03 EXHIBIT B SUPL 032026.pdf

PDF 218 KB Posted

Attached to
The USDA Seeks to Lease Office and Related Space in Mountain City, Johnson County, Tennessee
Solicitation number
57-47019-26-FA-RLP
Issued by

About this file

This document is a Supplemental Lease Requirements template (Exhibit B) for federal real property leases, revised May 2025, establishing comprehensive standards for building shell construction, tenant improvements, utilities, services, and operational obligations during the lease term.

The requirements cover six major sections: (1) General Terms and Conditions defining real property measurements (ANSI/BOMA standards, rentable square footage, common area factors), authorized representatives, waiver of restoration, novation procedures, and asbestos compliance; (2) Construction Standards and Shell Components specifying work performance by skilled workers, wood product standards, adhesive/sealant requirements, building shell completion, means of egress (minimum two remote exits), automatic fire sprinkler systems (below-grade and hazardous areas, sixth floor and above, or buildings over 35,000 ANSI/BOMA occupant area square feet), fire alarm systems for third floor and above, energy efficiency (ENERGY STAR certification or cost-effective improvements), elevator safety and accessibility, ceilings (acoustical throughout), exterior doors, windows, permanent partitions, insulation, painting, floor loads (50 pounds per square foot for office areas, 100 pounds for storage), mechanical/electrical/plumbing systems, drinking fountains (within 200 feet, ADA-compliant), restrooms (separate facilities for men and women, within 500 feet), HVAC systems (central systems with sufficient capacity, ductwork cleaning per NADCA standards, ASHRAE 62.1 ventilation compliance, MERV filtration, refrigerant tracking for ozone-depleting substances), telecommunications infrastructure, and interior/parking lighting (minimum 50 foot-candles at desktop level, 1.4 watts per square foot maximum power density); (3) Design, Construction, and Post Award Activities requiring design intent drawings within 10 working days of award, construction documents within 10 working days of DID approval, 60 working days for completion after Notice to Proceed, biweekly progress reports, Certificate of Occupancy before acceptance, as-built CAD drawings within 30 days of acceptance, and seismic retrofit compliance where required; (4) Tenant Improvement Components including fixed pricing with unit costs for subdividing partitions, electrical outlets, doors, and telephone outlets, finish selections (minimum two coordinated options), window coverings, doors meeting NFPA 101/IBC standards, hardware with master keying, partitions with STC 45 minimum sound transmission class, painting, carpet specifications (static less than 3.5 kV, flammability compliance, TARR moderate or better), individual thermostat controls, electrical distribution per NFPA 70, telecommunications outlets (voice and data), data cable installation with cable trays within 30-foot distance, and systems furniture electrical/data connections; (5) Utilities, Services, and Obligations during the lease term including services during normal business hours (6:00 AM to 6:00 PM Monday-Friday), all utilities provided by lessor, HVAC maintenance (72°F ±3° heating, 75°F ±3° cooling, 55°F ±3° non-working hours, 65-78°F for server rooms at all times), janitorial services per specified schedule (daily trash/sweeping/restroom cleaning, weekly floor maintenance, monthly carpet vacuuming, semi-annual window washing, biennial carpet shampooing), paint and flooring maintenance, identity verification of personnel with access (HSPD-12 compliance, background investigations, PIV credential issuance and return), Randolph-Sheppard vending machine compliance, indoor air quality controls (safety data sheets required, odor-free products, board-certified industrial hygienist inspection within 15 days of complaints, HEPA filtration vacuums), radon testing (91+ days standard test or 14-day short test for at/below-grade space, action levels 4 pCi/L for childcare and 25 pCi/L for other space, corrective action program required), radon in water compliance with EPA Maximum Contaminant Levels, hazardous materials prohibition with testing rights reserved, mold and water intrusion remediation (48-hour repair requirement, industrial hygienist inspection within 15 days, 90-day remediation completion), and occupant emergency plan cooperation; and (6) Additional Terms and Conditions including Security Level I requirements in shell rent, modified paragraphs for scheduling and finish selections, and rental payment via electronic funds transfer with all costs (construction, improvements, taxes, operating costs) included in rent unless a separate parking rate is specified.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEASE NO. 57-47091-26-FA

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

REQUIREMENTS

REV (5/2025)

TABLE OF CONTENTS – SUPPLEMENTAL LEASE REQUIREMENTS

SECTION 1 GENERAL TERMS, CONDITIONS, AND STANDARDS

1.01 DEFINITIONS AND GENERAL TERMS (SMALL) (OCT 2023)

1.02 INTENTIONALLY DELETED

1.03 AUTHORIZED REPRESENTATIVES (OCT 2016)

1.04 WAIVER OF RESTORATION (OCT 2023)

1.05 NOVATION AND CHANGE OF OWNERSHIP (SMALL) (OCT 2016)

1.06 ASBESTOS (SMALL) (MAY 2025)

1.07 ADJUSTMENT FOR VACANT PREMISES (SMALL) (OCT 2022)

1.08 ENTITY NAME (OCT 2023)

SECTION 2 CONSTRUCTION STANDARDS AND SHELL COMPONENTS

2.01 WORK PERFORMANCE (SMALL) (SEP 2015)

2.02 EXISTING FIT-OUT, SALVAGED, OR REUSED BUILDING MATERIAL (SMALL) (SEP 2015)

2.03 WOOD PRODUCTS (SMALL) (OCT 2023)

2.04 ADHESIVES AND SEALANTS (SMALL) (OCT 2020)

2.05 BUILDING SHELL REQUIREMENTS (SMALL) (OCT 2019)

2.06 RESPONSIBILITY OF THE LESSOR AND LESSOR’S ARCHITECT/ENGINEER (SMALL) (SEP 2015)

2.07 MEANS OF EGRESS (MAY 2015)

2.08 AUTOMATIC FIRE SPRINKLER SYSTEM (OCT 2023)

2.09 FIRE ALARM SYSTEM (SEP 2013)

2.10 ENERGY INDEPENDENCE AND SECURITY ACT (SMALL) (SEP 2015)

2.11 ELEVATORS (SMALL) (OCT 2020)

2.12 DEMOLITION (JUN 2012)

2.13 ACCESSIBILITY (OCT 2024)

2.14 CEILINGS (SMALL) (OCT 2019)

2.15 EXTERIOR AND COMMON AREA DOORS AND HARDWARE (SEP 2013)

2.16 WINDOWS (SMALL) (OCT 2020)

2.17 PARTITIONS: PERMANENT (SMALL) (OCT 2019)

2.18 INSULATION: THERMAL, ACOUSTIC, AND HVAC (SMALL) (OCT 2020)

2.19 PAINTING – SHELL (SMALL) (OCT 2020)

2.20 FLOORS AND FLOOR LOAD (SMALL) (OCT 2019)

2.21 MECHANICAL, ELECTRICAL, PLUMBING: GENERAL (SMALL) (SEP 2015)

2.22 DRINKING FOUNTAINS (MAY 2025)

2.23 RESTROOMS (SMALL) (OCT 2022)

2.24 HEATING, VENTILATION, AND AIR CONDITIONING – SHELL (SMALL) (MAY 2025)

2.25 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (SMALL) (SEP 2015)

2.26 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (SMALL) (OCT 2020)

2.27 LIGHTING: INTERIOR AND PARKING – SHELL (SMALL) (OCT 2022)

2.28 INDOOR AIR QUALITY DURING CONSTRUCTION (SMALL) (OCT 2021)

2.29 INTENTIONALLY DELETED

SECTION 3 DESIGN, CONSTRUCTION, AND POST AWARD ACTIVITIES

3.01 SCHEDULE FOR COMPLETION OF SPACE (SMALL) (OCT 2020)

3.02 ACCESS BY THE GOVERNMENT PRIOR TO ACCEPTANCE (SMALL) (OCT 2020)

3.03 ACCEPTANCE OF SPACE AND CERTIFICATE OF OCCUPANCY (SMALL) (OCT 2021)

3.04 LEASE TERM COMMENCEMENT DATE AND RENT RECONCILIATION (SMALL) (OCT 2021)

3.05 AS-BUILT DRAWINGS (OCT 2021)

3.06 SEISMIC RETROFIT (OCT 2020)

3.07 GOVERNMENT PROJECT MANAGEMENT SYSTEM (MAY 2025)

SECTION 4 TENANT IMPROVEMENT COMPONENTS

4.01 TENANT IMPROVEMENTS AND PRICING (SMALL) (SEP 2015)

4.02 FINISH SELECTIONS (SMALL) (SEP 2015)

4.03 WINDOW COVERINGS (SMALL) (OCT 2020)

4.04 DOORS: SUITE ENTRY (SMALL) (OCT 2020)

4.05 DOORS: INTERIOR (SMALL) (OCT 2019)

4.06 DOORS: HARDWARE (SMALL) (SEP 2015)

4.07 PARTITIONS: SUBDIVIDING (SMALL) (OCT 2022)

4.08 PAINTING – TI (SMALL) (OCT 2020)

4.09 FLOOR COVERINGS AND PERIMETERS (SMALL) (OCT 2019)

4.10 HEATING AND AIR CONDITIONING (SMALL) (OCT 2022)

4.11 ELECTRICAL: DISTRIBUTION (SMALL) (SEP 2015)

4.12 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (JUN 2012)

4.13 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (AUG 2008)

EXHIBIT B

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

REQUIREMENTS

REV (5/2025)

4.14 DATA DISTRIBUTION (OCT 2020)

4.15 ELECTRICAL, TELEPHONE, DATA FOR SYSTEMS FURNITURE (OCT 2022)

4.16 LIGHTING: INTERIOR AND PARKING – TI (SMALL) (SEP 2015)

SECTION 5 UTILITIES, SERVICES, AND OBLIGATIONS DURING THE LEASE TERM

5.01 PROVISION OF SERVICES, ACCESS, AND NORMAL HOURS (SMALL) (OCT 2020)

5.02 UTILITIES (SMALL) (OCT 2022)

5.03 HEATING AND AIR CONDITIONING (SMALL) (OCT 2024)

5.04 OVERTIME HVAC USAGE (SMALL) (SEP 2016)

5.05 JANITORIAL SERVICES (SMALL) (MAY 2025)

5.06 MAINTENANCE OF PROVIDED FINISHES (SMALL) (SEP 2015)

5.07 IDENTITY VERIFICATION OF PERSONNEL (OCT 2022)

5.08 RANDOLPH-SHEPPARD COMPLIANCE (SMALL) (SEP 2015)

5.09 INDOOR AIR QUALITY (MAY 2025)

5.10 RADON IN AIR (MAY 2025)

5.11 RADON IN WATER (MAY 2025)

5.12 HAZARDOUS MATERIALS (MAY 2025)

5.13 MOLD AND WATER INTRUSION (OCT 2023)

5.14 OCCUPANT EMERGENCY PLANS (OCT 2020)

SECTION 6 ADDITIONAL TERMS AND CONDITIONS

6.01 SECURITY REQUIREMENTS (SMALL) (OCT 2019)

6.02 MODIFIED LEASE PARAGRAPHS (OCT 2016)

6.03 RENTAL CONSIDERATION FOR SMALL LEASES (OCT 2019)

6.04 INTENTIONALLY DELETED

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

REQUIREMENTS

REV (5/2025)

SECTION 1 GENERAL TERMS, CONDITIONS, AND STANDARDS

1.01 DEFINITIONS AND GENERAL TERMS (SMALL) (OCT 2023)

Unless otherwise specifically noted, all terms and conditions set forth in this Lease shall be interpreted by reference to the following definitions, standards, and formulas:

A. Real Property Terms.

1. “ANSI/BOMA” is an acronym for American National Standards Institute/Building Owners and Managers Association.

2. “ANSI/BOMA Occupant Area” or “ABOA” means the measurement standard (Z65.1-2017) provided by ANSI/BOMA for Occupant Area, which is “the total aggregated area used by an Occupant before Load Factors are applied, consisting of Tenant Area and Tenant Ancillary Area.” The Method A – Multiple Load Factor Method shall apply.

3. “Common Area Factor (CAF)” means a conversion factor determined and applied by the building owner to determine the rentable square feet for the leased space. The CAF is expressed as a percentage of the difference between the amount of rentable square feet (SF) and ABOA SF, divided by the ABOA SF. The CAF shall be determined in accordance with the applicable ANSI/BOMA standard for the type of space to which the CAF shall apply.

4. “Rentable Space or Rentable Square Feet (RSF)” means the area for which a tenant is charged rent. It is determined by the building owner and may vary by city or by building within the same city. Rentable space may include a share of common areas such as elevator lobbies, building corridors, and floor service areas. Floor service areas typically include restrooms, janitor rooms, telephone closets, electrical closets, and mechanical rooms. Rentable space does not include vertical building penetrations and their enclosing walls, such as stairs, elevator shafts, and vertical ducts. To determine the RSF, the ABOA SF is multiplied by the sum of one (1) plus the CAF, for each type of space included in the premises.

5. “Space” means that part of the premises to which the Government has exclusive use, such as occupant area, or other types of space. Appurtenant areas (e.g., parking areas) to which the Government has rights under the lease are not included in the space.

1.02 INTENTIONALLY DELETED

1.03 AUTHORIZED REPRESENTATIVES (OCT 2016)

Signatories to this Lease shall have full authority to bind their respective principals with regard to all matters relating to this Lease. No other persons shall be understood to have any authority to bind their respective principals except to the extent that such authority may be explicitly delegated by notice to the other party, or to the extent that such authority is transferred by succession of interest. The Government shall have the right to substitute its Lease Contracting Officer (LCO) by notice without an express delegation by the prior

LCO.

1.04 WAIVER OF RESTORATION (OCT 2023)

Lessor shall have no right to require the Government to restore the Premises upon expiration or earlier termination (full or partial) of the Lease, and waives all claims against the Government for:

A. Waste, or, B. Damages or restoration arising from or related to:

1. The Government's normal and customary use of the Premises during the term of the Lease (including any extensions thereof), as well as,

2. Any initial or subsequent alteration to the Premises regardless of whether such alterations are performed by the Lessor or by the Government.

At its sole option, the Government may abandon property in the Space following expiration or earlier termination (full or partial) of the Lease, in which case the property will become the property of the Lessor, and the Government will be relieved of any liability in connection therewith.

1.05 NOVATION AND CHANGE OF OWNERSHIP (SMALL) (OCT 2016)

Consistent with GSAM 570.115, in the event of a transfer of ownership of the leased premises or a change in the Lessor’s legal name, FAR 42.12 applies.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

1.06 ASBESTOS (SMALL) (MAY 2025)

The leased space shall be free of all asbestos containing materials, except undamaged asbestos flooring in the space or undamaged boiler or pipe insulation outside the space, in which case an asbestos management program conforming to Environmental Protection Agency guidance shall be implemented. The space shall be free of other hazardous materials and in compliance with applicable Federal, State, and local environmental laws and regulations. If asbestos abatement work is to be performed in the Space after occupancy, the Lessor shall provide relocation and submit to the Government documentation that the abatement was done in accordance with OSHA (29 CFR § 1910.1001, 29 CFR § 1926.1101), EPA (40 CFR Part 61 - National Emission Standards for Hazardous Air Pollutants and Part 763), state, and local regulations and that final clearance is achieved.

1.07 ADJUSTMENT FOR VACANT PREMISES (SMALL) (OCT 2022)

If the Government fails to occupy any portion of the leased Premises or vacates the Premises in whole or in part prior to expiration of the term of the Lease, the operating costs paid by the Government as part of the rent rental rate shall be reduced using the “Adjustment for Vacant Premises Rate” specified on GSA Form 3626 of this Lease. This reduction shall occur after the Government gives 30 calendar days’ prior notice to the Lessor and shall continue in effect until the Lease expires or is terminated.

1.08 ENTITY NAME (OCT 2023)

Lessor may not use Federal agency name(s) and/or acronym(s), e.g., General Services Administration, GSA, or Department of Agriculture (USDA) in its entity name that owns and/or leases Space to USDA.

SECTION 2 CONSTRUCTION STANDARDS AND SHELL COMPONENTS

2.01 WORK PERFORMANCE (SMALL) (SEP 2015)

All work in performance of this Lease shall be done by skilled and licensed workers or mechanics and shall be acceptable to the LCO.

2.02 EXISTING FIT-OUT, SALVAGED, OR REUSED BUILDING MATERIAL (SMALL) (SEP 2015)

The Lessor shall reuse items or materials in the construction phase of the project, as long as such meet the quality standards set forth by the Government in this Lease.

2.03 WOOD PRODUCTS (SMALL) (OCT 2023)

For all new installations of wood products, the Lessor is encouraged to use independently certified forest products. Refer to the Forest Stewardship Council United States (HTTPS://US.FSC.ORG/EN-US), or the Sustainable Forestry Initiative (HTTP://WWW.SFIPROGRAM.ORG/). Particle board, medium-density fiberboard, and hardwood plywood shall be free of formaldehyde and labeled as Toxic Substances Control Act (TSCA) Title VI compliant. Other wood types such as strawboard shall be free of formaldehyde or sufficiently aged prior to use such that indoor air levels in the finished leased space shall not exceed 0.016 parts per million (ppm) of formaldehyde. All materials comprised of combustible substances, such as wood plywood and wood boards, shall be treated with fire retardant chemicals by a pressure impregnation process or other methods that treats the materials throughout as opposed to surface treatment.

2.04 ADHESIVES AND SEALANTS (SMALL) (OCT 2020)

All adhesives employed on this project (including, but not limited to, adhesives for carpet, carpet tile, plastic laminate, wall coverings, adhesives for wood, or sealants) shall meet the requirements of the manufacturer of the products adhered or involved. The Lessor shall use adhesives and sealants with no heavy metals and that do not result in indoor air levels above 0.016 parts per million (ppm) of formaldehyde. Adhesives and other materials used for the installation of carpets shall be limited to those having a flash point of 140 degrees F or higher.

2.05 BUILDING SHELL REQUIREMENTS (SMALL) (OCT 2019)

A. The Building Shell shall be designed, constructed, and maintained in accordance with the standards set forth herein and completed prior to acceptance of Space.

B. Base structure and Building enclosure components shall be complete. All common areas accessible by the Government, such as lobbies, fire egress corridors and stairwells, elevators, garages, and service areas, shall be complete. Restrooms shall be complete and operational. All newly installed Building shell components, including but not limited to, heating, ventilation, and air conditioning (HVAC), electrical, ceilings, sprinklers, etc., shall be furnished, installed, and coordinated with TIs. Circulation corridors are provided as part of the base Building only on multi-tenanted floors where the corridor is common to more than one tenant. On single tenant floors, only the fire egress corridor(s) necessary to meet code is provided as part of the shell.

