Y1DA--632-22-137 Glycol Upgrade for Preheat Hot Water System

Closed Solicitation Posted

Solicitation number
36C24222Q1128
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Notice details come from SAM.gov. Updated .

Notice text

2 versions

Update #2 · Latest ·

Who is replacing the damaged HW Coils in the AHUs and will this scope be done prior to the Glycol replacement scope?

Answer: The HW coils have already been replaced by in-house personnel.

As the system failed due to freezing temperatures, a pressure test will be needed to confirm system integrity prior to glycol installation. Please confirm all bidders will be required to do so.

Answer: Repairs to damage from the freeze-up have already been made and pressure tested by inhouse personnel. All bidders are responsible for pressure testing their new work per contract specifications and drawings.

If the system fails the pressure test, who is responsible for system repairs in order to provide a sealed system.

Answer: All bidders are responsible to complete any required repairs to their new work, following pressure testing, per contract specification and drawings.

Update #1 ·

--End of Description--