties shall be adjustable in length to permit tightening of forms and not have any lugs, cones, washers to act as spreader within form, nor leave a hole larger than 20 mm (3/4 inch) diameter, or a depression in exposed concrete surface, or leave metal closer than 40 mm (1 1/2 inches) to concrete surface. Wire ties not permitted. Cutting ties back from concrete face not permitted.

2.2 MATERIALS

0. Portland Cement: ASTM C150 Type I or II.

Fly Ash: ASTM C618, Class C or F including supplementary optional requirements relating to reactive aggregates and alkalies, and loss on ignition (LOI) not to exceed 5 percent. Do not exceed more than 25 percent total cementitious content by weight.

Coarse Aggregate: ASTM C33.

Size 67 or Size 467 may be used for footings and walls over 300 mm (12 inches) thick.

Maximum size of coarse aggregates not more than one‑fifth of narrowest dimension between sides of forms, one‑third of depth of slabs, nor three‑fourth of minimum clear spacing between reinforcing bars.

Lightweight Aggregates for Structural Concrete: ASTM C330, Table 1. Maximum size of aggregate not larger than one‑fifth of narrowest dimension between forms, nor three‑fourth of minimum clear distance between reinforcing bars. Contractor to furnish certified report to verify that aggregate is sound and durable, and has a durability factor of not less than 80 based on 300 cycles of freezing and thawing when tested in accordance with ASTM C666.

Mixing Water: Fresh, clean, and potable.

Admixtures:

Water Reducing Admixture: ASTM C494, Type A and not contain more chloride ions than are present in municipal drinking water.

Water Reducing, Retarding Admixture: ASTM C494, Type D and not contain more chloride ions than are present in municipal drinking water.

High-Range Water-Reducing Admixture (Superplasticizer): ASTM C494, Type F or G, and not contain more chloride ions than are present in municipal drinking water. Use of superplasticizer requires COR approval.

Non-Corrosive, Non-Chloride Accelerator: ASTM C494, Type C or E, and not contain more chloride ions than are present in municipal drinking water. Admixture manufacturer must have long-term non-corrosive test data from an independent testing laboratory of at least one year duration using an acceptable accelerated corrosion test method such as that using electrical potential measures.

Air Entraining Admixture: ASTM C260.

Calcium Nitrite corrosion inhibitor: ASTM C494 Type C.

Prohibited Admixtures: Calcium chloride, thiocyanate or admixtures containing more than 0.05 percent chloride ions are not permitted.

Certification: Written conformance to the requirements above and the chloride ion content of the admixture prior to mix design review.

Reinforcing Steel: ASTM A615, or ASTM A996, deformed, grade as shown.

Cold Drawn Steel Wire: ASTM A1064.

Supports, Spacers, and Chairs: Types which will hold reinforcement in position shown in accordance with requirements of ACI 318 except as specified.

Expansion Joint Filler: ASTM D1751.

Sheet Materials for Curing Concrete: ASTM C171.

Non-Shrink Grout:

ASTM C1107, pre-mixed, produce a compressive strength of at least 18 MPa at three days and 35 MPa (5000 psi) at 28 days. Furnish test data from an independent laboratory indicating that the grout when placed at a fluid consistency shall achieve 95 percent bearing under a 1200 mm x 1200 mm (4 foot by 4 foot) base plate.

Where high fluidity or increased placing time is required, furnish test data from an independent laboratory indicating that the grout when placed at a fluid consistency shall achieve 95 percent under an 450 mm x 900 mm (18 inch by 36 inch) base plate.

Porous Backfill: Crushed stone or gravel graded from 25 mm to 20 mm (1 inch to 3/4 inch).

2.3 CONCRETE MIXES

0. Mix Designs: Proportioned in accordance with Section 5.3, "Proportioning on the Basis of Field Experience and/or Trial Mixtures" of ACI 318.

If trial mixes are used, make a set of at least 6 cylinders in accordance with ASTM C192 for test purposes from each trial mix; test three for compressive strength at 7 days and three at 28 days.

Submit a report of results of each test series, include a detailed listing of the proportions of trial mix or mixes, including cement, admixtures, weight of fine and coarse aggregate per m3 (cubic yard) measured dry rodded and damp loose, specific gravity, fineness modulus, percentage of moisture, air content, water‑cement ratio, and consistency of each cylinder in terms of slump.