C. The Building Shell rental rate shall also include, but is not limited to, insurance, taxes, lease commission and management, in addition to profit, reserve costs and loan financing for the Building.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

2.06 RESPONSIBILITY OF THE LESSOR AND LESSOR’S ARCHITECT/ENGINEER (SMALL) (SEP 2015)

The Lessor remains solely responsible for designing, constructing, operating, and maintaining the leased premises in full accordance with the requirements of the Lease. The Lessor shall, without additional compensation, correct or revise any errors or deficiencies in its designs, drawings, specifications, or other services, as noted by the Government’s review or otherwise.

2.07 MEANS OF EGRESS (MAY 2015)

A. Prior to occupancy, the Premises and any parking garage areas shall meet or will be upgraded to meet either the applicable egress requirements in the National Fire Protection Association, Life Safety Code (NFPA 101) or the International Code Council, International Building Code (IBC), each current as of the Lease Award Date, or use an alternative approach or method that achieves an equivalent level of safety deemed acceptable by the Government.

B. The Space shall have unrestricted access to a minimum of two remote exits on each floor of Government occupancy.

C. Interlocking or scissor stairs located on the floor(s) where Space is located shall only count as one exit stair.

D. A fire escape located on the floor(s) where Space is located shall not be counted as an approved exit stair.

E. Doors shall not be locked in the direction of egress unless equipped with special locking hardware in accordance with requirements of NFPA 101 or the IBC.

2.08 AUTOMATIC FIRE SPRINKLER SYSTEM (OCT 2023)

A. Any portion of the Space located below-grade, including parking garage areas, and all areas in a Building referred to as

"hazardous areas" (defined in National Fire Protection Association (NFPA) 101) that are located within the entire Building (including non-Government areas) shall be protected by an automatic fire sprinkler system or an equivalent level of safety.

B. For Buildings in which any portion of the Space on or above the sixth floor, then, at a minimum, the Building up to and including the highest floor of Government occupancy shall be protected by an automatic fire sprinkler system or an equivalent level of safety.

C. For Buildings in which the Government occupies, either through this Lease or in combination with other Government Leases in the Building any portion of the Space is on or above the sixth floor, and lease of the Space will result, either individually or in combination with other Government Leases in the Building, in the Government leasing 35,000 or more ANSI/BOMA Occupant Area SF of Space in the Building, then the entire Building shall be protected throughout by an automatic fire sprinkler system or an equivalent level of safety.

D. Automatic fire sprinkler system(s) shall be installed in accordance with the requirements of NFPA 13, Standard for the Installation of Sprinkler Systems that was in effect on the actual date of installation.

E. Automatic fire sprinkler system(s) shall be maintained in accordance with the requirements of NFPA 25, Standard for the

Inspection, Testing, and Maintenance of Water-based Fire Protection Systems (current as of the Lease Award Date).

F. "Equivalent level of safety" means an alternative design or system (which may include automatic fire sprinkler systems), based upon fire protection engineering analysis, which achieves a level of safety equal to or greater than that provided by automatic fire sprinkler systems.

2.09 FIRE ALARM SYSTEM (SEP 2013)

A. A Building-wide fire alarm system shall be installed in the entire Building in which any portion of the Space is located on the 3rd floor or higher.

B. The fire alarm system shall be installed in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling

Code, that was in effect on the actual date of installation.

C. The fire alarm system shall be maintained in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling

Code (current as of the Lease Award Date).

D. The fire alarm system shall transmit all fire alarm signals to the local fire department via any of the following means: directly to the local fire department, to the (911) public communications center, to a central station, to a remote supervising station, or to a proprietary supervising station.

E. If the Building’s fire alarm control unit is over 25 years old as of the date of award of this Lease, Lessor shall install a new fire alarm system in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code (current as of the Lease Award Date), prior to Government acceptance and occupancy of the Space.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

2.10 ENERGY INDEPENDENCE AND SECURITY ACT (SMALL) (SEP 2015)

The Lessor shall either earn the ENERGY STAR® Label or complete all cost-effective energy efficiency and conservation improvements, agreed to by Lessor prior to acceptance of the Space (or not later than one year after the Lease Award Date of a succeeding or superseding Lease).

2.11 ELEVATORS (SMALL) (OCT 2020)

A. The Lessor shall provide suitable passenger elevator and, when required by the Government, freight elevator service to any of the Premises not having ground level access. Service shall be available during the normal hours of operation specified in the in this Lease.

B. Code. Elevators shall conform to the requirements of the American Society of Mechanical Engineers ASME A17.1/CSA B44, Safety Code for Elevators and Escalators that were in effect based on the elevator installation date code year. Elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1/CSA B44. Fire alarm initiating devices (e.g., smoke detectors) used to initiate Phase I emergency recall operation shall be installed in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code. The elevators shall be inspected and maintained in accordance with the current edition of the ASME A17.2, Inspector’s Manual for Elevators. Except for the reference to ASME A17.1 in ABAAS, Section F105.2.2, all elevators must meet ABAAS requirements for accessibility in Sections 407, 408, and 409 of ABAAS.

C. Safety Systems. Elevators shall be equipped with telephones or other two-way emergency communication systems. The system used shall be marked and shall reach an emergency communication location staffed 24 hours per day, 7 days per week.

2.12 DEMOLITION (JUN 2012)

The Lessor shall remove existing abandoned electric, telephone, and data cabling and devices, as well as any other improvements or fixtures in place to accommodate the Government’s requirements. Any demolition of existing improvements that is necessary to satisfy the Government’s layout shall be done at the Lessor’s expense.

2.13 ACCESSIBILITY (OCT 2024)

The Building, leased Space, and areas serving the leased Space shall be accessible to persons with disabilities in accordance with the Architectural Barriers Act Accessibility Standard (ABAAS), Appendices C and D to 36 CFR Part 1191 (ABA Chapters 1 and 2, and Chapters 3 through 10) and 36 CFR 1190 to the extent applicable. To the extent the standards referenced in the preceding sentence conflicts with local accessibility requirements, the more stringent shall apply.

2.14 CEILINGS (SMALL) (OCT 2019)

A complete acoustical ceiling system (which includes grid and lay-in tiles, or other Building standard ceiling system as approved by the LCO) throughout the Premises and all common areas accessible to Government tenants shall be required. The acoustical ceiling system shall be furnished, installed, and coordinated with TIs.

Ceilings shall be uniform in color and appearance throughout the Space, with no obvious damage to tiles or grid.

2.15 EXTERIOR AND COMMON AREA DOORS AND HARDWARE (SEP 2013)

A. Exterior Building doors and doors necessary to the lobbies, common areas, and core areas shall be required. This does not include suite entry or interior doors specific to TIs.

B. Exterior doors shall be weather tight and shall open outward. Hinges, pivots, and pins shall be installed in a manner which prevents removal when the door is closed and locked. These doors shall have a minimum clear opening of 32" clear wide x 80" high (per leaf). Doors shall be heavy duty, flush, 1) hollow steel construction, 2) solid core wood, or 3) insulated tempered glass. As a minimum requirement, hollow steel doors shall be fully insulated, flush, #16-gauge hollow steel. Solid-core wood doors and hollow steel doors shall be at least 1-3/4 inches thick. Door assemblies shall be of durable finish and shall have an aesthetically pleasing appearance acceptable to the LCO. The opening dimensions and operations shall conform to the governing building, fire safety, accessibility, and energy codes and/or requirements. Fire door assemblies shall be listed and labeled. Labels on fire door assemblies shall be maintained in a legible condition. Fire door assemblies and their accompanying hardware, including frames and closing devices shall be installed in accordance with the requirements of NFPA 80, Standard for Fire Doors and Other Opening Protectives.

C. Exterior doors and all common area doors shall have door handles or door pulls with heavyweight hinges. All doors shall have corresponding doorstops (wall or floor mounted) and silencers. All public use doors and restroom doors shall be equipped with kick plates. All doors shall have automatic door closers. All Building exterior doors shall have locking devices installed to reasonably deter unauthorized entry.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

2.16 WINDOWS (SMALL) (OCT 2020)

All exterior window assemblies shall be locked, weather resistant and watertight. Windows intended for use as a secondary means of egress must be openable from the egress side (e.g., inside) of the Building without the use of a key, tool, or special knowledge or effort for operation from the egress side.

2.17 PARTITIONS: PERMANENT (SMALL) (OCT 2019)

Permanent partitions shall extend from the structural floor slab to the structural ceiling slab, surrounding the Space, stairs, corridors, elevator shafts, restrooms, all columns, and janitor closets. They shall have a flame spread rating of 25 or less and a smoke development rating of 450 or less (ASTM E-84). Stairs, elevators, and other floor openings shall be enclosed by partitions and shall have the fire resistance required by the applicable building code, fire code and ordinances adopted by the jurisdiction in which the Building is located (such as the International Building Code, etc.) current as of the Lease Award Date.

2.18 INSULATION: THERMAL, ACOUSTIC, AND HVAC (SMALL) (OCT 2020)

A. No insulation installed with this project shall be material manufactured using chlorofluorocarbons (CFCs), nor shall CFCs be used in the installation of the product.

B. All insulation containing fibrous materials exposed to air flow shall be rated for that exposure or shall be encapsulated.

C. Insulating properties for all materials shall meet or exceed applicable industry standards. Polystyrene products shall meet

American Society for Testing and Materials (ASTM) C578 91.

D. All insulation shall contain low emitting volatiles and not result in indoor air levels above 0.016 parts per million (ppm) of formaldehyde.

E. The maximum flame spread and smoke developed index for insulation shall meet the requirements of the applicable local codes and ordinances (current as of the Lease Award Date) adopted by the jurisdiction in which the Building is located.

2.19 PAINTING – SHELL (SMALL) (OCT 2020)

The Lessor shall bear the expense for all painting associated with the Building shell, including all common areas. Exterior perimeter walls and interior core walls within the Space shall be spackled and prime painted. If any Building shell areas are already painted prior to TIs, then the Lessor shall repaint, at the Lessor’s expense, as necessary during TIs.

2.20 FLOORS AND FLOOR LOAD (SMALL) (OCT 2019)

A. All adjoining floor areas shall be of a common level.

B. Under-floor surfaces shall be smooth and level. Office areas shall have a minimum live load capacity of 50 pounds per ABOA

SF plus 20 pounds per ABOA SF for moveable partitions. Storage areas shall have a minimum live load capacity of 100 pounds per ABOA SF, including moveable partitions. Lessor may be required to provide a report by a registered structural engineer showing the floor load capacity, at the Lessor’s expense. Calculations and structural drawings may also be required.

2.21 MECHANICAL, ELECTRICAL, PLUMBING: GENERAL (SMALL) (SEP 2015)

A. The Lessor shall be responsible for meeting the applicable requirements of all federal, state, and local codes and ordinances.

When codes conflict, the more stringent standard shall apply.

B. The Lessor shall provide and operate all Building equipment and systems in accordance with applicable technical publications, manuals, and standard procedures.

C. Convenience outlets shall be installed in accordance with NFPA Standard 70, National Electrical Code, or local code, whichever is more stringent. The Lessor shall provide duplex utility outlets in restrooms, corridors, and dispensing areas.

2.22 DRINKING FOUNTAINS (MAY 2025)

On each floor of Government-occupied Space, the Lessor shall provide drinking fountain(s) with chilled potable water within 200 feet of travel from any Government-occupied area on the floor. The fountain(s) shall comply with Section F211 of the Architectural Barriers Act Accessibility Standard. The Lessor shall provide two separate drinking fountains per F211.2 or a single drinking fountain per the F211.2 Exception. Either installation shall require compliance with 602.1 through 602.6 for the accessible fountain and 602.7 for the non-accessible fountain. Potable is defined as water meeting current EPA National Primary Drinking Water Regulations under the Safe Drinking Water Act of 1974 or more stringent, applicable state or local regulations. The Lessor shall serve as first responder to any occupant complaints about drinking water. The Lessor shall promptly investigate any such complaints and implement the necessary controls to address the complaints and maintain potable water conditions.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

2.23 RESTROOMS (SMALL) (OCT 2022)

A. Separate restroom facilities for men and women shall be provided in accordance with local code or ordinances, on each floor occupied by the Government in the Building. The facilities shall be located so that employees will not be required to travel more than 500 feet, on one floor to reach the restrooms. Each restroom shall have sufficient water closets enclosed with stall partitions and doors, urinals (in men's room), and hot (set in accordance with applicable building codes) and cold water. Water closets and urinals shall not be visible when the exterior door is open.

B. Restrooms must meet ABAAS requirements as stated under this Lease.

2.24 HEATING, VENTILATION, AND AIR CONDITIONING – SHELL (SMALL) (MAY 2025)

A. Central HVAC systems shall be installed and operational, including, as appropriate, main and branch lines, VAV boxes, dampers, flex ducts, and diffusers, for an open office layout, including all Building common areas. Systems shall be designed with sufficient systems capacity to meet all requirements in this Lease; equipment shall be concealed. Areas having excessive heat gain or heat loss or affected by solar radiation at different times of the day, shall be independently controlled.

B. Any ductwork to be reused and/or to remain in place shall be cleaned, tested, and demonstrated to be clean in accordance with the standards set forth by NADCA. The cleaning, testing, and demonstration shall occur immediately prior to Government occupancy to avoid contamination from construction dust and other airborne particulates.

C. During working hours in periods of heating and cooling, ventilation shall be provided in accordance with the American National

Standards Institute, American Society of Heating, Refrigeration and Air-Conditioning Engineers (ANSI/ASHRAE) Standard 62.1, Ventilation for Acceptable Indoor Air Quality Lessors must comply with: (a) the version of ASHRAE Standard 62.1 that corresponds with how the HVAC system was designed to perform, or (b) ASHRAE Standard 62.1-2004 – whichever is later.

D. Heating and air-conditioning air distribution systems (air handling units, VAV boxes, fan coil units, etc.) for the Space shall be equipped with particulate matter air filters that meet the Minimum Efficiency Reporting Value (MERV) specified in the ANSI/ASHRAE Standard 62.1 version referenced in the sub-paragraph above. Where practicable, the Lessor is encouraged to use a MERV 13 air filter or the highest-level filter that is compatible with the HVAC system. Locations that do not meet the EPA National Ambient Air Quality Standards (NAAQS) for particulates (PM 10 or PM 2.5) must be equipped with additional filtration on outdoor air intakes as required in ANSI/ASHRAE Standard 62.1. NAAQS information can be found at

HTTPS://WWW.EPA.GOV/GREEN-BOOK.

E. For all refrigerant-containing equipment with over 50 pounds of ozone-depleting substances (including chlorofluorocarbons-

CFCs or hydrochlorofluorocarbons- HCFCs), the Lessor shall comply with the associated regulations (40 CFR 82 and 84) to use acceptable refrigerant substitutes when equipment is replaced, retrofitted, or when newly purchased. The Lessor must comply with the associated regulations (40 CFR 82 and 84). The Lessor must track the type and quantity of refrigerant used in each chiller, air conditioning, and refrigeration system containing 50 pounds or more of refrigerant. Upon request, the Lessor must provide the Government with the dates for planned replacement or retrofit of equipment with CFC or HCFC refrigerant. Upon request, the Lessor must provide the Government with the dates for planned replacement or retrofit of equipment with CFC or HCFC refrigerant.

2.25 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (SMALL) (SEP 2015)

A. Building telecommunication rooms must be completed, operational, and ready for use by Government’s telecommunications provider. The telephone closets shall be equipped with deadlocking latch bolt and include a telephone backboard.

B. Telecommunications switch rooms, wire closets, and related spaces shall meet applicable Telecommunications Industry

Association (TIA), Electronic Industries Alliance (EIA) and NFPA standards. Bonding and grounding shall be in accordance with NFPA Standard 70, NEC National Electrical Code, and other applicable NFPA standards and/or local code requirements.

2.26 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (SMALL) (OCT 2020)

A. The Government may elect to contract its own telecommunications service in the Space.

B. The Lessor shall allow the Government’s designated telecommunications providers access to utilize existing Building wiring to connect its services to the Government’s Space, or, if existing Building wiring is insufficient, the Lessor shall provide access from the point of entry into the Building to the Government’s floor Space, subject to any inherent limitations in the pathway involved.

C. The Lessor shall allow the Government’s designated telecommunications providers to affix telecommunications antennas to roof, parapet, or Building envelope (access from the antennas to the Premises shall be provided) and to affix transmission devices in appropriate common areas so as to allow the use of cellular telephones and other emerging technologies.

2.27 LIGHTING: INTERIOR AND PARKING – SHELL (SMALL) (OCT 2022)

Note. for pricing estimating purposes, fixtures will be installed at the average ratio of 1 fixture per 80 ABOA sf.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

A. Interior Fixtures. Light fixtures (and associated ballasts or drivers) shall be installed to match the other luminaries in the Space as either ceiling grid or pendant mounted for an open-office plan. Ceiling grid fixtures shall be either 2’ wide by 4’ long or 2’ wide by 2’ long. Lessor shall provide, as part of Shell Rent, a minimum overall lighting fixture efficiency of 85 percent. Lamps shall maintain a uniform color level throughout the lease term.

B. Lighting Levels. Fixtures shall have a minimum of two tubes and shall provide 50 foot-candles at desktop level (30” above finished floor) with a maximum uniformity ratio of 1.5:1. Lessor shall provide, as part of Shell Rent, 10 average foot-candles in all other Building areas within the Premises with a uniformity ratio of 4:1. Emergency egress lighting levels shall be provided in accordance with the local applicable building codes (but not less than 1 foot-candle, measured at the floor) by either an onsite emergency generator or fixture mounted battery packs.

C. Power Density. The maximum fixture power density shall not exceed 1.4 watts per ABOA SF.

D. Building Perimeter. Exterior parking areas, vehicle driveways, pedestrian walks, and the Building perimeter lighting levels shall be designed per Illuminating Engineering Society (IES) standards. Provide 5 foot-candles for doorway areas, 3 foot-candles for transition areas and at least 1 foot-candle at the surface throughout the parking lot. Parking lot fixtures shall provide a maximum to minimum uniformity ratio of 15:1 and a maximum to average uniformity ratio of 4:1.

E. Parking Structures. The minimum illuminance level for parking structures is 5 foot-candles as measured on the floor with a uniformity ratio of 10:1.

F. Exterior Power Backup. Exterior egress, walkway, parking lot, and parking structure lighting must have emergency power backup to provide for safe evacuation of the Building.

G. Video Surveillance System (VSS). Lighting shall be provided in such a manner to adequately support VSS operations and not limit or preclude adequate fields of view.

2.28 INDOOR AIR QUALITY DURING CONSTRUCTION (SMALL) (OCT 2021)

A. All safety data sheets (SDS) shall comply with Occupational Safety and Health Administration (OSHA) requirements for the

Globally Harmonized System of Classification and Labeling of Chemicals (GHS). The Lessor and its agents shall comply with all recommended measures in the MSDS to protect the health and safety of personnel.

B. Where demolition or construction work occurs adjacent to occupied Space, the Lessor shall erect appropriate barriers (noise, dust, odor, etc.) and take necessary steps to minimize interference with the occupants. This includes maintaining acceptable temperature, humidity, and ventilation in the occupied areas during window removal, window replacement, or similar types of work.

C. The Lessor shall sufficiently flush-out or ventilate the area(s) following construction and prior to occupancy in order to remove any detectable odors or visible dust related to the work.

2.29 INTENTIONALLY DELETED

SECTION 3 DESIGN, CONSTRUCTION, AND POST AWARD ACTIVITIES

3.01 SCHEDULE FOR COMPLETION OF SPACE (SMALL) (OCT 2020)

Design and construction activities for the Space shall commence upon Lease award. The Lessor shall schedule the following activities to achieve timely completion of the work required by this Lease:

A. Design Intent Drawings. The Lessor shall prepare and deliver to the Government, as part of the shell cost, design intent drawings

(DIDs) meeting all requirements set forth in the Lease within 10 WORKING DAYS of the Lease Award Date. The Government shall respond within 10 WORKING DAYS of receipt of the DIDs by either issuing a Notice to Proceed or providing notice indicating the manner in which the DIDs do not meet all requirements of the Lease. If the DIDs do not conform to the Lease requirements, the Lessor shall revise and resubmit the DIDs within 3 WORKING DAYS. The Lessor shall be responsible for delays to Acceptance of the Premises attributable to the Lessor's failure to prepare DIDs conforming to the Lease requirements.

For the purposes of this Lease, DIDs are defined as layout line drawings of the leased Space, reflecting all Lease requirements, showing partitions and doors; schematic demolition; voice, data, and electrical outlet locations; finishes; generic furniture layout, and any additional details necessary to communicate the design intent to the lessor’s architect for the purpose of preparing the construction documents (CDs). A full DID set must include the following elements:

1. Level 1 (included in Shell rent).

a. Cover Sheet;

b. Demolition Plan (if applicable);

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

c. Construction (Partition) Plan;

d. Power/ Data/ Telecommunication (Electrical) Plan;

e. Reflected Ceiling Plan

f. Furniture Plan (generic); and

g. Finish Plan.

h. Security Plan

B. Lessor Preparation and Submission of Construction Drawings.

If required per local jurisdiction for purposes of construction and permitting,

1. The Lessor as part of the TI shall complete construction drawings (CDs) conforming to the approved DIDs not later than 10 WORKING DAYS following the approval of DIDs. If during the preparation of CDs the Lessor becomes aware that any material requirement indicated in the approved DIDs cannot be reasonably achieved, the Lessor shall promptly notify USDA and shall not proceed with completion of CDs until direction is received from the LCO. The LCO shall provide direction within 5 WORKING DAYS of such notice, but the Government shall not be responsible for delays to completion of CDs occasioned by such circumstances. For the purpose of this paragraph, a "material requirement" shall mean any requirement necessary for the Government's intended use of the Space as provided for in, or reasonably inferable from, the Lease and the approved DIDs (e.g., number of workstations and required adjacencies).

2. The Lessor's CDs shall include, and not be limited to, all mechanical, electrical, plumbing, fire protection, life safety, lighting, structural, security, and architectural improvements scheduled for inclusion into the Space. CDs may also include signage, audio/visual, IT, furniture, and other specialties. CDs shall be annotated with all applicable specifications. CDs shall also clearly identify TIs already in place and the work to be done by the Lessor or others. Notwithstanding the Government’s review of the CDs, the Lessor is solely responsible and liable for their technical accuracy and compliance with all applicable Lease requirements.

C. Government review of CDs. The Government shall have 10 Working Days to review CDs before Lessor proceeds to prepare a

TI price proposal for the work described in the CDs. At any time during this period of review, the Government shall have the right to require the Lessor to modify the CDs to enforce conformance to Lease requirements and the approved DIDs.

D. Notice to Proceed (NTP). If the DIDs conform to the Lease requirements, the Government shall issue NTP; however, the

Government shall not be obligated to issue a NTP less than 10 WORKING DAYS from receipt of DIDs, as originally submitted or revised. Issuance of NTP shall not be construed as a waiver of any requirement set forth in this Lease.

E. Construction Schedule. The Lessor shall complete all required build-out conforming to the Lease and approved DIDs within 60

WORKING DAYS of issuance of NTP.

F. Construction schedule and initial construction meeting. The Lessor shall furnish a detailed construction schedule to the Government within 10 WORKING DAYS of issuance of the NTP. Such schedule shall also indicate the dates available for Government contractors to install telephone/data lines or equipment, if needed. Within 5 WORKING DAYS of NTP, the Lessor shall initiate a construction meeting. This meeting may be held in person or virtually, at the discretion of the Government. The Lessor will have subcontractor representatives including its architects, engineers, general contractor and subcontractors’ representatives in attendance. The Lessor shall keep meeting minutes of discussion topics and attendance and shall distribute to all parties within 3 WORKING DAYS of the meeting.

G. Progress Reports. After the start of construction, the Lessor shall submit to the LCO or designated representative written progress reports at intervals of 10 WORKING DAYS. Each report shall include information as to the percentage of the work completed by phase and trade; along with labeled photographs, a statement as to expected completion and occupancy dates;

changes introduced into the work; and general remarks on such items as material shortages, strikes, weather, etc., that may affect timely completion. In addition, at the Government’s discretion, the Lessor shall conduct meetings every two weeks to brief Government personnel and/or contractors regarding the progress of design and construction of the Space. These meetings may be held in person or virtually, at the discretion of the Government. The Lessor shall be responsible for taking and distributing minutes of these meetings.

H. Construction Inspections. The LCO or the LCO's designated technical representative may periodically inspect construction work to review compliance with Lease requirements and approved DIDs, if applicable. Periodic reviews, witnessing of tests, and inspections by the Government shall not constitute approval of the Lessor's apparent progress toward meeting the Government's objectives but are intended to discover any information which the LCO may be able to call to the Lessor's attention to prevent costly misdirection of effort. The Lessor shall remain responsible for designing, constructing, operating, and maintaining the Building in full accordance with the requirements of the Lease. At the discretion of the LCO, minutes from the progress meetings may satisfy the requirement for written progress reports.

3.02 ACCESS BY THE GOVERNMENT PRIOR TO ACCEPTANCE (SMALL) (OCT 2020)

Subject to the Lessor's permission, which shall not be unreasonably withheld, the Government or its contractors shall have access to the Premises prior to acceptance of the Space to prepare the Space for occupancy. If the work to be completed by the Government is a prerequisite for the issuance of a Certificate of Occupancy, or its equivalent, the Government shall be entitled to at least 10 Working Days to complete work by its own contractors.

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

3.03 ACCEPTANCE OF SPACE AND CERTIFICATE OF OCCUPANCY (SMALL) (OCT 2021)

A. The Government shall accept the Space only if the construction of Building shell and TIs, as applicable, conforming to this Lease and any layout drawings is substantially complete, as determined by the Lease Contracting Officer, and a Certificate of Occupancy (C of O) has been issued. The Space shall be considered substantially complete only if the Space may be used for its intended purpose and completion of remaining work will not interfere unreasonably with the Government's enjoyment of the Space.

B. The Lessor shall provide a valid C of O, issued by the local jurisdiction, for the intended use of the Government. If the local jurisdiction does not issue C of O’s or if the C of O is not available, the Lessor may satisfy this condition by providing a report prepared by a licensed fire protection engineer that indicates the Space and Building are compliant with all applicable local codes and ordinances and all fire protection and life safety-related requirements of this Lease.

C. If applicable, upon acceptance of the Space, the Government will issue lump sum payment to the Lessor after substantial completion, in accordance with invoicing procedures outlined under any lease amendment(s) authorizing such lump sum payment. The Government shall not issue this payment in increments or as partial payments.

3.04 LEASE TERM COMMENCEMENT DATE AND RENT RECONCILIATION (SMALL) (OCT 2021)

The Lease Term Commencement Date, and final measurement verification of the Space, shall be memorialized by Lease Amendment.

3.05 AS-BUILT DRAWINGS (OCT 2021)

Not later than 30 days after the acceptance of the Space, the Lessor, at Lessor’s expense, shall furnish to the Government a complete set of Computer Aided Design (CAD) files of as-built floor plans showing the Space under Lease, as well as corridors, stairways, and core areas. As-built drawings shall include those for Civil, Architectural, Mechanical, Electrical, and Plumbing features, including, but not limited to, those for IT, Communications, Security, and Fire Protection. The plans shall have been generated by a CAD program which is compatible with the latest release of AutoCAD. The required file extension is “.DWG.” Clean and purged files shall be submitted in a digital format. They shall be labeled with Building name, address, list of drawing(s), date of the drawing(s), and Lessor's architect and architect’s phone number.

3.06 SEISMIC RETROFIT (OCT 2020)

The following requirements apply to Leases requiring seismic retrofit:

A. The Lessor shall provide a final construction schedule, all final design and construction documents for the seismic retrofit, including structural calculations, drawings, and specifications to the Government for review and approval prior to the start of construction. When required by local building code, a geotechnical report shall be made available to the Government.

B. The Lessor’s registered civil or structural engineer shall perform special inspections to meet the requirements of Chapter 17 of the International Building Code (IBC).

C. For Leases requiring seismic retrofit, the Space will not be considered substantially complete until a Seismic Form E - Certificate of Seismic Compliance - Retrofitted Building, certifying that the Building meets the Basic Safety Objective of ASCE/SEI 41, executed by a registered civil or structural engineer, has been delivered to the LCO.

3.07 GOVERNMENT PROJECT MANAGEMENT SYSTEM (MAY 2025)

The Government may require the Lessor to use the Government’s project management system for post-award and post-occupancy activities. This includes, but is not limited to, design submittals (DIDs, CD, as-builts), schedule submissions, pricing proposals, requests for information (RFI) that are directed toward the Government, and Lease Submittals, such as reuse plans, commissioning plans, and product data sheets. Licensing costs and access to the system are the responsibility of the Government.

SECTION 4 TENANT IMPROVEMENT COMPONENTS

4.01 TENANT IMPROVEMENTS AND PRICING (SMALL) (SEP 2015)

The Lease is a fully serviced, turnkey Lease with a fixed rent that covers all Lessor costs, including all demolition, shell upgrades, TIs, insurance, operating costs, taxes, parking, and security upgrades. Rent will be based upon a proposed rental rate per rentable square foot (RSF), limited by the offered rate and the maximum ABOA SF solicited under this RLP. The Tenant Improvements to be delivered by the Lessor will be based upon information provided with this Lease. The Lessor will be required to design and build the TIs and will be compensated for the TI costs through the rent. Offerors are encouraged to consider the use of existing fit-out and other improvements to minimize waste.

A. The TI Unit Costs listed below will be used to make the adjustment for variances between turnkey pricing based on the agency specific requirements package (ASRs), and the approved design intent drawings. The prices quoted will also be used to order

LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE

alterations during the first year of the Lease. The prices quoted shall be the cost to furnish, install, and maintain each item, unless otherwise specified. These prices may be indexed or renegotiated to apply to subsequent years of the Lease upon mutual agreement of the Lessor and the Government. Final rent calculations will be reconciled and the Lease will be amended after acceptance of the Space.

1. The cost per linear foot of office subdividing ceiling-high partitioning: ______________

2. The cost per floor-mounted duplex electrical outlet: ______________

3. The cost per wall-mounted duplex electrical outlet: _____________

4. The cost per floor-mounted fourplex (double duplex) electrical outlet: _____________

5. The cost per wall-mounted fourplex (double duplex) electrical outlet: _____________

6. The cost per dedicated clean electrical computer receptacle: _____________

7. The cost per floor-mounted telephone outlet: _____________

8. The cost per wall-mounted telephone outlet: _____________

9. The cost per interior door: _____________

The Government shall have the right to make lump sum payments for any or all TI work.

4.02 FINISH SELECTIONS (SMALL) (SEP 2015)

The Lessor must consult with the Government prior to developing a minimum of two (2) options of coordinated finish samples. The finish options must be approved by GSA prior to installation. The Lessor may not make any substitutions.

4.03 WINDOW COVERINGS (SMALL) (OCT…

This is the start of the file's text. The full file is on GovTribe.