Z2DA--657-27-111JB, Install Continuous Water Monitoring System

Closed Pre-Solicitation Posted

Solicitation number
36C25527Q0052
Agency
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Place of performance
St Louis Vamc Jefferson Barracks 1 Jefferson Barracks Drive, St. Louis MO 63125

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Integrated Service Network 15 Network Contracting Office is conducting sources sought market research to identify service-disabled veteran-owned small business (SDVOSB) firms for an SDVOSB set-aside to install a continuous water monitoring system, with capability statements due November 12, 2026 at 10:00 a.m. Central under Modification 1, which supersedes the November 9, 2026 date on the original notice. The notice is for planning only, does not commit the government to issue a solicitation or award a contract, and will be followed by a Best Value request for proposals under solicitation 36C25527Q0052.

Work is performed at Jefferson Barracks VA Medical Center in St. Louis, Missouri, in Buildings 3, 51, 52, 53, and 59. The system monitors biocides, pH, pressure, and temperature at domestic cold water sources and hot water generation, consistent with VHA Directive 1061. Sensors cover incoming and distal cold and hot water points, hot water source supply and return temperatures, and mid-point and end-of-line temperatures on hot distribution risers. Data must be capable of integration with the building automation system through a VA Johnson Controls tie-in for real-time monitoring. The contractor must provide full training on the equipment and basic instrumentation and controls training.

Modification 1 corrects the NAICS code to 238220, Plumbing, Heating, and Air-Conditioning Contractors. Responses submitted under 236220 will not be considered. Capability statements are limited to 10 single-sided pages and must include at least three comparable projects from the past five years, SDVOSB certification, socio-economic status under NAICS 238220, percentage of self-performed labor, joint venture information if applicable, and bonding capability. Submit responses to Contracting Officer Jennifer Hill at Jennifer.Hill@va.gov with the subject line "SOURCES SOUGHT: 36C25527Q0052 Project 657-27-111JB, Install Continuous Water Monitoring System."

Notice text

2 versions

Update #2 · Latest ·

657-27-111JB, Install Continuous Water Monitoring System

 This modification is to correct the NAICS code to 238220 Plumbing, Heating, and Air-Conditioning Contractors. If you have submitted a response for NAICS code 236220 this response will not be considered. If eligible please resubmit under NAICS code 238220.

This is a Sources Sought Notice to determine the availability of service disabled veteran owned small business (SDVOSB) firms for a possible small business category type set-aside for Construction Services project: This is a Sources Sought Notice that is issued for information and planning purposes only and is not to be construed as a commitment by the government, implied or otherwise to issue a solicitation or ultimately award a contract. An award will not be made on information received in response to this notice. This notice is not a Request for Proposal (RFP); it is a market research tool being utilized to determine the availability of sources prior to issuing a Best Value type RFP.

PROJECT DESCRIPTION AND SCOPE

This project will install continuous monitoring equipment for biocides, PH level, pressure and temperature at domestic cold water sources and hot water generation for VHA DIR 1061 Buildings, additional temperature sensors on the hot distribution will be installed at mid-point and end-of-line for each major distribution system of the buildings. Data will be back net capable for Building automation system (BAS) VA Johnson controls tie-in and real-time monitoring. Scope includes: JB Bldgs 3, 51, 52, 53, 59

Jefferson Barracks VAMC:

Building 3:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 51:

1 incoming cold water continuous monitoring with pressure and temperature

2 cold water distal -Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 52:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 53:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 59:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Provide full training of new water monitoring equipment and basic I&C training relating to this project.

Contractor work must fully comply with VHA Directive 1061

The intent of this notice is to identify potential Small Business firms capable of performing these services. The Government will use the information obtained from this sources sought announcement to make a set-aside determination including further restriction under a socio-economic status, firms must identify their socio-economic status for NAICS code 238220 Plumbing, Heating, and Air-Conditioning Contractors. The appropriate North American Industry Classification System (NAICS) code for this acquisition is 238220 with the applicable business size of 19.0 million. If interested in this opportunity, please provide via email a Capability Statement: The Capability Statement is designed to inform the Department of Veteran Affairs, of any prospective construction contractors' project execution capabilities. The submission is limited to 10 single sided pages which shall include the following information:

1) Offeror's name, address, point of contact, phone number, e-mail address, and EIN number;

2) Offeror's interest in bidding on the solicitation when it is issued;

3) Offeror's capability to perform a contract of this magnitude and complexity and comparable work performed within the past 5 years - brief description of the project, customer name, timeliness of performance, customer satisfaction, and dollar value of the project) - provide at least 3 examples;

4) Offeror's CVE certification as a Veteran owned business;

5) Please provide Socio-economic status for NAICS code 238220 Plumbing, Heating, and Air-Conditioning Contractors and provide percentage of self-performed labor your company can perform for this type of project;

6) Offeror's Joint Venture information if applicable - existing and potential;Â

7) Offeror's Bonding Capability in the form of a letter from Surety providing bonding level per contract and aggregate.Â

The Response Due Date for this Sources Sought Notice is November 12. 2026 at 10:00 am Central Time. Respondents will not be notified of the results of analysis. Submit your responses to Jennifer.Hill@va.gov. PLEASE REFERENCE "SOURCES SOUGHT: 36C25527Q0052 Project 657-27-111JB, Install Continuous Water Monitoring System" IN THE SUBJECT LINE and first page of the response. The point of contact for submission of Capabilities Statement and questions is:

Jennifer Hill Contracting Officer

Email: jennifer.hill@va.gov

NCO 15 Contracting Office

Leavenworth, Kansas 66048

No basis for claim against the Government shall arise as a result of a response to this sources sought or Government use of any information provided. The Government will not pay for information or comments provided and will not recognize any costs associated with submission of comments. There is no guarantee, expressed or implicit, that market research for this acquisition will result in a particular set-aside, or any other guarantee of award or acquisition strategy. Respondents will not be contacted regarding their submission or information gathered as a result of this Sources Sought notice. Interested firms shall be required to respond to additional announcements separately from this announcement without further notice from the Government when posted to the Contract Opportunities website at https://sam.gov/. The Contract Opportunities website is the only official site to obtain these documents.

Update #1 ·

657-27-111JB, Install Continuous Water Monitoring System

This is a Sources Sought Notice to determine the availability of service disabled veteran owned small business (SDVOSB) firms for a possible small business category type set-aside for Construction Services project: This is a Sources Sought Notice that is issued for information and planning purposes only and is not to be construed as a commitment by the government, implied or otherwise to issue a solicitation or ultimately award a contract. An award will not be made on information received in response to this notice. This notice is not a Request for Proposal (RFP); it is a market research tool being utilized to determine the availability of sources prior to issuing a Best Value type RFP.

PROJECT DESCRIPTION AND SCOPE

This project will install continuous monitoring equipment for biocides, PH level, pressure and temperature at domestic cold water sources and hot water generation for VHA DIR 1061 Buildings, additional temperature sensors on the hot distribution will be installed at mid-point and end-of-line for each major distribution system of the buildings. Data will be back net capable for Building automation system (BAS) VA Johnson controls tie-in and real-time monitoring. Scope includes: JB Bldgs 3, 51, 52, 53, 59

Jefferson Barracks VAMC:

Building 3:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 51:

1 incoming cold water continuous monitoring with pressure and temperature

2 cold water distal -Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 52:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 53:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Building 59:

1 incoming cold water continuous monitoring with pressure and temperature

1 cold water distal Furthest point from incoming cold water

1 hot water distal Furthest point from incoming hot water

1 hot water source equipment supply temperature

1 hot water source equipment return temperature

Monitoring cold and hot temperature at midpoints at each riser

Provide full training of new water monitoring equipment and basic I&C training relating to this project.

Contractor work must fully comply with VHA Directive 1061

The intent of this notice is to identify potential Small Business firms capable of performing these services. The Government will use the information obtained from this sources sought announcement to make a set-aside determination including further restriction under a socio-economic status, firms must identify their socio-economic status for NAICS code 236220, General Construction. The appropriate North American Industry Classification System (NAICS) code for this acquisition is 236220 with the applicable business size of $45 million. If interested in this opportunity, please provide via email a Capability Statement: The Capability Statement is designed to inform the Department of Veteran Affairs, of any prospective construction contractors' project execution capabilities. The submission is limited to 10 single sided pages which shall include the following information:

1) Offeror's name, address, point of contact, phone number, e-mail address, and EIN number;

2) Offeror's interest in bidding on the solicitation when it is issued;

3) Offeror's capability to perform a contract of this magnitude and complexity and comparable work performed within the past 5 years - brief description of the project, customer name, timeliness of performance, customer satisfaction, and dollar value of the project) - provide at least 3 examples;

4) Offeror's CVE certification as a Veteran owned business;

5) Please provide Socio-economic status for NAICS code 236220, General Construction and provide percentage of self-performed labor your company can perform for this type of project;

6) Offeror's Joint Venture information if applicable - existing and potential;Â

7) Offeror's Bonding Capability in the form of a letter from Surety providing bonding level per contract and aggregate.Â

The Response Due Date for this Sources Sought Notice is November 12. 2026 at 10:00 am Central Time. Respondents will not be notified of the results of analysis. Submit your responses to Jennifer.Hill@va.gov. PLEASE REFERENCE "SOURCES SOUGHT: 36C25527Q0052 Project 657-27-111JB, Install Continuous Water Monitoring System" IN THE SUBJECT LINE and first page of the response. The point of contact for submission of Capabilities Statement and questions is:

Jennifer Hill Contracting Officer

Email: jennifer.hill@va.gov

NCO 15 Contracting Office

Leavenworth, Kansas 66048

No basis for claim against the Government shall arise as a result of a response to this sources sought or Government use of any information provided. The Government will not pay for information or comments provided and will not recognize any costs associated with submission of comments. There is no guarantee, expressed or implicit, that market research for this acquisition will result in a particular set-aside, or any other guarantee of award or acquisition strategy. Respondents will not be contacted regarding their submission or information gathered as a result of this Sources Sought notice. Interested firms shall be required to respond to additional announcements separately from this announcement without further notice from the Government when posted to the Contract Opportunities website at https://sam.gov/. The Contract Opportunities website is the only official site to obtain these documents.

Files

File Type Posted
36C25527Q0052_1.docx DOCX document
36C25527Q0052.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
Z2DA--657-27-111JB, Install Continuous Water Monitoring System St. Louis Vamc Jefferson Barracks St. Louis MO 63125, United States · NAICS 238220 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business
6685--Equipment-Temperature monitoring VANJHCS for East Orange and Lyons(VA-27-00007647) Nj Va Healthcare Facilities East Orange 07018, United States · NAICS 334513 Veterans Integrated Service Network 2 Service-Disabled Veteran-Owned Small Business
H346--Legionella Water Testing United States · NAICS 541620 Veterans Integrated Service Network 22 Service-Disabled Veteran-Owned Small Business
Z1DA--CON-NRM-668-22-106 Correct Domestic Water System NAICS 238220 Veterans Integrated Service Network 20 No set-aside
Z2NZ--Turn Key Chiller Equipment (Purchase and Install) Pineville, Louisiana 71360, United States · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors