Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
BID DOCUMENTS
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GLYCOL UPGRADE FOR PREHEAT
HOT WATER SYSTEM
79 Middleville Rd, Northport, NY 11768
632-22-137
B200N
JUNE 6, 2022 KNRevisions: Date:
200N
JD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
BID DOCUMENTS
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GLYCOL UPGRADE FOR PREHEAT
HOT WATER SYSTEM
79 Middleville Rd, Northport, NY 11768
632-22-137
B200N
JUNE 6, 2022 KNRevisions: Date:
200N
JD
MH-001
MECHANICAL NOTES, LEGEND,
ABBREVIATIONS AND SCHEDULES
JD
AutoCAD SHX Text MECHANICAL NOTES A. THE INTENTION OF THESE CONTRACT DOCUMENTS IS TO REPLACE WATER IN THE PREHEAT GLYCOL HEATING WATER SYSTEM WITH 30% SOLUTION PROPYLENE GLYCOL. CONTRACTOR SHALL FURNISH THE GLYCOL AND THE MEANS FOR FILLING THE SYSTEM INCLUDING PUMP AND ALL APPURTENANCES AS DESCRIBED IN THE CONTRACT DOCUMENTS. IN ADDITION, THE CONTRACTOR SHALL FURNISH ONE ADDITIONAL 55 GALLON DRUM OF 30% PROPYLENE GLYCOL FOR FUTRUE USE. THE 55 GALLON DROM SHALL BE LOCATED IN THE BASEMENT MER. (APPROXIMATELY 1,000 GALLONS OF 30% SOLUTION PROPYLENE GLYCOL IS REQUIRED; THE VA MEDICAL CENTER WILL PAY FOR ONLY THE AMOUNT OF GLYCOL ACTUALLY SUPPLIED) B. THIS PROJECT INVOLVES MODIFICATIONS TO PIPING SYSTEMS, MUCH OF WHICH IS CONCEALED IN WALLS AND CEILINGS. ALL EXISTING PIPING INDICATED ON DRAWINGS ARE DIAGRAMMATIC BASED ON AVAILABLE DRAWINGS AND FIELD OBSERVATIONS, AND DO NOT SHOW ALL OFFSETS, DROPPING AND RISING OF RUNS AS MAY BE NECESSARY TO COMPLETE THE WORK AS SHOWN. PRIOR TO SUBMITTING BID, CONTRACTOR SHALL VISIT SITE TO EXAMINE THE EXISTING CONDITIONS AND INCLUDE ADDITIONAL PIPING, ACCESSORIES AND APPURTENANCES AS DEEMED NECESSARY TO COMPLETE THE WORK. THE CONTRACTOR SHALL PROVIDE FOR ALL REASONABLE ADDITIONAL PIPE EXTENSIONS, OFFSETS, DROPPING AND RISING OF PIPING AS REQUIRED TO AVOID OBSTRUCTIONS, WITHOUT ADDITIONAL COST TO THE OWNER. STANDARDS AND CODES: A. VA STANDARDS B. ASHRAE STANDARDS AS APPLICABLE C. SMACNA MANUALS AS APPLICABLE D. BUILDING STANDARDS AND REQUIREMENTS E. NFPA STANDARDS AS APPLICABLE F. NATIONAL ELECTRIC CODE STANDARDS AND REQUIREMENTS G. EPA REQUIREMENTS H. FEDERAL CODES HAVING JURISDICTION SPECIAL REQUIREMENTS: A. IDENTIFY EQUIPMENT WITH LAMINATED PLASTIC NAMEPLATES EQUAL TO SETON NAME PLATE CORP., STYLE M4564 ENGRAVED SETONPLY NAMEPLATE. SCAFFOLDING AND RIGGING: A. CONTRACTOR SHALL PROVIDE ALL SCAFFOLDING, RIGGING AND SERVICES NECESSARY FOR ERECTION AND DELIVERY ONTO THE PREMISES OF ALL MATERIALS FURNISHED AND/OR INSTALLED UNDER THIS SECTION OF THE SPECIFICATIONS AND REMOVE SAME FROM PREMISES WHEN NO LONGER REQUIRED. PIPING AND FITTINGS: A. INSTALL PIPING SYSTEMS USING THE BEST STANDARD PRACTICES OF THE TRADE TO MAKE THE CONNECTED EQUIPMENT AND SYSTEM COMPONENTS COMPLETE AND READY FOR REGULAR OPERATION. INSTALLATION SHALL BE IN ACCORDANCE WITH ALL WRITTEN INSTALLATION PROCEDURES, PIPING ACCESSORY MANUFACTURER'S RECOMMENDATIONS, REQUIREMENTS OF BUILDING SERVICES PIPING (ANSI B31.9) AND POWER PIPING (ANSI B31.1) AS APPLICABLE, AND AS SPECIFIED. B. STEEL PIPING: 1. THE USE OF STEEL PIPE SHALL NOT BE ACCEPTABLE FOR THIS PROJECT. 2. ALL COPPER PIPING SHALL BE TYPE "L". CUTTING AND PATCHING A. CONTRACTOR SHALL PROVIDE ANY REQUIRED CUTTING AND PATCHING INCLUDING PATCHING OF ALL OPENINGS IN WALLS, ETC. RESULTING FROM DEMOLITION, MODIFICATIONS TO EXISTING SYSTEMS, NEWLY INSTALLED CONSTRUCTION, ETC. REQUIRED FOR THE WORK OF THIS DIVISION.
AutoCAD SHX Text PIPING CLEANING A. DO NOT OPERATE PIPING SYSTEMS UNTIL ALL CONSTRUCTION DIRT AND DEBRIS HAVE BEEN REMOVED FROM THE SYSTEM. 2. FLUSH OUT ALL NEWLY INSTALLED GLYCOL WATER PIPING WITH CLEAN WATER UNTIL ALL CUTTING AND EXTRANEOUS DEBRIS HAVE BEEN REMOVED. PIPING INSULATION: A. ASTM E-84 MINIMUM FIRE HAZARD RATING SHALL BE 25 FLAME SPREAD, 50 FUEL CONTRIBUTED AND 50 SMOKE DEVELOPED. B. INSULATE ALL NEW PIPING INSTALLED UNDER THIS PROJECT. PIPING TEST: A. TESTS: NO TESTS SHALL BE STARTED UNTIL SYSTEMS HAVE BEEN CLEANED. PROVIDE TEMPORARY PIPING AND CONNECTIONS FOR TESTING, FLUSHING OR DRAINING SYSTEMS TO BE TESTED. IF LEAK DEVELOP, REPAIRS SHALL BE MADE AND TESTS REPEATED. TESTING SHALL BE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
FPC
AutoCAD SHX Text
CIRCUIT BALANCING VALVE
AutoCAD SHX Text
PLUG VALVE
AutoCAD SHX Text
FLEXIBLE PIPE CONNECTION
AutoCAD SHX Text
DEAD END - SCREWED CAP
AutoCAD SHX Text
BUTTERFLY AUTOMATIC CONTROL VALVE
AutoCAD SHX Text
GLOBE VALVE
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
DEAD END - WELDED CAP
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
ECCENTRIC REDUCER - FLAT BOTTOM
AutoCAD SHX Text
ECCENTRIC REDUCER - FLAT TOP
AutoCAD SHX Text
FLANGED END
AutoCAD SHX Text
FLANGED CONNECTION
AutoCAD SHX Text
CONCENTRIC REDUCER
AutoCAD SHX Text
PIPE RISE
AutoCAD SHX Text
UNION
AutoCAD SHX Text
PIPE DROP
AutoCAD SHX Text
NEW PIPE WITH DIRECTION OF FLOW
AutoCAD SHX Text
EXISTING PIPE ETC.
