Sources_Sought__VLF_Testing_of_Medium_Voltage_Power_Lines.docx

DOCX document 29 KB Posted

Attached to
VLF Voltage Testing
Solicitation number
FA6712VoltageTestingVLF
Issued by

About this file

This is a Sources Sought Notice and Request for Information (RFI) posted by the 911th Air Force Reserve Base (Pittsburgh Air Reserve Station) to conduct market research on contractor capability for Very Low Frequency (VLF) testing services. The Air Force is seeking qualified contractors to provide materials, labor, and equipment necessary to perform VLF testing of medium voltage power lines at an estimated 75 locations on base. The primary objective is to verify insulation integrity and strength to ensure safe and reliable operation. Key work elements include developing a comprehensive VLF testing plan compliant with IEEE 400.2 standards, conducting site surveys and equipment preparation with Lockout/Tagout procedures, performing VLF testing (0.01 Hz to 0.1 Hz) and insulation resistance testing per IEEE 43, isolating circuits to identify insulation weaknesses, and resolving defects through repair or replacement. The contractor must deliver a comprehensive digital spreadsheet report containing test results, leakage current readings, defect records, and Pass/Fail determinations. The anticipated Period of Performance is 300 days from Notice to Proceed.

All work must be performed by personnel certified in VLF and medium voltage cable testing and must comply with DoD Unified Facility Criteria, Air Force Engineering Technical Letters, NFPA-70 and NFPA-70B, IEEE standards (400.2, 400-2012, 43), NETA standards, and OSHA regulations. Contractors must also meet base access requirements including background checks and Commercial Vehicle Inspections. Interested parties must submit a Capability Statement by 12:00 PM on August 6, 2026, to Ryan.Scott.34@us.af.mil and Crystal.Spurlin@us.af.mil, addressing company profile, socio-economic status, technical capability to service 75 locations within 300 days, personnel certifications, and past performance examples from the previous three years, preferably on military installations. This is market research only and does not constitute a solicitation for proposals or a commitment to award a contract.

View the file

Other files

File Type Posted
Revised_Statement_of_Work_-_VLF_Testing.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOURCES SOUGHT NOTICE

Project Title: VLF Testing of Medium Voltage Power Lines Location: 911th Air Force Reserve Base / Pittsburgh Air Reserve Station (ARS) Notice Type: Sources Sought / Request for Information (RFI)

1. Introduction This Sources Sought notice is being posted in accordance with Request for Offers (RFO) procedures and Federal Acquisition Regulation (FAR) Part 10, Market Research, requirements.

This is a Request for Information (RFI) ONLY to conduct market research and determine the availability and technical capability of qualified businesses to provide the required services. This is NOT a solicitation for proposals, proposal abstracts, or quotations. The Government does not intend to award a contract on the basis of this Sources Sought notice or to otherwise pay for the information solicited.

2. Project Description The 911th Air Force Reserve Base (Pittsburgh ARS) is seeking capable and qualified contractors to provide all materials, labor, and equipment necessary to perform Very Low Frequency (VLF) Testing of Medium Voltage Power Lines. The primary objective is to verify the integrity and insulation strength of the designated power lines to ensure safe and reliable operation.

There are an estimated 75 locations that will need to be tested on base.

Key work elements include, but are not limited to:

Developing and executing a comprehensive VLF testing plan demonstrating that the system meets or exceeds IEEE 400.2 standards.

Conducting site surveys, equipment preparation, and Lockout/Tagout (LOTO) procedures.

Performing VLF testing (0.01 Hz to 0.1 Hz) and insulation resistance testing (IAW IEEE 43).

Isolating circuits, identifying potential insulation weaknesses, and resolving defects (repair or replace damaged equipment).

Providing a comprehensive report in digital spreadsheet format outlining test results, leakage current readings, defect records, and definitive Pass/Fail determinations.

The anticipated Period of Performance is 300 days from the Notice to Proceed (NTP).

3. Contractor must follow these Requirements All installation, testing, and materials must be completed by qualified personnel certified in VLF testing and medium voltage cable testing. Work must be performed in accordance with the latest versions of applicable standards, including:

DoD Unified Facility Criteria (UFC) (that we can provide) Air Force Engineering Technical Letters (that we can provide) National Fire Protection (NFPA-70, NFPA-70B) Institute of Electrical and Electronics Engineers (IEEE 400.2, 400-2012, IEEE 43) International Electrical Testing Association (NETA) State and Federal OSHA regulations Contractors must also comply with base access requirements, including background checks for passes and Commercial Vehicle Inspections.

4. Requested Information (Capability Statement) Interested parties are requested to submit a Capability Statement addressing the following:

Company Profile: Company name, address, Point of Contact (POC), phone number, email, CAGE Code, and Unique Entity ID (UEI).

Socio-Economic Status: Specify any applicable small business classifications (e.g., 8(a), HUBZone, Service-Disabled Veteran-Owned, Women-Owned).

Technical Capability: A brief statement detailing your company's ability to perform the VLF testing as described, including the capability to service the estimated 75 locations within the 300-day performance period.

Certifications: Confirmation that personnel are properly trained and hold necessary VLF and medium voltage testing certifications.

Past Performance: Brief examples of similar work performed in the past three (3) years, preferably on military installations or large commercial facilities.

5. Submission Instructions All responses to this Sources Sought notice must be submitted electronically to the Contracting Office via email at Ryan.Scott.34@us.af.mil and Crystal.Spurlin@us.af.mil no later than 12:00 PM on 08/6/2026. Please include "Sources Sought Response: VLF Testing - Company Name and CAGE CODE" in the subject line.

Disclaimer: Telephone inquiries will not be accepted or acknowledged, and no feedback or evaluations will be provided to companies regarding their submissions.

File details come from the government source that posted it. Updated .