Non-Refrigerated Water Re-circulating System
Closed Solicitation Posted
- Solicitation number
- 385226
- Agency
-
Fermi National Accelerator Laboratory
Office of Science, Department of Energy
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 333415 Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
- Place of performance
- Batavia, Illinois 60510, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
Fermi National Accelerator Laboratory, procuring on behalf of the Department of Energy Office of Science, seeks quotes for one Haskris Non-Refrigerated Water Re-Circulating System Model WW3, with quotes due August 12, 2026. This is a Request for Quote for a commercial product under FAR subpart 12.6, with award as a single Firm Fixed Price purchase order.
Place of performance is Batavia, Illinois, with delivery F.O.B. to Fermilab Warehouse 2, freight prepaid. The equipment specification includes 115V-10-60Hz electrical, dimensions 40"(W) × 26"(D) × 47"(H), PLC temperature controller with alarm logging, electronic facility water valve, regenerative turbine pump with bypass relief valve, and integrated non-pressurized fluid tank with level switch. Design parameters require maximum facility water inlet temperature of +45°F, minimum available water flow of 8.8 GPM, maximum inlet pressure of 100 psi, optimal differential pressure 15–50 psi, application heat load of 10.6 kW, and supply water temperature of +68°F at 60 psi. The equipment must be factory tested under full load. An NRTL label is also required.
NAICS code 333415; PSC 4130. This is an all-or-none requirement with no set-asides. Offerors must submit quotes on the RFP page with pricing, a completed SARC form, and a PUR-466 Proposal Certifications form. Offerors must accept FRA General Terms and Conditions for Commercial Products and Commercial Services (8/2025) without exceptions; any deviations from specifications or additional terms result in disqualification. Procurement Specialist Cathleen E. Stadler handles questions at 630-840-2763 or cstadler@fnal.gov. Oral communications are not acceptable.
Notice text
Request for Quote | brand name or item specifications equal to
Fermi Forward Discovery Group (FFDG) FOR FERMILAB has a requirement for a Haskris Non-Refrigerated Water RE-Circulating System Model WW3
NAICS Code for this procurement is 333415
Fermi Forward Discovery Group (FFDG) Strategic Commercial Purchasing located in Batavia, Illinois issuing a Request for Quote (RFQ) for a commercial, single award contract to be shipped to Batavia, Illinois Warehouse 2. This is a /solicitation for commercial products or commercial services prepared in accordance with the format in FAR subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued.
Fermi Forward Discovery Group (FFDG) intends to award Firm Fixed Price (FFP) contract. This is an all-or-non requirement, and the government will award a single purchase order to the offeror responsible whose offer conforms to the requirements as stated in the solicitation and is most advantageous to the Government based on the criteria listed within this solicitation.
- Haskris Non-Refrigerated Water Re-Circulating Systen Model WW3 QTY 1
Electrical 115V-10-60Hz
Dimensions: 40”(W) x 26” (D) x 47” (H)
Features
PLC temperature controller with alarm descriptions and logging
Built-in, electronic facility water valve for temperature control
High supply water temperature system cut out
Regenerative turbine pump with robust seal and bypass relief valve
Integrated fluid tank (non-pressurized) with fluid level switch
Factory tested under full load
Heat Exchanger Design Parameters
Primary (Facility) Water Loop
Max Water Inlet Temp: +45°F
Min Available Water Flow: 8.8 GPM
Max Water Inlet Pressure: 100 psi
Optimal Differential Pressure: 15-50 psi
Secondary (Application) Water Loop
Application Heat Load: 10.6 kW
Supply Water Temp: +68°F
Supply Water Flow: 8.8 GPM
Supply Water Pressure: 60 psi (max)
2. NRTL Label
Oral communications are not acceptable in response to this notice.
Interested organizations may submit their capabilities and qualifications to perform the effort in writing to the identified point of contact no later than 4:00 p.m. Central Standard Time on 12 AUG 2026.Such capabilities /qualifications will be evaluated solely for the purpose of determining whether to conduct this procurement on a competitive basis. A decision by the Government not to compete this proposed effort on full and open competition basis, based upon responses to this notice, is solely with the discretion of the government.
The following terms and conditions shall become a part of any subsequent purchase order/subcontract resulting from this RFP.
- FRA General Terms and Conditions for Commercial Products and Commercial Services (8/2025)
The above referenced terms and conditions are available on the Fermilab Business Services Web Site. They are PDF Format and can be accessed at the following URL:
https://procurement.fnal.gov/terms-conditions/
NOTE TO OFFERORS: Please be advised that any exceptions to the specifications or to FFDG’s terms and conditions may cause your proposal to be disqualified with no further consideration for an award.
Any exceptions or additional terms noted on a Quote Form will not be considered and are hereby expressly rejected. Likewise, any references—whether through language or hyperlink—to additional terms and conditions are not accepted and are similarly rejected.
FERMI Strategic Commercial Purchasing will be the procuring center for this effort. All equipment and or services are to be delivered F.O.B. Fermi National Accelerator Laboratory (Fermilab), Batavia, IL 60510, Freight prepaid (delivered).
The following Representations must be completed and returned with your proposal.
- SARC – Subcontractor Annual Reps & Certs
- PUR-466 – Proposal Certifications
The RFP response shall include a completed RFP page include a price, with a completed SARC and PUR-466.
All contractual questions shall be directed to:
Cathleen E. Stadler
Procurement Specialist
630-840-2763
cstadler@fnal.gov
Files
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| PIP-II f-37 building LWC pump room piping system installation | Fermi National Accelerator Laboratory | No set-aside | |
| 5W Pulse Tube CryoCooler | Fermi National Accelerator Laboratory | No set-aside | |
| PIP-II ssrs and LB650 vacuum gauge and readout | Fermi National Accelerator Laboratory | No set-aside | |
| 500-Ton Trailer-Mounted Air-Cooled Chiller | Kennedy Space Center | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity