About this file

This document is a detailed Room Data Matrix (RDM) for a VA Buffalo Research and Development facility lease project, providing comprehensive interior design and technical specifications for various rooms across multiple functional areas including R&D, VMU (Veterinary Medical Unit), Biomedical Laboratory, Logistics, and support spaces. The matrix meticulously outlines specific requirements for each room, including interior finishes, doors and hardware, electrical and mechanical systems, with precise details such as floor and wall materials, ceiling heights, sound isolation ratings, temperature and humidity controls, lighting fixtures, power outlets, and specialized environmental considerations for research and animal handling spaces.

The document covers approximately 50-60 distinct rooms with granular specifications, ranging from general office areas and conference rooms to specialized spaces like surgical preparation rooms, microscopy rooms, animal holding areas, and waste management facilities. Key technical specifications include specific environmental controls (temperature ranges of 68-79°F, humidity controls), specialized exhaust systems, lighting configurations (multilevel switching, dimming, occupancy sensors), power requirements (dedicated circuits, receptacle types), and unique room-specific needs such as clean room ceilings, acoustic sealing, and specific door and hardware configurations. The matrix is associated with VA Solicitation Number 36C10F25R0010 for the Buffalo Research and Development facility, indicating a comprehensive design and technical planning document for a federal construction/renovation project.

View the file

Other files

File Type Posted
VA RLP36C10F25R0010 Buffalo_Questions Round.pdf PDF
Exhibit 02F-Buffalo Appendix A.5 -VA Security Requirements_FSL Level II.pdf PDF
36C10F25R0010 0002.docx DOCX document
VA RLP 36C10F250010_Buffalo Amendment No. 2.pdf PDF
36C10F25R0010 0001.docx DOCX document
VA RLP 36C10F250010_Buffalo Amendment No. 1.pdf PDF
18-Buffalo Erie County DOL Wage Determination.pdf PDF
11-Buffalo SF-330.pdf PDF
03-Buffalo Appendix B - Lease Service Narrative.pdf PDF
02A-Buffalo Appendix A - Progam For Design _PFD 06022024 rv3.pdf PDF
13-Buffalo VA Handbook 6500.6 Appendix C.pdf PDF
09-Buffalo VA Form 10091.pdf PDF
04-Buffalo Offering Entity Acknowledgement Form.docx DOCX document
15-Buffalo GSA Form 3517B _Feb. 2025.pdf PDF
00-Buffalo RLP.pdf PDF
19-Buffalo FAR 52.204-24.pdf PDF
02G-Buffalo Appendix A.6 - R_D Conceptual Floor Plan - 01072025.pdf PDF
05-Buffalo Offeror Proposal Compliance Matrix_Oct 24.docx DOCX document
06-Buffalo Proposal to Lease Space_Form 1364.pdf PDF
02F-Buffalo Appendix A.5 -VA Security Requirements_FSL Level III_ Oct 2024.pdf PDF
02C-Buffalo Appendix A.2 - Lease Design Narrative _LDN for Buffalo R_D - 02132025.pdf PDF
02E-Buffalo Appendix A.4 - VA CBOC Information Transport Systems Specifications.pdf PDF
02D-Buffalo Appendix A.3 - Room Data Matrix _RDM_ -Refer To Accompanying Excel File For Ease of Use.pdf PDF
02B-Buffalo Appendix A.1 - Project Room Contents List _PRCL - 01092025.xlsx XLSX spreadsheet
12-Buffalo GSA Form 527.pdf PDF
20-Buffalo VA Subcontracting Plan Template.docx DOCX document
14-Buffalo GSA Form 3516_Feb. 2025.pdf PDF
02-Buffalo ASR Cover Page.pdf PDF
16-Buffalo GSA Form 12000.pdf PDF
17-Buffalo Certification of Building Energy Performance.pdf PDF
07-Buffalo Attachment No. 1 to 1364.xlsx XLSX spreadsheet
36C10F25R0010.docx DOCX document
22-Buffalo Pre-Bid Registration Form.docx DOCX document
10-Buffalo Past Performance Questionnaire Form for VA _REV. Nov 23.pdf PDF
21-Buffalo Seismic Offer Forms.pdf PDF
02B-Buffalo Appendix A.1 - Project Room Contents List _PRCL - 01092025.pdf PDF
08-Buffalo GSA Form 1217.pdf PDF
01-Buffalo L100.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RDM Org

VA BUFFALO RESEARCH LEASE
R&D ROOM DATA MATRIXINTERIOR CONSTRUCTIONDOORS AND HARDWAREMECHANICALELECTRICALIT
ROOM IDENTIFICATIONFLOORWALLSCEILINGNOTESNote: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise.POWERLIGHTING
Functional AreaDEPARTMENTROOM NAMEROOM CODE (VA) / BLDG AREA
FGI EQUIVALENT FOR ASHRAE 170FGI EQUIVALENT FOR TABLE 1.2-5 Minimum Sound IsolationFloor FinishBaseWall FinishWainscot MaterialWainscot HeightSTCCeiling FinishHeightInterior Finishes NotesSize (Width)
s:Type
t: xMaterial
m:GlazingRatingHardware GroupHardware NotesIndoor Temperature
Cooling FIndoor Temperature
Heating FIndoor Relative Humidity
% RH MaxIndoor Relative Humidity
% RH MinMinimum Total ACHMinimum OA ACHRoom Air Return
Gen. Exh G Spec Exh SMaximum Noise
Level NCRoom Air BalanceHVAC Notes# Duplex Receptacles# Quad ReceptaclesPower - NotesFixture TypeControlsLighting - Special RequirementsLighting - Notes# Data Outlets (standard density WAO)IT -

Special Requirements

1R&D General / ShowerVMU Female Staff Shower, Bldg Sprt
VMU Male Staff Shower, Bldg SprtSB184
SB173PTPTCT----SEE FGIGWB / SC9'-0"2, 193'-6"------7570603010NAExhaust (G)40(-)Individual Temperature Controll1---2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A--
1R&D General / ToiletsGeneral Toilet,

Female Staff, Toilet Male Staff, Toilet SB191

SB202

SB203PTPTGWB / PPT4'-0"AT9'-0"3'-6"9Wood__2G_7570603010NAExhaust (G)40(-)Individual Temperature Controll2---2x2 / 2x4 TrofferOccupancy SensorN/AN/A--
1R&D General / H.A.C.Housekeeping Aides Closet (HAC)SB244QTQTGWB/SC-4'-0"--AT9'-0"3'-6" PAIRFlushWood----5D_NANANANA10NAExhaust (G)40(- -)No1---2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A--
1R&D GeneralWalk-in Vestibule, Bldg SprtSB291MATRBGWB / P---GYP9'-0"NANANANANANANA40(+)Individual Temperature Controll1---2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A--
1R&D General / OI&TBLR&D Telecommunications Room (TR), OITSC391SDRBGWB/P------EXP.12'-0"3'-0"9WoodNarrow Vision--SH-3H; Card Reader816460302NAReturn45(+)Individual Temperature Controll6--P15Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A--
1R&D General / ConferenceR&D Conference / Multipurpose Room, Educ SvcSS101CPTRBGWB / P----40AT9'-0"173'-0"FlushWood__4J_7570603042Return35(o)Individual Temperature Control4--P22x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyProvide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections.N/A2Floor data for table
1R&D OfficeBLR&D PI Office, Stff Sprt

R&D Administrative Chief of Staff (ACOS) Office, Stff Sprt R&D Research Office, Stff Sprt - HRPP & RD prog manager R&D Administrative Officer (AO) Office, Stff Sprt VMU Veterinarian Office/VMU Facility Manager Office, Stff Sprt

SS204CPTRBGWB / P------AT9'-0"3'-0"9Wood----3E7570603042Return40(o)Individual Temperature Control4--P22x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
1R&D OfficeR&D Admin Shared Office, Stff Sprt

VMU Shared Office, Stff Sprt

SS209CPTRBGWB / P------AT9'-0"3'-0"9Wood----3E7570603042Return40(o)Individual Temperature Control4--P22x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
1R&D General / Staff LoungeBLR&D Staff Breakroom, Stff Sprt
VMU Staff Breakroom, Stff SprtSS262SVTRBGWB / P----40AT9'-0"43'-0"9WoodNarrow Vision--SH-4_7570603042Exhaust (G)40(-)Individual Temperature Control3---2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A--Provide Data Outlets to match IT Requiremnets in PRCL
1R&D General / OfficeBLR&D Copy / Supply Alcove, Stff Sprt
R&D Copy / Supply Alcove, Stff SprtSS268CPTRBGWB / P------AT9'-0"6OPENOPENOPEN------7570603062Return40(0)Individual Temperature Control2---2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Corridors (General Circulation), R&DBLR&D CorridorRESRESGWB / P / SC------AT / SP9'-0"-4'-0"--MetalNarrow Vision----7570603042Return40(+)Individual Temperature Control11 Receptacles should be provided every 5'-0"--P112x2 / 2x4 TrofferN/AN/A11 Data Outlets should be provided every 5'-0"
2Biomedical LaboratoryBLR&D Mail Alcove, Lgstcs SvcSB653LVTRBGWB / P--GWB9'-0"3'-0"OPENOPEN----7570603042Return40(o)Individual Temperature Controll1---2x2 / 2x4 TrofferOccupancy SensorN/AN/A--
2Biomedical LaboratoryBLR&D Lab Access / Protocol Room, R&DSC701RESRESGWB / P------AT9'-0"3'-6"
PAIR10MetalNarrow VisionSH-3E7570603042Return40(+)Individual Temperature Controll2P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
2Biomedical LaboratoryBLR&D Bench Unit, R&DSC702RESRESGWB / P--STC 50AT10'-0"Exposed ceilings are to have a clear ceiling height as listed above and at minimum 4'-0" clear below the structural beams and slab for MEPT equipment.3'-6"10N/A----SH-3E7570603062Return40(-)Individual Temperature Control2--1. Power for laboratory benches shall generally be provided by twist lock receptacles in ceiling service panels. 2. Provide convenience receptables throughout laboratory. 3. Dual channel raceways at laboratory benches shall contain duplex receptables and data spaced 18" O.C. P102x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A4
2Biomedical LaboratoryBLR&D Ghost Corridor, R&DSC703RESRESGWB / P--STC 50AT10'-0"3'-6"10N/A----SH-3EExposed ceilings are to have a clear ceiling height as listed above and at minimum 4'-0" clear below the structural beams and slab for MEPT equipment.7570603062Return40(-)Individual Temperature Controll----1. Power for laboratory benches shall generally be provided by twist lock receptacles in ceiling service panels. 2. Provide convenience receptables throughout laboratory. 3. Dual channel raceways at laboratory benches shall contain duplex receptables and data spaced 18" O.C.2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A--
2Biomedical LaboratoryBLR&D Bench Support, R&DSC704RESRESGWB / P-STC 50AT10'-0"3'-6"10N/A----SH-3EExposed ceilings are to have a clear ceiling height as listed above and at minimum 4'-0" clear below the structural beams and slab for MEPT equipment.7570603062Return40(-)Individual Temperature Controll----1. Power for laboratory benches shall generally be provided by twist lock receptacles in ceiling service panels. 2. Provide convenience receptables throughout laboratory. 3. Dual channel raceways at laboratory benches shall contain duplex receptables and data spaced 18" O.C.2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Core Room, R&DSC711RESRESGWB / P / SC------GYP / P9'-0"3'-6"10MetalNarrow Vision_3F7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Microscopy Room (Confocal), R&DSC712RESRESGWB / P / SC------CAT Clean Room Ceiling9'-0"3'-6"7Metal__4NAdd light seals7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Microscopy Room (Photonic), R&DSC712RESRESGWB / P / SC------CAT Clean Room Ceiling9'-0"3'-6"7Metal_R/F Shielded3FAdd light seals7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Microscopy Room, R&DSC712RESRESGWB / P / SC------CAT Clean Room Ceiling9'-0"3'-6"7Metal__3FAdd light seals7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Super Resolution Microscope Room (Microscopy), R&DSC712RESRESGWB / P / SC------GYP / P9'-0"3'-6"7Wood__3FAdd light seals7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryGlassware Washing / Sterilizer RoomSC713RESRESGWB / P / SC------RES-W9'-0"--3'-6"10WoodNarrow Vision-4S--NANANANA102Exhaust (S)40(-)No21-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AFixtures to be sealed and gasketed with a minimum rating of IP65.2
2Biomedical LaboratoryBLR&D Walk-in Refrigerator / Cold Room, R&D

BLR&D Walk-in Refrigerator / Cold Room, R&D - Infectious Disease

BL Walk-in Refrigerator / Cold Room, R&D (VMU)SC714PRE-FAB--PRE-FAB------PRE-FAB9'-0--PRE-FABPRE-FABPRE-FAB--------8640NANA6NAReturn45(o)Individual Temperature Control---2x2 / 2x4 TrofferN/A--
2Biomedical LaboratoryBLR&D General Storage Room, R&DSC716RESRESGWB / P / SC------AT9'-0"--3'-6"10MetalNarrow Vision--5--NANANANA4NAReturn40(+)No4--P22x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A--
2Biomedical LaboratoryBLR&D Equipment Room, R&DSC717RESRESGWB / P / SCRWC4'-0"--AT9'-0--3'-6"10MetalNarrow Vision--5--NANANANA44Exhaust (G)40(o)No----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Freezer Equipment Room, R&DSC717RESRESGWB / P / SC------GWB / P / SC9'-0"--4'-0"4WoodNarrow Vision--4N--NANANANA44Exhaust (G)40(o)No----P11 / P142x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Darkroom, R&DSC719RESRESGWB / SC
Darkroom Applique------GYP / SC9'-0"---Revolving Dark Room Door
PRE-FAB------3J--7272604566Exhaust (G)40(-)Individual Temperature Control----P11--Multilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Tissue Culture Room, R&D,SC721WSFWSFGWB / P / SC------AT / SP10'-0"-3'-6"10Metal__4K--7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Stem Cell Research RoomSC721*WSFWSFGWB / P / SCRWC4'-0"GWB/ P / SC9'-0"-3'-6"10MetalNarrow Vision4--686860301212Exhaust40(-)Individual Temperature Control----P112x2 / 2x4 TrofferN/A2
2Biomedical LaboratoryBLR&D Flow Cytometry, R&DSC724RESRESGWB / P------GYP / P10'-0"-3'-6"10Metal__4K--7570603062Exhaust (S)40(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Fume Hood Room, R&DSC725RESRESGWB / P------AT / SP9'-0"-3'-6"10Metal-4K--7570603062Exhaust (S)40(-)Individual Temperature Control31Provide dual channel surface mounted raceway at laboratory benches. P10 / P11
2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
2Biomedical LaboratoryBLR&D Stem Cell Research AnteroomSC881*WSFWSFGWB / P / SCGWB / P / SC9'-0"-3'-6"10MetalNarrow VisionILIL--686860303535Exhaust (G)40(+)Individual Temperature Control2--2x2 / 2x4 TrofferN/A1
2Biomedical LaboratoryBLR&D Male Staff Locker Room, Stff Sprt
BLR&D Female Staff Locker Room, Stff SprtSS241
SS232PTPTGWB / P------AT9'-0"-3'-0"5Metal----SH-4--7570603010NAExhaust (G)40(-)Individual Temperature Control----2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
2VMU Animal AreaVMU Medication Room
SV582RESRESGWP / SC------AT9'-0"-3'-0"10Wood----SH-3D--7570603062Return35(o)Individual Temperature Control442x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Treatment AreaVMU General Procedure / Treatment Room, R&DSC741RESRESGWB/RES-W------GWB/RES-W9'-0"-08 32 13 ICU Sliding Door with Automatic Door Operatotrs10Metal---4C37272554088Exhaust (G)35(+)HVAC Room Balance (-). General exhaust air at approximately 7 inches above floor through 1 inch thick MERV 6 filter grille.31P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Treatment AreaVMU Surgical Preparation Room, R&DSC751RESRESGWB/RES-W------GWB/RES-W9'-0"-08 32 13 ICU Sliding Door with Automatic Door Operatotrs10MetalNarrow Vision-4C-6565604544Exhaust (G)35(+)General Exhaust

HVAC Room Balance (-)

Individual Temperature Control21-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Treatment AreaVMU Recovery Room, R&DSC753RESRESGWB/RES-W------GWB/RES-W9'-0"-08 32 13 ICU Sliding Door with Automatic Door Operatotrs10MetalNarrow Vision-4C-656560451010Exhaust (G)40(+)Individual Temperature Control21-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Treatment AreaVMU Gown / Scrub Room, R&DSC754RESRESGWB/RES-W------GWB/RES-W9'-0"-3'-0"10MetalNarrow Vision4C-7272604544Exhaust (G)35(+)Individual Temperature Control1--2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A-
3VMU Treatment AreaVMU Surgical Supply Storage Room, R&DSC756RESRESGWB/RES-W------GWB/RES-W9'-0"-3'-0"6MetalNarrow Vision4C-7272604544Exhaust (G)35(o)Individual Temperature Control1--2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Imaging / Behavioral Study AreaVMU Imaging / Behavioral Animal Preparation Control Room, R&DSC761RESRESGWB /RES-WRWC4'-0"STC 60RES-W10'-0"-3'-6"20MetalNarrow Vision--4C-7272604588Exhaust (G)40(-)Provide exhaust air inlets at base corners and center ceiling supply outlet. Room Balance (-). Individual Temperature Controls1-P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Imaging / Behavioral Study AreaVMU Imaging / Behavioral Animal Holding Room, R&DSC762RESRESGWB /RES-W----RES-W9'-0"-4'-0"FlushMetal----4Q-7272604588Exhaust (G)40(-)Provide exhaust air inlets at base corners and center ceiling supply outlet. Room Balance (-). Individual Temperature Controls--2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A-
3VMU Imaging / Behavioral Study AreaVMU Behavioral Study Room, R&DSC763RESRESGWB /RES-W----STC 60RES-W9'-0"-4'-0"FlushMetal----4Q-796870301515Exhaust (G)35(-)Individual Temperature Control4--P42x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Imaging / Behavioral Study AreaVMU Blast Study Room, R&DSC764RESRESGWB /RES-W----STC 60RES-W9'-0"-4'-0"FlushMetal__4Q-796870301515Exhaust (G)35(-)Individual Temperature Control4-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Imaging / Behavioral Study AreaVMU Imaging Study Room, R&DSC764RESRESGWB /RES-W----STC 60RES-W9'-0"-4'-0"FlushMetal----4Q-7968703015 ACH15 ACHExhaust (G)35(-)Individual Temperature Control----P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Animal AreaVMU Small Animal Holding Room (Positive Pressure), R&D (1 Room)

VMU Small Animal Holding Room, R&D

VMU Behavioral / Metabolic Studies Small Animal Holding, R&DSC771
SC772RESRESGWB /RES-W----STC 60RES-W9'-0"-4'-0"20MetalNarrow Vision--4C(1). Provide red glass with door to cover.

(2). Add light and acoustic seals.

(3). See Specification 08 71 13 Automatic Door Operators.7968703015 ACH15 ACHExhaust (G)35(+) (Only 1 Room)
(-)Individual Temperature Control41Provide watertight, twist lock receptacles for blower units in animal holding rooms.
1x4 /2x2 / 2x4 Troffer (Surface-mounted, gasketed IP65)Multilevel Switching, Dimming & OccupancyDiurnal LightingGeneral illumination shall be provided by recessed or surface mounted, gasketed IP65 1x4/2x2/2x4 fixtures or similar.2
3VMU Animal AreaVMU BSL-2 Small Animal Holding Room, R&DSC773RESRESGWB /RES-WRWC4'-0"STC 60RES-W08 32 13 ICU Sliding Door (4'x 7'). Light & acoustic seals. Red glass w/door to cover.-3'-6"20MetalNarrow Vision--4C-7968703015 ACH15 ACHExhaust (G)35(-)Individual Temperature Control9Power Outlets Watertight twist lock receptacles for blower units in animal holding.1x4 /2x2 / 2x4 Troffer (Surface-mounted, gasketed IP65)Multilevel Switching, Dimming & OccupancyDiurnal Lighting. May need shielding, depending on use.N/A2
3VMU Animal AreaVMU BSL-2 Small Animal Holding Anteroom, R&DSC774RESRESGWB / SCRWC4'-0"STC 60AT/ SP9'-0"-3'-6"10MetalNarrow Vision--1F-7968703015 ACH15 ACHExhaust (G)35(-)Individual Temperature Control4--1x4 /2x2 / 2x4 Troffer (Surface-mounted, gasketed IP65)Multilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Animal AreaVMU Small Animal Quarantine Holding Room, R&DSC778RESRESGWB /RES-WRWC4'-0"STC 60RES-W10'-0"-3'-6"20MetalNarrow Vision--4C-7272554515 ACH15 ACHExhaust (S)35(-)Individual Temperature Control4--1x4 /2x2 / 2x4 Troffer (Surface-mounted, gasketed IP65)Multilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Animal AreaVMU Necropsy Room, R&DSC781RESRESGWB/ RES-W------RES-W9'-0"-3'-6"20MetalNarrow Vision--4C-7272554015 ACH15 ACHExhaust (S)40(-)Individual Temperature Control22P22x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2Additional raceways on benches for power and data.Additionally provide wall mounted individual power outlets: 5 and 1 wall mounted data outlet.
3VMU Cagewash AreaVMU Soiled Cage Room, R&D - Inc cage staging/storageSC791RESRESGWB/ RES-WRWC--GWB/RES-W9'-0-3'-6"
PAIR10MetalNarrow Vision--10A-727255402020Exhaust (S)40(-)Individual Temperature Control---P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Cagewash AreaVMU Cagewash Equipment Room, R&DSC792RESRESGWB/ RES-W------GWB/RES-W9'-0-3'-6"10MetalNarrow Vision--10A-777755401515Exhaust (S)40(-)Wet Exhaust System
(-) Individual Temperature Control---P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Cagewash AreaVMU Clean Cage Room, R&D - inc cage staging/storageSC793RESRESGWB /RES-WRWC4'-0"--GWB/RES-W9'-0-3'-6"
PAIR10MetalNarrow Vision--10A-7770554066Exhaust (G)40(+)Wet Exhaust System
(-) Individual Temperature Control---P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
3VMU Cagewash AreaVMU Sterilizer Equipment Room, R&DSC794RESRESGWB/ RES-W------GWB/RES-W9'-0-3'-6"10MetalNarrow Vision--10A-777755401515Exhaust (S)40(-)Wet Exhaust System
(-) Individual Temperature Control---P112x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A2
3VMU Cagewash AreaVMU Cagewash Detergent Storage Room, R&DSC797RESRESGWB/RES-W------GWB/SC9'-0-3'-6"FlushMetalNarrow Vision--5D-7770554066Exhaust (G)40(+)Individual Temperature Control1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Support AreaVMU Bedding Room, R&DSC798RESRESGWB/RES-W------GWB/RES-W9'-0"-4'-0"FlushMetal----5B-NANANANA44Exhaust (G)40(o)No Individual Temperature Control2-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Support AreaVMU Receiving Room, R&DSC801RESRESGWB / P------OPEN9'-0-3'-6" PAIR6Metal1F-727255451010Exhaust (G)35(-)Collect room exhaust air at approximately 7 inches above the floor level through 1 inch thick MERV 6 filter grille. 10 ACH. Overhead motorzied roll up door. Access control on exterior door(s). Air curtain with heating element.2-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Support AreaVMU Laundry Room, R&DSC802RESRESGWB / P------AT9'-0-4'-0"103E-7870603062Exhaust (G )45(-)Individual Temperature Control1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Support AreaVMU General Storage Room, R&DSC803RESRESGWB/RES-W------GWB/RES-W9'-0-3'-0"12MetalNarrow Vision--5B-NANANANA4NAReturn40(+)No1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Support AreaVMU Waste Room, R&DSC805RESRESGWB / SCRWC4'-0"--AT / SP
9'-0"-3'-6"6Metal----SH-3F-NANANANA1010Exhaust (S)40(- -)Dedicated exhaust system. Terminate exhaust at least 10 feet above highest roof level. Discharge exhaust at 3500 FPM and according to the dispersion analysis recommendations. Evaluate the need for filtration in the exhaust air duct discharging outdoors. Consult end users and local safety officer for exhaust air filtration requirements.1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Support AreaVMU Food Storage Room, R&DSC806RESRESGWB/RES-W------GWB/RES-W9'-0"-4'-0"10Metal----5B-3636NANANANAExhaust (G)40(-)Individual Temperature Control1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
3VMU Animal AreaVMU Auto Clave 0 VMU BSL-2SC902RESRESRES-WRWC4'-0"--AT: SP9'-0"-3'-6"20MetalNarrow Vision--4-796870301515Exhaust (S)40(-)Individual Temperature Control1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A1
4LogisticsR&D Gas Manifold Room, Bldg SprtSB241RESRESCMU / P / SC------GWB / SC9'-0"-3'-0"6Metal--45 MIN5B-NANANANA6NAExhaust (G)40(- -)No-1x4 / 2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
4LogisticsR&D Recycling Room, Bldg SprtSB297WSFWSFGWB / SCRWC4'-0"--AT / SP9'-0"-3'-0"5Wood--SH-3C-NANANANA44Exhaust (G)40(o)No1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/A
4LogisticsR&D - Breakdown Room, Lgstcs SvcSB522RESRESGWB / P------AT9'-0-3'-0"5Metal--4F-7570603042Return40(o)Individual Temperature Control1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
4LogisticsVMU Staging Room, Lgstcs SvcSB531RESRESGWB /P------AT9'-0-3'-0"5Metal--11-796870301515Exhaust (G)40(-)No1-2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/A
4LogisticsR&D Full / Empty Gas Cylinder Storage Room, Lgstcs SvcSB551RESRESGWB / P------AT9'-0"-3'-0"5 Undercut by 1"Metal--5B-NANANANA6Exhaust (G)40(- -)No-1x4 / 2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
4LogisticsR&D Flammable Storage Room, Lgstcs SvcSB561
RESRESGWB / PRWC4'-0"--GWB / SC9'-0"-3'-0"----5B-NANANANA1010Exhaust (S)40(- -)No-1x4 / 2x2 / 2x4 Troffer-N/A
4LogisticsR&D Corrosive Storage Room, Lgstcs SvcSB565RESRESGWB / PRWC4'-0"--AT / SP9'-0"-3'-0"----5B-NANANANA1010Exhaust (S)40(- -)No-1x4 / 2x2 / 2x4 Troffer-N/A
4LogisticsReceiving/ Shipping DockSB684CCGWB/ P------EXP.---9'-0" x 10'-0"Motorized Roll UpMetal-----NA60NANANANAReturn45(o)Individual Temperature Control2-1x4 / 2x2 / 2x4 TrofferMultilevel Switching, Dimming & OccupancyN/AN/A
4LogisticsChemical Waste Room, R&DSC821RESRESGWB / PRWC4'-0"--AT / SP9'-0"-3'-0"----SH-3F-NANANANA1010Exhaust (S)40(- -)No-2x2 / 2x4 Troffer-N/A
4LogisticsBiological Waste Room, R&DSC823RESRESGWB / PRWC4'-0"--AT / SP9'-0"-3'-0"----SH-3F-NANANANA1010Exhaust (S)40(- -)No-2x2 / 2x4 Troffer-N/A

