Fire Trainer Liner
Closed Pre-Solicitation Posted
- Solicitation number
- FA480926Q0065
- Agency
-
Air Combat Command
Air Force, Department of Defense
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 238990 All Other Specialty Trade Contractors
- PSC
- 4240 Safety And Rescue Equipment
- Place of performance
- Goldsboro, North Carolina 27531, United States
Notice details come from SAM.gov. Updated .
About this opportunity
Air Combat Command intends to procure a structural trainer liner replacement for fire training facilities, with responses due July 30, 2026, under a Total Small Business set-aside.
The liner is designed for extreme live-fire training and must meet NFPA 1402 compliance standards for Class A, B, C, D, Electrical, and F/K fires within controlled burn cells. The material is a cementitious high-temperature composite with Kevlar additives, installed via a unique tongue-and-groove method with stainless steel mounting hardware. The liner must be 1.5 inches thick, withstand 150 psi nozzle forces, achieve heat transfer of 10.4 percent (1000 degree to 140 degree in 10 minutes), and require no additional insulation. The product carries a five to ten year warranty and is certified as a protective skin for flammable hazmat storage cells. Installation by certified installers is required.
Place of performance is Seymour Johnson Air Force Base, North Carolina. The project includes removal and installation of new fire command boards in two burn rooms totaling 1,430 square feet, along with associated equipment and system upgrades documented in architectural drawings filed with the opportunity.
NAICS 238990 (All Other Specialty Trade Contractors) and PSC 4240 (Safety and Rescue Equipment) apply.
Notice text
SALIENT CHARACTERISTICS
for
Structural Trainer Liner
DESCRIPTION: Replace liner inside the structural trainer
REQUIREMENTS: The liner components units shall:
1. Designed to meet all referenced safety, thermal, and regulatory specifications, this specific material is engineered for extreme live-fire training evolutions.
2. Specifically formulated for Class A, B, C, D, Electrical, and F/K fires within a controlled burn cell which complies with NFPA 1402 and related standards.
3. Made of a cementitious high temp composite formula, which has a negative health impact when installed by certified installers.
4. Have Kevlar additives
5. Unique tongue and groove installation method
6. Stainless Steel mounting hardware
7. Have five (5) to ten (10) year warranty to replace
8. Able to withstand 150 psi nozzle forces
9. 1.5 inches thick requires no additional insulation behind its barrier
10. Heat transfer 10.4% (1000 degree / 140 degree in 10 minutes)
11. Complies with all NFPA suggested burn matrix formulas
12. Certified as a protective skin for flammable hazmat storage cells
Files
| File | Type | Posted |
|---|---|---|
| 02 A-01 - FLOOR PLANS.pdf | ||
| Fire Trainer Drawings.png | PNG image |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Extinguisher, fire | Construction and Equipment | Total Small Business | |
| Cylinder, fire extin | Aviation | No set-aside | |
| FD2030-26-01457 | Air Force Sustainment Center | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity