The 911th Air Force Reserve Base (Pittsburgh Air Reserve Station) is conducting market research through a Sources Sought notice and Request for Information to identify qualified contractors capable of performing Very Low Frequency (VLF) testing of medium voltage power lines; capability statements are due by August 6, 2026 at 12:00 PM. This is a Total Small Business set-aside anticipated procurement. Work is located at Pittsburgh Air Reserve Station and encompasses an estimated 75 on-base locations requiring testing over a 300-day performance period from Notice to Proceed.

Contractors must provide all materials, labor, and equipment to verify insulation integrity and strength in compliance with IEEE 400.2 standards, DoD Unified Facility Criteria, Air Force Engineering Technical Letters, NFPA-70 and NFPA-70B, IEEE standards (400.2, 400-2012, 43), NETA standards, and OSHA regulations. All personnel performing work must hold certifications in VLF testing and medium voltage cable testing. Key scope elements include developing a comprehensive testing plan, conducting site surveys and Lockout/Tagout procedures, performing VLF testing between 0.01 Hz and 0.1 Hz, performing insulation resistance testing per IEEE 43, and delivering a digital spreadsheet report containing test results, leakage current readings, defect records, and definitive Pass/Fail determinations with time-stamped photographs. Contractors must provide a 20-year manufacturer's warranty on materials and a five-year general contractor bonded watertightness warranty. Work availability is Monday through Friday, 7:00 a.m. to 6:30 p.m., excluding federal holidays and Unit Training Assembly weekends; contractor personnel require base passes and escorts. Capability statements must address company profile, socio-economic status, technical capability to complete 75 locations within 300 days, personnel certifications, and past performance examples from the previous three years, preferably on military installations. Submit responses to Ryan.Scott.34@us.af.mil and Crystal.Spurlin@us.af.mil.

Notice text

SOURCES SOUGHT NOTICE

Project Title: VLF Testing of Medium Voltage Power Lines
Location: 911th Air Force Reserve Base / Pittsburgh Air Reserve Station (ARS)
Notice Type: Sources Sought / Request for Information (RFI)

1. Introduction

This Sources Sought notice is being posted in accordance with Request for Offers (RFO) procedures and Federal Acquisition Regulation (FAR) Part 10, Market Research, requirements.

This is a Request for Information (RFI) ONLY to conduct market research and determine the availability and technical capability of qualified businesses to provide the required services. This is NOT a solicitation for proposals, proposal abstracts, or quotations. The Government does not intend to award a contract on the basis of this Sources Sought notice or to otherwise pay for the information solicited.

2. Project Description

The 911th Air Force Reserve Base (Pittsburgh ARS) is seeking capable and qualified contractors to provide all materials, labor, and equipment necessary to perform Very Low Frequency (VLF) Testing of Medium Voltage Power Lines. The primary objective is to verify the integrity and insulation strength of the designated power lines to ensure safe and reliable operation.

There are an estimated 75 locations that will need to be tested on base.

Key work elements include, but are not limited to:

  • Developing and executing a comprehensive VLF testing plan demonstrating that the system meets or exceeds IEEE 400.2 standards.
  • Conducting site surveys, equipment preparation, and Lockout/Tagout (LOTO) procedures.
  • Performing VLF testing (0.01 Hz to 0.1 Hz) and insulation resistance testing (IAW IEEE 43).
  • Isolating circuits, identifying potential insulation weaknesses, and resolving defects (repair or replace damaged equipment).
  • Providing a comprehensive report in digital spreadsheet format outlining test results, leakage current readings, defect records, and definitive Pass/Fail determinations.

The anticipated Period of Performance is 300 days from the Notice to Proceed (NTP).

3. Contractor must follow these Requirements

All installation, testing, and materials must be completed by qualified personnel certified in VLF testing and medium voltage cable testing. Work must be performed in accordance with the latest versions of applicable standards, including:

  • DoD Unified Facility Criteria (UFC) (that we can provide)
  • Air Force Engineering Technical Letters (that we can provide)
  • National Fire Protection (NFPA-70, NFPA-70B)
  • Institute of Electrical and Electronics Engineers (IEEE 400.2, 400-2012, IEEE 43)
  • International Electrical Testing Association (NETA)
  • State and Federal OSHA regulations

Contractors must also comply with base access requirements, including background checks for passes and Commercial Vehicle Inspections.

4. Requested Information (Capability Statement)

Interested parties are requested to submit a Capability Statement addressing the following:

  1. Company Profile: Company name, address, Point of Contact (POC), phone number, email, CAGE Code, and Unique Entity ID (UEI).
  2. Socio-Economic Status: Specify any applicable small business classifications (e.g., 8(a), HUBZone, Service-Disabled Veteran-Owned, Women-Owned).
  3. Technical Capability: A brief statement detailing your company's ability to perform the VLF testing as described, including the capability to service the estimated 75 locations within the 300-day performance period.
  4. Certifications: Confirmation that personnel are properly trained and hold necessary VLF and medium voltage testing certifications.
  5. Past Performance: Brief examples of similar work performed in the past three (3) years, preferably on military installations or large commercial facilities.

5. Submission Instructions

All responses to this Sources Sought notice must be submitted electronically to the Contracting Office via email at Ryan.Scott.34@us.af.mil and Crystal.Spurlin@us.af.mil no later than 12:00 PM on 08/6/2026. Please include "Sources Sought Response: VLF Testing - Company Name and CAGE CODE" in the subject line.

Disclaimer: Telephone inquiries will not be accepted or acknowledged, and no feedback or evaluations will be provided to companies regarding their submissions.

Files

File Type Posted
Sources_Sought__VLF_Testing_of_Medium_Voltage_Power_Lines.docx DOCX document
Revised_Statement_of_Work_-_VLF_Testing.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
J061--541 Electrical Power Distribution Equipment Testing, Inspection, and Maintenance - VAMC Cleveland Department of Veterans Affairs Louis Stokes Cleveland VA Medical Center, Ohio 44106, United States · NAICS 238210 Veterans Integrated Service Network 10 Total Small Business
Repair Electrical Systems Wright-Patterson AFB, OH 45433 (Area A, Area B and all other properties owned by Wright-Patterson Air Force Base, Ohio) 45433 · NAICS 238210 AFLCMC Wright Patterson AFB No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity