02D RLP 36C10F23R0095 Appendix A_3 Room Data Matrix RDM Allentown PA CBOC.pdf

PDF 243 KB Posted

Attached to
X1DB--Allentown PA OPC - RLP Extension - Electric Vehicle Supply Equipment -EVSE- Requirements
Solicitation number
36C10F23R0095
Issued by

About this file

This document contains a room data matrix and facility security requirements for the Allentown VA Outpatient Clinic major lease project in Pennsylvania.

The room data matrix provides construction specifications and design parameters for over 60 room types. It includes details on flooring, wall, and ceiling finishes; interior construction; doors and hardware; mechanical, electrical, and plumbing requirements; and IT needs. Requirements are delineated for examination, treatment, procedure, consultation, waiting, and support rooms as well as imaging, laboratory, pharmacy, dental, and other service areas. The facility security requirements outline security standards for perimeter barriers, intrusion detection, access control, surveillance systems, duress alarms and response protocols.

View the file

Other files

File Type Posted
36C10F23R0095 - Allentown PA OPC - RLP Amendment 05 - 01.18.2023.pdf PDF
36C10F23R0095 0005.docx DOCX document
26 RLP 36C10F23R0095 Allentown Electric Vehicle Supply Equipment -EVSE- Requirements.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 04 - GSA Form 3517B _ General Clauses_Dec 23.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 04 - 01.04.2024.pdf PDF
36C10F23R0095 0004.docx DOCX document
36C10F23R0095 - Allentown PA OPC - RLP Amendment 04 - GSA Form 3516 _ Solicitation Provisions_Dec 23.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 3 - GSA Form 3516 _ Solicitation Provisions_Dec 23.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 3 - GSA Form 3517B - General Clauses_Dec 23.pdf PDF
36C10F23R0095 0003.docx DOCX document
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 -02G - Facility Security Level Req for FSL II _REV_ Dec 23.pdf PDF
36C10F23R0095 0002.docx DOCX document
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - MRI Block Diagram-Example Only.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - Pre-Bid Q_A Matrix 12.15.2023.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - Pre-Bid Meeting Transcript.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - Pre Bid Conference Presentation.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - Pre Bid Conference Attendance Roster.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - 12.15.2023.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment 2 - 02D - App A.3 - Room Data Matrix_RDM - REV_ Dec 23.pdf PDF
36C10F23R0095 - Allentown PA OPC - RLP Amendment No 1 11.27.23.pdf PDF
36C10F23R0095 0001.docx DOCX document
36C10F23R0095 - Allentown PA OPC - RLP Amendment No 1 - Past Performance Questionnaire Form - Rev Nov 23.pdf PDF
01 RLP 36C10F23R0095 Lease Allentown PA CBOC.pdf PDF
13 RLP 36C10F23R0095 GSA Form 527 Contractors Qualifications and Financial Information Allentown PA CBOC.pdf PDF
03 RLP 36C10F23R0095 Appendix A_6 Conceptual Floor Plans Allentown PA CBOC.pdf PDF
08 RLP 36C10F23R0095 Attachment No 1 to GSA Form 1364 Allentown PA CBOC.xlsx XLSX spreadsheet
02C RLP 36C10F23R0095 Appendix A_2 Lease Design Narrative LDN Allentown PA CBOC.pdf PDF
02E RLP 36C10F23R0095 Appendix A_4 VA CBOC Information Transport Systems Specs Allentown PA CBOC.pdf PDF
06 RLP 36C10F23R0095 Offeror Proposal Compliance Matrix Allentown PA CBOC.pdf PDF
25 RLP 36C10F23R0095 Contractor Confidentiality Certificate Allentown PA CBOC.pdf PDF
02B RLP 36C10F23R0095 Appendix A_1 Project Room Contents List PRC Allentown PA CBOC.pdf PDF
05 RLP 36C10F23R0095 Offering Entity Acknowledgement Form Allentown PA CBOC.pdf PDF
0 RLP 36C10F23R0095 RLP Allentown PA CBOC.pdf PDF
18 RLP 36C10F23R0095 Certification of Building Energy Performance Allentown PA CBOC.pdf PDF
16 RLP 36C10F23R0095 GSA Form 3517B General Clauses Allentown PA CBOC.pdf PDF
21 RLP 36C10F23R0095 Seismic Offer Forms Allentown PA CBOC.pdf PDF
11 RLP 36C10F23R0095 Past Performance Questionnaire Allentown PA CBOC.pdf PDF
15 RLP 36C10F23R0095 GSA Form 3516 Solicitation Provisions Allentown PA CBOC.pdf PDF
09 RLP 36C10F23R0095 GSA Form 1217 Lessor_s Annual Cost Statement Allentown PA CBOC.pdf PDF
04 RLP 36C10F23R0095 Appendix B VA Janitorial and Site Management Services Allentown PA CBOC.pdf PDF
02 RLP 36C10F23R0095 Cover Page for Agency Specific Requirements ASR Allentown PA CBOC.pdf PDF
23 RLP 36C10F23R0095 Pre Bid Conference Registration Form Allentown PA CBOC.pdf PDF
12 RLP 36C10F23R0095 SF 330 Architect Engineer Qualifications Allentown PA CBOC.pdf PDF
19 RLP 36C10F23R0095 DOL Lehigh County Wage Determination Allentown PA CBOC.pdf PDF
02G RLP 36C10F23R0095 Appendix A_5 FSL II Allentown PA CBOC.pdf PDF
07 RLP 36C10F23R0095 Proposal to Lease Space GSA Form 1364 Allentown PA CBOC.pdf PDF
20 RLP 36C10F23R0095 FAR 52_204_24 Representation Regarding Certain Telecom Allentown PA CBOC.pdf PDF
14 RLP 36C10F23R0095 VA Handbook 6500_6 Allentown PA CBOC.pdf PDF
10 RLP 36C10F23R0095 VA Form 10091 FSC Vendor File Request Form Allentown PA CBOC.pdf PDF
17 RLP 36C10F23R0095 GSA Form 12000 for Prelease Fire Protection and Life Safety Evaluation for an Office Building Allentown PA CBOC.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ALLENTOWN OUTPATIENT CLINIC MAJOR LEASE

ROOM DATA MATRIX

NOTES

Functional

Area

DEPARTMENT ROOM NAME ROOM NAMES (VA)

FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR

TABLE 1.2-5 Minimum Sound

Isolation

F lo o r

F in is h

B a s e

W a ll F in is h

W a in s c o t M a te ri a l

W a in s c o t H e ig h t

S T

C

C e il in g F in is h

H e ig h t

N o te s

S iz e

W id th

T y p e

M a te ri a l

G la z in g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r

T e m p e ra tu re

C o o li n g

F

In d o o r

T e m p e ra

H e a ti n g

F

In d o o r R e la ti v u m id it y

R

H M a x

In d o o r R e la ti m id it y

R

H M in

M in im u m T o ta l

A C

H

M in im u m O

A A

C H

R o o m

A ir

R e rn

G n

E x h

G S p c

E x h

S

M a x im u m

N o is

L v e l N

C

R o o m

A ir

B a la n

V

A C

N o te s

D u p le

R c e p ta c le s

Q u a d c e p ta c le s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

L ig h ti n g

S p e c ia l

R e q u ir e m e n ts

L ig h ti n g

N o te s

D a ta

O u tl ts

(s ta n d a rd d e n s it y

W A

O

IT

S p e c ia l

R e q u ir e m e n ts

GENERAL

ROOMS/SPACES

Exam Room PACT Exam EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10

3'-0"

3'-6"

Flush Wood _ _ 12 SE 3 75 70 60 30 6 2 Return 35 0 8 1 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

Multi-level switching or manual dimming L7 3

GENERAL

ROOMS/SPACES

Exam Room

Exam Room - Multi-Specialty, Exam / Treatment, Exam -

Consult, Consult Room - PACT, Exam/Consult Room (Mental

Health/Social Work), Exam Room

EMG/EEG, Exam Room-

Cardiology, Exam/Consult, Nurse

Practitioner, Women's Health

Exam, Tele-Health Exam, Optometry Exam Treatment

Room, Eye Lane, Tele-Retinal, Tele-Derm, TECHS, Appliance

Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment Room, Derm Biop, Pulmonary, Podiatry, Speech Pathology, Pulmonary

Function Room, Tele-Health, EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10 3'-6" Flush Wood _ _ 12 S 75 70 60 30 6 2 Return 35 0 8 1 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

Multi-level switching or manual dimming L7, L8 3

GENERAL

ROOMS/SPACES

Consult Room

Consult Room, Audiology

Rehabilitation Counceling Room, Dental Consult Room, Group

Therapy Room - Speech

Pathology, Consult Room -

Mental Health, PACT

CONSULTATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 4 2 Return 40 0 6 P2, 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

Multi-level switching or manual dimming N/A 1

GENERAL

ROOMS/SPACES

Procedure Room

Procedure Room, General, Urology, Gynecology, Specialty

Care, Multi-Specialty Care, Cast

Room, Pain Management, Women's Health

PROCEDURE TREATMENT WSF WSF EP RWC 4'-0" SEE FGI AT 9'-0" 3

3'-0"

3'-6"

Flush Wood -- -- 12 SE 3 75 70 60 20 15 3 7 P13

Multilevel Switching, Dimming &

Occupancy

Wall mounted exam light L7 2

GENERAL

ROOMS/SPACES

Laboratory Laboratory (Typical)

LABORATORY

WORKROOM

__ WSF WSF EP -- -- 40 AT-SP 9'-0" 3 3'-0" Flush Wood _ _ 15 AG 4 6 P3, P4

Multilevel Switching, Dimming &

Occupancy

N/A N/A 5

GENERAL

ROOMS/SPACES

Conference Room

Conference Room, Multi-Purpose

Room, Group Room, Shared

Medical Appointment Room, Education Room, Staff Training

Room, Classroom, Group

Therapy Room - Mental Health

__ LVT RB P RWC 4'-0" 40 AT 9'-0" 17 3'-6" Flush Wood _ _ 15 S _ 75 70 60 30 4 2 Return 35 0 M2 8 P14 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

Provide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections.

N/A 4 Floor data for table

GENERAL

ROOMS/SPACES

TOILET

Toilet, Family; Toilet, Staff;

Toilet, General Procedure Room

Patient; Toilet, Women's Health

Procedure Room Patient; Toilet, PACT Patient; Toilet, Women's

Health Patient; Toilet, Women's

Health Exam Room Patient;

Toilet, Audiology Patient;

Universal Patient, Eye; Universal

Patient Toilet; Toilet, Multi-

Specialty Patient; Toilet, Multi-

Specialty Procedure Room

Patient; Toilet, PM&R Patient;

Toilet, R/F Patient; Toilet, Ultrasound Patient; Toilet, Employee Blood Specimen

Collection Room; Toilet, Specimen Collection; Female Six-

Stall Non-Patient Multi-User

Toilet, Bldg Sprt; Male Four-Stall

Non-Patient Multi-User Toilet, Bldg Sprt; Universal Non-Patient

Toilet, Bldg Sprt

TOILET ROOM TOILET ROOM PT PT P CT 7'-0" SEE FGI AT 9'-0" 1,2 3'-6" Flush Wood _ _ 11 _ 75 70 60 20 10 N/A Exh (G) 40 (-) 1 Downlights/Mirror or vanity Occupancy Sensor N/A N/A

GENERAL

ROOMS/SPACES

OFFICE Any Office -- CONSULTATION LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 75 70 60 30 4 2 Return 40 0 4 1 P2 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A 2

GENERAL

ROOMS/SPACES

WAITING

Waiting - Family - PACT, Waiting -

PACT 3, Waiting - General - 20

People, Waiting - General - 10

People, Waiting - General - 6

People, Waiting-General

EXAM - PUBLIC SPACE LVT RB P -- -- SEE FGI AT 9'-0" 10, 17 75 70 60 30 6 2 Return 40 0 M4 4 -- P2 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A 1

GENERAL

ROOMS/SPACES

RECEPTION

Reception, Information Desk, Travel Window, Reception -

Accessible

-- -- RFT RB P -- -- -- AT 9'-0" -- 3'-0"

Flush w/ narrow vision Wood _ _ 12 CG 3 75 70 60 30 4 2 Return 40 M4 1 1

Downlights, pendants, decorative, and accent

Multilevel Switching, Dimming &

Occupancy

N/A N/A 10

Data/phone feeds to systems furniture

GENERAL

ROOMS/SPACES

COPY ALCOVE

Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy Room

Match

Adjacent

Match

Adjacent P -- -- -- AT 9'-0" 6 _ _ _ _ _ _ 6 75 70 N/A N/A 6 2 Return 40 3 P3 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A 3

GENERAL

ROOMS/SPACES

CLEAN UTILITY

Clean Utility, Clean Supply, Clean

Workroom, Clean Linen, Sterile

Storage, Sterile Supply Storage

Room, Clean Scope, Dental

Clean Cart, Central Sterile

-- -- WSF RB P RWC 4'-0" -- AT 9'-0" -- 3'-0" Flush Wood -- 45 MIN 121 AG _ 66 75 55 30 4 N/A Return 40 (+) 1 2x2 recessed lensed Occupancy Sensor N/A N/A

GENERAL

ROOMS/SPACES

SOILED UTILITY

Soiled Utility Room, Recycled

Material, Soiled Holding, Soiled

Linen, Soiled Workroom, Soiled

Supply, Soiled Cart

SOILED HOLDING /

SOILED WORK ROOM

-- WSF WSF P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 121 AG _ 78 72 NR NR 10 2 Exh. (G) 40 (-) 2 -- 2x2 recessed lensed Occupancy Sensor N/A N/A --

GENERAL

ROOMS/SPACES

STORAGE

Storage - Medical Equipment, Storage - Shared Medical

Appointments, DME - Prosthetics

Storage, Storage - Homeless, EMS Storage, Storage -

Bistro/Coffee Bar, Storage -

Patient Clothing and Luggage, Laundry / Storage, Tray Cart

Storage Area, Bulk Storage, General Storage, Secure

Storage, CBOC PT/OT

Equipment Storage Room, PMR

Svc; Storage

CLEAN

WORKROOM/CLEAN

SUPPLY

RFT RB P RWC 4'-0"N/A -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG N/A N/A N/A N/A 4 N/A Return 40 (+) 1 per wall, not to exceed

12' spacing -- Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A 1

GENERAL

ROOMS/SPACES

JANITOR'S CLOSET

Housekeeping Aides Closet

(HAC)

ENVIRONMENTAL

SERVICES ROOM

-- QT RB P FRP 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 34 A _ NR NR NR NR 10 N/A Ehx. (G) 40 (-) 2 --

P7 Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A --

GENERAL

ROOMS/SPACES

KITCHENETTE Social Activities Space/ Kitchen -- -- RFT RB P -- -- -- AT 9'-0" 17 3'-0" Flush Wood -- -- 15 A _ 4 --

Multilevel switching/dimming/occ N/A N/A --

GENERAL

ROOMS/SPACES

EQUIPMENT ALCOVE

AED Alcove, Height and Weight

Alcove, Scale Alcove, Stretcher

Alcove, Med Alcove, Portable

Patient Lift Alcove, Wheelchair

Alcove, My Health eVet, Kiosk, Match

Adjacent

Match

Adjacent Match Adjacent RWC 4'-0" -- AT

Match

Adjacent 3 -- -- -- -- -- 6 1 -- 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A --

GENERAL

ROOMS/SPACES

STAFF LOUNGE Staff Lounge -- -- LVT RB P -- -- 40 AT 9'-0" 4 3'-0"

Flush w/ narrow vision Wood -- -- 13 _ 75 70 60 30 4 2 Exh. (G) (-) 8 --

P7 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A 2

GENERAL

ROOMS/SPACES

MEDICATION ROOM

Medication Room, Phrm Svc; CT

Medication Preparation, Imgng

Svcs

MEDICATION ROOM -- RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 34 75 70 60 30 4 2 Return 40 (+) 5 1 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A 1

GENERAL

ROOMS/SPACES

LACTATION ROOM

Employee Wellness, Lactation

Room, Quiet Room, CBOC

Lactation Room, Wm Vet Svc;

Lactation Room

-- -- RFT RB P -- -- 50 AT 9'-0" 10 3'-0" Flush Wood -- -- 12 CS 75 70 60 30 6 2 Return 35 0 4 -- P2 2X2 recessed lensed and downlights

Multilevel Switching, Dimming &

Occupancy

N/A N/A 1

GENERAL

ROOMS/SPACES

LOCKER ROOM

Locker Room, Locker Room

(Male/ Female) Locker - Staff

Personal Property, Locker Room -

Staff

-- -- RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- Push/Pull 75 70 60 30 6 N/A Exh. (G) 40 (-) 4 -- 2 X 2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A --

GENERAL

ROOMS/SPACES

OFFICE, CUBICLE, Open

Office

Cubicle - Administrative, Data

Processing, Workstation -

Extended Team, Homeless, Workstation - MICHM, Workstation - Suicide Prevention, Workstation - VOC Rehab, Workstation - Rad Tech, Workstation - Shipping /

Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical, -- -- CPT RB P -- -- -- AT 9'-0" 75 70 60 30 4 4 Exh. (G) 40 (+) 2 per workstation -- P16 2 X 2 recessed lensed and task lighting as required for type of work.

Multilevel Switching, Dimming &

Occupancy

N/A N/A 1 per workstation

GENERAL

ROOMS/SPACES

SUB-WAITING

Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-

Waiting, Sub-Waiting - Diagnostic

Patient, Sub-Waiting - Dilation

Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-

Zone 2

-- -- CPT RB P -- -- -- AT 9'-0" 10, 17 -- -- -- -- -- - 6, 10, 17 75 70 60 30 6 2 Return 40 (0) M4 4 --

2 X 2 recessed lensed and downlights as required for the type of sub waiting

(ie.: eye dilation, etc.)

Multilevel Switching, Dimming &

Occupancy

N/A N/A --

19 CANTEEN SERVICE VENDING

Randolph Sheppard Vending, Mini-mart Café, Canteen

RFT RB P -- -- 50 AT 9'-0" -- -- -- -- -- -- 6

75 70 60 30 6 2 Return 40 0 M4 8 -- P3, P7 2x2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A 4

GENERAL

ROOMS/SPACES

TOILET/SHOWER ROOM

Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff

TOILET ROOM TOILET ROOM PT PT CT -- -- SEE FGI GWB/P 9'-0" 2, 19 3'-6" Flush Wood -- -- 11 G 2 --

Multilevel Switching, Dimming &

Occupancy

N/A N/A

GENERAL

ROOMS/SPACES

CHANGING ROOM Dressing room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Wood -- -- 11 K 75 70 60 - 4 2 Return NR NR 1 -- 2 X 2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

N/A N/A

PRIMARY CARE,

SPECIALTY CARE,

PACT

PACT TEAM WORK

SPACE

PACT Team Work Space, Team

Work Area- Home Based Primary

Care, Team Work Area - Dental

Clinic

-- CPT RB P -- AT 9'-0" -- _ _ _ _ _ 14 MP 6 75 70 60 30 4 2 Return 35 (0) M3 2 per workstation -- P16 2 X 2 recessed lensed

Multilevel Switching, Dimming &

Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

L7 1 per workstation

PRIMARY CARE,

SPECIALTY CARE,

PACT

EXAM ROOM, AIRBORNE

INFECTION ISOLATION

Exam, Isolation, Negative

Pressure AII Room EXAMINATION WSF WSF P -- -- SEE FGI GWB:P 9'-0" 3,7 3'-6" Flush Wood -- -- 12 S 6 --

Multilevel Switching, Dimming & Occupancy

Sealed fixture, flat lens surface on exterior N/A 1

AUDIOLOGY AND

SLP

AUDIOLOGY HEARING

AID TESTING

Hearing Aid Lab, Hearing Aid

Processing, Hearing Aid Repair -- RFT RB P -- -- 40 AT 9'-0" -- 3'-0" Flush Wood _ _ 15 S _ 75 70 60 - Exh. (G) (-) 7 0 P4

Multilevel Switching, Dimming & Occupancy N/A N/A 2

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

ROOM IDENTIFICATION

NOTES

Functional

Area

DEPARTMENT ROOM NAME ROOM NAMES (VA)

FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR

TABLE 1.2-5 Minimum Sound

Isolation

F lo o r

F in is h

B a s e

W a ll F in is h

W a in s c o t M a te ri a l

W a in s c o t H e ig h t

S T

C

C e il in g F in is h

H e ig h t

N o te s

S iz e

W id th

T y p e

M a te ri a l

G la z in g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r

T e m p e ra o li n g

F

In d o o r

T e m p e ra a ti n g

F

In d o o r R e la ti m id it y

R

H M a x

In d o o r R e la ti m id it y

R

H M in

M in im u m T o ta l

A C

H

M in im u m O

A A

C H

R o o m

A ir

R e n

E x h

G S p h

S

M a x im u m

N o v e l N

C

R o o m

A ir

B a la n

A C

N o te s

D u p c e p ta c le s

Q u c e p ta c le s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

L ig h ti n g

S p e c ia l

R e q u ir e m e n ts

L ig h ti n g

N o te s

D a ta

O u tl n d a rd d e n s

O e c ia l

R e q u ir e m e n ts

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

ROOM IDENTIFICATION

AUDIOLOGY AND

SLP

AUDIOLOGY HEARING

AID FITTING

Audiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology

Assistive Technology Romm, Speech Language Pathology

Voice Treatment Room

EXAM -- RFT RB P -- -- 60 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 6 2 Return 25 (0) 6 P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A N/A 2

AUDIOLOGY AND

SLP

AUDIOMETRIC EXAM

BOOTH

Audiometric Exam Suite, Exam -

Audiometric Booth, Aud: Suite -

Audiometric Exam, Hearing/Diagnostics, Booth, 1-

Person

EXAM -- Pre-Fab Pre-Fab Pre-Fab -- --

Pre-Fab

Review during design

Pre-Fab 8'-0" --

3'-0"

3'-6"

Pre-Fab Pre-Fab _ _ 1 2,4 75 70 60 30 6 2 Return 25 (0) 9 P1 Provided with booth

Typically pre-packaged unit including lighting and switching

N/A L1 5

AUDIOLOGY AND

SLP

ELECTROPHYSIOLOGY

Electrophysiology, Posturography, Vestibulography, Cerument Management Room

EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 P2, P3, P14 Multilevel Switching, Dimming & Occupancy N/A N/A 3

4 DENTAL SERVICE

SPECIALTY EQUIPMENT

MECHANICAL ROOM

Dental Equipment Mech. Room, Mechanical Rooms - Electrical -- -- CS/EPY -- P -- -- 60 EXP 9'-0" 3'-6" Flush Wood -- -- 14 S 80 65 Exh. (G) (-) 2 -- P3, P17 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 1

4 DENTAL SERVICE

DENTAL PROSTHETICS

LABORATORY

Laboratory, Dental Prosthetics -- RF WSF P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 15 AG 75 70 60 20 6 2

Return

Exh. (G) 45 (-) M13 7 -- P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L7 5

4 DENTAL SERVICE

DENTAL TREATMENT

ROOM

Dental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, Bariatric

EXAM TREATMENT RF WSF P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 75 70 NR NR 3 2 Return 40 (+) 7 -- P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L7 2

4 DENTAL SERVICE DENTAL X-RAY ROOM

X-Ray Room, Panoramic /

Cephalometric (Cone Beam)

CLASS 1 IMAGING

ROOM

TREATMENT

LVT/

Electrostatic

Dissipative

Flooring

WSF P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 17 AGL 8 75 70 60 30 6 2 Return 35 (0) 7 -- P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L7 2

5 EYE CLINIC

FITTING & DISPENSING,

EYEGLASSES

Fitting & Dispensing, Eyeglasses -- RFT RB P -- -- -- AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S 6 75 70 60 - 4 2 Return 40 NR 2 Downlights and accent/display

Multilevel Switching, Dimming & Occupancy N/A N/A 2

5 EYE CLINIC

LOW VISION EXAM/

THERAPY/ TRAINING

Low Vision Exam/ Therapy/

Training EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 6 2 Return 35 (0) 6 2 X 2 recessed lensed / downlights

Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 3

5 EYE CLINIC PRE-TESTING/ INTAKE Pre-Testing/ Intake EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 6 2 Return 35 (0) 6 1 Downlights / 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 2

5 EYE CLINIC VISUAL FIELDS ROOM

Visual Fields Room, Photography

Room, Ultrasound Room, Tomography Room, Imaging

Room, OCT Laser

EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 15 3 Return 35 (+) 7 P3 Downlights Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.

N/A 2

6 MENTAL HEALTH QUIET ROOM Quiet Room for Patients EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 1

6 MENTAL HEALTH

BIOFEEDBACK

TREATMENT ROOM

Biofeedback Treatment Room EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 15 S 75 70 60 30 6 2 Return 35 (0) 4 -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A L7 2

SPECIALTY CARE

SERVICES

PULMONARY FUNCTION

ROOM (EXAM ROOM)

Pulmonary Function - Analysis EXAM TREATMENT WSF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 G 6 --

Multilevel Switching, Dimming & Occupancy N/A N/A 2

SPECIALTY CARE

SERVICES

TREADMILL ROOM Treadmill Room EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 MS 75 70 60 30 8 2 Return 35 (0) 6 -- P9

Multilevel Switching, Dimming & Occupancy N/A N/A 2

SPECIALTY CARE

SERVICES

EKG TESTING ROOM

(EXAM ROOM)

EKG Testing Room EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 12 S One per wall --

Multilevel Switching, Dimming & Occupancy N/A N/A 2

RECREATION

THERAPY

GROUP THERAPY

ROOM, MUSIC

Creative Arts - Group Therapy

Room - Music -- TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 --

Multilevel Switching, Dimming & Occupancy N/A N/A 1

RECREATION

THERAPY

GROUP THERAPY

ROOM, ART

Creative Arts - Group Therapy

Room - Large -- TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 --

Multilevel Switching, Dimming & Occupancy N/A N/A 1

RECREATION

THERAPY

WEIGHT ROOM, SMALL

Recreation Therapy Exercise /

Weight Room - Small -- TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 34 AG 12 --

Multilevel Switching, Dimming & Occupancy N/A N/A --

PHYSICAL MEDICINE

AND REHAB (PM&R)

PHYSICAL THERAPY

GYM

Treatment Exercise Area

(includes workstations therapists) EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 14 S 75 70 60 30 6 2 Return 35 (-) 14 -- P14 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 4

PHYSICAL MEDICINE

AND REHAB (PM&R)

Activities Daily Living (ADL)

Training

ADL Evaluation and Training

Center, Toilet, Tub, Bed, Kitchen, Laundry

EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A

RADIOLOGY

SERVICE

GENERAL PURPOSE

RADIOLOGY

Radiology, ES: General Purpose

Radiology Room

CLASS 1 IMAGING

ROOM

TREATMENT WSF RB P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 LS 8 75 70 60 30 6 2 Return 35 (0) M14 5 P3, P13, P17 2 X 2 recessed lensed

Fully dimmable, occupancy sensor N/A L2 4

RADIOLOGY

SERVICE

C.T. CONTROL ROOM

CT Control Area, X-Ray -

Computed Tomography - Control TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 3'-0" Flush Wood -- LEAD LINED 12 LS 75 70 60 30 6 2 Return 45 (0) M14 6 -- P3, P17 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 8

RADIOLOGY

SERVICE

C.T. EQUIPMENT ROOM

CT Equipment Room, X-Ray -

Computed Tomography - Indep

View Console, CT System

Component Room

-- VT WSF P -- -- -- AT 9'-0" 5 6'-0" Flush Wood -- -- 45 AG 7 50 M14 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 2

RADIOLOGY

SERVICE

C.T. SCAN ROOM

CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography -

Scanner

CLASS 1 IMAGING

ROOM

TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 ALG 75 70 60 30 6 2 Return 35 (0) 7 -- P3, P13, P17 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 4

RADIOLOGY

SERVICE

MAMMOGRAPHY SCAN

ROOM

Mammo - X-ray, Mammography

Room

CLASS 1 IMAGING

ROOM

TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 12 LS 75 70 60 30 6 2 Return 35 (0) 7 -- P3 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 1

RADIOLOGY

SERVICE

RADIOGRAPHIC /

FLOURO SCAN ROOM

Radiographic / Fluoroscopic (R/F)

Room

CLASS 1 IMAGING

ROOM

TREATMENT WSF WSF P - - SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 15 AGL 75 70 60 30 6 2 Return 36 (0) 7 -- P3, P13 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 4

RADIOLOGY

SERVICE

ULTRASOUND SCAN

ROOM

Ultrasound Room

CLASS 1 IMAGING

ROOM

TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- --

12 S 75 70 60 30 8 2 Return 35 (0) M14 7 -- P3, P13 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 1

RADIOLOGY

SERVICE

PACS SERVER ROOM

X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System

(PACS)

-- RFT RB P - - - AT 9'-0" 3'-0" Flush Wood -- -- 15 GK 50 4 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

RADIOLOGY

SERVICE

MRI CONTROL ROOM

MRI Control Room, X-Ray -

Magnetic Resonance - Control, MRI Zone 3

CLASS 1 IMAGING

ROOM

EXAM - MRI RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 45 M14 6 -- P3

Multilevel Switching, Dimming & Occupancy N/A N/A 4

RADIOLOGY

SERVICE

MRI EQUIPMENT ROOM

MRI System Component Room, X-Ray - Magnetic Resonance -

System Component

TREATMENT RFT RB P RWC 4'-0" AT 9'-0" 11 4'-0" Flush Wood -- -- 35 AG 40 50 M14 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 1

RADIOLOGY

SERVICE

MRI FERROMAGNETIC

DETECTION

X-Ray - Magnetic Resonance -

Ferromagnetic Detection, MRI

Zone 2, MRI Viewing Room

EXAM - MRI RFT RB P -- -- SEE FGI AT 9'-0" 11, 16 4'-0" Flush Wood -- -- 15 G 75 70 60 40 12 2 Return 40 NR 1 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 1

RADIOLOGY

SERVICE

MRI SCAN ROOM

MRI Scanning, X-Ray - Magnetic

Resonance - Scanner, EXAM - MRI WSF RB P -- -- SEE FGI AT VARIES 11,13,16 4'-0" Flush Wood -- R/F Shielded 1 75 70 60 40 12 2

Return

Exh. (S)

50 NR M17 2 -- P3

Multilevel Switching, Dimming & Occupancy MRI rated fixtures N/A 1

RADIOLOGY

SERVICE

READING ROOM

MRI Viewing Room, X-Ray -

Magnetic Resonance - Viewing -- CPT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 40 6 -- P3

Multilevel Switching, Dimming & Occupancy N/A N/A 6

RADIOLOGY

SERVICE

BONE DENSITOMETRY Bone Densitometer EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 75 70 60 30 6 2 Return 35 0 7 -- P3 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 2

PATHOLOGY AND

LABORATORY

MEDICINE

SPECIMEN COLLECTION

Blood Specimen Collection, Alcove - Specimen Collection

Point of Care (also for Substance

Abuse plus Coumadin), Blood

Draw Alcove, Support Area, Laboratory-Satellite, Laboratory-

Venipuncture, Blood Draw

EXAM __ WSF WSF EP -- -- -- AT-SP 9'-0" 3 -- _ _ _ _ _ 6 75 70 60 30 6 2 Return 35 (0) 4 P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming N/A 2

PATHOLOGY AND

LABORATORY

MEDICINE

SPECIMEN

ACCESSIONING,

PROCESSING &

DISTRIBUTION ROOM

Specimen Accessioning, Processing & Distribution Room, Shipping/Receiving

LABORATORY WORK

ROOM

-- WSF WSF EP -- -- --

GYP/EP or

AT-SP

9'-0 3, 7 3'-6"

Flush w/

Narrow Vision Wood Narrow Vision -- 15 AG

One per wall, 6' spacing, one adjacent to sink One at each workstation

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A

One at each workstation

PHARMACY

SERVICE

PHARMACY

Pharmacy, Pharmacy, PACT 3

(Controlled Substance) (w/3

AutoDispensing)

PHARMACY -- RF RB P -- -- -- AT 9'-0" -- 6'-0" Flush Metal - - 200 AS 7 15 P5 Multilevel Switching, Dimming & Occupancy N/A N/A 9

PHARMACY

SERVICE

PHARMACY DISPENSING

WINDOW

Dispense/Consult Window, Workroom, Pharmacist

PHARMACY -- RF RB P -- -- -- AT 9'-0" -- - - - - - - OPEN 12

Multilevel Switching, Dimming & Occupancy N/A N/A 5

PHARMACY

SERVICE

CLEAN ROOM,

COMPOUNDING

Pharmacy - Clean Room -

Chemotherapy Compounding

-- -- RF RF P -- -- -- GWB:P 9'-0" 3 7'-0"

Single Slide

Auto Sliding

Door

Aluminum/

Glass Yes -- 850 68 68 60 20 30 2 Exh. (S) 55 (-) M12 14 --

P10 Multilevel Switching, Dimming & Occupancy

Sealed fixture, flat lens surface on exterior N/A 5

PHARMACY

SERVICE

IV ADMIXTURE

Pharmacy - IV Admixture - Low

Volume

-- -- RF RF P -- -- -- GWB:P 9'-0" 3 7'-0"

Single Slide

Auto Sliding

Door

Aluminum/

Glass Yes -- 850 68 68 60 20 30 2 Return 55 (++) M12 14 --

P10 Multilevel Switching, Dimming & Occupancy

Sealed fixture, flat lens surface on exterior N/A 5

PHARMACY

SERVICE

PRESCRIPTION

DISPENSING AREA

Prescription Dispensing Area -

OmniCell Station

-- -- RF RF P -- -- -- AT 9'-0" 3 -- -- -- -- -- - 6 8 --

Multilevel Switching, Dimming & Occupancy N/A N/A 2

PHARMACY

SERVICE

SECURE STORAGE

VAULT

Secure Storage, Vault

CLEAN WORK ROOM/

CLEAN SUPPLY

-- RFT RB P RWC 4'-0" -- GWB:P 9'-0" 3'-0" Flush Hollow Metal -- -- 1 1 --

Multilevel Switching, Dimming & Occupancy N/A N/A --

PHARMACY

SERVICE

ANTEROOM

Anteroom, Compound Sterile

Preparation

-- WSF WSF EP -- -- -- GWB:SP 9'-0" 3 7'-0"

Single Slide

Auto Sliding

Door

Aluminum/

Glass Yes -- 850 68 68 60 20 30 2 Return 55 (+) M12 2 --

Multilevel Switching, Dimming & Occupancy

Sealed fixture, flat lens surface on exterior N/A --

0 BUSINESS OFFICE SECURE CASH ROOM Secure Money Handling Room -- RFT RB P -- -- -- AT 9'-0 3'-0" Flush w/ 1-

Way Viewer Steel -- -- 200 GV 4 --

Multilevel switching/dimming/occ upancy

N/A N/A 1

16 ENGINEERING BIOMED. REPAIR SHOP Repair Shop, Biomedical Eng. -- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-6" Flush Wood -- -- 35 AG 75 70 60 30 6 2 Exh. (G) (-) M7 10 -- P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 2

17 LOGISTICS LOADING DOCK Receiving/ Shipping Dock -- -- CS RB EP -- -- -- EXP. -- 8 6'-0" Flush Wood -- -- 44 APW 7 - 60 - - Exh. (G) (+) M5 2 -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 2

17 LOGISTICS MAIL ROOM

Support: Mail Room and Dist.

Center, Mailing Room - Prosthetic

Appliances

-- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 15 G 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

NOTES

Functional

Area

DEPARTMENT ROOM NAME ROOM NAMES (VA)

FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR

TABLE 1.2-5 Minimum Sound

Isolation

F lo o r

F in is h

B a s e

W a ll F in is h

W a in s c o t M a te ri a l

W a in s c o t H e ig h t

S T

C

C e il in g F in is h

H e ig h t

N o te s

S iz e

W id th

T y p e

M a te ri a l

G la z in g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r

T e m p e ra o li n g

F

In d o o r

T e m p e ra a ti n g

F

In d o o r R e la ti m id it y

R

H M a x

In d o o r R e la ti m id it y

R

H M in

M in im u m T o ta l

A C

H

M in im u m O

A A

C H

R o o m

A ir

R e n

E x h

G S p h

S

M a x im u m

N o v e l N

C

R o o m

A ir

B a la n

A C

N o te s

D u p c e p ta c le s

Q u c e p ta c le s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

L ig h ti n g

S p e c ia l

R e q u ir e m e n ts

L ig h ti n g

N o te s

D a ta

O u tl n d a rd d e n s

O e c ia l

R e q u ir e m e n ts

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

ROOM IDENTIFICATION

17 LOGISTICS

GAS CYLINDER

STORAGE

Storage - Gas Cylinders

(Full/Empty) -- -- CS RB P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 34 G 6

Exh. (S) (-) 1 -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 1

21 SUPPORT AREA BIO-HAZARD STORAGE

Storage - Bio Hazardous

Material, Storage - Hazardous

Material, Infectious / Hazardous

Waste

REGULATED WASTE -- RES WSF EP RWC 4'-0" -- GWB:SP 9'-0" 3 3'-6" Flush Hollow Metal -- -- 34 G 68 68 60 30 12 12 Exhaust 40 (-) 1 -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A N/A --

17 LOGISTICS STORAGE WAREHOUSE

Bulk Storage, General Storage, Warehouse, Medical Equipment, Office Storage Room

CLEAN

WORKROOM/CLEAN

SUPPLY

CS RB P -- -- -- Exp 10'-0" 6'-0" Flush Wood -- -- 45 AG 4 Return (+) minimum, 1 per wall, not to exceed 12' spacing -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 1

17 LOGISTICS BREAK DOWN

Receiving Break Down /

Inspection Room

CLEAN

WORKROOM/CLEAN

SUPPLY

RFT RB EP -- -- -- AT 9'-0" 8 4'-0" Flush Wood -- -- 34 AG 4 Return (+) 1 -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L3 1

18 POLICE SERVICE POLICE HOLDING ROOM Holding Room -- -- RFT/LVT RB P -- -- 40 AT 9'-0" 3,15 3'-6" Flush Hollow Metal

Half Glass w/

Laminated

Glass

18 P 75 70 60 20 6 2 Return 33 0 -- 2x2 recessed lensed Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A --

18 POLICE SERVICE OPERATIONS ROOM Operations Room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Hollow Metal

Half Glass w/

Laminated

Glass

-- 200 APS 75 70 60 20 6 2 Return 34 M15 0 8 2x2 recessed lensed Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A 8

18 POLICE SERVICE SECURE STORAGE

Small Arms Armory, Storage -

Secure RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Hollow Metal -- -- 200 P 75 70 60 - 4 2 Return NR NR 1 -- 2x2 recessed lensed

Multilevel Switching, Dimming & Occupancy N/A N/A 1

21 SUPPORT AREA RETAIL AREA Retail Area EXAM - PUBLIC SPACE RFT RB P -- -- SEE FGI AT 9'-0 17 6'-0" Flush w/ Full

Vision Wood Full Vision 47 KM 7, 9 M4 One per wall, 6' spacing --

Multilevel Switching, Dimming & Occupancy

Track or adjustable accent lighting for retail displays.

L5 3

21 SUPPORT AREA TELECOMM.

Telecommunications Room/

Closet, IT Telecommunications

Room

-- -- RFT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS D 64 75 55 30 - - - - NR 6 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A --

21 SUPPORT AREA SERVER ROOM Central Server Room -- -- RFT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS 72 81 60 6 M8 10 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A --

21 SUPPORT AREA I.T. WORKROOM

IT Workroom, Equip.

Configuration/ Repair -- -- RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG 10 --

P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 8

24 SPS

ANTEROOM, SOILED

TRANSITION

Anteroom, Soiled Transition/Drop-

Off

DECONTAM

ROOM

-- RES RES EP -- -- -- GYP-EP 9'-0 3, 7 3'-6"

Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 10 10 Exhaust (G) 40 (-) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 2

24 SPS

DECONTAMINATION

ROOM

Decontamination Work Room, Scope Decontamination Room

DECONTAM

ROOM

-- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6"

Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 6 6 Exhaust (G) 40 (--) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 4

24 SPS Cart Wash Cart Wash -- RES RES CT -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 70 75 10 10 Exhaust (S) 40 (-) M18, M19 One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A

24 SPS

Water Treatment Storage

Room Water Treatment Storage Room -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush Steel -- 15 AG 70 75 10 10 Exhaust (G) 40 (-) M18, M19 One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 1

21 SUPPORT AREA

RE-USABE MEDICAL

EQUIPMENT

Reprocessing Room, Optometry

Reusable Equipment (RME)

Room, Eye Clnc

-- WSF RSF EP -- GYP-EP 9'-0 3, 7 3'-6"

Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 6 6 Exhaust (G) 40 (-) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 2

24 SPS Instrument Assembly Instrument Assembly -- WSF WSF EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 4 4 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 4

24 SPS Sterilization Area Steam Sterilization Area, Low

Temp Sterilization Area

-- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6"

Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 75 60 30 10 10 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 2

24 SPS Cooling Area Cooling Area -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Steel Narrow Vision -- 15 AG 66 75 60 30 10 10 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 1

24 SPS

Equipment Room, Steam

Generator

Equipment Room, Steam

Generator -- RFT RB EP -- ACT-SP 9'-0 3, 7 3'-6" Flush Steel -- 15 AG 85 10 10 Exhaust (G) 45 (-) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A --