Prepare a curve showing relationship between water‑cement ratio at 7‑day and 28‑day compressive strengths. Plot each curve using at least three specimens.

If the field experience method is used, submit complete standard deviation analysis.

After approval of mixes no substitution in material or change in proportions of approval mixes may be made without additional tests and approval of the COR or as specified. Making and testing of preliminary test cylinders may be carried on pending approval of cement providing Contractor and manufacturer certify that ingredients used in making test cylinders are the same. The COR may allow Contractor to proceed with depositing concrete for certain portions of work, pending final approval of cement and approval of design mix.

Cement Factor: Maintain minimum cement factors in Table I regardless of compressive strength developed above minimums.

TABLE I - CEMENT AND WATER FACTORS FOR CONCRETE

Concrete Strength
Non-Air-Entrained
Air-Entrained

Min. 28 Day Comp. Str.

MPa (psi) Min. Cement kg/m3 (lbs/c. yd)

Max. Water Cement Ratio
Min. Cement

kg/m3 (lbs/c. yd) Max. Water Cement Ratio

35 (5000)1,3
375 (630)
0.45
385 (650)
0.40
30 (4000)1,3
325 (550)
0.55
340 (570)
0.50
25 (3000)1,3
280 (470)
0.65
290 (490)
0.55
25 (3000)1,2
300 (500)
See 4 below
310 (520)
See 4 below

If trial mixes are used, the proposed mix design shall achieve a compressive strength 8.3 MPa (1200 psi) in excess of f'c. For concrete strengths above 35 Mpa (5000 psi), the proposed mix design shall achieve a compressive strength 9.7 MPa (1400 psi) in excess of f’c.

Lightweight Structural Concrete. Pump mixes may require higher cement values.

For concrete exposed to high sulfate content soils maximum water cement ratio is 0.44.

Determined by Laboratory in accordance with ACI 211.1 for normal concrete or ACI 211.2 for lightweight structural concrete.

Maximum Slump: Maximum slump, as determined by ASTM C143 with tolerances as established by ASTM C94, for concrete to be vibrated shall be as shown in Table II.

TABLE II ‑ MAXIMUM SLUMP, mm (INCHES)

Type of Construction
Normal Weight Concrete
Lightweight Structural Concrete
Reinforced Footings and Substructure Walls
75mm (3 inches)
75 mm (3 inches)
Slabs, Beams, Reinforced Walls, and Building Columns
100 mm (4 inches)
100 mm (4 inches)

Slump may be increased by the use of the approved high-range water-reducing admixture (superplasticizer). Tolerances as established by ASTM C94. Concrete containing the high-range-water-reducing admixture may have a maximum slump of 225 mm (9 inches). The concrete shall arrive at the job site at a slump of 50 mm to 75 mm (2 inches to 3 inches), and 75 mm to 100 mm (3 inches to 4 inches) for lightweight concrete. This should be verified, and then the high-range-water-reducing admixture added to increase the slump to the approved level.

Air-Entrainment: Air-entrainment of normal weight concrete shall conform with Table III. Air-entrainment of lightweight structural concrete shall conform with Table IV. Determine air content by either ASTM C173 or ASTM C231.

TABLE III ‑ TOTAL AIR CONTENT

FOR VARIOUS SIZES OF COARSE AGGREGATES (NORMAL CONCRETE)

Nominal Maximum Size of Total Air Content
Coarse Aggregate, mm (Inches) Percentage by Volume
10 mm (3/8 in).6 to 10
13 mm (1/2 in).5 to 9
20 mm (3/4 in).4 to 8
25 mm (1 in).3‑1/2 to 6‑1/2

40 mm (1 1/2 in).3 to 6

TABLE IV

AIR CONTENT OF LIGHTWEIGHT STRUCTURAL CONCRETE

Nominal Maximum size of Total Air Content
Coarse Aggregate, mm’s (Inches) Percentage by Volume
Greater than 10 mm (3/8 in) 4 to 8
10 mm (3/8 in) or less 5 to 9

High early strength concrete, made with Type III cement or Type I cement plus non-corrosive accelerator, shall have a 7-day compressive strength equal to specified minimum 28‑day compressive strength for concrete type specified made with standard Portland cement.

Lightweight structural concrete shall not weigh more than air‑dry unit weight shown. Air‑dry unit weight determined on 150 mm by 300 mm (6 inch by 12 inch) test cylinders after seven days standard moist curing followed by 21 days drying at 23 degrees C 1.7 degrees C (73.4 3 degrees Fahrenheit), and 50 (plus or minus 7) percent relative humidity. Use wet unit weight of fresh concrete as basis of control in field.

Concrete slabs placed at air temperatures below 10 degrees C (50 degrees Fahrenheit) use non-corrosive, non-chloride accelerator. Concrete required to be air entrained use approved air entraining admixture. Pumped concrete, synthetic fiber concrete, architectural concrete, concrete required to be watertight, and concrete with a water/cement ratio below 0.50 use high-range water-reducing admixture (superplasticizer).

Durability: Use air entrainment for exterior exposed concrete subjected to freezing and thawing and other concrete shown or specified. For air content requirements see Table III or Table IV.

Enforcing Strength Requirements: Test as specified in Section 01 45 29, TESTING LABORATORY SERVICES, during the progress of the work. Seven‑day tests may be used as indicators of 28‑day strength. Average of any three 28‑day consecutive strength tests of laboratory‑cured specimens representing each type of concrete shall be equal to or greater than specified strength. No single test shall be more than 3.5 MPa (500 psi) below specified strength. Interpret field test results in accordance with ACI 214. Should strengths shown by test specimens fall below required values, the COR may require any one or any combination of the following corrective actions, at no additional cost to the Government:

Require changes in mix proportions by selecting one of the other appropriate trial mixes or changing proportions, including cement content, of approved trial mix.

Require additional curing and protection.

If five consecutive tests fall below 95 percent of minimum values given in Table I or if test results are so low as to raise a question as to the safety of the structure, the COR may direct Contractor to take cores from portions of the structure. Use results from cores tested by the Contractor retained testing agency to analyze structure.

If strength of core drilled specimens falls below 85 percent of minimum value given in Table I, the COR may order load tests, made by Contractor retained testing agency, on portions of building so affected. Load tests in accordance with ACI 318 and criteria of acceptability of concrete under test as given therein.

Concrete work, judged inadequate by structural analysis, by results of load test, or for any reason, shall be reinforced with additional construction or replaced, if directed by the COR.

2.4 BATCHING AND MIXING

0. General: Concrete shall be "Ready‑Mixed" and comply with ACI 318 and ASTM C94, except as specified. Batch mixing at the site is permitted. Mixing process and equipment must be approved by the COR. With each batch of concrete, furnish certified delivery tickets listing information in Paragraph 16.1 and 16.2 of ASTM C94. Maximum delivery temperature of concrete is 38 degrees C (100 degrees Fahrenheit). Minimum delivery temperature as follows:

Atmospheric Temperature
Minimum Concrete Temperature

-1. degrees to 4.4 degrees C (30 degrees to 40 degrees F)

15.6 degrees C (60 degrees F.)

-17 degrees C to -1.1 degrees C (0 degrees to 30 degrees F.)
21 degrees C (70 degrees F.)

Services of aggregate manufacturer's representative shall be furnished during the design of trial mixes and as requested by the COR for consultation during batching, mixing, and placing operations of lightweight structural concrete. Services will be required until field controls indicate that concrete of required quality is being furnished. Representative shall be thoroughly familiar with the structural lightweight aggregate, adjustment and control of mixes to produce concrete of required quality. Representative shall assist and advise the COR.

PART 3 – EXECUTION

3.1 FORMWORK

0. General: Design in accordance with ACI 347 is the responsibility of the Contractor. The Contractor shall retain a registered Professional Engineer to design the formwork, shores, and reshores.

Form boards and plywood forms may be reused for contact surfaces of exposed concrete only if thoroughly cleaned, patched, and repaired and the COR approves their reuse.

Provide forms for concrete footings unless the COR determines forms are not necessary.

Treating and Wetting: Treat or wet contact forms as follows:

Coat plywood and board forms with non‑staining form sealer. In hot weather, cool forms by wetting with cool water just before concrete is placed.

Clean and coat removable metal forms with light form oil before reinforcement is placed. In hot weather, cool metal forms by thoroughly wetting with water just before placing concrete.

Use sealer on reused plywood forms as specified for new material.

Size and Spacing of Studs: Size and space studs, wales and other framing members for wall forms so as not to exceed safe working stress of kind of lumber used nor to develop deflection greater than 1/270 of free span of member.

Unlined Forms: Use plywood forms to obtain a smooth finish for concrete surfaces. Tightly butt edges of sheets to prevent leakage. Back up all vertical joints solidly and nail edges of adjacent sheets to same stud with 6d box nails spaced not over 150 mm (6 inches) apart.

Lined Forms: May be used in lieu of unlined plywood forms. Back up form lining solidly with square edge board lumber securely nailed to studs with all edges in close contact to prevent bulging of lining. No joints in lining and backing may coincide. Nail abutted edges of sheets to same backing board. Nail lining at not over 200 mm (8 inches) on center along edges and with at least one nail to each square foot of surface area; nails to be 3d blued shingle or similar nails with thin flatheads.

Wall Form Ties: Locate wall form ties in symmetrically level horizontal rows at each line of wales and in plumb vertical tiers. Space ties to maintain true, plumb surfaces. Provide one row of ties within 150 mm (6 inches) above each construction joint. Space through‑ties adjacent to horizontal and vertical construction joints not over 450 mm (18 inches) on center.

Tighten row of ties at bottom of form just before placing concrete and, if necessary, during placing of concrete to prevent seepage of concrete and to obtain a clean line. Ties to be entirely removed shall be loosened 24 hours after concrete is placed and shall be pulled from least important face when removed.

Coat surfaces of all metal that is to be removed with paraffin, cup grease or a suitable compound to facilitate removal.

Inserts, Sleeves, and Similar Items: Flashing reglets, steel strips, masonry ties, anchors, wood blocks, nailing strips, grounds, inserts, wire hangers, sleeves, drains, guard angles, forms for floor hinge boxes, inserts or bond blocks for elevator guide rails and supports, and other items specified as furnished under this and other sections of specifications and required to be in their final position at time concrete is placed shall be properly located, accurately positioned, and built into construction, and maintained securely in place.

Install sleeves, inserts and similar items for mechanical services in accordance with drawings prepared specially for mechanical services. Contractor is responsible for accuracy and completeness of drawings and shall coordinate requirements for mechanical services and equipment.

Minimum clear distance of embedded items such as conduit and pipe is at least three times diameter of conduit or pipe, except at stub‑ups and other similar locations.

Construction Tolerances:

Set and maintain concrete formwork to assure erection of completed work within tolerances specified and to accommodate installation of other rough and finish materials. Accomplish remedial work necessary for correcting excessive tolerances. Erected work that exceeds specified tolerance limits shall be remedied or removed and replaced, at no additional cost to the Government.

Permissible surface irregularities for various classes of materials are defined as "finishes" in specification sections covering individual materials. They are to be distinguished from tolerances specified which are applicable to surface irregularities of structural elements.

3.2 PLACING REINFORCEMENT

0. General: Details of concrete reinforcement in accordance with ACI 318 unless otherwise shown.

Placing: Place reinforcement conforming to CRSI DA4, unless otherwise shown.

Place reinforcing bars accurately and tie securely at intersections and splices with 1.6 mm (16 gauge) black annealed wire. Secure reinforcing bars against displacement during the placing of concrete by spacers, chairs, or other similar supports. Portions of supports, spacers, and chairs in contact with formwork shall be made of plastic in areas that will be exposed when building is occupied. Type, number, and spacing of supports conform to ACI 318.

Spacing: Minimum clear distances between parallel bars, except in columns and multiple layers of bars in beams shall be equal to nominal diameter of bars. Minimum clear spacing is 25 mm (1 inch) or 1‑1/3 times maximum size of coarse aggregate.

Splicing: Splices of reinforcement made only as required or shown or specified. Accomplish splicing as follows:

Lap splices: Do not use lap splices for bars larger than Number 36 (Number 11). Minimum lengths of lap as shown.

Welded splices: Splicing by butt‑welding of reinforcement permitted providing the weld develops in tension at least 125 percent of the yield strength (fy) for the bars. Welding conform to the requirements of AWS D1.4. Welded reinforcing steel conform to the chemical analysis requirements of AWS D1.4.

Submit test reports indicating the chemical analysis to establish weldability of reinforcing steel.

Submit a field quality control procedure to insure proper inspection, materials and welding procedure for welded splices.

Department of Veterans Affairs retained testing agency shall test a minimum of three splices, for compliance, locations selected by the COR.

Mechanical Splices: Develop in tension and compression at least 125 percent of the yield strength (fy) of the bars. Stresses of transition splices between two reinforcing bar sizes based on area of smaller bar. Provide mechanical splices at locations indicated. Use approved exothermic, tapered threaded coupling, or swaged and threaded sleeve. Exposed threads and swaging in the field not permitted.

Initial qualification: In the presence of the COR, make three test mechanical splices of each bar size proposed to be spliced. Department of Veterans Affairs retained testing laboratory will perform load test.

During installation: Furnish, at no additional cost to the Government, one companion (sister) splice for every 50 splices for load testing. Department of Veterans Affairs retained testing laboratory will perform the load test.

Bending: Bend bars cold, unless otherwise approved. Do not field bend bars partially embedded in concrete, except when approved by the COR.

Cleaning: Metal reinforcement, at time concrete is placed, shall be free from loose flaky rust, mud, oil, or similar coatings that will reduce bond.

Future Bonding: Protect exposed reinforcement bars intended for bonding with future work by wrapping with felt and coating felt with a bituminous compound unless otherwise shown.

3.3 PLACING CONCRETE

Preparation:

Remove hardened concrete, wood chips, shavings and other debris from forms.

Remove hardened concrete and foreign materials from interior surfaces of mixing and conveying equipment.

Have forms and reinforcement inspected and approved by the COR before depositing concrete.

Bonding: Before depositing new concrete on or against concrete which has been set, thoroughly roughen and clean existing surfaces of laitance, foreign matter, and loose particles.

Preparing surface for applied topping:

Remove laitance, mortar, oil, grease, paint, or other foreign material by sand blasting. Clean with vacuum type equipment to remove sand and other loose material.

Broom clean and keep base slab wet for at least four hours before topping is applied.

Use a thin coat of one part Portland cement, 1.5 parts fine sand, bonding admixture; and water at a 50: 50 ratio and mix to achieve the consistency of thick paint. Apply to a damp base slab by scrubbing with a stiff fiber brush. New concrete shall be placed while the bonding grout is still tacky.

Conveying Concrete: Convey concrete from mixer to final place of deposit by a method which will prevent segregation. Method of conveying concrete is subject to approval of the COR.

Placing: For special requirements see Paragraphs, HOT WEATHER and COLD WEATHER.

Do not place concrete when weather conditions prevent proper placement and consolidation, or when concrete has attained its initial set, or has contained its water or cement content more than 1 1/2 hours.

Deposit concrete in forms as near as practicable in its final position. Prevent splashing of forms or reinforcement with concrete in advance of placing concrete.

Do not drop concrete freely more than 3000 mm (10 feet) for concrete containing the high-range water-reducing admixture (superplasticizer) or 1500 mm (5 feet) for conventional concrete. Where greater drops are required, use a tremie or flexible spout (canvas elephant trunk), attached to a suitable hopper.

Discharge contents of tremies or flexible spouts in horizontal layers not exceeding 500 mm (20 inches) in thickness, and space tremies such as to provide a minimum of lateral movement of concrete.

Continuously place concrete until an entire unit between construction joints is placed. Rate and method of placing concrete shall be such that no concrete between construction joints will be deposited upon or against partly set concrete, after its initial set has taken place, or after 45 minutes of elapsed time during concrete placement.

On bottom of members with severe congestion of reinforcement, deposit 25 mm (1 inch) layer of flowing concrete containing the specified high-range water-reducing admixture (superplasticizer). Successive concrete lifts may be a continuation of this concrete or concrete with a conventional slump.

Consolidation: Conform to ACI 309. Immediately after depositing, spade concrete next to forms, work around reinforcement and into angles of forms, tamp lightly by hand, and compact with mechanical vibrator applied directly into concrete at approximately 450 mm (18 inch) intervals. Mechanical vibrator shall be power driven, hand operated type with minimum frequency of 5000 cycles per minute having an intensity sufficient to cause flow or settlement of concrete into place. Vibrate concrete to produce thorough compaction, complete embedment of reinforcement and concrete of uniform and maximum density without segregation of mix. Do not transport concrete in forms by vibration.

Use of form vibration shall be approved only when concrete sections are too thin or too inaccessible for use of internal vibration.

Carry on vibration continuously with placing of concrete. Do not insert vibrator into concrete that has begun to set.

3.4 HOT WEATHER

0. Follow the recommendations of ACI 305 or as specified to prevent problems in the manufacturing, placing, and curing of concrete that can adversely affect the properties and serviceability of the hardened concrete. Methods proposed for cooling materials and arrangements for protecting concrete shall be made in advance of concrete placement and approved by the COR.

3.5 COLD WEATHER

0. Follow the recommendations of ACI 306 or as specified to prevent freezing of concrete and to permit concrete to gain strength properly. Use only the specified non-corrosive, non-chloride accelerator. Do not use calcium chloride, thiocyantes or admixtures containing more than 0.05 percent chloride ions. Methods proposed for heating materials and arrangements for protecting concrete shall be made in advance of concrete placement and approved by the COR.

3.6 PROTECTION AND CURING

0. Conform to ACI 308: Initial curing shall immediately follow the finishing operation. Protect exposed surfaces of concrete from premature drying, wash by rain and running water, wind, mechanical injury, and excessively hot or cold temperatures. Keep concrete not covered with membrane or other curing material continuously wet for at least 7 days after placing, except wet curing period for high-early-strength concrete shall be not less than 3 days. Keep wood forms continuously wet to prevent moisture loss until forms are removed. Cure exposed concrete surfaces as described below. Other curing methods may be used if approved by the COR.

Liquid curing and sealing compounds: Apply by power-driven spray or roller in accordance with the manufacturer’s instructions. Apply immediately after finishing. Maximum coverage 10m2/L (400 square feet per gallon) on steel troweled surfaces and 7.5m2/L (300 square feet per gallon) on floated or broomed surfaces for the curing/sealing compound.

Plastic sheets: Apply as soon as concrete has hardened sufficiently to prevent surface damage. Utilize widest practical width sheet and overlap adjacent sheets 50 mm (2 inches). Tightly seal joints with tape.

3.7 REMOVAL OF FORMS

0. Remove in a manner to assure complete safety of structure after the following conditions have been met.

Where structure as a whole is supported on shores, forms for beams and girder sides, columns, and similar vertical structural members may be removed after 24 hours, provided concrete has hardened sufficiently to prevent surface damage and curing is continued without any lapse in time as specified for exposed surfaces.

Take particular care in removing forms of architectural exposed concrete to insure surfaces are not marred or gouged, and that corners and arises are true, sharp and unbroken.

Control Test: Use to determine if the concrete has attained sufficient strength and curing to permit removal of supporting forms. Cylinders required for control tests taken in accordance with ASTM C172, molded in accordance with ASTM C31, and tested in accordance with ASTM C39. Control cylinders cured and protected in the same manner as the structure they represent. Supporting forms or shoring not removed until strength of control test cylinders have attained at least 70 percent of minimum 28‑day compressive strength specified. Exercise care to assure that newly unsupported portions of structure are not subjected to heavy construction or material loading.

3.8 CONCRETE SURFACE PREPARATION

0. Metal Removal: Unnecessary metal items cut back flush with face of concrete members.

Patching: Maintain curing and start patching as soon as forms are removed. Do not apply curing compounds to concrete surfaces requiring patching until patching is completed. Use cement mortar for patching of same composition as that used in concrete. Use white or gray Portland cement as necessary to obtain finish color matching surrounding concrete. Thoroughly clean areas to be patched. Cut out honeycombed or otherwise defective areas to solid concrete to a depth of not less than 25 mm (1 inch). Cut edge perpendicular to surface of concrete. Saturate with water area to be patched, and at least 150 mm (6 inches) surrounding before placing patching mortar. Give area to be patched a brush coat of cement grout followed immediately by patching mortar. Cement grout composed of one part Portland cement, 1.5 parts fine sand, bonding admixture, and water at a 50:50 ratio, mix to achieve consistency of thick paint. Mix patching mortar approximately 1 hour before placing and remix occasionally during this period without addition of water. Compact mortar into place and screed slightly higher than surrounding surface. After initial shrinkage has occurred, finish to match color and texture of adjoining surfaces. Cure patches as specified for other concrete. Fill form tie holes which extend entirely through walls from unexposed face by means of a pressure gun or other suitable device to force mortar through wall. Wipe excess mortar off exposed face with a cloth.

Upon removal of forms, clean vertical concrete surface that is to receive bonded applied cementitious application with wire brushes or by sand blasting to remove unset material, laitance, and loose particles to expose aggregates to provide a clean, firm, granular surface for bond of applied finish.

END OF SECTION