0000-2220 E1_1 Tennis Court

378 KB Posted

Attached to
Exterior Athletic Lighting
Solicitation number
0000-2220
Issued by
Georgia

About this file

This is a construction drawing for the Tennis Court Lighting Replacement project at East Georgia State College in Swainsboro, Georgia, prepared by Chatham Engineering Company, LLC. The project (No. 0000-2220) involves replacing the existing tennis court lighting system with new LED lighting fixtures and control infrastructure across eight tennis court poles (T1-T8). The scope includes installing multiple LED fixtures of varying wattages (400W, 600W, and 900W) on existing poles, removing existing fixtures and junction boxes, and establishing a new Musco control panel system with three 60-amp three-phase breakers. The project also requires providing new concrete pads for vertical and diagonal support structures, new terminal strips for circuit connections, and grounding systems in compliance with 2020 NEC standards. The drawing was released for construction on May 19, 2022, and includes detailed electrical schematics, pole schedules, and control station specifications.

The electrical work specified in the plan requires coordination with existing 480/277-volt infrastructure, with connections to the existing electrical panel H2 in the gymnasium. All exposed conduits must be rigid galvanized steel, with stranded copper type THWN wiring color-coded and labeled per circuit. The lighting fixtures and control cabinet are specified to be supplied by Musco with no substitutions permitted, and all work must conform to applicable Georgia state ordinances. Coordination with the existing site conditions and college facilities management is required throughout the project, with Rob Staples designated as the contact for all lighting fixture and control cabinet information at (706) 870-2177. The project involves replacing breaker capacities from 100-amp to 60-amp configurations in the existing panel to accommodate the new LED system's reduced power requirements compared to the original fixtures.

Text of this file

CADD PLOT

lcauley

13:35

01-JUN-2022

c

Sheet No.Date

Checked

Drawn

Job No.

Sheet Title

Revisions

No. Date Description

P a rk o f

C o m m e rc e D ri v e S u it e

S a v a n n a h

G e o rg ia

T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d

R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e

E:\E Ga College Tennis Court Lighting - 22051.00\CADD\E1_1.dgn1 INCH

Stamp

P H

O N

E -2

F

A X -2

C h a th a m E n g in e e ri n g C o m p a n y L L C

P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f

C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d

R E L E

A S E

D

F O

C O

N S T R

U C

T

IO

N

22051.00

05/19/22

S W

A

IN

S B

O R

O

G E

O R

G

IA

P

O J E

C T N

O -2

T E

N N

IS

C

O U

R T L

IG

H T

IN

G R

E P

L A

C E

M E

N T

E A S

T G

E O

R G

IA

S

T A T E C

O L L E

G E

TE

N

N

IS

C

O U R

TS

6 LAMPS

6 LAMPS

6 LAMPS

6 LAMPS

4 LAMPS

4 LAMPS

4 LAMPS

4 LAMPS

6 LAMPS

6 LAMPS

6 LAMPS

480V

#6

3-CIRCUITS

CONTINUED

TO

D1-MECH. RM.

GYM EXTERIOR WALL

COURT 1

COURT 2

COURT 3

COURT 3

COURT 1

COURT 2

6 LAMPS

PBX

PBX

DISC.

DISC.

DISC.

TO REMAIN

PULL BOX

EXISTING

THIS SHEET

SEE POLE SCHEDULE

POLE NUMBER

AND 3/E1.1

SEE DETAILS 2/E1.1

TENNIS CONTROL STATION.

(TYP OF 3)

CONTACTORS

60A/3P

TO CONTROLS

NEW MUSCO PANEL

1 NO.8(G)

1"C W/ 3 NO.6,

PULL BOX TO REMAIN

EXISTING IN GROUND

NOTE 2IN EXISTING GYM

EXISTING PANEL H2

8" BOX. NOTE D2

EXISTING 24" SQ X

NOTE D1

DISCONNECT SWITCH.

EXISTING COURT 2

NOTE D1

DISCONNECT SWITCH.

EXISTING COURT 3

NOTE D1

DISCONNECT SWITCH.

EXISTING COURT 1TO REMAIN

EXISTING SUPPORTS

VERTICAL SUPPORT.

PAD - 12"SQ FOR EACH NEW

PROVIDE NEW 6" CONCRETE

TO MATCH EXISTING.

AND DIAGONAL SUPPORTS

SUPPORTS WITH HORIZONTAL

PROVIDE TWO NEW VERTICAL

FLUSH IN COVER OF PANEL

THREE LABELED PUSHBUTTONS

AS SPECIFIED. LOCATE

NEW MUSCO CONTROL PANEL

IN NEW BOX.

INTERCEPT EXISTING CONDUITS

AND PAD LOCKABLE TAB.

EXISTING WITH CLAMPS

NEMA 4 BOX SIMILAR TO

PROVIDE NEW 24"SQ X 8"

NOTE 3

NEW 24"SQ X 8" BOX.

STRIP (TYP)

NEW TERMINAL

L.C.

C.C.

E1.1

LIGHTING PLAN

TENNIS COURT

1 TENNIS COURT LIGHTING PLAN

SCALE: 1" = 20' - 0"E1.1

GENERAL NOTES:NOTES - POLE SCHEDULE

EXISTING POLES AND WIRING TO POLES TO REMAIN.D.

CIRCUIT. MOUNT EACH FIXTURE ON OPPOSITE SIDE OF SUPPORT.

CAGE AREA. AIM IN FIELD. CONNECT LIGHTS TO COURT 2 LIGHTING

PROVIDE 2 - 900 W LED FIXTURES AIMED AT EXISTING BATTINGC.

SEE ONE LINE DIAGRAMS FOR TENNIS COURT WIRING.B.

FOR ALL EXISTING FIXTURES ON ALL POLES.

REMOVE EXISTING FIXTURES, JUNCTION BOX AND CORD CONNECTIONSA.

RETURN 2 - 100A/3P BREAKERS TO OWNER.

H2-26 AND 32 WITH 2 - 60A/3P BREAKERS TO MATCH EXISTING.

IN FIELD. REMOVE AND REPLACE 2 - 100A/3P BREAKERS IN SPACES

PANEL H2 IN EXISTING ELECTRICAL ROOM. VERIFY EXACT LOCATION

3 EXISTING CIRCUITS EXTEND TO EXISTING 480/277V SQUARE D

T1

T2

T3

T4

T5

T6

T7

T8

POLE T5 TOWARDS BATTING CAGE AREA.

AIM TWO LIGHT FIXTURES FROM

EXISTING BATTING CAGE AREA.

C

C

C

COURT 1

COURT 2

COURT 3

SWITCHES

CONTROL

MANUAL

60/3

60/3

60/3

NOTE 4

NOTE 4

NOTE 4

60/3 - NOTE 1

60/3 - NOTE 1

#32

#26

#20

60/3 - EXISTING

NOTES:

MAINTAIN CONNECTIONS TO EXISTING POLES.

CONNECT TO EXISTING 277 VOLT BRANCH CIRCUIT WIRING TO4.

IDENTIFIED TERMINAL STRIPS IN NEW BOX.

CONDUCTORS TO CONNECT TO WIRING EXTENDING TO POLES ON

EXTEND NEW BRANCH CIRCUIS TO CONTACTORS AND EXTEND NEW LOAD

EXISTING BRANCH CIRCUITS EXTENDING FROM PANEL H2.

PROVIDE 3 - 60A/3P BREAKERS INSIDE NEW BOX TO CONNECT TO3.

EXISTING 1"C W/ 3 NO.6, 1 NO.8(G) TO REMAIN.2.

BREAKER TO MATCH EXSITING IN EXISTING PANEL.

REMOVE EXISTING 100A/3P BREAKER AND PROVIDE NEW 60A/3P1.

4 ONE-LINE DIAGRAM

SCALE: SCHEMATICE1.1

2 EXISTING TENNIS COURT CONTROL STATION

SCALE: NOT TO SCALEE1.1

NOTES:

REMOVE EXISTING BOX AND REPLACE WITH NEW.D2.

EXISTING BOX.

REMOVE EXISTING DISCONNECT SWITCHES AND WIRING BACK TOD1.

3 NEW TENNIS COURT CONTROL STATION

SCALE: NOT TO SCALEE1.1

AS EXISTING

LOCATE IN SAME LOCATION

NO.

POLE

NOTE A

FIXTURES

EXISTING

NEW FIXTURES COURT NOTES

T1 6 2 - 600W 1 B

T2 10 2 - 400W 2 B

T2 2 - 600W 1 B

T3 10 2 - 400W 2 B

T3 2 - 600W 1 B

T4 6 2 - 600W 1 B

T5 10 2 - 400W 2 B

T5 2 - 900W 3 B

T5 2 - 900W -

T6 10 2 - 400W 2 B

T6 2 - 900W 3 B

T7 6 2 - 900W 3 B

T8 6 2 - 900W 3 B

B,C

POLE SCHEDULE - NOTE D

PROVIDE POLE GROUNDING PER SPEC 265668-2.1C8.G7.

MOUNTING OF PANELS AND FIXTURES WITH EXISTING POLES.

INFORMATION (706) 870-2177. SEE SPEC 265668. COORDINATE

MUSCO. NO SUBSTITUTIONS PERMITTED. CONTACT ROB STAPLES FOR

ALL LIGHTING FIXTURES AND NEW CONTROL CABINET TO BE BYG6.

ALL EXPOSED CONDUITS TO BE RIGID GALVANIZED.G5.

PROVIDE GREEN EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS.G4.

MATCH EXISTING AND LABEL ALL CIRCUITS ON CONDUCTORS.

ALL WIRING TO BE STRANDED COPPER TYPE THWN. COLOR CODE TOG3.

COORDINATE ALL WORK WITH EXISTING CONDITIONS AND OWNER.G2.

ALL WORK TO CONFORM TO 2020 NEC AND ALL STATE ORDINANCES.G1.

E1_1
References
SCRBGND, TENNIS COURT-UTILITIES.dwg, Model
BDR, CHATHAM 30X42.dgn

Other files

File Type Posted
0000-2220 Lighting Addendum —
0000-2220 Bid Tabulation Sheet —
0000-2220 Addendum 1 —
Award Information —
0000-2220 Bid Requirements —
0000-2220 Specifications —

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .