Questions & Answers
36C26123Q0576 Fire Protection System Service
For each building can you provide the type/quantity of devices (smoke detector, heat detector, waterflow, duct detectors, etc..) to be tested? We need an accurate count of devices to develop the pricing as different devices take different time to inspect.
Also, section 1.3 of the PWS, the contractor to provide an initial assessment and provide an initial inventory.
Building
Post indicator Valve (PIV)
Fire Pumps
Fire Department Connections
Pre-Action Systems
Pull Station
Heat Detector
Smoke Detector
Duct Detector
Door holders
T1 E-Wing
1
N/A
1
2
29
6
17
8
50
30 - ACC
1
2
1
2
30
2
33
6
30
32 - Parking Structure
1
N/A
1
2
19
1
4
N/A
N/A
110 - CFA
1
N/A
1
N/A
28
1
4
7
12
2. Can the audio/visuals & door holders be tested during normal hours? If not, when should these be tested?
Yes. Testing can be done during normal business hours. VA requires a full year of schedule and a minimum two week notice to perform testing to allow the notification of VA staff.Â
3. Can the elevator recall/shunt trip be tested during normal working hours?
The PWS does not include the elevator. Elevator recall is tested by another vendor.
4. Bldg 110 CFA: How many fusible links and tanks in the kitchen hood systems?
There are two. One in the main kitchen and one in A129 Kitchenette.
5. Bldg 30 ACC: Are we to perform the monthly fire pump run?
EP6
Fire Pumps Tested (No Flow)
Only for Building 30 ACC. All other buildings do not have fire pumps.
Monthly (Electric)
NFPA 2512020J 8.3.1.2.
Pages 3 to 5 states the frequency to inspect the equipment and devices per NFPA and Joint Commission requirements.
Files
| File | Type | Posted |
|---|---|---|
| 36C26123Q0576 0002.docx | DOCX document | |
| 36C26123Q0576 0001.docx | DOCX document | |
| Wage Determination15-5689 RV19-December-27-2022.txt | TXT text file | |
| 36C26123Q0576.docx | DOCX document | |
| Quality Assurance Surveillance Plan.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| H912-- Fire Protection System Services | VAPIHCS | Award Notice | |
| This notice | Solicitation | |
| H912--36C261-23-AP-2041 | Fire Protection System Service(VA-23-00049067) | Pre-Solicitation |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity