This is a Statement of Work (SOW) attachment establishing telecommunications requirements for furniture packages at Wright-Patterson Air Force Base, Ohio. The contractor shall provide communications cable installation support for new furniture requirements, including inter-building and intra-building cable plant work. Inter-building work encompasses installing, upgrading, re-routing, terminating, splicing, testing, removal, and documentation of copper and fiber optic cabling through manhole/hand-hole systems, duct systems, and direct burial applications. Intra-building work includes similar services for internal building infrastructure. A certified data cabling installer must meet Installation Facility Standard (IFS) requirements as specified in appendix G11.
The vendor must adhere to Base Facility Standard (BFS) or IFS current version standards and Telecommunications Industry Association (TIA)/Electronic Industries Association (EIA) standards listed in the document. Key requirements include: preparing a performance schedule, accessing Base Civil Engineering drawings upon request while protecting proprietary information, performing pre-installation quality inspections of fiber optic and copper cables, conducting comprehensive end-to-end testing of all installed cabling with specific pass/fail criteria for continuity, splice errors, loop resistance, and light loss measurements, providing post-testing results via electronic media for government verification, correcting discrepancies within two business days, and participating in final inspection with the Quality Assurance Evaluator (QAE). The vendor must maintain safe work environments, immediately report safety violations and mishaps, and provide all information necessary for access to secured work areas. Applicable standards include TIA/EIA-526-7, TIA/EIA-568, TIA/EIA-569, TIA/EIA-598, TIA/EIA-606, J-STD-607, and TIA/EIA-758, among others.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment B –88 ABW/CS Telecommunication Requirements for Furniture Packages Wright Patterson AFB, OH
1 | P a g e
88 ABW/CS Telecommunication Requirements For
Furniture Packages
2 | P a g e
1. DESCRIPTION OF SERVICES
The Contractor shall use provide communications cable installation support for new furniture requirements designed in the Statement of Work Furniture Package associated with this attachment. A certified data cabling installer must meet the Installation Facility Standard (IFS) requirements in appendix G11.
1.1 Scope of Work
This Service will provide for sound management, installing, upgrading, re-routing, terminating, testing and removal of communications cable infrastructure at WPAFB as identified in the MOA.
1.1.1 The vendor will provide inter-building cable plant work to include installing, upgrading, re-routing, terminating, splicing, testing, removal, cable acceptance, inspection, and labeling documentation of copper and/or fiber optic cabling running through the manhole/hand-hole, duct systems and/or directly buried of copper and fiber optic cabling.
1.1.2 The vendor will provide intra-building cable plant work to include installing, upgrading, re-routing, removal, termination, inspection, testing, cable acceptance, inspection, labeling, documentation and installation/removal of copper and fiber optic cabling.
1.2 Requirements
1.2.1 Regulations and Guidance. The following standards will be used as applicable in the performance of this task. It is the vendor’s responsibility to obtain and adhere to all industry standards and best commercial practice documentation. A list of applicable standards is identified in section 1.3.3.
1.2.1.1 Base Facility Standard (BFS) or Installation Facility Standard (IFS), current version, Wright-Patterson Air Force Base, Ohio OPR: 88 ABW/CE and 88 CS/SCX.
1. Telecommunications Industry Association (TIA)/Electronic Industries Association
(EIA) Standards (See Appendix B).
1.2.2 Site survey. A survey between the 88 ABW/CS and CE Interior Design, and the customer have already taken place. If required after Furniture Package Award, another walk through may be requested by the vendor/installer.
1.2.3 Schedule. The vendor will prepare a schedule showing the order in which the vendor proposes to perform the work and the dates on which the vendor contemplates starting and completing the salient features of the work.
1.2.3.1 The vendor will follow all requirements provided on the Telecommunication drawings supplied.
3 | P a g e
1.2.3.2 The vendor will have access to all available Base Civil Engineering (BCE) drawings, upon request, and base communications drawings to identify existing utilities and future utilities and/or construction, which impact the project. Base communications drawings will be supplied, when required. The drawings provided are For Official
Use Only and the vendor will not dispose of or destroy them in any manner. The
Vendor will verify the accuracy as applicable to the requirement and notify the
Government PM of inaccuracies or discrepancies.
1.2.4 Labeling. The Vendor will refer to the IFS for labeling requirements.
1.2.5 Pre-testing. The vendor will perform a pre-installation quality inspection of Fiber Optic
(FO) and copper cable on reels and already installed government cables prior to using.
1.2.5.1 The vendor will perform end-to-end testing on all installed communications cabling.
Installed copper cabling will be continuity tested for shorts, grounds, splice errors
(i.e., reverses, opens, transpositions and split pairs), and loop resistance. Installed fiber will be tested to ensure the light loss will not be greater than manufacturer's specifications for cable and properly connected connectors.
1.2.6 Post-testing. The vendor will perform end-to-end testing on all installed communications cabling. Installed copper cabling will be continuity tested for shorts, grounds, splice errors (i.e., reverses, opens, transpositions and split pairs), and loop resistance. All deficiencies will be corrected prior to government acceptance. All horizontal cabling will be end-to-end tested after all terminations have been accomplished to ensure they pass the applicable category specifications. Fiber optic cabling will have both Optical Time Domain Reflectometry (OTDR) and attenuation testing. Installed fiber will be tested to ensure the light loss will not be greater than manufacturer's specifications for cable and properly connected connectors. The Vendor will test all fiber optic cables and make sure that any fiber optic cabling that does not meet the fiber optic standard will be checked, troubleshot, fixed, and re-tested; any fiber optic cabling that can’t be fixed after troubleshooting will be re-installed and tested to meet fiber optic standards.
1.2.7 Test Results. The vendor will ensure the cable ID on the test results reflect the run locations as identified on the cable labels.
1.2.7.1 The vendor will provide post-testing results via electronic media (CD OR DVD) for review.
1.2.7.2 All test results will be verified by a Government 88 ABW/CS representative prior to the Final Inspection.
1.2.7.3 If the Government finds any discrepancies with the test results the vendor will be notified and have 2 business days to make the appropriate correction and return them to the Government PM.
1.2.8 Final Inspection. The 88 ABW/CS PM and customer will perform a final inspection with the vendor, confirming all task requirements were met. Exceptions will be documented, 4 | P a g e fixed, and re-inspected for acceptance. The QAE will make the final decision on whether the task requirements have been met and can be accepted.
1.2.9 Secured Work Areas. In secured work areas requiring special access, the vendor will provide the customer/PM with all information requested and/or needed to get proper access.
1.3 Safety Requirements
1.3.1 The vendor will provide and maintain work environments and procedures which will safeguard the public and government personnel, property, materials, supplies and equipment exposed to vendor operations and activities, avoid interruptions of government operations and delays in project completion dates, and control costs in the performance of this requirement.
1.3.2 The vendor will immediately correct safety violations and notify the customer when a potentially hazardous or unsafe conditions exists. The vendor will immediately notify the customer of all mishaps resulting in personnel injury, government property damage, or financial loss to the Government. The vendor will secure the mishap scene and immediately impound all wreckage, related items, and documentation. The vendor will fully support the Government in any mishap or hazard investigation.
1.3.3 Applicable Industry Standards
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) /
ELECTRONIC INDUSTRIES ASSOCIATION (EIA) LIST
TIA/EIA-526-7
Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant
TIA/EIA-526-14
Optical Power Loss Measurements of Installed Multimode Fiber Cable Plant
TIA/EIA-455-204
Measurement of Bandwidth on Multimode Fiber
TIA/EIA-492AAAA
Detail Specification for 62.5 micron Core Diameter/125 micron Cladding Diameter Class 1a Multimode, Graded-Index Optical Waveguide Fibers
TIA/EIA-568
Commercial Building Telecommunications Wiring Standard
TIA/EIA-569
Commercial Building Standard for Telecommunications Pathway and Spaces
TIA/EIA-570
5 | P a g e
Residential Telecommunications Cabling Standard
TIA/EIA-598
Optical Fiber Cable Color Coding
TIA/EIA-606
Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
J-STD-607
Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications
TIA/EIA-758
Customer-Owned Outside Plant Telecommunications Cabling Standard
TIA/EIA TSB3
Additional Cable Specifications for Unshielded Twisted Pair Cables