AutoCAD SHX Text
(TP)
AutoCAD SHX Text (120V)
AutoCAD SHX Text
STEAM TRAP
AutoCAD SHX Text
PUMP/FAN
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
LINE VOLTAGE (120 VOLTS)
AutoCAD SHX Text
PNEUMATIC
AutoCAD SHX Text
CONTROL AIR
AutoCAD SHX Text
PN
AutoCAD SHX Text
EXISTING PIPE, EQUIPMENT, ETC. TO BE DEMOLISHED
AutoCAD SHX Text
DO
AutoCAD SHX Text
WFS
AutoCAD SHX Text
2-WAY AUTOMATIC CONTROL VALVE (ELECTRIC)
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
PRESSURE GAUGE WITH "T" HANDLE
AutoCAD SHX Text
AO : ANALOGUE OUTPUT
AutoCAD SHX Text
AI : ANALOGUE INPUT
AutoCAD SHX Text
COCK & BRASS SIPHON (STEAM)
AutoCAD SHX Text
LOW VOLTAGE CONTROL WIRE
AutoCAD SHX Text
DI : DIGITAL INPUT
AutoCAD SHX Text
DO : DIGITAL OUTPUT
AutoCAD SHX Text
WATER FLOW SWITCH
AutoCAD SHX Text
COCK & PULSATION SNUBBER (WATER)
AutoCAD SHX Text
PRESSURE SENSOR
AutoCAD SHX Text
PRESSURE GAUGE WITH "T" HANDLE
AutoCAD SHX Text
THERMOMETER AND WELL
AutoCAD SHX Text
"Y" TYPE STRAINER
AutoCAD SHX Text
AUTOMATIC AIR VENT
AutoCAD SHX Text
PRESSURE SAFETY RELIEF VALVE
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
3-WAY AUTOMATIC CONTROL VALVE (ELECTRIC)
AutoCAD SHX Text
2-WAY AUTOMATIC CONTROL VALVE (PNEUMATIC)
AutoCAD SHX Text
TEMPERATURE SENSOR
AutoCAD SHX Text (24V)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
PIPE
AutoCAD SHX Text GAURANTEE: A. CONTRACTOR SHALL PROVIDE A ONE YEAR GAURANTEE FOR WORKMANSHIP AND A ONE YEAR WARRANTY ON ALL EQUIPMENT INSTALLED UNDER THIS PROJECT COMMENCING FROM TIME OF OWNER'S ACCEPTANCE.
AutoCAD SHX Text
SCOPE OF WORK
AutoCAD SHX Text A. THE FOLLOWING PROCEDURE TO BE PERFORMED DURING SHOULDER OR COOLING SEASON. THIS WORK
AutoCAD SHX Text SHOULD NOT BE PERFORMED ANYTIME WHERE WEATHER IS EXPECTED TO DROP BELOW 55 DEGRRES
AutoCAD SHX Text
FAHRENHEIT.
AutoCAD SHX Text
1. MATERIALS
AutoCAD SHX Text
a. APPROXIMATELY 1000 GALLONS OF 30%%% SOLUTION PROPYLENE GLYCOL WILL BE REQUIRED.
AutoCAD SHX Text
THE VA MEDICAL CENTER WILL PAY FOR ONLY THE ACTUAL AMOUNT OF GLYCOL REQUIRED
AutoCAD SHX Text
b. IN ADDITION, FURNISH TWO (2) ADDITIONAL 55 -GALLON DRUMS OF 30%%% PROPYLENE GLYCOL
AutoCAD SHX Text
FOR FUTURE USE
AutoCAD SHX Text
c. STORE DRUMS TEMPORARILY IN THE BASEMENT MER.
AutoCAD SHX Text
2. SHUT DOWN GLYCOL WATER PUMPS P-5 AND P-6, LOCK-OUT RESPECTIVE PUMP STARTERS PER VA
AutoCAD SHX Text
STANDARDS
AutoCAD SHX Text
3. CLOSE OFF COLD-WATER MAKE-UP TO THE PREHEAT SYSTEM
AutoCAD SHX Text
4. OPEN ALL PREHEAT WATER STOP VALVES IN MER THAT MAY BE CLOSED INCLUDING THE BYPASS LINE;
AutoCAD SHX Text
CONFIRM ALL CONTROL VALVES ON PREHEAT SYSTEM ARE IN THE OPEN POSITION.
AutoCAD SHX Text
5. LOCATE ALL DRAIN VALVES IN LOWEST POINT OF PREHEAT WATER SUPPLY AND RETURN LINES IN BASEMENT
AutoCAD SHX Text
MER.
AutoCAD SHX Text
6. CONNECT ONE HOSE EACH TO RESPECTIVE DRAIN VALVES FOR PREHEAT WATER SUPPLY AND RETURN LINES
AutoCAD SHX Text AND EXTEND HOSES TO THE NEAREST FLOOR DRAIN; IF POSSIBLE, EXTEND EACH HOSE TO A SEPARATE FLOOR
AutoCAD SHX Text DRAIN. OPEN DRAIN VALVES AND DRAIN PREHEAT WATER INTO THE FLOOR DRAIN(S) AT A FLOW RATE THAT
AutoCAD SHX Text WILL NOT OVERFLOW THE FLOOR DRAIN(S) IN MER OR CAUSE THE DRAINAGE WATER TO RISE UP OUT OF ANY
AutoCAD SHX Text
OTHER FLOOR DRAINS IN BASEMENT.
AutoCAD SHX Text
7. VENT THE PREHEAT GLYCOL HEATING WATER SYSTEM FOR HIGH POINT IN THE ROOF PENTHOUSES.
AutoCAD SHX Text
8. ALLOW THE PREHEAT WATER SYSTEM TO DRAIN COMPLETELY. WHEN WATER STOPS DRAINING FROM THE
AutoCAD SHX Text HOSES IN BASEMENT MER, OPEN DRAINS TO ANY OTHER LOW POINTS WHERE THERE MAY BE RESIDUAL
AutoCAD SHX Text WATER SUCH AS STRAINERS, PUMPS, AIR SEPARATOR, HEAT EXCHANGERS,ETC. AT BASEMENT MER AND TWO
AutoCAD SHX Text
PENTHOUSES.
AutoCAD SHX Text
9.REPLACE PRESSURE GAUGES AT PUMPS P-5 AND P-6, SUCTION AND DISCHARGE.
AutoCAD SHX Text 10.DISCONNECT THE DOMESTIC COLD WATER MAKE-UP WATER LINE IN BASEMENT MER FROM THE PREHEAT
AutoCAD SHX Text WATER RETURN, INSTALL BALL VALVES AND CAPPED 3/4-INCH HOSE FITTINGS AT BOTH ENDS.
AutoCAD SHX Text 11.DISCONNECT THE EXISTING GLYCOL MAKE-UP SYSTEM FROM EXISTING 3/4-INCH COPPER PIPE, LEAVING THE
AutoCAD SHX Text 3/4-INCH CONNECTION WHERE IT CURRENTLY IS CONNECTED TO THE PREHEAT WATER RETURN AND CAP IT;
AutoCAD SHX Text
RETAIN AS MUCH OF THE EXISTING COPPER PIPING AS POSSIBLE.
AutoCAD SHX Text 12.CLOSE ALL DRAIN VALVES IN THE BASEMENT MER AND THE PENTHOUSE MERS, THEN DOUBLE CHECK.
AutoCAD SHX Text 13.CLOSE ALL OPEN VENT VALVES IN BASEMENT MER AND EACH PENTHOUSE MER, INCLUDING AT PREHEAT
AutoCAD SHX Text
COILS, THEN DOUBLE CHECK.
AutoCAD SHX Text
14.FILL THE SYSTEM FULLY WITH 30%%% PROPYLENE GLYCOL AND VENT AIR FROM SYSTEM.
AutoCAD SHX Text
FROM SYSTEM.
AutoCAD SHX Text 15.START UP GLYCOL PREHEAT HEATING WATER SYSTEM, RECORD PUMP AMPERAGE AND SUCTION AND DISCHARGE
AutoCAD SHX Text
AND SUCTION AND DISCHARGE PRESSURES.
AutoCAD SHX Text 16.ONCE SYSTEM IS OPERATING SATISFACTORILY, PREPARE TO INSTALL NEW GLYCOL MAKE-UP SYSTEM.
AutoCAD SHX Text 17.CONNECT THE NEW GLYCOL MAKE-UP SYSTEM, PER MANUFACTURER'S PRINTED INSTALLATION INSTRUCTION
AutoCAD SHX Text
TO THE EXISTING CONNECTION POINT IN PREHEAT WATER RETURN.
AutoCAD SHX Text
19.PLUG IN GLYCOL MAKE-UP SYSTEM TO LOCAL 120 VOLT RECEPTACLE IN BASEMENT MER.
AutoCAD SHX Text 20.SET CONTROLS FOR START AT PRESSURE 3 PSI BELOW SYSTEM OPERATING PRESSURE AT BASEMENT LEVEL.