Repair Building 510 HVAC

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
FA670326Q0002_2
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Marietta, Georgia 30069, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of the Air Force Reserve Command seeks repair of Building 510 HVAC systems at Dobbins Air Reserve Base, with proposals due August 19, 2026. This amendment uploads legible drawings for the project.

Place of performance is Marietta, Georgia 30069. The project involves demolition of existing HVAC equipment (FC-2 fan coil unit, CU-2 condenser unit, associated refrigerant linesets, electrical feeders, combustion air ducts, and condensate drain piping) and relocation of the FC-1 fan coil unit. All exterior penetrations must be flashed, counterflashed, and sealed to maintain watertight conditions on this historic building.

Technical requirements include G60 galvanized sheet metal ductwork with internal 1-inch fiberglass wrap insulation meeting ASTM E84 flame spread index of 25 and smoke development index of 50. All ductwork must be constructed to SMACNA standards with 2-inch W.G. static pressure classification and Class A seals. Refrigerant piping must be Type-L or ASTM B280 copper tubing with brazed joints, pressure-tested at 445 PSIG minimum with nitrogen, and vacuum-tested at 27 inches for one hour. The contractor must perform comprehensive HVAC duct cleaning per NADCA standards with a certified supervisor, provide 12-month equipment warranties, and complete testing and balancing services through a licensed TAB contractor with minimum five years experience. Control setpoints include cooling at 78°F and heating at 68°F with coordinated reprogramming of the JACE building management system. All work must comply with UFC standards, 2024 International Building Code, NFPA 70 (2023 Edition), and Dobbins Air Reserve Base facility standards. NAICS code is 238220, Plumbing, Heating, and Air-Conditioning Contractors; PSC is Z2AA, Repair or Alteration of Office Buildings.

Notice text

The purpose of this amendment is to upload legible drawing.

Files

File Type Posted
Attach 10 Drawing_2.pdf PDF

Notice history

Notice Type Posted
Repair Building 510 HVAC Award Award Notice
This notice Latest solicitation Solicitation
Repair Building 510 HVAC Special Notice
Repair Building 510 HVAC Original Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
HVAC Replacement, Bldg. 2821 NAICS 238220 Air Combat Command Total Small Business
Replace HVAC Rooftop Units at Building 2275 March Air Reserve Base, California 92518, United States · NAICS 238220 Army National Guard No set-aside
Or-bandon marsh NWR-bandon HVAC NAICS 238220 — No set-aside
DCDO - HVAC Maintenance 96367 Japan · NAICS 238220 Pacific Air Forces No set-aside
HVAC Unit Replacement NAICS 238220 National Oceanic and Atmospheric Administration Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity