This document contains a room data matrix and facility security requirements for the Allentown VA Outpatient Clinic major lease project in Pennsylvania.
The room data matrix provides construction specifications and design parameters for over 60 room types. It includes details on flooring, wall, and ceiling finishes; interior construction; doors and hardware; mechanical, electrical, and plumbing requirements; and IT needs. Requirements are delineated for examination, treatment, procedure, consultation, waiting, and support rooms as well as imaging, laboratory, pharmacy, dental, and other service areas. The facility security requirements outline security standards for perimeter barriers, intrusion detection, access control, surveillance systems, duress alarms and response protocols.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ALLENTOWN OUTPATIENT CLINIC MAJOR LEASE
ROOM DATA MATRIX
NOTES
Functional
Area
DEPARTMENT ROOM NAME ROOM NAMES (VA)
FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR
TABLE 1.2-5 Minimum Sound
Isolation
F lo o r
F in is h
B a s e
W a ll F in is h
W a in s c o t M a te ri a l
W a in s c o t H e ig h t
S T
C
C e il in g F in is h
H e ig h t
N o te s
S iz e
W id th
T y p e
M a te ri a l
G la z in g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r
T e m p e ra tu re
C o o li n g
F
In d o o r
T e m p e ra
H e a ti n g
F
In d o o r R e la ti v u m id it y
R
H M a x
In d o o r R e la ti m id it y
R
H M in
M in im u m T o ta l
A C
H
M in im u m O
A A
C H
R o o m
A ir
R e rn
G n
E x h
G S p c
E x h
S
M a x im u m
N o is
L v e l N
C
R o o m
A ir
B a la n
V
A C
N o te s
D u p le
R c e p ta c le s
Q u a d c e p ta c le s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
L ig h ti n g
S p e c ia l
R e q u ir e m e n ts
L ig h ti n g
N o te s
D a ta
O u tl ts
(s ta n d a rd d e n s it y
W A
O
IT
S p e c ia l
R e q u ir e m e n ts
GENERAL
ROOMS/SPACES
Exam Room PACT Exam EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10
3'-0"
3'-6"
Flush Wood _ _ 12 SE 3 75 70 60 30 6 2 Return 35 0 8 1 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
Multi-level switching or manual dimming L7 3
GENERAL
ROOMS/SPACES
Exam Room
Exam Room - Multi-Specialty, Exam / Treatment, Exam -
Consult, Consult Room - PACT, Exam/Consult Room (Mental
Health/Social Work), Exam Room
EMG/EEG, Exam Room-
Cardiology, Exam/Consult, Nurse
Practitioner, Women's Health
Exam, Tele-Health Exam, Optometry Exam Treatment
Room, Eye Lane, Tele-Retinal, Tele-Derm, TECHS, Appliance
Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment Room, Derm Biop, Pulmonary, Podiatry, Speech Pathology, Pulmonary
Function Room, Tele-Health, EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10 3'-6" Flush Wood _ _ 12 S 75 70 60 30 6 2 Return 35 0 8 1 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
Multi-level switching or manual dimming L7, L8 3
GENERAL
ROOMS/SPACES
Consult Room
Consult Room, Audiology
Rehabilitation Counceling Room, Dental Consult Room, Group
Therapy Room - Speech
Pathology, Consult Room -
Mental Health, PACT
CONSULTATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 4 2 Return 40 0 6 P2, 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
Multi-level switching or manual dimming N/A 1
GENERAL
ROOMS/SPACES
Procedure Room
Procedure Room, General, Urology, Gynecology, Specialty
Care, Multi-Specialty Care, Cast
Room, Pain Management, Women's Health
PROCEDURE TREATMENT WSF WSF EP RWC 4'-0" SEE FGI AT 9'-0" 3
3'-0"
3'-6"
Flush Wood -- -- 12 SE 3 75 70 60 20 15 3 7 P13
Multilevel Switching, Dimming &
Occupancy
Wall mounted exam light L7 2
GENERAL
ROOMS/SPACES
Laboratory Laboratory (Typical)
LABORATORY
WORKROOM
__ WSF WSF EP -- -- 40 AT-SP 9'-0" 3 3'-0" Flush Wood _ _ 15 AG 4 6 P3, P4
Multilevel Switching, Dimming &
Occupancy
N/A N/A 5
GENERAL
ROOMS/SPACES
Conference Room
Conference Room, Multi-Purpose
Room, Group Room, Shared
Medical Appointment Room, Education Room, Staff Training
Room, Classroom, Group
Therapy Room - Mental Health
__ LVT RB P RWC 4'-0" 40 AT 9'-0" 17 3'-6" Flush Wood _ _ 15 S _ 75 70 60 30 4 2 Return 35 0 M2 8 P14 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
Provide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections.
N/A 4 Floor data for table
GENERAL
ROOMS/SPACES
TOILET
Toilet, Family; Toilet, Staff;
Toilet, General Procedure Room
Patient; Toilet, Women's Health
Procedure Room Patient; Toilet, PACT Patient; Toilet, Women's
Health Patient; Toilet, Women's
Health Exam Room Patient;
Toilet, Audiology Patient;
Universal Patient, Eye; Universal
Patient Toilet; Toilet, Multi-
Specialty Patient; Toilet, Multi-
Specialty Procedure Room
Patient; Toilet, PM&R Patient;
Toilet, R/F Patient; Toilet, Ultrasound Patient; Toilet, Employee Blood Specimen
Collection Room; Toilet, Specimen Collection; Female Six-
Stall Non-Patient Multi-User
Toilet, Bldg Sprt; Male Four-Stall
Non-Patient Multi-User Toilet, Bldg Sprt; Universal Non-Patient
Toilet, Bldg Sprt
TOILET ROOM TOILET ROOM PT PT P CT 7'-0" SEE FGI AT 9'-0" 1,2 3'-6" Flush Wood _ _ 11 _ 75 70 60 20 10 N/A Exh (G) 40 (-) 1 Downlights/Mirror or vanity Occupancy Sensor N/A N/A
GENERAL
ROOMS/SPACES
OFFICE Any Office -- CONSULTATION LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 75 70 60 30 4 2 Return 40 0 4 1 P2 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A 2
GENERAL
ROOMS/SPACES
WAITING
Waiting - Family - PACT, Waiting -
PACT 3, Waiting - General - 20
People, Waiting - General - 10
People, Waiting - General - 6
People, Waiting-General
EXAM - PUBLIC SPACE LVT RB P -- -- SEE FGI AT 9'-0" 10, 17 75 70 60 30 6 2 Return 40 0 M4 4 -- P2 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A 1
GENERAL
ROOMS/SPACES
RECEPTION
Reception, Information Desk, Travel Window, Reception -
Accessible
-- -- RFT RB P -- -- -- AT 9'-0" -- 3'-0"
Flush w/ narrow vision Wood _ _ 12 CG 3 75 70 60 30 4 2 Return 40 M4 1 1
Downlights, pendants, decorative, and accent
Multilevel Switching, Dimming &
Occupancy
N/A N/A 10
Data/phone feeds to systems furniture
GENERAL
ROOMS/SPACES
COPY ALCOVE
Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy Room
Match
Adjacent
Match
Adjacent P -- -- -- AT 9'-0" 6 _ _ _ _ _ _ 6 75 70 N/A N/A 6 2 Return 40 3 P3 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A 3
GENERAL
ROOMS/SPACES
CLEAN UTILITY
Clean Utility, Clean Supply, Clean
Workroom, Clean Linen, Sterile
Storage, Sterile Supply Storage
Room, Clean Scope, Dental
Clean Cart, Central Sterile
-- -- WSF RB P RWC 4'-0" -- AT 9'-0" -- 3'-0" Flush Wood -- 45 MIN 121 AG _ 66 75 55 30 4 N/A Return 40 (+) 1 2x2 recessed lensed Occupancy Sensor N/A N/A
GENERAL
ROOMS/SPACES
SOILED UTILITY
Soiled Utility Room, Recycled
Material, Soiled Holding, Soiled
Linen, Soiled Workroom, Soiled
Supply, Soiled Cart
SOILED HOLDING /
SOILED WORK ROOM
-- WSF WSF P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 121 AG _ 78 72 NR NR 10 2 Exh. (G) 40 (-) 2 -- 2x2 recessed lensed Occupancy Sensor N/A N/A --
GENERAL
ROOMS/SPACES
STORAGE
Storage - Medical Equipment, Storage - Shared Medical
Appointments, DME - Prosthetics
Storage, Storage - Homeless, EMS Storage, Storage -
Bistro/Coffee Bar, Storage -
Patient Clothing and Luggage, Laundry / Storage, Tray Cart
Storage Area, Bulk Storage, General Storage, Secure
Storage, CBOC PT/OT
Equipment Storage Room, PMR
Svc; Storage
CLEAN
WORKROOM/CLEAN
SUPPLY
RFT RB P RWC 4'-0"N/A -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG N/A N/A N/A N/A 4 N/A Return 40 (+) 1 per wall, not to exceed
12' spacing -- Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A 1
GENERAL
ROOMS/SPACES
JANITOR'S CLOSET
Housekeeping Aides Closet
(HAC)
ENVIRONMENTAL
SERVICES ROOM
-- QT RB P FRP 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 34 A _ NR NR NR NR 10 N/A Ehx. (G) 40 (-) 2 --
P7 Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A --
GENERAL
ROOMS/SPACES
KITCHENETTE Social Activities Space/ Kitchen -- -- RFT RB P -- -- -- AT 9'-0" 17 3'-0" Flush Wood -- -- 15 A _ 4 --
Multilevel switching/dimming/occ N/A N/A --
GENERAL
ROOMS/SPACES
EQUIPMENT ALCOVE
AED Alcove, Height and Weight
Alcove, Scale Alcove, Stretcher
Alcove, Med Alcove, Portable
Patient Lift Alcove, Wheelchair
Alcove, My Health eVet, Kiosk, Match
Adjacent
Match
Adjacent Match Adjacent RWC 4'-0" -- AT
Match
Adjacent 3 -- -- -- -- -- 6 1 -- 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A --
GENERAL
ROOMS/SPACES
STAFF LOUNGE Staff Lounge -- -- LVT RB P -- -- 40 AT 9'-0" 4 3'-0"
Flush w/ narrow vision Wood -- -- 13 _ 75 70 60 30 4 2 Exh. (G) (-) 8 --
P7 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A 2
GENERAL
ROOMS/SPACES
MEDICATION ROOM
Medication Room, Phrm Svc; CT
Medication Preparation, Imgng
Svcs
MEDICATION ROOM -- RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 34 75 70 60 30 4 2 Return 40 (+) 5 1 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A 1
GENERAL
ROOMS/SPACES
LACTATION ROOM
Employee Wellness, Lactation
Room, Quiet Room, CBOC
Lactation Room, Wm Vet Svc;
Lactation Room
-- -- RFT RB P -- -- 50 AT 9'-0" 10 3'-0" Flush Wood -- -- 12 CS 75 70 60 30 6 2 Return 35 0 4 -- P2 2X2 recessed lensed and downlights
Multilevel Switching, Dimming &
Occupancy
N/A N/A 1
GENERAL
ROOMS/SPACES
LOCKER ROOM
Locker Room, Locker Room
(Male/ Female) Locker - Staff
Personal Property, Locker Room -
Staff
-- -- RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- Push/Pull 75 70 60 30 6 N/A Exh. (G) 40 (-) 4 -- 2 X 2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A --
GENERAL
ROOMS/SPACES
OFFICE, CUBICLE, Open
Office
Cubicle - Administrative, Data
Processing, Workstation -
Extended Team, Homeless, Workstation - MICHM, Workstation - Suicide Prevention, Workstation - VOC Rehab, Workstation - Rad Tech, Workstation - Shipping /
Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical, -- -- CPT RB P -- -- -- AT 9'-0" 75 70 60 30 4 4 Exh. (G) 40 (+) 2 per workstation -- P16 2 X 2 recessed lensed and task lighting as required for type of work.
Multilevel Switching, Dimming &
Occupancy
N/A N/A 1 per workstation
GENERAL
ROOMS/SPACES
SUB-WAITING
Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-
Waiting, Sub-Waiting - Diagnostic
Patient, Sub-Waiting - Dilation
Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-
Zone 2
-- -- CPT RB P -- -- -- AT 9'-0" 10, 17 -- -- -- -- -- - 6, 10, 17 75 70 60 30 6 2 Return 40 (0) M4 4 --
2 X 2 recessed lensed and downlights as required for the type of sub waiting
(ie.: eye dilation, etc.)
Multilevel Switching, Dimming &
Occupancy
N/A N/A --
19 CANTEEN SERVICE VENDING
Randolph Sheppard Vending, Mini-mart Café, Canteen
RFT RB P -- -- 50 AT 9'-0" -- -- -- -- -- -- 6
75 70 60 30 6 2 Return 40 0 M4 8 -- P3, P7 2x2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A 4
GENERAL
ROOMS/SPACES
TOILET/SHOWER ROOM
Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff
TOILET ROOM TOILET ROOM PT PT CT -- -- SEE FGI GWB/P 9'-0" 2, 19 3'-6" Flush Wood -- -- 11 G 2 --
Multilevel Switching, Dimming &
Occupancy
N/A N/A
GENERAL
ROOMS/SPACES
CHANGING ROOM Dressing room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Wood -- -- 11 K 75 70 60 - 4 2 Return NR NR 1 -- 2 X 2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
N/A N/A
PRIMARY CARE,
SPECIALTY CARE,
PACT
PACT TEAM WORK
SPACE
PACT Team Work Space, Team
Work Area- Home Based Primary
Care, Team Work Area - Dental
Clinic
-- CPT RB P -- AT 9'-0" -- _ _ _ _ _ 14 MP 6 75 70 60 30 4 2 Return 35 (0) M3 2 per workstation -- P16 2 X 2 recessed lensed
Multilevel Switching, Dimming &
Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.
L7 1 per workstation
PRIMARY CARE,
SPECIALTY CARE,
PACT
EXAM ROOM, AIRBORNE
INFECTION ISOLATION
Exam, Isolation, Negative
Pressure AII Room EXAMINATION WSF WSF P -- -- SEE FGI GWB:P 9'-0" 3,7 3'-6" Flush Wood -- -- 12 S 6 --
Multilevel Switching, Dimming & Occupancy
Sealed fixture, flat lens surface on exterior N/A 1
AUDIOLOGY AND
SLP
AUDIOLOGY HEARING
AID TESTING
Hearing Aid Lab, Hearing Aid
Processing, Hearing Aid Repair -- RFT RB P -- -- 40 AT 9'-0" -- 3'-0" Flush Wood _ _ 15 S _ 75 70 60 - Exh. (G) (-) 7 0 P4
Multilevel Switching, Dimming & Occupancy N/A N/A 2
ROOM DATA MATRIX
FLOOR WALLS CEILING
IT
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING
INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
ROOM IDENTIFICATION
NOTES
Functional
Area
DEPARTMENT ROOM NAME ROOM NAMES (VA)
FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR
TABLE 1.2-5 Minimum Sound
Isolation
F lo o r
F in is h
B a s e
W a ll F in is h
W a in s c o t M a te ri a l
W a in s c o t H e ig h t
S T
C
C e il in g F in is h
H e ig h t
N o te s
S iz e
W id th
T y p e
M a te ri a l
G la z in g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r
T e m p e ra o li n g
F
In d o o r
T e m p e ra a ti n g
F
In d o o r R e la ti m id it y
R
H M a x
In d o o r R e la ti m id it y
R
H M in
M in im u m T o ta l
A C
H
M in im u m O
A A
C H
R o o m
A ir
R e n
E x h
G S p h
S
M a x im u m
N o v e l N
C
R o o m
A ir
B a la n
A C
N o te s
D u p c e p ta c le s
Q u c e p ta c le s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
L ig h ti n g
S p e c ia l
R e q u ir e m e n ts
L ig h ti n g
N o te s
D a ta
O u tl n d a rd d e n s
O e c ia l
R e q u ir e m e n ts
ROOM DATA MATRIX
FLOOR WALLS CEILING
IT
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING
INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
ROOM IDENTIFICATION
AUDIOLOGY AND
SLP
AUDIOLOGY HEARING
AID FITTING
Audiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology
Assistive Technology Romm, Speech Language Pathology
Voice Treatment Room
EXAM -- RFT RB P -- -- 60 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 6 2 Return 25 (0) 6 P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A N/A 2
AUDIOLOGY AND
SLP
AUDIOMETRIC EXAM
BOOTH
Audiometric Exam Suite, Exam -
Audiometric Booth, Aud: Suite -
Audiometric Exam, Hearing/Diagnostics, Booth, 1-
Person
EXAM -- Pre-Fab Pre-Fab Pre-Fab -- --
Pre-Fab
Review during design
Pre-Fab 8'-0" --
3'-0"
3'-6"
Pre-Fab Pre-Fab _ _ 1 2,4 75 70 60 30 6 2 Return 25 (0) 9 P1 Provided with booth
Typically pre-packaged unit including lighting and switching
N/A L1 5
AUDIOLOGY AND
SLP
ELECTROPHYSIOLOGY
Electrophysiology, Posturography, Vestibulography, Cerument Management Room
EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 P2, P3, P14 Multilevel Switching, Dimming & Occupancy N/A N/A 3
4 DENTAL SERVICE
SPECIALTY EQUIPMENT
MECHANICAL ROOM
Dental Equipment Mech. Room, Mechanical Rooms - Electrical -- -- CS/EPY -- P -- -- 60 EXP 9'-0" 3'-6" Flush Wood -- -- 14 S 80 65 Exh. (G) (-) 2 -- P3, P17 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 1
4 DENTAL SERVICE
DENTAL PROSTHETICS
LABORATORY
Laboratory, Dental Prosthetics -- RF WSF P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 15 AG 75 70 60 20 6 2
Return
Exh. (G) 45 (-) M13 7 -- P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L7 5
4 DENTAL SERVICE
DENTAL TREATMENT
ROOM
Dental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, Bariatric
EXAM TREATMENT RF WSF P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 75 70 NR NR 3 2 Return 40 (+) 7 -- P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L7 2
4 DENTAL SERVICE DENTAL X-RAY ROOM
X-Ray Room, Panoramic /
Cephalometric (Cone Beam)
CLASS 1 IMAGING
ROOM
TREATMENT
LVT/
Electrostatic
Dissipative
Flooring
WSF P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 17 AGL 8 75 70 60 30 6 2 Return 35 (0) 7 -- P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L7 2
5 EYE CLINIC
FITTING & DISPENSING,
EYEGLASSES
Fitting & Dispensing, Eyeglasses -- RFT RB P -- -- -- AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S 6 75 70 60 - 4 2 Return 40 NR 2 Downlights and accent/display
Multilevel Switching, Dimming & Occupancy N/A N/A 2
5 EYE CLINIC
LOW VISION EXAM/
THERAPY/ TRAINING
Low Vision Exam/ Therapy/
Training EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 6 2 Return 35 (0) 6 2 X 2 recessed lensed / downlights
Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.
N/A 3
5 EYE CLINIC PRE-TESTING/ INTAKE Pre-Testing/ Intake EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 6 2 Return 35 (0) 6 1 Downlights / 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.
N/A 2
5 EYE CLINIC VISUAL FIELDS ROOM
Visual Fields Room, Photography
Room, Ultrasound Room, Tomography Room, Imaging
Room, OCT Laser
EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 30 15 3 Return 35 (+) 7 P3 Downlights Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.
N/A 2
6 MENTAL HEALTH QUIET ROOM Quiet Room for Patients EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 1
6 MENTAL HEALTH
BIOFEEDBACK
TREATMENT ROOM
Biofeedback Treatment Room EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 15 S 75 70 60 30 6 2 Return 35 (0) 4 -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A L7 2
SPECIALTY CARE
SERVICES
PULMONARY FUNCTION
ROOM (EXAM ROOM)
Pulmonary Function - Analysis EXAM TREATMENT WSF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 G 6 --
Multilevel Switching, Dimming & Occupancy N/A N/A 2
SPECIALTY CARE
SERVICES
TREADMILL ROOM Treadmill Room EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 MS 75 70 60 30 8 2 Return 35 (0) 6 -- P9
Multilevel Switching, Dimming & Occupancy N/A N/A 2
SPECIALTY CARE
SERVICES
EKG TESTING ROOM
(EXAM ROOM)
EKG Testing Room EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 12 S One per wall --
Multilevel Switching, Dimming & Occupancy N/A N/A 2
RECREATION
THERAPY
GROUP THERAPY
ROOM, MUSIC
Creative Arts - Group Therapy
Room - Music -- TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 --
Multilevel Switching, Dimming & Occupancy N/A N/A 1
RECREATION
THERAPY
GROUP THERAPY
ROOM, ART
Creative Arts - Group Therapy
Room - Large -- TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 --
Multilevel Switching, Dimming & Occupancy N/A N/A 1
RECREATION
THERAPY
WEIGHT ROOM, SMALL
Recreation Therapy Exercise /
Weight Room - Small -- TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 34 AG 12 --
Multilevel Switching, Dimming & Occupancy N/A N/A --
PHYSICAL MEDICINE
AND REHAB (PM&R)
PHYSICAL THERAPY
GYM
Treatment Exercise Area
(includes workstations therapists) EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 14 S 75 70 60 30 6 2 Return 35 (-) 14 -- P14 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 4
PHYSICAL MEDICINE
AND REHAB (PM&R)
Activities Daily Living (ADL)
Training
ADL Evaluation and Training
Center, Toilet, Tub, Bed, Kitchen, Laundry
EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A
RADIOLOGY
SERVICE
GENERAL PURPOSE
RADIOLOGY
Radiology, ES: General Purpose
Radiology Room
CLASS 1 IMAGING
ROOM
TREATMENT WSF RB P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 LS 8 75 70 60 30 6 2 Return 35 (0) M14 5 P3, P13, P17 2 X 2 recessed lensed
Fully dimmable, occupancy sensor N/A L2 4
RADIOLOGY
SERVICE
C.T. CONTROL ROOM
CT Control Area, X-Ray -
Computed Tomography - Control TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 3'-0" Flush Wood -- LEAD LINED 12 LS 75 70 60 30 6 2 Return 45 (0) M14 6 -- P3, P17 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 8
RADIOLOGY
SERVICE
C.T. EQUIPMENT ROOM
CT Equipment Room, X-Ray -
Computed Tomography - Indep
View Console, CT System
Component Room
-- VT WSF P -- -- -- AT 9'-0" 5 6'-0" Flush Wood -- -- 45 AG 7 50 M14 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 2
RADIOLOGY
SERVICE
C.T. SCAN ROOM
CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography -
Scanner
CLASS 1 IMAGING
ROOM
TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 ALG 75 70 60 30 6 2 Return 35 (0) 7 -- P3, P13, P17 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 4
RADIOLOGY
SERVICE
MAMMOGRAPHY SCAN
ROOM
Mammo - X-ray, Mammography
Room
CLASS 1 IMAGING
ROOM
TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 12 LS 75 70 60 30 6 2 Return 35 (0) 7 -- P3 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 1
RADIOLOGY
SERVICE
RADIOGRAPHIC /
FLOURO SCAN ROOM
Radiographic / Fluoroscopic (R/F)
Room
CLASS 1 IMAGING
ROOM
TREATMENT WSF WSF P - - SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 15 AGL 75 70 60 30 6 2 Return 36 (0) 7 -- P3, P13 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 4
RADIOLOGY
SERVICE
ULTRASOUND SCAN
ROOM
Ultrasound Room
CLASS 1 IMAGING
ROOM
TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- --
12 S 75 70 60 30 8 2 Return 35 (0) M14 7 -- P3, P13 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 1
RADIOLOGY
SERVICE
PACS SERVER ROOM
X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System
(PACS)
-- RFT RB P - - - AT 9'-0" 3'-0" Flush Wood -- -- 15 GK 50 4 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4
RADIOLOGY
SERVICE
MRI CONTROL ROOM
MRI Control Room, X-Ray -
Magnetic Resonance - Control, MRI Zone 3
CLASS 1 IMAGING
ROOM
EXAM - MRI RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 45 M14 6 -- P3
Multilevel Switching, Dimming & Occupancy N/A N/A 4
RADIOLOGY
SERVICE
MRI EQUIPMENT ROOM
MRI System Component Room, X-Ray - Magnetic Resonance -
System Component
TREATMENT RFT RB P RWC 4'-0" AT 9'-0" 11 4'-0" Flush Wood -- -- 35 AG 40 50 M14 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 1
RADIOLOGY
SERVICE
MRI FERROMAGNETIC
DETECTION
X-Ray - Magnetic Resonance -
Ferromagnetic Detection, MRI
Zone 2, MRI Viewing Room
EXAM - MRI RFT RB P -- -- SEE FGI AT 9'-0" 11, 16 4'-0" Flush Wood -- -- 15 G 75 70 60 40 12 2 Return 40 NR 1 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 1
RADIOLOGY
SERVICE
MRI SCAN ROOM
MRI Scanning, X-Ray - Magnetic
Resonance - Scanner, EXAM - MRI WSF RB P -- -- SEE FGI AT VARIES 11,13,16 4'-0" Flush Wood -- R/F Shielded 1 75 70 60 40 12 2
Return
Exh. (S)
50 NR M17 2 -- P3
Multilevel Switching, Dimming & Occupancy MRI rated fixtures N/A 1
RADIOLOGY
SERVICE
READING ROOM
MRI Viewing Room, X-Ray -
Magnetic Resonance - Viewing -- CPT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 40 6 -- P3
Multilevel Switching, Dimming & Occupancy N/A N/A 6
RADIOLOGY
SERVICE
BONE DENSITOMETRY Bone Densitometer EXAM TREATMENT RFT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 75 70 60 30 6 2 Return 35 0 7 -- P3 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 2
PATHOLOGY AND
LABORATORY
MEDICINE
SPECIMEN COLLECTION
Blood Specimen Collection, Alcove - Specimen Collection
Point of Care (also for Substance
Abuse plus Coumadin), Blood
Draw Alcove, Support Area, Laboratory-Satellite, Laboratory-
Venipuncture, Blood Draw
EXAM __ WSF WSF EP -- -- -- AT-SP 9'-0" 3 -- _ _ _ _ _ 6 75 70 60 30 6 2 Return 35 (0) 4 P3 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy
Multi-level switching or manual dimming N/A 2
PATHOLOGY AND
LABORATORY
MEDICINE
SPECIMEN
ACCESSIONING,
PROCESSING &
DISTRIBUTION ROOM
Specimen Accessioning, Processing & Distribution Room, Shipping/Receiving
LABORATORY WORK
ROOM
-- WSF WSF EP -- -- --
GYP/EP or
AT-SP
9'-0 3, 7 3'-6"
Flush w/
Narrow Vision Wood Narrow Vision -- 15 AG
One per wall, 6' spacing, one adjacent to sink One at each workstation
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A
One at each workstation
PHARMACY
SERVICE
PHARMACY
Pharmacy, Pharmacy, PACT 3
(Controlled Substance) (w/3
AutoDispensing)
PHARMACY -- RF RB P -- -- -- AT 9'-0" -- 6'-0" Flush Metal - - 200 AS 7 15 P5 Multilevel Switching, Dimming & Occupancy N/A N/A 9
PHARMACY
SERVICE
PHARMACY DISPENSING
WINDOW
Dispense/Consult Window, Workroom, Pharmacist
PHARMACY -- RF RB P -- -- -- AT 9'-0" -- - - - - - - OPEN 12
Multilevel Switching, Dimming & Occupancy N/A N/A 5
PHARMACY
SERVICE
CLEAN ROOM,
COMPOUNDING
Pharmacy - Clean Room -
Chemotherapy Compounding
-- -- RF RF P -- -- -- GWB:P 9'-0" 3 7'-0"
Single Slide
Auto Sliding
Door
Aluminum/
Glass Yes -- 850 68 68 60 20 30 2 Exh. (S) 55 (-) M12 14 --
P10 Multilevel Switching, Dimming & Occupancy
Sealed fixture, flat lens surface on exterior N/A 5
PHARMACY
SERVICE
IV ADMIXTURE
Pharmacy - IV Admixture - Low
Volume
-- -- RF RF P -- -- -- GWB:P 9'-0" 3 7'-0"
Single Slide
Auto Sliding
Door
Aluminum/
Glass Yes -- 850 68 68 60 20 30 2 Return 55 (++) M12 14 --
P10 Multilevel Switching, Dimming & Occupancy
Sealed fixture, flat lens surface on exterior N/A 5
PHARMACY
SERVICE
PRESCRIPTION
DISPENSING AREA
Prescription Dispensing Area -
OmniCell Station
-- -- RF RF P -- -- -- AT 9'-0" 3 -- -- -- -- -- - 6 8 --
Multilevel Switching, Dimming & Occupancy N/A N/A 2
PHARMACY
SERVICE
SECURE STORAGE
VAULT
Secure Storage, Vault
CLEAN WORK ROOM/
CLEAN SUPPLY
-- RFT RB P RWC 4'-0" -- GWB:P 9'-0" 3'-0" Flush Hollow Metal -- -- 1 1 --
Multilevel Switching, Dimming & Occupancy N/A N/A --
PHARMACY
SERVICE
ANTEROOM
Anteroom, Compound Sterile
Preparation
-- WSF WSF EP -- -- -- GWB:SP 9'-0" 3 7'-0"
Single Slide
Auto Sliding
Door
Aluminum/
Glass Yes -- 850 68 68 60 20 30 2 Return 55 (+) M12 2 --
Multilevel Switching, Dimming & Occupancy
Sealed fixture, flat lens surface on exterior N/A --
0 BUSINESS OFFICE SECURE CASH ROOM Secure Money Handling Room -- RFT RB P -- -- -- AT 9'-0 3'-0" Flush w/ 1-
Way Viewer Steel -- -- 200 GV 4 --
Multilevel switching/dimming/occ upancy
N/A N/A 1
16 ENGINEERING BIOMED. REPAIR SHOP Repair Shop, Biomedical Eng. -- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-6" Flush Wood -- -- 35 AG 75 70 60 30 6 2 Exh. (G) (-) M7 10 -- P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 2
17 LOGISTICS LOADING DOCK Receiving/ Shipping Dock -- -- CS RB EP -- -- -- EXP. -- 8 6'-0" Flush Wood -- -- 44 APW 7 - 60 - - Exh. (G) (+) M5 2 -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 2
17 LOGISTICS MAIL ROOM
Support: Mail Room and Dist.
Center, Mailing Room - Prosthetic
Appliances
-- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 15 G 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
NOTES
Functional
Area
DEPARTMENT ROOM NAME ROOM NAMES (VA)
FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR
TABLE 1.2-5 Minimum Sound
Isolation
F lo o r
F in is h
B a s e
W a ll F in is h
W a in s c o t M a te ri a l
W a in s c o t H e ig h t
S T
C
C e il in g F in is h
H e ig h t
N o te s
S iz e
W id th
T y p e
M a te ri a l
G la z in g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r
T e m p e ra o li n g
F
In d o o r
T e m p e ra a ti n g
F
In d o o r R e la ti m id it y
R
H M a x
In d o o r R e la ti m id it y
R
H M in
M in im u m T o ta l
A C
H
M in im u m O
A A
C H
R o o m
A ir
R e n
E x h
G S p h
S
M a x im u m
N o v e l N
C
R o o m
A ir
B a la n
A C
N o te s
D u p c e p ta c le s
Q u c e p ta c le s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
L ig h ti n g
S p e c ia l
R e q u ir e m e n ts
L ig h ti n g
N o te s
D a ta
O u tl n d a rd d e n s
O e c ia l
R e q u ir e m e n ts
ROOM DATA MATRIX
FLOOR WALLS CEILING
IT
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING
INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
ROOM IDENTIFICATION
17 LOGISTICS
GAS CYLINDER
STORAGE
Storage - Gas Cylinders
(Full/Empty) -- -- CS RB P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 34 G 6
Exh. (S) (-) 1 -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 1
21 SUPPORT AREA BIO-HAZARD STORAGE
Storage - Bio Hazardous
Material, Storage - Hazardous
Material, Infectious / Hazardous
Waste
REGULATED WASTE -- RES WSF EP RWC 4'-0" -- GWB:SP 9'-0" 3 3'-6" Flush Hollow Metal -- -- 34 G 68 68 60 30 12 12 Exhaust 40 (-) 1 -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A N/A --
17 LOGISTICS STORAGE WAREHOUSE
Bulk Storage, General Storage, Warehouse, Medical Equipment, Office Storage Room
CLEAN
WORKROOM/CLEAN
SUPPLY
CS RB P -- -- -- Exp 10'-0" 6'-0" Flush Wood -- -- 45 AG 4 Return (+) minimum, 1 per wall, not to exceed 12' spacing -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 1
17 LOGISTICS BREAK DOWN
Receiving Break Down /
Inspection Room
CLEAN
WORKROOM/CLEAN
SUPPLY
RFT RB EP -- -- -- AT 9'-0" 8 4'-0" Flush Wood -- -- 34 AG 4 Return (+) 1 -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy N/A L3 1
18 POLICE SERVICE POLICE HOLDING ROOM Holding Room -- -- RFT/LVT RB P -- -- 40 AT 9'-0" 3,15 3'-6" Flush Hollow Metal
Half Glass w/
Laminated
Glass
18 P 75 70 60 20 6 2 Return 33 0 -- 2x2 recessed lensed Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A --
18 POLICE SERVICE OPERATIONS ROOM Operations Room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Hollow Metal
Half Glass w/
Laminated
Glass
-- 200 APS 75 70 60 20 6 2 Return 34 M15 0 8 2x2 recessed lensed Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A 8
18 POLICE SERVICE SECURE STORAGE
Small Arms Armory, Storage -
Secure RFT RB P -- -- 40 AT 9'-0" 3'-0" Flush Hollow Metal -- -- 200 P 75 70 60 - 4 2 Return NR NR 1 -- 2x2 recessed lensed
Multilevel Switching, Dimming & Occupancy N/A N/A 1
21 SUPPORT AREA RETAIL AREA Retail Area EXAM - PUBLIC SPACE RFT RB P -- -- SEE FGI AT 9'-0 17 6'-0" Flush w/ Full
Vision Wood Full Vision 47 KM 7, 9 M4 One per wall, 6' spacing --
Multilevel Switching, Dimming & Occupancy
Track or adjustable accent lighting for retail displays.
L5 3
21 SUPPORT AREA TELECOMM.
Telecommunications Room/
Closet, IT Telecommunications
Room
-- -- RFT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS D 64 75 55 30 - - - - NR 6 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A --
21 SUPPORT AREA SERVER ROOM Central Server Room -- -- RFT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS 72 81 60 6 M8 10 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A --
21 SUPPORT AREA I.T. WORKROOM
IT Workroom, Equip.
Configuration/ Repair -- -- RFT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG 10 --
P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 8
24 SPS
ANTEROOM, SOILED
TRANSITION
Anteroom, Soiled Transition/Drop-
Off
DECONTAM
ROOM
-- RES RES EP -- -- -- GYP-EP 9'-0 3, 7 3'-6"
Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 10 10 Exhaust (G) 40 (-) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 2
24 SPS
DECONTAMINATION
ROOM
Decontamination Work Room, Scope Decontamination Room
DECONTAM
ROOM
-- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6"
Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 6 6 Exhaust (G) 40 (--) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 4
24 SPS Cart Wash Cart Wash -- RES RES CT -- GYP-EP 9'-0 3, 7 3'-6" Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 70 75 10 10 Exhaust (S) 40 (-) M18, M19 One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A
24 SPS
Water Treatment Storage
Room Water Treatment Storage Room -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush Steel -- 15 AG 70 75 10 10 Exhaust (G) 40 (-) M18, M19 One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 1
21 SUPPORT AREA
RE-USABE MEDICAL
EQUIPMENT
Reprocessing Room, Optometry
Reusable Equipment (RME)
Room, Eye Clnc
-- WSF RSF EP -- GYP-EP 9'-0 3, 7 3'-6"
Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 6 6 Exhaust (G) 40 (-) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 2
24 SPS Instrument Assembly Instrument Assembly -- WSF WSF EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 66 72 60 30 4 4 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 4
24 SPS Sterilization Area Steam Sterilization Area, Low
Temp Sterilization Area
-- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6"
Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 66 75 60 30 10 10 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 2
24 SPS Cooling Area Cooling Area -- RES RES EP -- GYP-EP 9'-0 3, 7 3'-6" Flush w/
Narrow Vision Steel Narrow Vision -- 15 AG 66 75 60 30 10 10 Exhaust (G) 40 (++) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 1
24 SPS
Equipment Room, Steam
Generator
Equipment Room, Steam
Generator -- RFT RB EP -- ACT-SP 9'-0 3, 7 3'-6" Flush Steel -- 15 AG 85 10 10 Exhaust (G) 45 (-) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A --
24 SPS Clean Dispatch Clean Dispatch -- RFT RB EP -- ACT-SP 9'-0 3, 7 70 75 60 30 4 4 Exhaust (G) 40 One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A 1
17 LOGISTICS STORAGE, STERILE
Sterile Supplies Room, Lgstcs
Svc; Sterile Consumables (Soft
Goods) Storage Room, Lgstcs
Svc
CLEAN SUPPLY -- RES RES EP RWC 4'-0" -- GYP-EP 9'-0 3, 7 3'-6"
Flush w/
Narrow Vision Wood Narrow Vision -- 15 AG 66 75 55 30 4 (+) One per wall -- 2 X 2 recessed lensed
Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A --
Interior Finishes Notes
General Notes
A. Hollow metal frames and doors to be painted.
B. Window sills to be solid surface fabrication.
C. Resilient base to be 4", unless otherwise noted.
D. Provide painted finishes only on inside of exterior walls (no wall covering).
E. Floor material transitions to occur at centerline of door, unless otherwise noted.
F. Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.
G. Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.
H. Coordinate height of wall protection with wall-mounted devices.
I. Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and lobby/waiting areas.
J. Soffit above upper cabinets to be gypsum board.
K. Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.
L. Solid surface countertops to have sides and backsplash at walls.
Schedule Notes
1. CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.
2. Tile base to be coved.
3. Integral coved base 6" high tightly sealed to walls.
4. If sink is present, use hard suface flooring as noted.
5. Lead lined walls and control area view window.
6. Flooring and base to match adjacent area flooring material and base.
7. Use gasketed, clip down ACT/grid system
8. Use slip-retardant finish on floor material
9. Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.
10. Note that if wall saver designed chairs are used, no wall protection is required.
11. Extend all room partitions to structural deck.
12. CT above countertop on wall.
13. Ceiling height as required to acommodate equipment.
14. Cove QT base, 6" high.
15. No separate trim at top of base, use alternate method to seal to wall.
16. Ceiling suspension system should be fabricated from nonferromagnetic material.
17. Aesthetic specialty materials may be used as accents where the design and budget permits.
18. Ceiling tile to meet USDA regulations.
19. Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces
20. Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.
21. Wall CT and ceiling to meet building code light reflectancy standards.
22. Space may be room or area within a room. Coordinate finishes with adjacent spaces.
23. Provide 3/4" painted plywood where required by Telecommunications.
AT Acoustical Ceiling Tile
AT-SP Acoustical Scrubbable Ceiling Tile (with sprayed plastic finish)
CS Concrete, Sealed
CPT Carpet Tile
CT Ceramic Tile (Wall)
EP Epoxy Paint
EPY Epoxy Flooring
EXP Exposed Ceiling
GWB Gypsum Wallboard System
LVT Luxury Vinyl Tile
MAT Modular Carpet Walk Off Mat
P Paint
PT Porcelain Tile
QT Quarry Tile
RB Resilient Base
RES Resinous Flooring and Base
RF Rubber Flooring
RFT Resilient Floor Tile
RSF Resilient Sheet Flooring - Heterogeneous
RWC Rigid Wall Covering (Wall Protection)
SD Static Dissipative Tile
S Solid Surface Fabrication
WSF Welded Seam Sheet Flooring - Homogeneous
Finish Codes
Doors and Hardware Notes
General Notes
A.
Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to the group.
B. All doors to be 7'-0" high, unless otherwise noted.
C.
Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in
Room Data Matrix - Interior Finishes in Appendix.
D. All Communications Closets to have security hinges.
Schedule Notes
1. Hollow metal frame cased opening
2. Two door (in swing and swing out) acoustical door and frame assembly.
3. Two doors required at this room/space.
4. Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.
5. Provide STC 50 rated acoustical door.
6. No door in this room/space.
7. Equal leaf pair of doors.
8. Lead lined door and hardware.
9. Space may be a room or area within another room. Omit door if space is not a separate room.
ELECTRICAL NOTES
POWER NOTES LIGHTING NOTES
P1. Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.
L1. EMI/RFI emissions to be controlled
P2. Receptacles on all walls L2. Dimmable to 5 fc
P3. Coordinate electrical connections with equipment to be installed.
Receptacles on all walls.
L3. May not have ceiling - then use industrial fixture type
P4. Plug strip at 44" above counters L4. May not have ceiling. If no ceiling, use industrial fixture type
P5. Multiple receptacles above and below desk for device charging L5. Treat like a store. Adjustable lighting, General lighting.
P6. Cord reel(s) for freestanding workbenches L6. No ceiling in these rooms. No prescription for lighting.
P7. All outlets on dedicated circuits. L7 Provide task lighting at work counters if not already part of workstation furniture.
P8. Cord reel(s) for freestanding workbenches L8 Provide ultraviolet specialty lighting in Tele-derm/Tele-health Exam Rooms.
P9. Treadmill on dedicated circuit
P10. Each hood on dedicated circuit
P11. Provide receptacles per equipment plan
P12. Electrical to review redundancy requirements with OIT guidelines.
P13. Receptacle above ceiling for overhead lift
P14. Recessed power quad floor box
P15. L21-20R receptical above each rack
P16. Provide connections to cubicle furniture
P17 Coordinate ESS power requirements for equipment and receptacles.
MECHANICAL HVAC NOTES
M1. Intentioanlly Left Blank
M2. Per ASHRAE 62 for ventilation, and FGI Guidelines for NC
M3. General Open Office area
M4. General Open/Public area
M5. Per ASHRAE 62 for ventilation if interior enclosed space.
M6. Comply with ASHRAE 15 if Special Refrigeration Systems are used
M7. If chemicals are used, provide specialized exhaust
M8. Data Center
M9. Transfer air to Food Prep Kitchen
M10. Intentioanlly Left Blank
M11. MEP Room
M12. See USP-797 and -800
M13. Counter-height specialized exhaust system required
M14. Provide air conditioning and ventilation per imaging manufacturer recommendations
M15. General Office Area
M16. Verify specific vendor/manufacturer requirements.
M17. Non-ferrous construction
M18. Provide cooling only air terminal unit to serve the manual equipment wash room.M19. Provide a dedicated wet exhaust system