24 SPS Clean Dispatch Clean Dispatch -- RFT RB EP -- ACT-SP 9'-0 3, 7 70 75 60 30 4 4 Exhaust (G) 40 One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A 1

17 LOGISTICS STORAGE, STERILE

Sterile Supplies Room, Lgstcs

Svc; Sterile Consumables (Soft

Goods) Storage Room, Lgstcs

Svc

CLEAN SUPPLY -- RES RES EP RWC 4'-0" -- GYP-EP 9'-0 3, 7 3'-6"

Flush w/

Narrow Vision Wood Narrow Vision -- 15 AG 66 75 55 30 4 (+) One per wall -- 2 X 2 recessed lensed

Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A --

Interior Finishes Notes

General Notes

A. Hollow metal frames and doors to be painted.

B. Window sills to be solid surface fabrication.

C. Resilient base to be 4", unless otherwise noted.

D. Provide painted finishes only on inside of exterior walls (no wall covering).

E. Floor material transitions to occur at centerline of door, unless otherwise noted.

F. Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.

G. Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.

H. Coordinate height of wall protection with wall-mounted devices.

I. Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and lobby/waiting areas.

J. Soffit above upper cabinets to be gypsum board.

K. Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.

L. Solid surface countertops to have sides and backsplash at walls.

Schedule Notes

1. CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.

2. Tile base to be coved.

3. Integral coved base 6" high tightly sealed to walls.

4. If sink is present, use hard suface flooring as noted.

5. Lead lined walls and control area view window.

6. Flooring and base to match adjacent area flooring material and base.

7. Use gasketed, clip down ACT/grid system

8. Use slip-retardant finish on floor material

9. Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.

10. Note that if wall saver designed chairs are used, no wall protection is required.

11. Extend all room partitions to structural deck.

12. CT above countertop on wall.

13. Ceiling height as required to acommodate equipment.

14. Cove QT base, 6" high.

15. No separate trim at top of base, use alternate method to seal to wall.

16. Ceiling suspension system should be fabricated from nonferromagnetic material.

17. Aesthetic specialty materials may be used as accents where the design and budget permits.

18. Ceiling tile to meet USDA regulations.

19. Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces

20. Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.

21. Wall CT and ceiling to meet building code light reflectancy standards.

22. Space may be room or area within a room. Coordinate finishes with adjacent spaces.

23. Provide 3/4" painted plywood where required by Telecommunications.

AT Acoustical Ceiling Tile

AT-SP Acoustical Scrubbable Ceiling Tile (with sprayed plastic finish)

CS Concrete, Sealed

CPT Carpet Tile

CT Ceramic Tile (Wall)

EP Epoxy Paint

EPY Epoxy Flooring

EXP Exposed Ceiling

GWB Gypsum Wallboard System

LVT Luxury Vinyl Tile

MAT Modular Carpet Walk Off Mat

P Paint

PT Porcelain Tile

QT Quarry Tile

RB Resilient Base

RES Resinous Flooring and Base

RF Rubber Flooring

RFT Resilient Floor Tile

RSF Resilient Sheet Flooring - Heterogeneous

RWC Rigid Wall Covering (Wall Protection)

SD Static Dissipative Tile

S Solid Surface Fabrication

WSF Welded Seam Sheet Flooring - Homogeneous

Finish Codes

Doors and Hardware Notes

General Notes

A.

Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to the group.

B. All doors to be 7'-0" high, unless otherwise noted.

C.

Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in

Room Data Matrix - Interior Finishes in Appendix.

D. All Communications Closets to have security hinges.

Schedule Notes

1. Hollow metal frame cased opening

2. Two door (in swing and swing out) acoustical door and frame assembly.

3. Two doors required at this room/space.

4. Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.

5. Provide STC 50 rated acoustical door.

6. No door in this room/space.

7. Equal leaf pair of doors.

8. Lead lined door and hardware.

9. Space may be a room or area within another room. Omit door if space is not a separate room.

ELECTRICAL NOTES

POWER NOTES LIGHTING NOTES

P1. Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.

L1. EMI/RFI emissions to be controlled

P2. Receptacles on all walls L2. Dimmable to 5 fc

P3. Coordinate electrical connections with equipment to be installed.

Receptacles on all walls.

L3. May not have ceiling - then use industrial fixture type

P4. Plug strip at 44" above counters L4. May not have ceiling. If no ceiling, use industrial fixture type

P5. Multiple receptacles above and below desk for device charging L5. Treat like a store. Adjustable lighting, General lighting.

P6. Cord reel(s) for freestanding workbenches L6. No ceiling in these rooms. No prescription for lighting.

P7. All outlets on dedicated circuits. L7 Provide task lighting at work counters if not already part of workstation furniture.

P8. Cord reel(s) for freestanding workbenches L8 Provide ultraviolet specialty lighting in Tele-derm/Tele-health Exam Rooms.

P9. Treadmill on dedicated circuit

P10. Each hood on dedicated circuit

P11. Provide receptacles per equipment plan

P12. Electrical to review redundancy requirements with OIT guidelines.

P13. Receptacle above ceiling for overhead lift

P14. Recessed power quad floor box

P15. L21-20R receptical above each rack

P16. Provide connections to cubicle furniture

P17 Coordinate ESS power requirements for equipment and receptacles.

MECHANICAL HVAC NOTES

M1. Intentioanlly Left Blank

M2. Per ASHRAE 62 for ventilation, and FGI Guidelines for NC

M3. General Open Office area

M4. General Open/Public area

M5. Per ASHRAE 62 for ventilation if interior enclosed space.

M6. Comply with ASHRAE 15 if Special Refrigeration Systems are used

M7. If chemicals are used, provide specialized exhaust

M8. Data Center

M9. Transfer air to Food Prep Kitchen

M10. Intentioanlly Left Blank

M11. MEP Room

M12. See USP-797 and -800

M13. Counter-height specialized exhaust system required

M14. Provide air conditioning and ventilation per imaging manufacturer recommendations

M15. General Office Area

M16. Verify specific vendor/manufacturer requirements.

M17. Non-ferrous construction

M18. Provide cooling only air terminal unit to serve the manual equipment wash room.M19. Provide a dedicated wet exhaust system