&"Franklin Gothic Demi,Regular"&14VA Buffalo Lease RLP

Sheet1

Interior Finishes Notes Interior Finishes Notes

General Notes
A.Hollow metal frames and doors to be painted.
B.Window sills to be solid surface fabrication.
C.Resilient base to be 4", unless otherwise noted.
D.Provide painted finishes only on inside of exterior walls (no wall covering).
E.Floor material transitions to occur at centerline of door, unless otherwise noted.
F.Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.
G.Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.
H.Coordinate height of wall protection with wall-mounted devices.
I.Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and
lobby/waiting areas.
J.Soffit above upper cabinets to be gypsum board.
K.Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.
L.Solid surface countertops to have sides and backsplash at walls.
Schedule Notes
1.CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.
2.Tile base to be coved.
3.Integral coved base 6" high tightly sealed to walls.
4.If sink is present, use hard suface flooring as noted.
5.Lead lined walls and control area view window.
6.Flooring and base to match adjacent area flooring material and base.
7.Use gasketed, clip down ACT/grid system
8.Use slip-retardant finish on floor material
9.Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.
10.Note that if wall saver designed chairs are used, no wall protection is required.
11.Extend all room partitions to structural deck.
12.CT above countertop on wall.
13.Ceiling height as required to acommodate equipment.
14.Cove QT base, 6" high.
15.No separate trim at top of base, use alternate method to seal to wall.
16.Ceiling suspension system should be fabricated from nonferromagnetic material.
17.Aesthetic specialty materials may be used as accents where the design and budget permits.
18.Ceiling tile to meet USDA regulations.
19.Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces
20.Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.
21.Wall CT and ceiling to meet building code light reflectancy standards.
22.Space may be room or area within a room. Coordinate finishes with adjacent spaces.
23.Provide 3/4" painted plywood where required by Telecommunications.
Finish Codes
ATAcoustical Ceiling Tile
AT-SPAcoustical Scrubbable Ceiling Tile (with sprayed plastic finish)
CPTCarpet Tile
CSConcrete, Sealed
CTCeramic Tile (Wall)
EPEpoxy Paint
EXPExposed Ceiling
GWBGypsum Wall Board
MATModular Carpet Walk Off Mat
PPaint
PTPorcelain Tile
QTQuarry Tile
RBResilient Base
RESResinous Flooring and Base
RFRubber Flooring
RFTResilient Floor Tile
RSFResilient Sheet Flooring - Heterogeneous
RWCRigid Wall Covering (Wall Protection)
SCSpecial Coating
SDStatic Dissipative Tile
SSolid Surface Fabrication
WSFWelded Seam Sheet Flooring - Homogeneous

Doors and Hardware Notes Doors and Hardware Notes

General Notes
A.Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to
the group.
B.All doors to be 7'-0" high, unless otherwise noted.
C.Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in Room Data Matrix - Interior Finishes in Appendix.
Schedule Notes
1.Hollow metal frame cased opening
2.Two door (in swing and swing out) acoustical door and frame assembly.
3.Two doors required at this room/space.
4.Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.
5.Provide STC 50 rated acoustical door.
6.No door in this room/space.
7.Equal leaf pair of doors.
8.Lead lined door and hardware.
9.Space may be a room or area within another room. Omit door if space is not a separate room.
10Door to have automatic door opener hardware.

Electrical Notes

ELECTRICAL NOTES

POWER NOTESLIGHTING NOTES
P1.Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.L1.EMI/RFI emissions to be controlled
P2.Receptacles on all wallsL2.Dimmable to 5 fc
P3.Coordinate electrical connections with equipment to be installed. Receptacles on all walls.L3.May not have ceiling - then use industrial fixture type
P4.Plug strip at 44" above countersL4.May not have ceiling. If no ceiling, use industrial fixture type
P5.Multiple receptacles above and below desk for device chargingL5.Treat like a store. Adjustable lighting, General lighting.
P6.Cord reel(s) for freestanding workbenchesL6.No ceiling in these rooms. No prescription for lighting.
P7.All outlets on dedicated circuits.
P8.Cord reel(s) for freestanding workbenches
P9.Treadmill on dedicated circuit
P10.Each hood on dedicated circuit
P11.Provide receptacles per equipment plan
P12.Electrical to review redundancy requirements with OIT guidelines.
P13.Receptacle above ceiling for overhead lift
P14.Recessed power quad floor box
P15.L21-20R receptical above each rack
P16.

Mechanical Notes

MECHANICAL HVAC NOTES

M1.Intentioanlly Left Blank
M2.Per ASHRAE 62 for ventilation, and FGI Guidelines for NC
M3.General Open Office area
M4.General Open/Public area
M5.Per ASHRAE 62 for ventilation if interior enclosed space.
M6.Comply with ASHRAE 15 if Special Refrigeration Systems are used
M7.If chemicals are used, provide specialized exhaust
M8.Data Center
M9.Transfer air to Food Prep Kitchen
M10.Intentioanlly Left Blank
M11.MEP Room
M12.See USP-797 and -800
M13.Counter-height specialized exhaust system required
M14.Provide air conditioning and ventilation per imaging manufacturer recommendations
M15.General Office Area
M16.Verify specific vendor/manufacturer requirements.
M17.Non-ferrous construction
M18.Provide cooling only air terminal unit to serve the manual equipment wash room.
M19.Provide a dedicated wet exhaust system

File details come from the government source that posted it. Updated .