This is a mechanical and electrical design document for the Georgia World Congress Center (GWCC) Authority's GESPC II Building C Chilled Water Plant Upgrades project, prepared by TLC Engineering Solutions, Inc. The project involves comprehensive modifications to the existing chilled water plant located in Building C, including replacement of water-cooled chillers and hydronic pumps, as well as replacement of secondary heating hot water pumps. The scope encompasses three new Trane CVHF water-cooled chillers (one 1,300-ton unit rated at 4160V and two 1,000-ton units rated at 480V), multiple new circulating water pumps including primary and secondary chilled water pumps, condenser water pumps, and heating hot water pumps manufactured by Bell & Gosset. The design includes installation of new refrigerant monitoring panels compatible with R-514A refrigerant, electromagnetic insertion flowmeters (Onicon F-3500 or equivalent), temperature sensors, and BTU meter interface displays. New variable frequency drives with electronic bypass capability are specified for pump operation, and all equipment requires vibration isolation on concrete housekeeping pads with inertia bases. The electrical scope includes connection of existing feeders to new chillers, installation of new breakers and feeders for new equipment, and integration with the building automation system's direct digital controls (DDC) for monitoring operating KW and KWH.
The design specifies detailed mechanical and electrical demolition requirements, including removal of existing 1,100-ton water-cooled chillers, disconnection of refrigerant and electrical services, and reclamation of refrigerant prior to demolition activities. All equipment connections must be verified with manufacturer certified drawings, and field modifications such as piping or ductwork offsets required due to obstructions shall be provided at no additional cost to the contractor. The project requires coordination with existing building elements and other trades, with minimum 6-inch clearance maintained between ductwork and fire-rated partitions. All piping penetrations must be sleeved and sealed, and manual air vents shall be provided at high points in chilled and hot water systems. The electrical connection schedule indicates feeder sizes and circuit requirements for each piece of equipment, with copper conductors rated for MV-90 5KV service. A communication restriction is in effect for this procurement, prohibiting interested firms from communicating with Authority staff, GWCC officials, or their consultants except through formal question submission processes. Finalists and apparent awardees are further restricted from making public statements or press releases regarding their selection, with violations subject to submittal rejection.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| GESPCII COMMISSIONING SERVICES (003).pdf | ||
| GESPC II Commissioning Fee Proposal Form.docx | DOCX document | |
| 01KTW19HYAGV486HFH489XWFMW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
P
M
TS
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION
SYMBOL DESCRIPTION
RHC-1-1
PCHWP-1
M-1
-TEMPERATURE SENSOR
-MOTORIZED CONTROL DAMPER
-THERMOSTAT/TEMPERATURE SENSOR
-REVISION REFERENCE
-DETAIL REFERENCE: TOP-DETAIL#,
BOTTOM-DRAWING# SHOWN ON
-PRESSURE SENSOR
-CONNECT TO EXISTING
-DEMOLISH TO POINT INDICATED
DDC -DIRECT DIGITAL CONTROLS
PRS -PRESSURE REDUCING STATION
SP -STATIC PRESSURE
-CFM (CUBIC FEET PER MINUTE)
P -CHANGE IN PRESSURE
CV -CONSTANT AIR VOLUME
RS/L -REFRIGERANT SUCTION & LIQUID LINES
CL
-VARIABLE AIR VOLUMEVAV
-SUPPLY AIRSA
-REHEAT COILRHC
-REVOLUTIONS PER MINUTERPM
-RETURN AIRRA
-POLYVINYL CHLORIDE PIPEPVC
-PSI GAUGEPSIG
-POUNDS PER SQUARE INCHPSI
-PRESSURE REDUCING VALVEPRV
-NOT TO SCALENTS
-NORMALLY OPENNO
-NORMALLY CLOSEDNC
-GALLONS PER MINUTEGPM
-FEET PER MINUTE
-ENTERING WATER TEMPERATURE
-DOWN
-CHANGE IN TEMPERATURE
-COOLING TOWER
-CEILING DIFFUSER
-CENTER LINE
-BRITISH THERMAL UNIT
-BRAKE HORSEPOWER
-BOTTOM OF PIPE
-ABOVE FINISHED FLOOR
FPM
EWT
DN
T
CT
CD
BTU
BOP
BHP
AFF
MBH -THOUSAND BTUs PER HOURAFD -ADJUSTABLE FREQUENCY DRIVE
KW -KILOWATT
MCA -MINIMUM CIRCUIT AMPS
MOCP -MAXIMUM OVER CURRENT PROTECTION
UNO
TSP -TOTAL STATIC PRESSURE
-VOLTS/PHASEV/PH
VFD -VARIABLE FREQUENCY DRIVE
-UNLESS NOTED OTHERWISE
FLA -FULL LOAD AMPS
-CONTROL VALVE
-45° PIPE RISE (R) / DROP (D)
-CONDENSER WATER SUPPLY
-CONDENSER WATER RETURN
-CHILLED WATER SUPPLY
-CHILLED WATER RETURN
-HOT WATER RETURN
-HOT WATER SUPPLY
-REFRIGERANT LIQUID
-REFRIGERANT SUCTION
-VALVE ON RISER
-CAP
-CONNECTION, BOTTOM
-CONNECTION, TOP
-COUPLING
-ELBOW, 90°
-ELBOW, 45°
-ELBOW, TURNED DOWN
-ELBOW, TURNED UP
-TEE, OUTLET DOWN
-TEE, OUTLET UP
CWS
CWR
CHWS
CHWR
RL
RS
-FLOW SWITCH
-CHECK VALVE
-PSI REG.
-SOLENOID VALVE
-STRAINER
-GAS COCK
-BUTTERFLY VALVE
-CALIBRATING BALANCING VALVE
-BALL VALVE
-GATE VALVE
-UNION
DD
-SLOPE DIRECTION (DOWN)
-FLEX CONNECTION
-O.S.&Y. GATE VALVE
-THREE-WAY CONTROL VALVE
-THERMOMETER
- P-TRAP
-TWO-WAY CHECK VALVE
EQUIP.
-MANUAL VENT
-PRESSURE GAUGE
-RELIEF VALVE
-FLOW METER
-WATER METER
-INLINE PUMP
-INLINE PUMP
-PRIMARY CHILLED WATER PUMP
-REHEAT COIL
MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
-CONCENTRIC REDUCER
-ECCENTRIC REDUCER
-STEAM TRAP
-FLOW DIRECTION
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-ABOVE FINISHED ROOFAFR
HVAC GENERAL NOTESHVAC ABBREVIATIONSHVAC SYMBOL LEGEND
HVAC EQUIPMENT TAGS
HVAC PIPING SYMBOL LEGEND
HWR
HWS
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL
EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND ELECTRICAL
CONDUIT.
3. ALL EQUIPMENT, SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED
TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
4. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
5. ALL PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
6. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO SPECIFICATIONS FOR
DETAILED REQUIREMENTS.
7. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED WIT OWNER. SUCH INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.
8. ALL EQUIPMENT TO BE REMOVED SHALL REMAIN PROPERTY OF THE OWNER OR DISPOSED OF LEGALLY, AS DIRECTED BY
OWNER.
9. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND
FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
10. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED FULL SIZE TO THE
NEAREST PLUMBING DRAIN.
11. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR VENTS AT ALL
HIGH POINTS IN CHILLED WATER AND HOT WATER PIPING.
12. PIPING, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE
WITH NEC-110.26.
13. DDC SYSTEM SHALL MONITOR AND TREND OPERATING KW AND KWH FOR CHILLED WATER PLANT PUMPS (PRIMARY AND SECONDARY), CONDENSER WATER PUMPS, WATER-COOLED CHILLERS AND COOLING TOWER FANS. OPERATING KW AND KWH FOR FANS AND PUMPS SHALL BE OBTAINED THOUGH INTERFACE WITH FAN OR PUMP MOTOR VFD. OPERATING KW AND KWH FOR WATER-COOLED CHILLERS SHALL BE OBTAINED THROUGH CHILLER SERIAL INTERFACE.
S
MV
FM
M
T
PUMP NUMBER
AHU NUMBER COIL NUMBER
CFM
PROJECT SCOPE OF WORK
THIS PROJECT INCLUDES MECHANICAL AND ELECTRICAL MODIFICATIONS TO THE EXISTING CHILLED WATER PLANT LOCATED IN BUILDING C OF THE GEORGIA WORLD CONGRESS CENTER. MODIFICATIONS TO THE CHILLED WATER PLANT INCLUDE REPLACEMENTS OF WATER-COOLED CHILLERS AND HYDRONIC PUMPS, AS INDICATED IN THESE DOCUMENTS. ADDITIONALLY, SCOPE OF WORK INCLUDES REPLACEMENT OF EXISTING SECONDARY HEATING HOT WATER PUMPS, AS INDICATED IN THESE DOCUMENTS.
PROJECT SCOPE OF WORK
THIS PROJECT INCLUDES MECHANICAL AND ELECTRICAL MODIFICATIONS TO THE EXISTING CHILLED WATER PLANT LOCATED IN BUILDING C OF THE GEORGIA WORLD CONGRESS CENTER. MODIFICATIONS TO THE CHILLED WATER PLANT INCLUDE REPLACEMENTS OF WATER-COOLED CHILLERS AND HYDRONIC PUMPS, AS INDICATED IN THESE DOCUMENTS. ADDITIONALLY, SCOPE OF WORK INCLUDES REPLACEMENT OF EXISTING SECONDARY HEATING HOT WATER PUMPS, AS INDICATED IN THESE DOCUMENTS.
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
12" = 1'-0"
/1
/2
:4 :0
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL
SYMBOLS, LEGEND,
NOTES AND INDEX
M001
824273
No. Date Description
NEW WATER-COOLED CHILLER SCHEDULE
NOTES & ACCESSORIES:
1. AHRI AND ETL/cETL APPROVAL.
2. ASME VESSEL CODE.
3. CAPACITY CONTROL VIA VARIABLE FREQUENCY DRIVE AND INLET GUIDE VANES.
4. SINGLE POINT POWER CONNECTION.
5. DOOR-MOUNTED CIRCUIT BREAKER ON VARIABLE FREQUENCY DRIVE.
6. GROOVED PIPE CONNECTIONS, EVAPORATOR AND CONDENSER.
7. THERMAL DISPERSION FLOW SWITCH (IFM), EVAPORATOR AND CONDENSER.
8. UNIT MOUNTED LOW VOLTAGE ADAPTIVE FREQUENCY DRIVE (NEMA 1 ENCLOSURE).
9. R-514A WORKING REFRIGERANT.
10. ADAPTI-VIEW CONTROL PANEL.
11. NEOPRENE VIBRATION ISOLATORS AT BASE OF UNIT.
12. CHILLER SHALL BE CAPABLE OF INTERFACING WITH BUILDING AUTOMATION SYSTEM (NEW OR EXISTING). COORDINATE WITH EXISTING CONDITIONS AND REQUIREMENTS OF PROJECT.
13. COMPRESSOR INLET GUIDE VANES.
14. 65,000 AMP WITHSTAND/AIC RATING, CHILLER AND VARIABLE FREQUENCY DRIVE.
15. FACTORY STARTUP SHALL BE INCLUDED.
16. STANDARD 3/4" UNIT INSULATION PACKAGE, FACTORY-PROVIDED 3/4" (MINIMUM) THERMAL INSULATION ON EVAPORATOR SHELL.
17. STANDARD 3/4" UNIT INSULATION PACKAGE, FACTORY-PROVIDED 3/4" (MINIMUM) THERMAL INSULATION ON SUCTION PIPING COMPRESSOR INLET, MOTOR BARREL & HIGH HUMIDITY.
18. FACTORY INSULATE EVAPORATOR RETURN & CONNECTION HEADS.
19. FACTORY DISCONNECT SWITCH AND GROUND FAULT PROTECTION WITH VARIABLE FREQUENCY DRIVE.
20. HYDRONIC FLUID - WATER, NO GLYCOL.
21. TWO (2) CONDENSER WATER TUBE PASSES.
22. TWO (2) EVAPORATOR WATER TUBE PASSES.
23. RUPTUREGUARD-RELIEF VALVE-FIELD INSTALL.
24. FACTORY DISCONNECT SWITCH.
C-12 1,2,4,6,7,9,10,11,12,14,15,16,17,18,20,21,22,23,24,25,26
NOTES & ACCESSORIESTAG ENTERING
WATER
TEMPERATURE
56.0°F
UNIT WEIGHT
OPERATING
CONDITIONS
LBS.
COMPRESSORS
TYPE QUANTITY
CENTRIFUGAL 1
ELECTRICAL
SERVICE
4160V
DESIGN BASIS
RATED
TONNAGE
1,300
FULL
LOAD
KW/TON
0.5662
NPLV W/ TOWER
RELIEF
(PER AHRI 550/590)
EVAPORATOR
LEAVING
WATER
TEMPERATURE
42.0°F
WATERFLOW
GPM
2,218
MAXIMUM WATER
PRESSURE
DROP @ DESIGN
CONDITIONS
(FT. W.G.)
19.5
FOULING
FACTOR
0.00010
ENTERING
WATER
TEMPERATURE
95.0°F
CONDENSER
LEAVING
WATER
TEMPERATURE
85.0°F
MAXIMUM WATER
PRESSURE
DROP @ DESIGN
CONDITIONS
(FT. W.G.)
22.1
FOULING
FACTOR
0.00025
MINIMUM DESIGN
522.2
WATERFLOW
GPM
3,668
MINIMUM DESIGN
1,479 38,0000.4704
MAXIMUM
3,809
MAXIMUM
5,425 TRANE CVHF
C-13 4160V 38,000TRANE CVHF 1,2,4,6,7,9,10,11,12,14,15,16,17,18,20,21,22,23,24,25,26
C-11 56.0°F CENTRIFUGAL 1 480V1000 0.5759 42.0°F 1,706 18.0 0.00010 95.0°F 85.0°F 23.9 0.00025420.7 2,819968.1 32,0000.3774 3,069 3,550 TRANE CVHF 1070 1 THRU 23
NEW CIRCULATING WATER PUMPS
NOTES & ACCESSORIES:
1. PROVIDE SPARE SEAL KIT.
2. STAINLESS STEEL SHAFT, CAST IRON CASING, CONFINED NON-ASBESTOS FIBER CASING GASKET.
3. SHAFT GROUNDING RING.
4. PREMIUM EFFICIENT, INVERTER DUTY PUMP MOTOR.
5. SUCTION DIFFUSER AT PUMP INLET.
6. PROVIDE THERMAL SENSORS FOR ADDITIONAL PROTECTION OF PUMP MOTOR. THERMAL SENSORS SHALL BE INTERLOCKED WITH PUMP MOTOR VARIABLE
FREQUENCY DRIVE CONTROL CIRCUIT. THIS REQUIREMENT IS IN ADDITION TO THE STANDARD OVERCURRENT PROTECTION REQUIRED AT MOTORS.
NOTES &
ACCESSORIES
DESCRIPTIONTAG
DEVELOPE
D HEAD
(FEET W.G.)
SERVICE
IMPELLER
DIAMETER
(INCHES)
GPM HP
PUMP
EFFICIENCY
AT DUTY POINT
ELECTRICAL
SERVICE
(VOLTS / PHASE)
MANUFACTURER
DESIGN BASIS
MANUFACTURER
DESIGN SERIES
MANUFACTURER
DESIGN MODEL
PCHWP-4-3 70.0HORIZONTAL SPLIT CASE CHILLED WATER, PRIMARY MAXIMUM 2,685 460 / 3 BELL & GOSSET60.0 83.7 E-HSC 8 x 10 x 16 1 THRU 7
PHWP-4-1 HEATING HOT WATER, PRIMARY 1,100 45.0 460 / 3
PHWP-4-2
PHWP-4-3
MAXIMUM
PHWP-4-4
81.6
OPERATING
SPEED AT
DESIGN DUTY
POINT
1,180
1099 BELL & GOSSET E-HSC 5 x 8 x 12
PCHWP-4-4 CHILLED WATER, PRIMARY
PCHWP-4-5 CHILLED WATER, PRIMARY
PCHWP-4-6 CHILLED WATER, PRIMARY
CONDENSER WATER
HEATING HOT WATER, PRIMARY 1,100 45.0MAXIMUM
HEATING HOT WATER, PRIMARY 1,100 45.0MAXIMUM
HEATING HOT WATER, PRIMARY 1,100 45.0MAXIMUM
20.0
1 THRU 7
1 THRU 7
MAXIMUM 460 / 3 BELL & GOSSET E-HSC
MAXIMUM 460 / 3 BELL & GOSSET E-HSC
MAXIMUM 460 / 3 BELL & GOSSET E-HSC
85.0MAXIMUM 3,668 460 / 3 BELL & GOSSET100.0 89.4 E-HSC 10 x 12 x 15.51,162
PHWP-4-5 HEATING HOT WATER, PRIMARY 1,100 45.0MAXIMUM
460 / 381.6 1099 BELL & GOSSET E-HSC 5 x 8 x 1220.0
460 / 381.6 1099 BELL & GOSSET E-HSC 5 x 8 x 1220.0
460 / 381.6 1099 BELL & GOSSET E-HSC 5 x 8 x 1220.0
460 / 381.6 1099 BELL & GOSSET E-HSC 5 x 8 x 1220.0
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
HORIZONTAL SPLIT CASE
56.0°F CENTRIFUGAL 11,300 0.5662 42.0°F 2,218 19.5 0.00010 95.0°F 85.0°F 22.1 0.00025522.2 3,6681,4790.4704 3,809 5,425
7. PROVIDE STAINLESS STEEL DRAIN PAN UNDER PUMP HEAD WITR DRAIN LINE PIPED TO FLOOR DRAIN.
70.02,685 60.0 83.7
70.02,685 60.0 83.7
70.02,685 60.0 83.7
CWP-4-3
1,180
1,180
1,180
CONDENSER WATER 85.0MAXIMUM 3,668 460 / 3 BELL & GOSSET100.0 89.4 E-HSC1,162HORIZONTAL SPLIT CASECWP-4-4
CONDENSER WATER 85.0MAXIMUM 3,668 460 / 3 BELL & GOSSET100.0 89.4 E-HSC1,162HORIZONTAL SPLIT CASECWP-4-5
CONDENSER WATER 85.0MAXIMUM 3,668 460 / 3 BELL & GOSSET100.0 89.4 E-HSC1,162HORIZONTAL SPLIT CASECWP-4-6
8 x 10 x 16 1 THRU 7
8 x 10 x 16 1 THRU 7
8 x 10 x 16 1 THRU 7
1 THRU 710 x 12 x 15.5
1 THRU 710 x 12 x 15.5
1 THRU 710 x 12 x 15.5
1 THRU 7
1 THRU 7
1 THRU 7
1 THRU 7
25. NON-MARINE WATER BOX ON CHILLER EVAPORATOR.
26. MARINE WATER BOX ON CHILLER CONDENSER.
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :0
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL
SCHEDULES
M002
824273
No. Date Description
12.6
G
M
K.8
K
F
14.3 14y 13.6 13.3 13y13.4
M101
CH-9 CH-10 CH-11 CH-12 CH-13
B-7 B-8 B-9 B-10
ET
R
0V
0A
S W
IT
C
HB
O
AR
D
ETR 480V 4000A SWITCHBOARD
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/8" = 1'-0"
/1
/2
:4 :1
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
1 OVERALL -
EXISTING
M100
824273
No. Date Description
1/8" = 1'-0"
LEVEL 1 OVERALL- EXISTING
K.8
K
14.3 14y 13.6 13.4
2 2 1 1 1
CH-9 CH-10 CH-11 CH-12 CH-13
6" REFRIGERANT RELIEF
4"
10"CHWS10"CHWS 10"CHWS 10"CHWS
14"CWR
14"CWS
14"CWR
10"CHWR
14"CWR14"CWS
5 5 5 55
6 6 6 6 6
EXISTING ELECTRICAL ON CONCRETE PADS. REFER TO SHEET E101 & E201 FOR ELECTRICAL SCOPE OF WORK
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :1
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. Coons
R. PARKINS
MECHANICAL LEVEL
1- EXISTING CHILLER
PLANT ENLARGED
M101
824273
No. Date Description
1/4" = 1'-0"
LEVEL 1 CHILLER PLANT ENLARGED - EXISTING
MECHANICAL DEMOLITION KEYNOTES:
1. EXISTING 1,100-TON WATER-COOLED CHILLER SHALL BE DEMOLISHED. PRIOR TO DEMOLITION OF CHILLER, EXISTING CHILLED AND CONDENSER WATER PIPING SHALL BE DISCONNECTED FROM CHILLER AND REMOVED BACK TO SHUT-OFF VALVE OR FURTHER AS REQUIRED FOR DEMOLITION OF CHILLER. EXISTING CHILLER ISOLATION/SHUT-OFF SHUT-OFF VALVE SHALL BE OPERATED TO THE CLOSED POSITION PRIOR TO DEMOLITION OF CHILLER OR HYDRONIC PIPING. DISCONNECT ELECTRICAL SERVICE AND REFRIGERANT RELIEF PIPING PRIOR TO CHILLER DEMOLITION. DEMOLISH EXISTING REFRIGERANT RELIEF PIPING BACK TO REFRIGERANT RELIEF MAIN AND CAP.
2. EXISTING 1,100-TON WATER-COOLED CHILLER SHALL BE DEMOLISHED. PRIOR TO DEMOLITION OF CHILLER, EXISTING CHILLED PIPING AND EXISTING CONDENSER WATER PIPING SHALL BE DISCONNECTED FROM CHILLER AND DEMOLISHED BACK TO SHUT-OFF VALVE OR FURTHER AS REQUIRED FOR DEMOLITION OF CHILLER. EXISTING CHLLER ISOLATION/SHUT-OFF VALVE SHALL BE OPERATED TO TEH CLOSED POSITION PRIOR TO DEMOLITION OF CHILLER OR HYDRONIC PIPINGG. INSTALL BLIND FLANGE AT OPEN ENDS OF PIPING. DISCONNECT ELECTRICAL SERVICE AND REFRIGERANT RELIEF PIPING PRIOR TO CHILLER DEMOLITION.
3. EXISTING REFRIGERANT DETECTORS SHALL BE DEMOLISHED. DEMOLISH EXISTING TUBING/WIRING BETWEEN EXISTING REFRIGERANT MONITORING PANEL AND REFRIGERANT DETECTORS. EXISTING CONDUIT, WHERE WIRING OR TUBING HAS
BEEN DEMOLISHED, CAN BE REUSED IF SUITABLE.
4. EXISTING REFRIGERANT MONITORING PANEL SHALL BE DEMOLISHED. DEMOLISH EXISTING TUBING/WIRING BETWEEN EXISTING REFRIGERANT MONITORING PANEL AND REFRIGERANT DETECTORS. EXISTING CONDUIT, WHERE WIRING OR TUBING
HAS BEEN DEMOLISHED, CAN BE REUSED IF SUITABLE. SEE SHEET M201 FOR NEW WORK..
5. EXISTING CONCRETE PAD SHALL REMAIN.
6. REFRIGERANT SHALL BE RECLAIMED FROM WATER-COOLED CHILLERS PRIOR TO START OF DEMOLITION ACTIVITIES.
R
EF
ER
T
O S
HE
ET
M
14.4 12.6
M
K.8
K
F
14.3 14y 13.6 13.3 13y13.4
PHWP-4-5 PHWP-4-4 PHWP-4-3 PHWP-4-2 PHWP-4-1
CWP-4-1
CWP-4-2 CWP-4-3 CWP-4-4 CWP-4-5 CWP-4-6
CWP-C-1
CWP-C-2
SHWP-4-1 SHWP-4-2 SHWP-4-3
PCHWP-4-2 PCHWP-4-3 PCHWP-4-4 PCHWP-4-5
PCHWP-4-6
PCHWP-4-1
SCHWP-4-1 SCHWP-4-2 SCHWP-4-3 SCHWP-4-4
SCHWP-4-5
M103
M104
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/8" = 1'-0"
/1
/2
:4 :2
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
2 OVERALL -
EXISTING
M102
824273
No. Date Description
1/8" = 1'-0"
LEVEL 2 OVERALL - EXISTING
ELECTRICAL SCOPE NARRATIVE: (BOILER ROOM)
1. CONTRACTOR SHALL REFER TO THE ELECTRICAL DEMO / RENO NOTES ON SHEET M001.
2. CONTRACTOR SHALL DISCONNECT EXISTING BOILERS CONTROLS, FEEDERS, ELECTRICAL CONNECTIONS, ETC. FROM
BOILER UNITS THAT ARE BEING DEMOLISHED.
3. CONTRACTOR SHALL SECURE AND STORE FEEDERS OUT OF THE WAY FOR DEMOLITION OF THE BOILER UNIT.
4. CONTRACTOR SHALL CONNECT EXISTING FEEDERS TO NEW VFD.
5. CONTRACTOR SHALL PURCHASE AND INSTALL A NEW BREAKER AND FEEDERS FOR NEW PRIMARY HOT WATER PUMP FOR
NEW HEAT PUMP CHILLER HP-CH-1.
14.4
M
K.8
K
14.3 14y 13.6 13.4
30"CWS 24"CWS 20"CWS 16"CWS
20"CWR14"CWR 24"CWR 30"CWR 30"CWR
10"CHWS16"CHWS20"CHWS24"CHWS
20"CHWS 24"CHWS
24"CHWR20"CHWR
"C
HW
S
"C
H W
R
"C
HW
S
"C
H W
R
14"CWS
20"CWR
"C
H W
R
CWP-4-1 CWP-4-2 CWP-4-3 CWP-4-4 CWP-4-5 CWP-4-6
SCHWP-4-1 SCHWP-4-2 SCHWP-4-3 SCHWP-4-4 SCHWP-4-5
PCHWP-4-6PCHWP-4-5PCHWP-4-4PCHWP-4-3PCHWP-4-2PCHWP-4-1
EXISTING PUMP DISCONNECT SWITCH
(TYPICAL, UNLESS NOTED OTHERWISE)
EXISTING VFD
EXISTING PUMP DISCONNECT SWITCH
(TYPICAL)
SCHWP-4-6
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :2
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
2 ENLARGED PART A
- EXISTING
M103
824273
No. Date Description
1/4" = 1'-0"
LEVEL 2 ENLARGED PART A - EXISTING
R
EF
ER
T
O S
HE
ET
M
4 4 5
5 5
44 2 2 2 2
MECHANICAL DEMOLITION KEYNOTES:
1. EXISTING PUMP SHALL BE DEMOLISHED. POWER SHALL BE DISCONNECTED FROM PUMP AND PUMP DISCONNECT. EXISTING PIPING TO/FROM PUMP SHALL BE DEMOLISHED BACK TO SHUT-OFF VALVES, WITH SHUT-OFF VAVES OPERATED TO THE CLOSED POSITON. EXISTING CONCRETE PAD AND INERTIA BASE SHALL REMAIN. EXISTING DISCONNECT SWITCH SHALL BE DEMOLISHED
2. EXISTING PRIMARY CHILLED WATER PUMP SHALL BE DEMOLISHED. POWER SHALL BE DISCONNECTED FROM PUMP AND PUMP DISCONNECT. EXISTING CHILLED WATER PIPING TO/FROM PUMP SHALL BE DEMOLISHED BACK TO CLOSEST SHUT- OFF VALVE OR AS REQUIRED FOR DEMOLITION OF PUMP. EXISTING CONCRETE PAD AND INERTIA BASE TO REMAIN. EXISTING DISCONNECT SWITCH SHALL BE DEMOLISHED. UNISTRUT SUPPORTING DISCONNECT SHALL REMAIN.
3. EXISTING SECONDARY CHILLED WATER PUMPS TO REMAIN. EXISTING PUMP VARIABLE FREQUENCY DRIVE TO REMAIN.
4. EXISTING HYDRONIC PUMPS TO REMAIN. EXISTING MEANS OF DISCONNECTION FOR PUMP (ELECTRICAL DISCONNECT OR VARIABLE FREQUENCY DRIVE) SHALL REMAIN.
5. EXISTING CONDENSER WATER PUMP SHALL BE DEMOLISHED. POWER SHALL BE DISCONNECTED FROM PUMP AND PUMP DISCONNECT OR VFD. EXISTING CONDENSER WATER PIPING TO/FROM PUMP SHALL BE DEMOLISHED BACK TO CLOSEST SHUT-OFF VALVE OR AS REQUIRED FOR DEMOLITION OF PUMP. EXISTING CONCRETE PAD AND INERTIA BASE TO REMAIN. EXISTING DISCONNECT OR VFD SWITCH SHALL BE DEMOLISHED. UNITSTRUT SUPPORTING DICONNECT SHALL REMAIN.
6. EXISTING PRIMARY CHILLED WATER PUMP SHALL BE DEMOLISHED. POWER SHALL BE DISCONNECTED FROM PUMP AND PUMP DISCONNECT. EXISTING CHILLED WATER PIPING TO/FROM PUMP SHALL BE DEMOLISHED BACK SHUT-OFF VALVES, WITH SHUT-OFF VALVES OPERATED TO THE CLOSED POSITION WITH ADDED BLIND FLANGE. EXISTING CONCRETE PAD AND INERTIA BASE TO REMAIN. EXISTING DISCONNECT SWITCH SHALL BE DEMOLISHED
7. EXISTING VFD SERVING SECONDARY CHILLED WATER PUMPS SHALL REMAIN
3 3
3 3
7 7 7 7
M
K.8
K
13.3 13y
EXISTING PUMP DISCONNECT SWITCH (TYPICAL)
EXISTING PUMP DISCONNECT
SWITCH (TYPICAL)
SHWP-4-1 SHWP-4-2 SHWP-4-3
PHWP-4-5 PHWP-4-4 SHWP-4-4 PHWP-4-3 PHWP-4-2 PHWP-4-1
16"HWS10"HWS
12"HWR14"HWR 8"HWR16"HWR
"H
W R
16"HWS 14"HWS 12"HWS
"H
W S
"H
W S
8" H
W S
8" H
W S
8" H
W S
8" H
W S
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :2
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
2 ENLARGED PART B
- EXISTING
M104
824273
No. Date Description
1/4" = 1'-0"
LEVEL 2 ENLARGED PART B - EXISTING
R
EF
ER
T
O S
HE
ET
M
MECHANICAL DEMOLITION KEYNOTES:
1. EXISTING PRIMARY HEATING HOT WATER WATER PUMP SHALL BE DEMOLISHED. POWER SHALL BE DISCONNECTED FROM PUMP AND PUMP DISCONNECT. EXISTING HEATING HOT WATER PIPING TO/FROM PUMP SHALL BE DEMOLISHED BACK TO CLOSEST SHUT-OFF VALVE OR FURTHER AS REQUIRED FOR DEMOLITION OF PUMP. EXISTING CONCRETE PAD AND INERTIA BASE TO REMAIN. EXISTING DISCONNECT SWITCH SHALL BE
DEMOLISHED. UNISTRUT SUPPORTING DICONNECT SWITCH SHALL REMAIN.
2. EXISTING SECONDARY HEATING HOT WATER PUMPS TO REMAIN
3. EXISTING HYDRONIC PUMPS TO REMAIN.
1 1 1
2 2 2
M
K.8
K
F
14.3 14y 13.6 13.3 13y13.4
M201
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/8" = 1'-0"
/1
/2
:4 :3
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
1 OVERALL - NEW
CONSTRUCTION
M200
824273
No. Date Description
1/8" = 1'-0"
LEVEL 1 OVERALL - NEW CONSTRUCTION
ELECTRICAL SCOPE NARRATIVE: (NEW)
1. FOR CHILLERS 11 AND 13, CONTRACTOR SHALL CONNECT THE EXISTING FEEDERS AND ALL ASSOCIATED ELECTRICAL
COMPONENTS BACK TO THE NEW CHILLERS.
2. FOR CHILLERS 9 AND 10 CONTRACTOR SHALL INSTALL NEW BREAKERS AND FEEDERS FROM THE EXISTING 4000A 480V
SWITCHBOARD LOCATED IN THE CHILLER ROOM.
Should be 12 and 13.
Should be Chiller 11
K
14.3 14y 13.6
EXISTING CHILLER
PAD TO REMAIN
ST
6" REFRIGERANT RELIEF
CH-11 CH-12 CH-13
1000 T 1300 T 1300 T
ST
14"CWR
14"CWR UP
14"CWS UP
14"CWS UP
14"CWR UP 14"CWR UP
14"CWS UP
10"CHWR UP10"CHWR UP
10"CHWR UP
10"CHWS UP
10"CHWS UP 10"CHWS UP
EXISTING CHILLER
PAD TO REMAIN
EXISTING ELECTRICAL ON CONCRETE PADS. REFER TO SHEET E101 & E201 FOR ELECTRICAL SCOPE OF WORK
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :3
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
1 CHILLER PLANT
ENLARGED - NEW
CONSTRUCTION
M201
824273
No. Date Description
MECHANICAL NEW CONSTRUCTION KEYNOTES:
1. A NEW 1,300-TON WATER-COOLED CHILLER SHALL BE INSTALLED IN PLACE OF EXISTING. ROUTE NEW 12"CHWS&R PIPING FROM CONNECTION AT EXISTING CHILLER ISOLATION VALVES AND CONNECT TO CHILLER EVAPORATOR OUTLET AND INLET, RESPECTIVELY. EXISTING 14"CWS&R SHALL BE RECONNECTED TO CHILLER CONDENSER INLET AND OUTLET, RESPECTIVELY.
NEW CHILLER'S REFRIGERANT RELIEF PORTS SHALL BE CONNECTED TO EXISTING REFRIGERANT RELIEF MAIN. ELECTRICAL SHALL BE RECONNECTED AS DIRECTED, SEE ELECTRICAL.
2. A NEW 1000-TON WATER-COOLED CHILLER SHALL BE INSTALLED IN PLACE OF EXISTING. THE THICKNESS OF ANY PAD EXTENSIONS SHALL MATCH THE THICKNESS OF THE EXISTING PAD.
EXISTING 10"CHWS&R PIPING SHALL BE RECONNECTED TO CHILLER EVAPORATOR OUTLET AND INLET, RESPECTIVELY. EXISTING 14"CWS&R SHALL BE RECONNECTED TO CHILLER CONDENSER INLET AND OUTLET, RESPECTIVELY. NEW CHILLER'S REFRIGERANT RELIEF PORTS SHALL BE CONNECTED TO EXISTING REFRIGERANT RELIEF MAIN. ELECTRICAL SHALL BE
RECONNECTED AS DIRECTED, SEE ELECTRICAL.
3. INSTALL NEW REFRIGERANT MONITORING PANEL BY GENESIS INTERNATIONAL, INC. OR AN EQUIVALENT. MONITORING SYSTEM SHALL SUPPORT A MINIMUM OF FOUR SENSORS AND SUPPORT AT LEAST THREE USER-SET ALARMS, INCLUDING A SYSTEM FAULT ALARM. THE PANEL SHALL INCLUDE A HORN, STROBE AND 3-WIRE CONNECTION FOR VARIOUS GAS TYPES.
THE PANEL SHALL OFFER A 4-20 MILLIAMP SINGAL OUTPUT, ADDITIONAL RELAYS FOR ISOLATED ALARMS AND DRY CONTACTS FOR MANUAL CONTROL. PENAL SHALL HAVE A NEMA 1 ENCLOSURE AND SHALL BE MODBUS READY. NEW REFRIGERANT MONITORING PANEL AND COMPONENTS SHALL BE CAPABLE OF MONITORING OF R-514A REFRIGERANT. NEW PANEL
SHALL BE INTEGRATED INTO BUILDING CONTROLS SYSTEM.
4. INSTALL NEW REFRIGERANT SENSOR BY GENESIS INTERNATIONAL, INC. OR AN EQUIVALENT. NEW INFRARED REFRIGERANT SENSOR SHALL BE COMPATIBLE WITH THE REFRIGERANT MONITORING PANEL. PROVIDE WIRING AND/OR TUBING BETWEEN SENSOR AND PANEL, AS REQUIRED, TO ALLOW FOR THE APPROPRIATE MONITORING.
