Z1DA--657-21-117JB (A) Correct Deficiencies Identified During Triennial Testing (VA-23-00098255)
Closed Pre-Solicitation Posted
This opportunity was awarded. See the award notice from , or the latest solicitation from .
- Solicitation number
- 36C25523R0123
- Agency
-
Veterans Integrated Service Network 15
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- Service-Disabled Veteran-Owned Small Business
Opportunity facts
- NAICS code
- 238210 Electrical Contractors and Other Wiring Installation Contractors
- Place of performance
- St. Louis Vamc 1 Jefferson Barracks Rd St. Louis MO 63125, United States
Notice details come from SAM.gov. Updated .
About this opportunity
The contract involves a construction firm providing services to correct deficiencies identified during the FY2019 Triennial Electrical Testing under VHA Directive 1028. The work includes replacing panels in various buildings, providing NEMA 3R, and installing protective covers to prevent water from getting into the electrical equipment and protective devices to protect sprinkler heads from physical damage. The project is expected to be completed by August 3, 2023.
Services and products to be provided:
- Replacement of panels in various buildings as per plans and specifications.
- Provision of NEMA 3R and miscellaneous items as per plans and specifications.
- Installation of protective covers to prevent water from getting into the electrical equipment.
- Installation of protective devices to protect sprinkler heads from physical damage.
- Correction of other issues in various buildings as per plans and specifications.
Notice text
657-21-117JB Correct Deficiencies Identified During Triennial Testing
8-3-2023
Scope of Work
(See Plans and Specifications for the full Scope of Work)
The Construction firm must provide construction services as delineated in the Plans and Specifications. The following deficiencies below were identified during the FY2019 Triennial Electrical Testing required under VHA Directive 1028. This project will correct deficiencies remaining after testing. New equipment shall have all the required working clearances.
Building 1 Replacement of panels per plans and specifications.
Building 3 Replace Panel P3 in Basement Mechanical Room 001. Provide NEMA 3R, and misc per plans and specifications.
Building 18 Replace panel(s) per plans and specifications.
Building 24 Replace panels in Ground Floor Kitchen Room G06 per plans and specifications.
Building 25 replace panels per plans and specifications.
Building 51A Replace other issues per plans and specifications.
Building 53 - Replace other issues per plans and specifications.
The majority of electrical equipment in this facility has sprinkler heads, related water pipes and drainpipes directly over or within the spray pattern of the electrical equipment as represented by the picture to the right. Install protective covers to prevent water from getting into the electrical equipment nor are physical protective devices installed to protect the actual sprinkler heads from physical damage. Both are required by National Electric Code section 110.26(F)(1)(a) through (F)(1)(d). Shields need to be installed in all areas where electrical components are within the spray pattern or have overhead water lines to prevent damage to prevent overhead water sources (sprinklers and water lines) from penetrating the enclosures. Such penetration could lead to a potentially catastrophic failure. Protective covers or cages need to be installed on unprotected sprinkler heads to prevent accidental activation with the same potential for catastrophic failure as mentioned above per plans and specifications.
Files
| File | Type | Posted |
|---|---|---|
| Phase 1 Vol 1.pdf | ||
| Phase 1 Vol 2.pdf | ||
| 36C25523R0123.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| Z1DA--657-21-117JB (A) Correct Deficiencies Identified During Triennial Testing | Award Notice | |
| Z1DA--657-21-117JB (A) Correct Deficiencies Identified During Triennial Testing (VA-23-00098255) | Solicitation | |
| This notice | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| J061--triennial electrical maintenance - amendment 4 POP: 12/01/2026 - 11/30/2027 plus 4 option years | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| Z2DA--652-24-101 Improve Electrical Distribution | Veterans Integrated Service Network 6 | Service-Disabled Veteran-Owned Small Business | |
| 657A5-26-111, Triennial Electrical Testing | Veterans Integrated Service Network 15 | Service-Disabled Veteran-Owned Small Business Sole Source | |
| J061--SOURCES SOUGHT NOTICE - Triennial Electrical Inspection Testing and Maintenance Services Requirement - Louis A Johnson VA Medical Center 36C24527Q0039 | Veterans Integrated Service Network 5 | No set-aside | |