R
EF
ER
T
O S
HE
ET
M
2 1 1
NSTALL NEW REMOTE NEMA 1 STROBE/BUZZER COMBINATION
LIGHT TOWER AT ENTRANCE TO MECHANICAL ROOM
NSTALL NEW REMOTE NEMA 1 STROBE/BUZZER COMBINATION
LIGHT TOWER AT ENTRANCE TO MECHANICAL ROOM
1/4" = 1'-0"
LEVEL 1 - CHILLER PLANT ENLARGED - NEW CONSTRUCTION
14.4 12.6
M
K.8
K
F
14.3 14y 13.6 13.3 13y13.4
M203
M204
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/8" = 1'-0"
/1
/2
:4 :4
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
2- NEW
CONSTRUCTION
M202
824273
No. Date Description
1/8" = 1'-0"
LEVEL 2 - NEW CONSTRUCTION
14.4
M
K.8
K
14.3 14y 13.6 13.4
S
F
S
CWP-4-3 CWP-4-4 CWP-4-5 CWP-4-6
SCHWP-4-1 SCHWP-4-2 SCHWP-4-3 SCHWP-4-4 SCHWP-4-5
PCHWP-4-3 PCHWP-4-4 PCHWP-4-5 PCHWP-4-6
"C
H W
R
20"CHWR 24"CHWR
"C
H W
R
24"CHWS20"CHWS
16"CHWS 10"CHWS20"CHWS24"CHWS
14"CWR 20"CWR 24"CWR 30"CWR
14"CWS
16"CWS20"CWS24"CWS30"CWS
"C
HW
S
"C
H W
R
"H
W R
"H
W R
CWP-4-2CWP-4-1
PCHWP-4-1 PCHWP-4-2
SCHWP-4-6
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :5
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
2 ENLARGED PART A
- NEW
CONSTRUCTION
M203
824273
No. Date Description
R
EF
ER
T
O S
HE
ET
M
MECHANICAL NEW CONSTRUCTION KEYNOTES:
1. NSTALL NEW CONDENSER WATER PUMP ON EXISTING CONCRETE PAD/INERTIA BASE IF EXISTING PAD AND INERTIA BASE IS SUITABLE FOR REUSE. IF UNSUITABLLE, PRIOR TO INSTALLATION OF NEW PUMP, EXISTING CONCRETE PAD SHALL BE EXPANDED AS REQUIRED SUCH THAT PAD EXTENDS NO LESS THAN 6 INCHES BEYOND THE PUMP BASE IN ALL DIRECTIONS. THE THICKNESS OF ANY PAD EXTENSIONS SHALL MATCH THE THICKNESS OF THE EXISTING PAD. PROVIDE NEW INERTIA BASE AS REQUIRED. ONCE NEW PUMP IS INSTALLED, EXTEND NEW CONDENSER WATER PIPING TO PUMP SUCTION AND DISCHARGE CONNECTIONS.
PROVIDE NEW VARIABLE FREQUENCY DRIVE WITH ELECTRONIC BYPASS. AFTER INSTALLATION OF PUMP AND NEW VARIABLE FREQUENCY DRIVE, POWER SHALL BE RECONNECTED TO NEW VFD AND PUMP.
2. INSTALL NEW PRIMARY CHILLED WATER PUMP ON EXISTING CONCRETE PAD/INERTIA BASE IF EXISTING PAD AND INERTIA BASE IS SUITABLE FOR REUSE. IF UNSUITABLLE, PRIOR TO INSTALLATION OF NEW PUMP, EXISTING CONCRETE PAD SHALL BE EXPANDED AS REQUIRED SUCH THAT PAD EXTENDS NO LESS THAN 6 INCHES BEYOND THE PUMP BASE IN ALL DIRECTIONS. THE THICKNESS OF ANY PAD EXTENSIONS SHALL MATCH THE THICKNESS OF THE EXISTING PAD. PROVIDE NEW INERTIA BASE AS REQUIRED. ONCE NEW PUMP IS INSTALLED, EXTEND NEW CHILLED WATER PIPING TO PUMP SUCTION AND DISCHARGE CONNECTIONS.
PROVIDE NEW VARIABLE FREQUENCY DRIVE WITH ELECTRONIC BYPASS. AFTER INSTALLATION OF PUMP AND NEW VARIABLE FREQUENCY DRIVE, POWER SHALL BE RECONNECTED TO NEW VFD AND PUMP.
3. INSTALL NEW ELECTROMAGNETIC INSERTION FLOWMETER AT THE LOCATION INDICATED. FLOWMETER SHALL BE SUITABLE FOR INSTALLATION IN PIPING/PIPING SIZE AT INDICATED LOCATION. FLOWMETER SHALL BE ONICON F-3500 OR EQUAL. INSTALL FLOWMETER IN COMPLIANCE WITH ALL MANUFACTURER RECOMMENDATIONS AND REQUIREMENTS, INCLUDING REQUIRED AMOUNT OF STRAIGHT PIPING UPSTREAM AND DOWNSTREAM OF FLOWMETER. FLOWMETER SHALL BE COMPATIBLE WITH 24V ELECTRICAL SERVICE. FLOWMETER SHALL BE UTILIZED BY ONICON SYSTEM-20 BTU METER.
4. NEW VARIABLE FREQUENCY DRIVE SHALL BE INSTALLED ON EXISTING UNISTRUT STAND.
5. EXISTING HYDRONIC PUMP SHALL REMAIN. EXISTING MEANS OF DISCONNECTION FOR PUMP (ELECTRICAL DISCONNECT OR VARIABLE FREQUENCY DRIVE) SHALL REMAIN.
6. EXISTING HYDRONIC PUMP SHALL REMAIN. EXISTING VARIABLE FREQUENCY DRIVE SERVING PUMP SHALL REMAIN.
7. EXISTING VARIABLE FREQUENCY DRIVES SERVING EXISTING SECONDARY CHILLED WATER PUMPS SHALL REMAIN.
1 1
2 2
INSTALL NEW TEMPERATURE SENSOR IN CHILLED WATER SUPPLY PIPING AT LOCATIONS
INDICATED. SENSORS SHALL BE UTILIZED BY ONICON SYSTEM-20 BTU METER.
INSTALL NEW TEMPERATURE SENSOR IN CHILLED WATER SUPPLY PIPING AT LOCATIONS
INDICATED. SENSORS SHALL BE UTILIZED BY ONICON SYSTEM-20 BTU METER.
INSTALL NEW BTU METER INTERFACE/DISPLAY AT LOCATION INDICATED. BTU METER
SHALL BE ONICON SYSTEM-20 OR EQUAL. FINAL LOCATION OF BTU METER
INTERFACE/DISPLAY SHALL BE COORDINATED WITH ACTUAL FIELD CONDITIONS.
1/4" = 1'-0"
LEVEL 2 - ENLARGED PART A - NEW CONSTRUCTION
4 4 4 4
4 444
7 7 7 7 7 7
M
K.8
K
13.3 13y
16"HWR 14"HWR
10"HWS
"H
W S
"H
W R
16"HWS 14"HWS 12"HWS
8"HWS
8"HWS
10"HWS
16"HWS
"H
W S
"H
W S
8" H
W S
8" H
W S
8" H
W S
8" H
W S
PHWP-4-5
PHWP-4-4
SHWP-4-4
PHWP-4-3
PHWP-4-2
PHWP-4-1
SHWP-4-1 SHWP-4-2 SHWP-4-3 F
S
S
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
1/4" = 1'-0"
/1
/2
:4 :5
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL LEVEL
2 ENLARGED PART B
- NEW
CONSTRUCTION
M204
824273
No. Date Description
R
EF
ER
T
O S
HE
ET
M
MECHANICAL NEW CONSTRUCTION KEYNOTES:
1. INSTALL NEW PRIMARY HEATING HOT WATER PUMP ON EXISTING CONCRETE PAD/INERTIA BASE. ONCE NEW PUMP IS INSTALLED, EXTEND NEW HEATING HOT WATER PIPING TO PUMP SUCTION AND DISCHARGE CONNECTIONS. PROVIDE NEW VARIABLE FREQUENCY DRIVE WITH ELECTRONIC BYPASS. AFTER INSTALLATION OF PUMP AND NEW VARIABLE FREQUENCY DRIVE, POWER SHALL BE RECONNECTED TO NEW VFD AND PUMP.
2. NSTALL NEW ELECTROMAGNETIC INSERTION FLOWMETER AT THE LOCATION INDICATED. FLOWMETER SHALL BE SUITABLE FOR INSTALLATION IN PIPING/PIPING SIZE AT INDICATED LOCATION. FLOWMETER SHALL BE ONICON F-3500 OR EQUAL. FLOWMETER SHALL BE COMPATIBLE WITH 24V
ELECTRICAL SERVICE. FLOWMETER SHALL BE UTILIZED BY ONICON SYSTEM-20 BTU METER.
3. INSTALL NEW VARIABLE FREQUENCY DRIVE ON EXISTING UNISTRUT STAND.
4. INSTALL NEW TEMPERATURE SENSOR IN HEATING HOT WATER RETURN PIPING AT LOCATION INDICATED. SENSOR SHALL BE UTILIZED BY ONICON
SYSTEM-20 BTU METER.
5. INSTALL NEW TEMPERATURE SENSOR IN HEATING HOT WATER SUPPLY PIPING AT LOCATION INDICATED. SENSOR SHALL BE UTILIZED BY ONICON
SYSTEM-20 BTU METER.
6. INSTALL NEW BTU METER INTERFACE/DISPLAY AT LOCATION INDICATED. BTU METER SHALL BE ONICON SYSTEM-20 OR EQUAL. FINAL LOCATION OF
BTU METER INTERFACE/DISPLAY SHALL BE COORDINATED WITH ACTUAL FIELD CONDITIONS.
7. INSTALL NEW ELECTROMAGNETIC INSERTION FLOWMETER AT THE LOCATION INDICATED. FLOWMETER SHALL BE SUITABLE FOR INSTALLATION IN PIPING/PIPING SIZE AT INDICATED LOCATION. FLOWMETER SHALL BE ONICON F-3500 OR EQUAL. INSTALL FLOWMETER IN COMPLIANCE WITH ALL MANUFACTURER RECOMMENDATIONS AND REQUIREMENTS, INCLUDING REQUIRED AMOUNT OF STRAIGHT PIPING UPSTREAM AND DOWNSTREAM OF FLOWMETER. FLOWMETER INSTALLATION SHALL BE DOWNSTREAM OF CONNECTION OF ALL SECONDARY HOT WATER PUMPS (INCLUDING SHWP 4-4) TO SECONDARY HOT WATER SUPPLY MAIN. FLOWMETER SHALL BE COMPATIBLE WITH 24V ELECTRICAL SERVICE. FLOWMETER SHALL BE UTILIZED BY
ONICON SYSTEM-20 BTU METER.
1 1
1 1
1/4" = 1'-0"
LEVEL 2 - ENLARGED PART B - NEW CONSTRUCTION
3 3333
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
TO SECONDARY
CHILLED WATER
PUMPS
FROM WATER-COOLED
CHILLERS/PRIMARY CHILLED
WATER LOOP
20-INCH TIE-IN TO
CHILLER PLANT B
CHILLED WATER
RETURN FROM
BUILDING
CHILLED WATER
SUPPLY TO
BUILDING
20-INCH TIE-IN TO
CHILLER PLANT B
EXISTING 10"CHWS EXISTING 10"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 24"
EXISTING 24"
EXISTING 10"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
EXISTING 10"CHWS EXISTING 10"CHWS EXISTING 10"CHWS
EXISTING 24"CHWR
EXISTING 20"CHWS
TO SYSTEM
EXPANSION
TANKS
EXISTING 10"CHWR
EXISTING 10"CHWR
EXISTING 10"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
VFD
PCWP-4-2 PCWP-4-1
SCWP-4-2 SCWP-4-3 SCWP-4-4 SCWP-4-6 SCWP-4-5SCWP-4-1
EXISTING AIR
SEPARATOR
NEW AIR
VENT
VFD VFD VFD VFD VFD
PCWP-4-5 PCWP-4-4 PCWP-4-3
EXISTING CHILLER CH-13
PCWP-4-6
EXISTING CHILLER CH-12 EXISTING CHILLER CH-11 EXISTING CHILLER CH-10 EXISTING CHILLER CH-9
1 1 1 1 1 1
2 2 2 2 2 2
2 2 2 2 2 2
2 2 2 2 2
2 2
4 4 4 4 2 2
3 3 3 9 9
4 4 4 4 4
2 2 2 2 22
2 2 2 2 2 2
2 2 2 2 2
2 2 2 2 2
2 2 2 2 2
2 2 2 2 2
2 2 2 2 2 22
7 7 7 7 7 7
8 8 8 8
6 6 6 6
8 888
EXISTING 24"CHWS EXISTING 24"CHWS
E X
IS
T
IN
G
4"
C H
W S
EXISTING 20"CHWS EXISTING 20"CHWS EXISTING 20"CHWS EXISTING 20"CHWS EXISTING 20"CHWS
EXISTING 20"CHWSEXISTING 20"CHWSEXISTING 20"CHWS
EXISTING 24"CHWSEXISTING 10"CHWS EXISTING 16"CHWS EXISTING 20"CHWS EXISTING 24"CHWS EXISTING 24"CHWS
EXISTING 10"CHWSEXISTING 16"CHWSEXISTING 20"CHWS EXISTING 10"CHWSEXISTING 24"CHWS
EXISTING 24"CHWS
EXISTING 10"CHWSEXISTING 10"CHWSEXISTING 10"CHWSEXISTING 10"CHWS
EXISTING 24"CHWREXISTING 24"CHWREXISTING 24"CHWR
EXISTING 24"CHWR EXISTING 20"CHWR EXISTING 20"CHWR EXISTING 20"CHWR EXISTING 20"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
MECHANICAL
ROOM
MECHANICAL
ROOM
MECHANICAL
ROOM
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
12" = 1'-0"
/1
/2
:4 :5
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL
HYDRONIC PIPING
DIAGRAM- EXISTING
M300
824273
No. Date Description
MECHANICAL DEMOLITION KEYNOTES:
1. EXISTING SECONDARY CHILLED WATR PUMP SHALL RMAIN
2. EXISTING CHILLED WATER PIPING TO REMAIN
3. EXISTING PRIMARY CHILLED WATER PUMP SHALL BE DEMOLISHED. EXISTING CHILLED
WATER PIPING AND ACCESSORIES SHALL BE DEMOLISHED BACK TO SHUT-OFF VALVES AS
INDICATED. EXISTING CONCRETE HOUSEKEEPING PAD, SUPPORTING PUMP, SHALL REMAIN.
4. EXSITING CHILLED WATER PIPING SHALL BE DEMOLISHED AS INDICATED.
5. EXISTING AIR SEPARATOR SHALL REMAIN.
6. EXISTING WATER-COOLED CHILLER SHALL BE DEMOLISHED. EXISTING CONCRETE
HOUSEKEEPING PAD, SUPPORTING CHILLER, SHAL REMAIN. CHILLED WATER PIPING SHALL
BE REMOVED BACK TO SHUT-OFF VALVES.
7. EXISTING VARIABLE FREQUENCY DRIVE SERVING CHILLED WATER PUMP.
8. POINT OF DISCONNECTION
9. EXISTING PRIMARY CHILLED WATER PUMP SHALL REMAIN.
12" = 1'-0"
HYDRONIC PIPING DIAGRAM- EXISTING
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 10"CHWR
NEW 12"CHWRNEW 12"CHWR
NEW 12"CHWS
F
S
S
TSTS
MODULATING
TSTS
MODULATING
TSTS
MODULATING
NEW 12"CHWS NEW 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
EXISTING 10"CHWS
TO SECONDARY
CHILLED WATER
PUMPS
FROM WATER-COOLED
CHILLERS/PRIMARY CHILLED
WATER LOOP
20-INCH TIE-IN TO
CHILLER PLANT B
CHILLED WATER
RETURN FROM
BUILDING
CHILLED WATER
SUPPLY TO
BUILDING
20-INCH TIE-IN TO
CHILLER PLANT B
EXISTING 10"CHWS EXISTING 10"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 20"CHWS
EXISTING 24"
EXISTING 24"
EXISTING 10"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
EXISTING 10"CHWS EXISTING 10"CHWS EXISTING 10"CHWS
EXISTING 24"CHWR
EXISTING 20"CHWS
TO SYSTEM
EXPANSION
TANKS
NEW CHILLER CH-13 NEW CHILLER CH-12 NEW CHILLER CH-11
PCWP-4-5 PCWP-4-4 PCWP-4-3PCWP-4-6
VFD VFD VFD VFD
VFD
PCWP-4-2 PCWP-4-1
SCWP-4-2 SCWP-4-3 SCWP-4-4 SCWP-4-6 SCWP-4-5SCWP-4-1
EXISTING AIR
SEPARATOR
NEW AIR
VENT
VFD VFD VFD VFD VFD
1 1 1 1 1 1
2 2 2 2 2 2
2 2 2 2 2 2
2 2 2 2 2
2 2
4 4 4 4
3 3 3
4 4 4
2 2 2 2 22
2 2 2 2 2 2
2 2 2 2 2
2 2 2 2 2
2 2 2 2 2
2 2 2 2 2
2 2 2 2 2 22
7 7 7 7 7
8 8 8 8
9 9
10 10
999 9
NEW BTU METER
11 12
151515151515
4 4
EXISTING 24"CHWS EXISTING 24"CHWS
E X
IS
T
IN
G
4"
C H
W S
EXISTING 20"CHWS EXISTING 20"CHWS EXISTING 20"CHWS EXISTING 20"CHWS EXISTING 20"CHWS
EXISTING 20"CHWSEXISTING 20"CHWSEXISTING 20"CHWS
EXISTING 24"CHWSEXISTING 10"CHWS EXISTING 16"CHWS EXISTING 20"CHWS EXISTING 24"CHWS EXISTING 24"CHWS
EXISTING 10"CHWSEXISTING 16"CHWSEXISTING 20"CHWS EXISTING 10"CHWSEXISTING 24"CHWS
EXISTING 24"CHWS
EXISTING 10"CHWSEXISTING 10"CHWSEXISTING 10"CHWSEXISTING 10"CHWS
EXISTING 24"CHWREXISTING 24"CHWREXISTING 24"CHWR
EXISTING 24"CHWR EXISTING 20"CHWR EXISTING 20"CHWR EXISTING 20"CHWR EXISTING 20"CHWR
EXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWREXISTING 10"CHWR
MECHANICAL
ROOM
MECHANICAL
ROOM
MECHANICAL
ROOM
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
12" = 1'-0"
/1
/2
:4 :5
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL
HYDRONIC PIPING
DIAGRAM- NEW
M301
824273
No. Date Description
MECHANICAL NEW CONSTRUCTION KEYNOTES:
1. EXISTING SECONDARY CHILLED WATR PUMP SHALL RMAIN
2. EXISTING CHILLED WATER PIPING TO REMAIN
3. INSTALL NEW CHILLED WATER PUMP ON EXISTING CONCRETE HOUSEKEEPING PAD. INSTALL
NEW CHILLED WATER PIPOING AND ACCESSORIES BETWEEN PUMP AND SHUT-OFF VALVES
AS INDICATED.
4. INSTALL NEW CHILLED WATER PIPING AS INDICATED.
5. EXISTING AIR SEPARATOR SHALL REMAIN.
6. NSTALL NEW WATER-COOLED CHILLER ON EXISTING CONCRETE HOUSEKEEPING PAD.
INSTALL NEW CHILLED WATER PIPNING AND ACCESSORIES BETWEEN CHILLER AND SHUT-
OFF VALVES, AS INDICATED.
7. EXISTING VARIABLE FREQUENCY DRIVE SERVING CHILLED WATER PUMP.
8. NEW PRIMARY CHILLED WATER PUMP SHALL BE PROVIDED WITH VARIABLE FREQUENCY
DRIVE.
9. POINT OF CONNECTION, NEW TO EXISTING.
10. OPERATE SHUT-OFF VALVE TO THE CLOSED POSITION.
11. INSTALL NEW ELECTROMAGNETIC FLOWMETER AT THE LOCATION INDICATED. FLOWMETER
SHALL BE SUITABLE FOR INSTALLATION IN PIPING/PIPING SIZE AT INDICATED LOCATION.
FLOWMETER SHALL BE ONICON F-3500 OR EQUAL. FLOWMETER SHALL BE COMPATIBLE
WITH 24V ELECTRICAL SERVICE.
12. FLOWMETER SHALL BE UTILIZED BY ONICON SYSTEM-20 BTU METER.
13. INSTALL NEW TEMPERATURES SENSOR IN CHILLED WATER SUPPLY AND RETURN PIPING AT
LOCATIONS INDICATED. SENSORS SHALL BE UTILIZED BY ONICON SYSTEM-20 BTU METER.
14. NEW BTU METER INTERFACE/DISPLAY. BTU METER SHALL BE ONICON SYSTEM-20 OR
EQUAL.
15. NEW DDC TEMPERATURE SENSOR.
12" = 1'-0"
HYDRONIC PIPING DIAGRAM- NEW
UNIT INSTALLER: _____________________
INSTALLER'S ADDRESS:_______________
UNIT REGRIGERANT NUMBER: _________
UNIT REFRIGERANT CHARGE: _________ lbs
UNIT LUBRICANT IDENTITY: _____________
UNIT LUBRICANT AMOUNT: ______________
FIELD TEST PRESSURE APPLIED: ________lbs
NOTES :
1.
LOCATE SIGN ON EXTERIOR OF CHILLER CONTROL PANEL FOR EACH CHILLER.
2.
FORMAT FOR WARNING SIGNAL PANEL SHALL BE WHITE LETTERS ON RED BACKGROUND. SIGN
SHALL BE SILKSCREENED ALUMINUM OR ENGRAVED PLASTIC.
3. LARGE PRINT LETTERS SHALL BE 1-3/4" TALL; SMALL PRINT LETTER SHALL BE 1" TALL.
4. CONTRACTOR SHALL FURNISH ALL DATA NEEDED TO FILL IN REQUIRED INFORMATION. ALL DATA TO BE COMPLETED BY CONTRACTOR SHALL BE PERMANENTLY APPLIED IN LETTERING MINIMUM 1/2" TALL
24" MINIMUM
18" MIN.
CH-_REFRIGERANT
DATA
#5 CONT. W/ MATCHING CORNER BAR AT MID DEPTH W/ 4"
EMBEDMENT INTO EXISTING PAD USING HILTI HY200 ADHESIVE
1' -0"
#4 DOWEL @12" O/C WITH MIN 4" CONCRETE EMBEDMENT
DEPTH
FS
P
PP
FS
P
EXISTING CONCRETE
EQUIPMENT PAD
THERMOMETER
(TYPICAL)
CWR
C W
R
PETE'S PLUG
(TYPICAL)
CONDENSER ISOLATION
VALVE, MODULATING
CWR
CWS
C W
S
CWS
CLEANABLE 30
MESH STRAINER
C W
S
DIFFERENTIAL PRESSURE SENSOR (TYPICAL)
BUTTERFLY
VALVE
(TYPICAL)
CLEANABLE 30
MESH STRAINER
PRESSURE
GAUGE
(TYPICAL)
C
HW
R C
HW
R
CHWR
C H
W S
EVAPORATOR
ISOLATION
VALVE, MODULATING
FLEXIBLE CONNECTOR
(TYPICAL) SHALL BE MASON
INDUSTRIES SAFEFLEX
SFDEJ OR EQUAL
CHWS
FLOWSWITCH (TYPICAL),
OMIT IF FLOWSWITCH IS
PROVIDED INTEGRAL TO
CHILLER
DRAIN W/VALVE,
PROVIDE WITH HOSE
CONNECTION (TYPICAL)
EXISTING WATER-COOLED
CHILLER
FINISHED FLOOR
EXISTING
NEW
AUTOMATIC FLOW
CONTROL VALVE
EXISTING
NEW
BOLTED OR WELDED
RECTANGULAR STEEL
CONCRETE FORM
ANCHOR BOLTS IN
SLEEVES, AS REQUIRED
STEEL REINFORCEMENT
HEIGHT SAVING
BRACKET
INERTIA BASE SPECIFICATIONS :
1. VIBRATION ISOLATION MANUFACTURER SHALL FURNISH
STEEL CONCRETE POURING FORMS FOR FLOATING
CONCRETE BASES. GEOMETRY OF THE BASE SHALL BE
SUITABLE FOR THE PUMP BEING SERVED. THE BASE
DEPTH SHALL NOT EXCEED 12 INCHES, UNLESS
SPECIFICALLY RECOMMENDED BY THE BASE
MANUFACTURER FOR MASS OR RIGIDITY. FORMS
SHALL INCLUDE MINIMUM CONCRETE REINFORCING
CONSISTING OF 1/2" BARS WELDED IN PLACE ON SIX
INCH CENTERS RUNNING BOTH WAYS IN A LAYER 1-1/2"
ABOVE THE BOTTOM. FORMS SHALL BE FURNISHED
WITH STEEL TEMPLATES TO HOLD THE ANCHOR BOLT
SLEEVES AND ANCHOR BOLTS WHILE CONCRETE IS
BEING POURED. HEIGHT SAVING BRACKETS SHALL BE
EMPLOYED IN ALL MOUNTING LOCATIONS TO MAINTAIN
A 1-INCH CLEARANCE BELOW THE BASE. WOODEN
FORMED BASES LEAVING A CONCRETE RATHER THAN A
STEEL FINISH ARE NOT ACCEPTABLE. INERTIA BASE
SHALL BE BMK CONCRETE BOLTED BASE, BY MASON
INDUSTRIES, INC., OR EQUAL.
2. SPRING ISOLATORS SHALL BE FREE STANDING AND
LATERALLY STABLE WITHOUT ANY HOUSING AND
COMPLETE WITH A MOLDED NEOPRENE CUP OR 1/4"
NEOPRENE ACOUSTICAL FRICTION PAD BETWEEN THE
BASEPLATE AND THE SUPPORT. ALL MOUNTINGS
SHALL HAVE LEVELING BOLTS THAT MUST BE RIGIDLY
BOLTED TO THE EQUIPMENT. INSTALLED AND
OPERATING HEIGHTS SHALL BE EQUAL. THE RATIO OF
THE SPRING DIAMETER DIVIDED BY THE COMPRESSED
SPRING HEIGHT SHALL BE NO LESS THAN 0.8. SPRINGS
SHALL HAVE A MINIMUM ADDITIONAL TRAVEL TO SOLID
EQUAL TO 50% OF THE RATED DEFLECTION.
SUBMITTALS SHALL INCLUDE SPRING DIAMETERS,
DEFLECTION, COMPRESSED SPRING HEIGHT AND
SOLID SPRING HEIGHT. MOUNTINGS SHALL BE TYPE
SLF, AS MANUFACTURED BY MASON INDUSTRIES, INC.,
OR EQUAL.
FREE STANDING
SPRING
ISOLATORS
NOTES :
1. INERTIA BASES SHALL BE PROVIDED FOR ALL NEW
BASE MOUNTED HYDRONIC PUMPS.
HYDRONIC PIPING
PIPE INSULATION
CAP, PROVIDE WITH CHAIN ATTACHED TO
THERMOWELL
THERMOWELL WITH EXTENSION, AS SPECIFIED.
THERMOWELL SHALL BE INSTALLED SO THAT
WELL IS INSTALLED NO DEEPER THAN CENTER
OF PIPE.
45°
CONCRETE
HOUSEKEEPING
PAD
VIBRATION ISOLATION PAD (TYPICAL)
FLANGED JOINT OR
UNION TO PERMIT
PIPING DISASSEMBLY
DIRT LEG
CAP HAND-TIGHT TO PERMIT
CLEANOUT, PROVIDE 1/4" DRAIN
VALVE AT CAP
EXISTING REFRIGERANT RELIEF PIPING
VENTED TO THE OUTSIDE OF THE BUILDING.
UNION (TYPICAL)
PIPING CONNECTION TO RELIEF VALVE AND ALL PIPING TO
OUTDOORS PROVIDED BY CONTRACTOR
FLEXIBLE STEEL CONNECTION
4-INCH REFRIGERANT RELIEF PIPING ATTACHED TO
REFRIGERANT RELIEF CONNECTION WATER-COOLED CHILLER
EVAPORATOR
CONDENSER
RUPTURE DISK ASSEMBLY
NOTES:
1. SEE STRUCTURAL DRAWING S401 FOR ADDITIONAL
INFORMATION ON REQUIRED SEISMIC BRACING OF HYDRONIC
PIPING.
ALL THREAD
ROD
NUT (TOP
& BOTTOM)
WASHER (TOP
& BOTTOM)
CLEVIS
HANGER
INSULATION
PIPE
INSULATION
PROTECTIVE
SHEETMETAL SHIELD
THREADED ROD CUT TO LENGTH
CLEVIS TYPE PIPE HANGER
CARRIER PIPE
INSULATION
A) SHIELD FOR INSULATION PROTECTION
ON INSULATED LINES - LENGTH 1.5
TIMES INSULATION DIAMETER
B) ELASTOMERIC PAD FOR NONMETALLIC
CARRIER PIPE
C) OMIT FOR BARE STEEL CARRIER PIPE
NOTES:
1. SEE STRUCTURAL DRAWING S401 FOR ADDITIONAL
INFORMATION ON REQUIRED SEISMIC BRACING OF HYDRONIC
PIPING.
HANGER ROD
WEB MEMBERS
O.W.S.J.WELDS
HANGER
NUT
BAR JOIST
BENT STRAP
1 1/2"X3/16"
OVER VERT LEGS
OF ANGLES
BOTTOM CHORD
OF O.W.S.J.
ONE ANGLE EACH SIDE OF WEB
MEMBERS REST ON TOP OF BOTTOM
CHORD OF O.W.S.J. BETWEEN PANEL
POINTS. SIZE FOR LOAD.
CONCRETE HOUSE
KEEPING PADFINISHED FLOOR
NOTES:
1. SHIM/LEVEL BED PLATE & TIGHTEN HOLD DOWN BOLTS. GROUT BED PLATE AFTER LEVELING. GROUT SHALL BE THE NON-SHRINKING
TYPE.
2. PROVIDE SNUBBERS AT EACH PRESSURE GAUGE. SEE PROJECT SPECIFICATIONS FOR REQUIREMENTS FOR SNUBBERS.
CONCRETE HOUSE
KEEPING PAD
FINISHED FLOOR
BUTTERFLY VALVE
3/4" DRAIN WITH
FULL PORT BALL
VALVE AND
THREADED OUTLET
FLANGED
REDUCER
CHECK VALVE
3/4" DRAIN WITH
FULL PORT BALL
VALVE AND
THREADED OUTLET
FLEXIBLE CONNECTION: DOUBLE
SPHERE RUBBER CONNECTOR
MANUFACTURED WITH KEVLAR
REINFORCED HIGH TEMPERATURE
PEROXIDE CURED EPDM, EQUAL
TO MASON SAFEFLEX, TYPICAL
GROUTABLE
FABRICATED
STEEL BASE PLATE
HORIZONTAL SPLIT
CASE PUMP
OSHA/ANSI
COUPLER GUARD
INERTIA BASE, SEE
INERTIA BASE DETAIL
STRAINER
12" SPOOL
12" SPOOL
MULT-PORT
PRESSURE GAUGE
SNUBBER
NEEDLE VALVE
(TYPICAL)
SIDE VIEW FRONT VIEW
BALL VALVE
(TYPICAL)
AUTOMATIC
AIR VENT
NEEDLE VALVE
1/2" x 4"
NIPPLE
FULL PIPE
SIZE
FLOW DIRECTION
PIPE TO FLOOR OR
INDIRECT DRAIN, FULL
SIZE OF CONNECTION
6"
PROVIDE BALL
VALVE IN
ACCESSIBLE
LOCATION WHERE
DISCHARGE FROM
TUBING CAN BE
OBSERVED.
1/2" STEEL
PIPE
1/2" HARD
COPPER 1/2" HARD
COPPER
NOTES :
1. IF MAIN BRANCH PIPING IS COPPER, ALL SUBSEQUENT
PIPING IS COPPER.
2. ALL HIGH POINTS, WHERE AIR POCKETS MAY DEVELOP,
SHALL BE VENTED.
3. PROVIDE BALL VALVE IN ACCESSIBLE LOCATION WHERE
DISCHARGE FROM TUBING CAN BE OBSERVED.
V
STRUCTURAL MEMBER
MALLEABLE
IRON BEAM
CLAMP
MALLEABLE IRON
EXTENSION PIECE
SUPPORT ROD -
SEE SPECS FOR
SIZE
BOLT
STRUCTURAL MEMBER
CARBON STEEL BEAM
CLAMP
BOLT
MALLEABLE
IRON
EXTENSION
PIECE
SLEEVE OVER BOLT FOR
SPACER SUPPORT ROD- SEE
SPECS FOR SIZE
4360 Chamblee Dunwoody Rd.
Suite 210
Atlanta, GA 30341 P 770.451.6757 www.tlc-engineers.com
© Copyright 2022 TLC Engineering Solutions, Inc.
TLC Project No.:
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
As indicated
/1
/2
:4 :0
P
M L
-J o b s \8
-G
W C
C P h a s e
I G
A a n d
P re lim D e s ig n \R e v it -C e n tr a l\
M E
P R
.r v t
G W
C C
G E
S P
C I
I
B U
IL
D
IN
G
C C
H
IL
L E
D W
A T
E R
P L
A N
T S
U P
G R
A D
E S
A n d re w
Y o u n g I n te rn a ti o n a l B lv d
N W
A tl a n ta
G
A
824273
07/11/2025
R. COONS
R. PARKINS
MECHANICAL-
DETAILS
M400
824273
No. Date Description
NOT TO SCALE
CHILLER REFRIGERANT DATA SIGN
NOT TO SCALE
EXISTING CONCRETE PAD EXPANSION DETAIL
NOT TO SCALE
WATER-COOLED CHILLER PIPING DETAIL
NOT TO SCALE
BASE-MOUNTED END SUCTION PUMP INERTIA BASE DETAIL
NOT TO SCALE
THERMOWELL INSTALLATION DETAIL
NOT TO SCALE
REFRIGERANT RELIEF DETAIL
NOT TO SCALE
TYPICAL CLEVIS HANGER DETAIL
NOT TO SCALE
CLEVIS PIPE HANGER DETAIL
NOT TO SCALE
STEEL BAR JOIST PIPE SUPPORT
NOT TO SCALE
HORIZONTAL SPLIT CASE PUMP DETAIL
1/2" = 1'-0"
AUTOMATIC AIR VENT DETAIL
1/2" = 1'-0"
BEAM CLAMPS FOR PIPE OR EQUIPMENT SUPPORT
DN
UP
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
SYMBOL DESCRIPTION
DDC
VFD
ELECTRICAL SYMBOL LEGEND
AUTOMATIC TRANSFER SWITCH
TRANSFORMERT
DIRECT DIGITAL CONTROL PANEL
VARIABLE FREQUENCY DRIVE
MOTOR CONNECTION
NEW (HEAVY, SOLID LINE)
EXISTING TO REMAIN (LIGHT, SOLID LINE)
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
FLEXIBLE CONDUIT
CONDUIT CONTINUED
CONDUIT STUBBED OUT OR UP
CONDUIT TURNING DOWN
CONDUIT TURNING UP
GROUND OR GROUND ROD AS NOTED
CONDUIT EXPOSED
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR
CONDUIT CONCEALED ABOVE CEILING OR IN WAL
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED
MULTI-SERVICE RACEWAY WITH 5-20R RECEPTACLES, 18" O.C. UNLESS
OTHERWISE NOTED
SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AS NOTED
NOTE: DIAGONAL MARKS INDICATED ON ANY DEVICE REPRESENTS DEVICE
CONNECTED TO EMERGENCY CIRCUIT (RED DEVICE FOR RECEPTACLE);
TYPICAL FOR ANY DEVICE IN LEGEND
TWO…